Selection Chemical Seal Connections

Guide DMS Series

Confidential Information

Direct Mount Seal System


and Diaphragm Seals

Yokogawa Corporation of America SGFP-01A


2 Dart Road Newnan, Georgia U.S.A. 30265 Copyright Jan. 1, 2002
Tel: 1-800-258-2552 Fax: 1-770-254-0928 1st Edition 5/23/02 1M
2

INTRODUCTION The major benefits are:


1. A Diaphragm Seal Mounting System
This sales guide describes the chemical seal process specifically designed for the DPharp Pressure
connections available from Yokogawa Corporation of Transmitter
America. There are two distinct types of chemical seal 2. A "seamless" and rugged connection which
process connections. The first is the Direct Mount Seal maintains structural integrity
system (DMS) with the chemical seal attached as an a) 250 lbs. Shear load
integral (close coupled) part of the DPharp body. b) Minimized fill volume for better thermal
characteristics
The second refers to remote mounted diaphragm seal 3) Flexible to adapt to a multitude of seals
process connections that have a capillary between the a) Single flange which welds to upper
chemical seal and the DPharp transmitter. housing

DMS ADVANTAGES

The Direct Mount Seal system, DMS, is a connection nA Diaphragm Seal Mounting System specifically
system to mount various types of diaphragm seals designed for the DPharp Pressure Transmitter
directly to the DPharp Pressure Transmitter. It was n Provides a "seamless" and rugged connection which

originally designed to incorporate sanitary type seals, maintains structural integrity


and has been expanded to include flanged and extended 250 lbs. Shear load
flanged diaphragm seals. Minimized fill fluid volume for better thermal
characteristics
These options have allowed us to broaden our flange- n Flexible to adapt to a multitude of seals

mounted (Level) transmitters with various fill fluids Single flange which welds to the seals upper
and wetted-materials not currently available on the housing
EJA210A & 220A series. This also provides Yokogawa n Majority of Applications in Level Measurement

the ability to offer custom type (not currently listed in n Requires close connection to Tank

the price book) seals with varying barrel diameters, Limits fill fluid volume
diaphragm materials and connection sizes. Limits temperature effect
n Secondary Applications for Gauge Pressure

The DMS mounting flange maintains the same profile Close coupling when diaphragm seal is required
as the DPharp flange, so the same bolt pattern and Easier mounting - No bracket required
mounting designs are used. This provides a "one piece" n Sanitary Applications

design solution that insures the integrity of the DPharp Capillaries are not recommended
by maintaining maximum shear load capability. The n Flexibility in applications

DMS also allows us to keep the fill fluid volume n No requirements for tokuchus

minimized through the design, thereby reducing overall n Special wetted parts available

temperature effect due to fluid expansion. This all- Monel Tantalum


welded construction adds to the aesthetic as well as the Titanium Etc.
structural presentation of the product. n Versatility of various different fill fluids

DMS vs. EJA210A/220A


Included with this release is an overview on the use of
diaphragm seals. Price sheets for these seals are located DMS Direct Mount
on the YCA Electronic Price Book. +Comprehensive seal offering
(flush, extended, sanitary, etc.)
Benefits:
+Versatility for materials and fill fluids
The obvious advantage to using a direct mount
system is the elimination of capillaries. This +Improved delivery on custom jobs
helps with the overall temperature effect and (No tokuchu)
necessity to mount and care for the capillaries.
Not compensated to temperature
Some of the other benefits of the direct mount
system are structural Accuracy will depend on application
integrity and ease of
installation and removal EJA210A/220A
and replacement. A graphic
representation of the DMS +Factory temperature compensation
is referenced to the right. +Stated accuracy on GS
Please keep in mind that
this DMS "flange" uses the +Instrument is complete Yokogawa product
same bolt pattern as the Limited offering
existing DP Harp series
Specials require tokuchu
transmitters.

GS 33G6E22-01E
3

REMOTE DIAPHRAGM SEALS n Shorter capillary lengths and smaller capillary ID help
reduce thermal expansion effects and response time
Overview n When using a two seal system, diaphragm size,
capillary length and fill fluid should be the same for
Remote diaphragm seals offer a cost-effective means of both sides
preventing the process medium from coming in contact n To reduce response time, select shorter capillary

with a pressure-sensing element. However, adding lengths, larger capillary ID and less viscous fill fluid
remote seals to pressure sensing elements can have a n For vacuum service in level applications, the seal

negative overall effect on system performance. should be mounted at or below the lower tap. Also a
Temperature, thermal expansion coefficient of the fill fill fluid that is mixed with water should never be used
fluid, diaphragm size, spring constant, capillary length in a vacuum application
and capillary diameter can all cause errors in n Fill fluid should be selected to meet the most extreme

measurement and response time if not properly selected. process variables and one which will not cause
contamination to the process in the event of seal
Operation failure

