Вы находитесь на странице: 1из 12

Electric Power Systems Research 105 (2013) 3950

Contents lists available at ScienceDirect

Electric Power Systems Research


journal homepage: www.elsevier.com/locate/epsr

Transient analysis of low-voltage ride-through in three-phase


grid-connected converter with LCL lter using the nonlinear modal
series method
Wei Wang , Xikui Ma
State Key Laboratory of Electrical Insulation and Power Equipment, School of Electrical Engineering, Xian Jiaotong University, Xian 710049, China

a r t i c l e i n f o a b s t r a c t

Article history: From a theoretical perspective, this paper develops a systematic approach to analyze the transient charac-
Received 31 January 2013 teristics of the low-voltage ride-through (LVRT) in three-phase grid-connected converter with LCL