The system to be considered consists of a diaphragm REMOTE DIAPHRAGM


seal, a pressure transmitter, a capillary connection SEAL APPLICATIONS
between the seal and transmitter, and a fill fluid. This
diaphragm, capillary and fill fluid act as a medium to When to use a remote seal
relay the process pressures to the sensor in the
transmitter. n High temperature applications where the process fluid
temperature is beyond the acceptable specifications of
A pressure is sensed by deflection of the thin film the transmitter sensing element
diaphragm at the process connection. This deflection n Corrosive service where the requirements for materials

causes a compression or expansion of the fill fluid, of construction is cost prohibitive


which then is sensed at the transmitter by displacing n To isolate the process for safety reasons

the transmitter element. This displacement is n Prevention of suspended solids from entering the cell

proportional to the measured variable and is converted body or the impulse lines which could become plugged
to a 4-20 mA and/or digital output. and solidification may occur
n Requirement for sanitary connections

Seal Selection n Replacement of wet legs


n Ease of cleaning between batches to avoid

Careful selection of seal size, capillary diameter, contamination


capillary length and fill fluid must be considered to
optimize the total system performance, minimize the Fill Fluid
effects of temperature and thermal expansion, and to
meet the process requirements. Overall variables to be When selecting fill fluid consider four criteria
considered are: 1. Do the temperature limits of the fill fluid cover the
n Larger diameter seals typically minimize temperature process and ambient ranges?
effects 2. Is this a sanitary application (food grade fill)?
3. Is the process Oxygen service (inert fill)?

Model Temp Range F Temp Range F S p e c i f i c T h e r m a l V i s c o s i t y


Fill Fluid Notes
Code [Pabs<15psi] [ P a b s 1 5 p s i ] G r a v i t y Expansion (cSt)

DC200-10 -40 to 250 F -40 to 400 F Standard Fill


A 0.934 0.0006 10
[ - 4 0 / 1 2 0 C] [ - 4 0 / 2 0 5 C]
DC704 78 to 280 F 30 to 500 F Vacuum
B 1.07 0.0008 39
[ 2 6 / 1 4 8 C] [ - 1 / 2 6 0 C] High Temp
Inert -40 to 176 F -40 to 347 F Oxygen and
C 1.97 0.00084 14
(Halocarbon) [ - 4 0 / 8 0 C] [ - 4 0 / 1 7 5 C] Chlorine Service
Neobee M20 -10 to 200 F -10 to 400 F Food Grade
D 0.92 0.00101 9.5
[ - 2 3 / 9 3 C] [ - 2 3 / 2 0 4 C] (FDA)
Glycerin N/A 60 to 462 F Food Grade
E 1.26 0.0005 1110
[ 1 6 / 2 3 9 C] (FDA)
Ethylene Glycol N/A -30 to 300 F
F 1.12 0.00062 30
[ - 3 4 / 1 4 9 C]
Hi Temp 14 to 392 C -4 to 750 F High Temp
G 1.07 0.0008 39
[ - 1 0 / 2 0 0 C] [ - 2 0 / 3 9 9 C] and Vacuum
Low Temp -130 to 176 F -130 to 356 F Low Temp
H 0.91 0.00108 4
(Silicone Based) [ - 9 0 / 8 0 C] [ - 9 0 / 1 8 0 C] and Vacuum
DC200-350 N/A 0 to 572 F Food Grade
J 0.97 0.00096 350
[ - 1 7 / 3 0 0 C] (FDA)
Vegetable Oil 14 to 200 F 14 to 400 F Food Grade
K 0.94 0.00082 66
[ - 1 0 / 9 3 C] [ - 1 0 / 2 0 4 C]

GS 33G6E22-01E
4

Diaphragm Size The pressure head created by the fill fluid causes a pre-
loading effect on the transmitter; therefore, the
The error induced in a system can be greatly affected by calibration of zero must be elevated. The capillary
differential temperature (between the process and the system in a level transmitter must be treated as a wet
fill fluid) and by the spring constant on the diaphragm leg where a negative pressure is created. This pre-
used. An error in a filled capillary system can be loading effect is proportional to the height and specific
calculated by the following equation: gravity of the fill fluid. Example: If a DP transmitter
with a full scale range of 400" H2O (which has a zero
Error ("H2O) = (DT) (Et) (Rs) (Vt) elevation limit of 400" H2O) were to be used in a wet leg
application and the wet leg has a specific gravity of 0.9,
T The differential temperature change the maximum height of the wet leg would be 444" H2O.
Et The coefficient of thermal expansion of the fill fluid This applies to filled capillary systems:
Rs The diaphragm spring constant
Vt The volume of the fill fluid subjected to temperature Dmax = Zmax
change S.G.

The following graph shows the comparison of two Dmax Maximum vertical distance between
different diaphragm sizes and their effect on total error diaphragm seals
induced. Zmax Maximum zero elevation of the transmitter
Error vs. Temperature S.G. Specific gravity of the fill fluid
25 Vertical Distance vs. Zero Evaluation
20 450
Silicone704
Error H2O

400
15 2.5"Seal Silicone200

4.0"Seal Vertical Distance ( H2O) 350 EthyleneGlycol


10
Halocarbon
300
5
250
0
200
0 10 20 30 40 50 60 70 80 90 100
150
Differential Temperature
100

This does not necessarily mean that a bigger diaphragm 50

is required. When a gauge pressure transmitter is 0


200 250 300 350 400

being used at pressures higher than 100 psig, a smaller Maximum Zero Elevation (H2O)
diaphragm can be used. Also, if a system has a large T
between the process and ambient temperature but the Example
system is stable, such that this temperature difference
is constant, the two legs of the system will compensate A DP Cell is being used to measure level in a closed
and the error can be zeroed out of the system. The tank. The range of the transmitter being used is 400"
following is a quick pick chart for reference. H2O. Four inch diaphragm seals are being used with a
volume of 0.42, a spring constant of 40, and are placed
Suggested
Transmitter Span Diaphragm
5 apart with the transmitter being positioned 3 below
Size the upper seal. The fill fluid is Silicone 200-10. Each
capillary has a volume of 0.053. The volume of the
10 100 "H2 O 3 . 0 "
transmitter cavity is 0.351. Ambient and Process
100 1000 "H2 O 2 . 4 "
temperatures are shown.
30 200 "H2 O 2 . 0 "
200 10000 "H2 O 1 . 0 "
Error= (T) (Et) (Rs) (Vt)

Capillary Length

Capillary length becomes a factor when using remote 160F


seals on closed tank level applications. The pressure
generated by the vertical height of the fill fluid has an LOW

effect on the zero suppression or elevation of the 5 Capillary

transmitter. Force equals mass times acceleration,


95F
which can be stated in the following manner when
specific gravity and vertical height of a fluid are known.
5 Capillary 220F
HIGH
Pressure = (Ht) (Sg)

Ht The vertical height of the fill fluid in the capillary


Sg The specific gravity of the fill fluid

GS 33G6E22-01E
5

Verify that the distance between the seals is not outside 2. Verify that the maximum vertical distance when
the range of the transmitter. compensated with the specific gravity of the fill fluid
Dmax = Zmax does not extend beyond the range of the transmitter
S.G.
What is the highest temperature and lowest pressure
Dmax = 400"/0.96 = 416.66" WC expected?
Calculate the total thermal error introduced into the If the combination of temperature and pressure on the
system. fill fluid exceed the vapor pressure point, accuracy will
ErrorH = (220-95)(0.0006)(40)(0.42+0.053+0.351) become unpredictable. Remember that as pressure
ErrorH = 2.472" WC for the high leg decreases, the temperature limits of the fill fluids are
ErrorL = (160-95)(0.0006)(40)(0.42+0.053+0.351) lowered.
ErrorL = 1.285" WC for the low leg
which produces a total differential error of +1.187" WC Is the process under vacuum?
Vacuum affects both the fill fluid selection and
NOTE: A 2.4" diaphragm with spring constant of 800 mounting position of the transmitter. The temperature
produces a total error of 23.73" WC. limits of the fill fluid are lowered when exposed to a
Also, the two diaphragms are not located equal vertical vacuum. Also if the transmitter is not seeing positive
distances from the transmitter. Therefore the zero has pressure, vaporization of the fill fluid is possible.
to be suppressed (5)(12")(0.93) = 55.80" WC. 1. Verify that the fill fluid will operate at the highest
temperature and lowest pressure
SUMMARY 2. Mount the transmitter at or below the lowest tap to
ensure a positive pressure on the measuring system at
In order to select an appropriate seal and capillary all times
combination, process conditions, installation
requirements and overall system performance must be What is the measurement span?
considered. The following is a list of questions in order Any error introduced into a system is greater when the
to take all effects into account. There is not a serve all span is smaller. When the span is under 50" H2O, more
solution. Sometimes conditions occur which will require scrutiny should be placed on the selection criteria.
sacrifice of one parameter in order to limit the effects on Remember on tank level applications, not to extend
the others. For instance, if there is a large temperature beyond the maximum working range of the transmitter
change requiring smaller capillary ID, this will have a when you compensate for the maximum vertical
greater effect on response time than a larger capillary distance of the fill fluid. Make sure that the
ID would. temperature effect is not a large percentage of span.

Questions to Ask and Points to Consider


What are the maximum pressure limits on the system?
What are the maximum process and ambient Maximum pressure is limited to the connection
temperature changes? parameters. Flange ratings can be verified from ANSI
Temperature changes introduce errors in the system specifications. Threaded connections typically handle
through fill fluid expansion and from the diaphragm higher pressures.
spring constant. If this is a major factor, the following
should be chosen:
1. Larger diameter diaphragm with a lower spring Is the process connection cleaned? With what type
constant solution?
2. Fill fluid with lower expansion rate Verify that the fill fluid will withstand the exposed
3. Shorter capillaries with smaller ID temperature (Sometimes a process tank or pipe is
cleaned at a higher temperature than the normal
How fast will the measured variable change? process generates) and that the diaphragm material of
Seals automatically introduce a delay in the system construction can withstand any corrosive exposure to
reading. In a rapid changing process, the following the introduced solution.
should be considered:
1. Shorter capillaries and/or larger ID What are the maximum pressure limits on the system?
2. Less viscous fill fluid Maximum pressure is limited to the connection
parameters. Flange ratings can be verified from ANSI
Where will the transmitter be installed? specifications. Threaded connections typically handle
The longer the capillary the longer the response time higher pressures.
and a larger increase in error due to thermal effects.
Always mount the transmitter as close as is practical.
Always remember:
1. Compensate for the effect of vertical height on the
capillary fill fluid

GS 33G6E22-01E
6

Is the process connection cleaned? With what type


solution?
Verify that the fill fluid will withstand the exposed
temperature (Sometimes a process tank or pipe is
cleaned at a higher temperature than the normal
process generates) and that the diaphragm material of
construction can withstand any corrosive exposure to
the introduced solution.

NEW PART NUMBERING SYSTEM


Direct Mount Seals

Field 1:
FLD, FXD, STD, FBD -The letter "D" must appear in
the third model string character to designate direct
mount.

Field 10:
000 -Zeros must be placed in this field for no capillary
length (describing a direct mount configuration).
CCC -Close coupled connection (no capillary) for use on
Direct-mount transmitters, EJA530A & 510A.

Field 11:
HGP, HDP -High Side Gauge or High Side D/P must be
chosen. Depending upon the application and a
Gauge/Absolute pressure or a Differential Pressure
transmitter has been selected.
DGP -Direct Gauge Pressure, should be for use with
EJA530A/510A.

All Remote Diaphragm Seals


(seals utilizing capillaries)

Field 11:
D/P Transmitter attach - Specify either HDP or LDP for
attachment of one seal and capillary.
Specify DDP for attachment of two identical seal
and capillaries (one line item with qty. in multiples
of 2)
OR
Specify both HDP and LDP for attachment of two
different seals on one transmitter (two separate line
items)
G/P Transmitter attach -Specify either HGP or DGP,
depending on type of Gauge/Absolute unit specified, for
attachment of one seal with capillary.

GS 33G6E22-01E
7

PART NUMBERS AND DESCRIPTIONS


Pancake Diaphragm Seals (ACS 9905)

Sometimes referred to as "paddle" or "pancake", these types of seals are mounted


between two flanges and connected to the transmitter by a capillary. These
diaphragm seals cannot be direct mounted.

Field1:ProcessConnection Field8:FlushingConnection
Code Description Code Description
PNK PancakeSeal 0 NoLowerHousing
1 Single1/4"
Field2:ConnectionSize 2 Dual1/4"
Code Description 3 Single
1/2"
-20 2.0" 4 Dual1/2
-30 3.0"
Field9:FillFluid
Field3:ConnectionRating Code Description
Code Description A SiliconeDC200
0 NoBackupFlange B SiliconeDC704
1 ANSI 150# C Inert
Fill(Halocarbon)
3 ANSI 300# D Neobee M20
G HighTemperatureFill(-4to740Deg.F)
Field4: H LowTemperatureFill(-130to356Deg.F)
Code Description
N Always Field10:CapillaryLength
Code Description
Field 5: Upper Housing/Wetted Upper Housing/Diaphragm 05A 5feetArmouredCapillary
Code Description 10A 10feetArmouredCapillary
SSS 316SS/316SS/316L 15A 15feetArmouredCapillary
HHC 316SS/HastC-276/HastC-276 20A 20feetArmouredCapillary
SHC 316SS/316SS/HastC-276 25A 25feetArmouredCapillary
STA 316SS/Tantalum/Tantalum 30A 30feetArmouredCapillary
SMM 316SS/Monel/Monel 05P 5feetPVCCoatedCapillary
STI 316SS/Titanium/Titanium 10P 10feetPVCCoatedCapillary
15P 15feetPVCCoatedCapillary
Field6: BackupFlange 20P 20feetPVCCoatedCapillary
Code Description 25P 25feetPVCCoatedCapillary
N NoneRequired 30P 30feetPVCCoatedCapillary
C CarbonSteel
S 316StainlessSteel Field11:Attachment
Code Description
Field7: LowerHousing(FlushingRing) HGP HighsideGP
Code Description HDP HighsideD/P
0 NoLowerHousing DDP BothsidesD/P(requires2seals)
S 316SS LDP Low Side D/P
H HastelloyC-276 DGP DirectGaugePressure(EJA510/EJA530)
M Monel
T TantalumPlated316SS Field12:Options
E Titanium Code Description
/S ThreadedCapillaryConnections
/K Degreased(usew/InertfillforO2service)
/M MillCert.forwettedpartsmatl
/C Calibration/NISTCert.
/T Teflon(PTFE)lineddiaphragm
/SD Stepshapeddiaphragm

Pressure
Size A B C D E
Rating
2" 150 to 2500 4 2.32 0.78 4 0.629
3" 150 to 2500 5.28 3.5 0.78 4 0.629

GS 33G6E22-01E
8

Flush Flanged Diaphragm Seals (ACS 9904)


[DMS Capable]

These diaphragm seals provide a direct flange connection to the process, with the
diaphragm welded directly to the sealing surface. The capillary connection is from
the back and does not require a backup flange. These seals are available for direct
mounting to the EJA transmitters.
Field1:ProcessConnection Field8:FlushingConnection
Code Description Code Description
FLG FlushFlanged 0 None
FGD FlushFlangedDirectMount 1 Single1/4"
2 Dual1/4"
Field2:ConnectionSize 3 Single
1/2"
Code Description 4 Dual1/2"
-20 2.0"
-30 3.0" Field9:FillFluid
-40 4.0" Code Description
A SiliconeDC200
Field3:ConnectionRating B SiliconeDC704
Code Description C Inert
Fill(Halocarbon)
1 ANSI 150# D Neobee M20
3 ANSI 300# E Glycerin(FGDonly)
6 ANSI 600# G HighTemperatureFill(-4to750Deg.F)
H LowTemperatureFill(-130to356Deg.F)
Field4:
Code Description Field10:CapillaryLength
N Always Code Description
000 DirectMount (FGDonly)
Field 5: Upper Housing/Wetted Upper Housing/Diaphragm 05A 5feetArmouredCapillary
Code Description 10A 10feetArmouredCapillary
SSS 316SS/316SS/316L 15A 15feetArmouredCapillary
HHC 316SS/HastC-276/HastC-276 20A 20feetArmouredCapillary
SHC 316SS/316SS/HastC-276 25A 25feetArmouredCapillary
STA 316SS/Tantalum/Tantalum 30A 30feetArmouredCapillary
SMM 316SS/Monel/Monel 05P 5feetPVCCoatedCapillary
STI 316SS/Titanium/Titanium 10P 10feetPVCCoatedCapillary
15P 15feetPVCCoatedCapillary
Field6: 20P 20feetPVCCoatedCapillary
Code Description 25P 25feetPVCCoatedCapillary
N Always 30P 30feetPVCCoatedCapillary
CCC CloseCoupledConnection(forEJA510/530)
Field7: LowerHousing(FlushingRing)
Code Description Field11:Attachment
0 None Code Description
S 316SS HGP HighsideGP
H HastelloyC-276 HDP HighsideD/P
M Monel DDP BothsidesD/P(requires2seals)
T TantalumPlated316SS LDP Low Side D/P
E Titanium DGP DirectGaugePressure(forEJA510/530)

Field12:Options
Code Description
/S ThreadedCapillaryConnections
/K Degreased(usew/InertfillforO2service)
/M MillCert.forwettedpartsmatl
/C Calibration/NISTCert.
/T Teflon(PTFE)lineddiaphragm
/SD Step-shapeddiaphragm

Size FlangeRating A B C D E F G
150# 5.9 4.74 0.77
0.625
2" 300# 3.62 2.32 0.89 0.79
6.5 5.0
600# 1.26 0.25
150# 7.48 6.0 0.94 0.79
0.625
3" 300# 5.0 3.5 1.14
8.27 6.63 0.91
600# 1.51 0.25
150# 9.06 7.5 0.94 0.79
0.625
4" 300# 10.04 7.87 6.22 3.5 1.26 0.91
600# 10.83 8.5 2.00 0.25 1.02

GS 33G6E22-01E
9

Extended Flanged Diaphragm Seals (ACS 9906)


[DMS Capable]

These are similar to the flanged diaphragm seals, but also provide an extended
barrel for insertion of the diaphragm into "jacketed" tanks. These have a standard
barrel diameter of 2.85" (3" 150#) and 3.7" (4" 150#). These seals can be direct
mounted to the EJA transmitters.
Field1:ProcessConnection Field8:
Code Description Code Description
FLX ExtendedFlange 0 Always
FXD ExtendedFlange-Direct
Field9:FillFluid
Field2:ConnectionSize Code Description
Code Description A SiliconeDC200
-30 3.0" B SiliconeDC704
-40 4.0" C Inert
Fill
(Halocarbon)
D Neobee
Field3:ConnectionRating E Glycerin(FXDonly)
Code Description G HighTemperatureFill(-4to750Deg.F)
1 ANSI 150# H LowTemperatureFill(-130to356Deg.F)
3 ANSI 300#
6 ANSI 600# Field10:CapillaryLength
Code Description
Field4:ExtensionLength 000 DirectMount
Code Description 05A 5feetArmouredCapillary
2 2.0"Extension(50mm) 10A 10feetArmouredCapillary
4 4.0"Extension(100mm) 15A 15feetArmouredCapillary
6 6.0"Extension(150mm) 20A 20feetArmouredCapillary
25A 25feetArmouredCapillary
Field5:Wetted,Extension/Diaphragm 30A 30feetArmouredCapillary
Code Description 05P 5feetPVCCoatedCapillary
SSS 316SS/316L 10P 10feetPVCCoatedCapillary
HHC AllHastelloyC-276 15P 15feetPVCCoatedCapillary
SHC 316SS/HastelloyC-276 20P 20feetPVCCoatedCapillary
MMM Monel/Monel 25P 25feetPVCCoatedCapillary
STA 316SS/Tantalum 30P 30feetPVCCoatedCapillary
STA 316SS/Tantalum CCC CloseCoupledConnection(forEJA510/530)

Field6: Field11:Attachment
Code Description Code Description
N Always HGP HighsideGP
HDP HighsideD/P
Field7: DDP BothsidesD/P(requires2seals)
Code Description LDP Low Side D/P
0 Always DGP DirectGaugePressure(forEJA510/530)

Field12:Options
Code Description
/S ThreadedCapillaryConnections
/K Degreased(usew/InertfillforO2service)
/M MillCert.forwettedpartsmatl
/C Calibration/NISTCert.

Size FlangeRating A B C D E F G L

150# 7.48 6.01 5.0 2.99 2.83 0.94 0.06


3" 2 4 6
300# 8.27 6.63 5.0 2.99 2.83 1.14 0.06
150# 9.06 7.5 6.22 3.7 3.5 0.94 0.06
4" 2 4 6
300# 10.04 7.87 6.22 3.7 3.5 1.26 0.06

GS 33G6E22-01E
10

Remote Flanged Diaphragm Seals (ACS 9901b)

Remote flanged seals use a 2.4" diaphragm and have a lower housing which acts as
a reducer to the process connection. This lower housing can also act as a flushing
ring. These seals utilize a filled capillary system and are not available for direct
mounting to transmitters.

Field1:ProcessConnection Field8:FlushingConnection
Code Description Code Description
FLR RemoteFlanged 0 None
FRD RemoteFlangeDirectMount 1 Single1/4"
2 Dual1/4
Field2:ConnectionSize
Code Description Field9:FillFluid
-05 0.5" Code Description
-10 1.0" A SiliconeDC200
-15 1.5" B SiliconeDC704
-20 2.0 C Inert
Fill(Halocarbon)
-30 3.0" D Neobee M20
-40 4.0" G HighTemperatureFill(-4to750Deg.F)
H LowTemperatureFill(-130to356Deg.F)
Field3:ConnectionRating
Code Description Field10:CapillaryLength
1 ANSI 150# Code Description
3 ANSI 300# 05A 5feetArmouredCapillary
6 ANSI 600# 10A 10feetArmouredCapillary
15A 15feetArmouredCapillary
Field4: 20A 20feetArmouredCapillary
Code Description 25A 25feetArmouredCapillary
N None 05P 5feetPVCCoatedCapillary
10P 10feetPVCCoatedCapillary
Field 5: Upper Housing/Diaphragm 15P 15feetPVCCoatedCapillary
Code Description 20P 20feetPVCCoatedCapillary
CSS CarbonSteel/316L 25P 25feetPVCCoatedCapillary
SSS 316SS/316L 30P 30feetPVCCoatedCapillary
SST 316SS/PTFElined316LSS CCC CloseCoupledConnection(forEJA510/530)
HHC AllHastelloyC-276
SHC 316SS/HastC-276 Field11:Attachment
STA 316SS/Tantalum Code Description
SMM 316SS/Monel400 HGP HighsideGP
STI 316SS/Titanium HDP HighsideD/P
DDP BothsidesD/P(requires2seals)
Field6: LDP Low Side D/P
Code Description DGP DirectGaugePressure(forEJA510/530)
N Always
Field12:Options
Field 7: Lower Housing Code Description
Code Description /S ThreadedCapillaryConnections
S 316SS /K Degreased(usew/InertfillforO2service)
H HastelloyC-276 /M MillCert.forwettedpartsmatl
M Monel /C Calibration/NISTCert.
T Tantalumlined316SS /T Teflon(PTFE)lineddiaphragm
E Titanium

G2 Process D D1 H G3
PressureRating
Connection
150# 4.25 1.66 4 x .5 13 UNC
1" 300# 3.74
4.88 1.79 4 x .5 11 UNC
600#
150# 5.00 4 x .5 13 UNC
1.7
1.5" 300# 3.74
6.12 4 x .75 10 UNC
600# 2.1
150# 6.00 1.85 -----
2" 300# 3.74 6.50 1.98 -----
600# 6.50 2.1 -----

GS 33G6E22-01E
11

Threaded Connection Diaphragm Seals (ACS9901a)

These are similar to the remote flange seals utilizing a 2.4" diaphragm; however,
the process connection is a Female NPT thread. These seals cannot be direct
mounted to transmitters.

Field1:ProcessConnection Field8:FlushingConnection
Code Description Code Description
THR ThreadedConnection 0 None
TRD ThreadedConnectionDirectMount 1 Single1/4"
2 Dual1/4"
Field2:ConnectionSize
Code Description Field9:FillFluid
- TA 1/2" Code Description
- TB 3/4" A SiliconeDC200
- TC 1" B SiliconeDC704
C Inert
Fill
Field3:ConnectionRating D Neobee M20
Code Description G HighTemperatureFill
T Threaded NPT - Female H LowTemperatureFill
M Threaded NPT - Male
Field10:CapillaryLength
Field4: Code Description
Code Description 05A 5feetArmouredCapillary
N Always 10A 10feetArmouredCapillary
15A 15feetArmouredCapillary
Field 5: Upper Housing/Diaphragm 20A 20feetArmouredCapillary
Code Description 25A 25feetArmouredCapillary
CSS CarbonSteel/316L 30A 30feetArmouredCapillary
SSS 316SS/316L 05P 5feetPVCCoatedCapillary
SST 316SS/PTFELined316L 10P 10feetPVCCoatedCapillary
HHC AllHastelloyC-276 15P 15feetPVCCoatedCapillary
SHC 316SS/HastelloyC-276 20P 20feetPVCCoatedCapillary
STA 316SS/Tantalum 25P 25feetPVCCoatedCapillary
SMM 316SS/Monel 30P 30feetPVCCoatedCapillary
TTI Titanium/Titanium CCC CloseCoupledConnection(forEJA510/530)

Field6: Field11:Attachment
Code Description Code Description
N Always HGP HighsideGP
HDP HighsideD/P
Field 7: Lower Housing DDP BothsidesD/P
Code Description LDP Low Side D/P
S 316SS DGP DirectGaugePressure(forEJA510/530)
H HastelloyC-276
M Monel Field12:Options
T Tantalumplate316SS Code Description
E Titanium /S ThreadedCapillaryConnections
/K Degreased(usew/InertfillforO2service)
/M MillCert.forwettedpartsmatl
/C Calibration/NISTCert.
/T Teflon(PTFE)lineddiaphragm

G2 Process
D D1 H
Connection
.5" 1.18 2.2
.75" 3.74 1.41 2.36
1" 1.77 3.46

GS 33G6E22-01E
12

Sanitary Diaphragm Seals (ACS 9908)


(DMS Capable)

Sanitary seals provide a connection that allows for quick disconnects from the
process for ease of cleaning and eliminates areas where bacterial growth can occur.
The sanitary In-line style seal provides a flow through diaphragm seal for gauge
pressure measurement. The In-line is the only member of the sanitary family
which cannot be direct mounted to the transmitters.
Field1:ProcessConnection Field6:
Code Description Code Description
STC SanitaryTriClamp N Always
CBI CherryBurrel I Line
CBQ CherryBurrel"Q"Line Field7: TankSpudSleeve
SNL SanitaryInLineTriClamp Code Description
TSP TankSpud(4"Only) 0 NOTankSpudSleeve(forAllothers)
ASP AsepticConnection 2 2 Ext. Tank Spud Sleeve (TSP & TSD Only)
APC APC Quick Connect 6 6 Ext. Tank Spud Sleeve (TSP & TSD Only)
GCH GC "H" Line
Field8:
STD SanitaryTriClampDirectMount Code Description
CID CherryBurrel I LineDirectMount 0 Always
CQD CherryBurrel"Q"LineDirectMount
TSD TankSpud(4"Only)DirectMount Field9:FillFluid
ASD AsepticConnectionDirectMount Code Description
APD APCQuickConnectDirectMount D Neobee M20
GHD GC"H"LineDirectMount E Glycerine(Directmountonly)
J DC200-350(FoodGrade)
Field2:ConnectionSize K VegetableOil
Code Description
- TB 3/4"(SanitaryIn-LineOnly) Field10:CapillaryLength
-TC 1"(SanitaryIn-LineOnly) Code Description
-TD 1.5"(SanitaryIn-LineOnly) 000 None-DirectMount
-TE 2"(SanitaryIn-LineOnly) 05A 5feetArmouredCapillary
-TF 3"(SanitaryIn-LineOnly) 10A 10feetArmouredCapillary
-TG 4"(SanitaryIn-LineOnly) 15A 15feetArmouredCapillary
-15 1.5" 20A 20feetArmouredCapillary
-20 2.0" 25A 25feetArmouredCapillary
-25 2.5" 30A 30feetArmouredCapillary
-30 3.0" CCC CloseCoupledConnection(forEJA510/530)
-40 4.0"
Field11:Attachment
Field3:ConnectionRating Code Description
Code Description HGP HighsideGP
S Sanitary HDP HighsideD/P
F Sanitary20RAFinish(electro-polish) DDP BothsidesD/P
L SanitaryIn-Line-20RAFinish LDP LowsideD/P
DGP DirectGaugePressure(forEJA510/530)
Field4:ExtensionLength
Code Description Field12:Options
N None Code Description
2 2.0"Extension(TSP&TSDonly) /S ThreadedCapillaryConnections
6 6.0"Extension(TSP&TSDonly) /M MillCert.forwettedpartsmatl
/C Calibration/NISTCert.
Field 5: Upper Housing/Diaphragm
Code Description
SSS 316SS/316L
HHC AllHastelloy(N/AonSanitaryIn-Line)

Size Weight A C D E

1.5" 1.33lbs 1.5 1.71 1.97 1.38


2" 1.67lbs 1.5 2.22 2.52 1.38
3" 2.00lbs 2.52 2.78 3.05 1.38

GS 33G6E22-01E
13

Low-Range Diaphragm Seals (ACS 9901b)

These seals are designed for applications requiring smaller measurement spans,
(< 150"w.c.). An expanded lower housing is used to accommodate a 3.6" diaphragm.
This lower housing also functions as the flushing ring when the appropriate flushing
connection is selected.
The seals are offered in remote, threaded, and/or direct mount configurations.

Field1:ProcessConnection Field8:FlushingConnection
Code Description Code Description
FBD Flanged-DirectMount 0 None
FBR RemoteFlange 1 Single1/4"
FBT RemoteFlange-Threaded 2 Dual1/4"
3 Single
1/2"
Field2:ConnectionSize 4 Dual1/2
Code Description
-TA 1/2" (FBD,FBT) Field9:FillFluid
-TB 3/4" (FBD,FBT) Code Description
-TC 1.0" (FBD,FBT) A SiliconeDC200
-TD 11/2"(FBD,FBT) B SiliconeDC704
-TE 2.0" (FBD,FBT) C Inert
Fill(Halocarbon)
-05 1/2" (FBD,FBR) D Neobee M20
-07 3/4" (FBD,FBR) E Glycerin(FBDonly)
-10 1.0" (FBD,FBR) G HighTemperatureFill(-4to750DegreesF)
-15 11/2" (FBD,FBR) H LowTemperatureFill(-130to356DegreesF)
-20 2.0" (FBD,FBR)
-30 3.0" (FBD,FBR) Field10:CapillaryLength
-40 4.0" (FBD,FBR) Code Description
000 DirectMount(FBDonly)
Field3:ConnectionRating 05A 5feetArmouredCapillary
Code Description 10A 10feetArmouredCapillary
T Threaded NPT Female 15A 15feetArmouredCapillary
M Threaded NPT Male 20A 20feetArmouredCapillary
1 ANSI 150# 25A 25feetArmouredCapillary
3 ANSI 300# 30A 30feetArmouredCapillary
6 ANSI 600# 05P 5feetPVCCoatedCapillary
10P 10feetPVCCoatedCapillary
Field4: 15P 15feetPVCCoatedCapillary
Code Description 20P 20feetPVCCoatedCapillary
N Always 25P 25feetPVCCoatedCapillary
30P 30feetPVCCoatedCapillary
Field5:UpperHousing/Diaphragm(wetted) CCC CloseCoupledConnection(forEJA510/530)
Code Description
SSS 316SS/316L Field11:Attachment
HHC AllHastelloyC-276 Code Description
SHC 316SS/HastelloyC-276 HGP HighsideGauge
STA 316SS/Tantalum HDP HighsideD/P
SMM 316SS/Monel DDP BothsidesD/P
STI 316SS/Titanium LDP Low Side D/P
DGP DirectGaugePressure(forEJA510/530)
Field6:
Code Description Field12:Options
N Always Code Description
/S ThreadedCapillaryConnections
Field7: LowerHousing(wetted) /K Degreased(usew/InertfillforO2service)
Code Description /M MillCert.forwettedpartsmatl
S 316SS /C Calibration/NISTCert.
H HastelloyC-276 /T Teflon(PTFE)lineddiaphragm
M Monel
T Tantalumlined316
E Titanium

G2 Process PressureRating D D1 H G3 Weight


Connection
150# 4.25 1.66 4 x .5" 13 UNC 4.4lbs
1" 300# 3.74
4.88 1.79 4 x .5" 11 UNC 8.5lbs
600#
150# 5.00 1.7 4 x .5" 13 UNC 6.9lbs
1.5" 300# 3.74 10.8lbs
6.12 2.1 4 x .75" 10 UNC
600# 11.5lbs

GS 33G6E22-01E
14

Flushing Rings

Flushing Rings, or calibration rings, are used when a process connection requires
cleaning without removal of the diaphragm seal. The standard flushing rings are
made from 316 Stainless Steel and come with single and dual 1/4" and 1/2" NPT
connections. These are selectable in the model configuration of most seals or
available as a separate item.

Flushing Rings
For Use with EJA210A and Remote Seals
Part Number Size Pressure Rating Flushing Connection
M1244CD-1 2 inch 150# to 2500# Single 1/4" NPT
M1244CD-2 2 inch 150# to 2500# Single 1/2" NPT
M1244CE-1 2 inch 150# to 2500# Dual 1/4" NPT
M1244CE-2 2 inch 150# to 2500# Dual 1/2" NPT
M1244CF-1 3 inch 150# to 2500# Single 1/4" NPT
M1244CF-2 3 inch 150# to 2500# Single 1/2" NPT
M1244CG-1 3 inch 150# to 2500# Dual 1/4" NPT
M1244CG-2 3 inch 150# to 2500# Dual 1/2" NPT

GS 33G6E22-01E
15

GS 33G6E22-01E
SG DMS
Copyright Jan. 1, 2002
1st Edition 5/23/02 1M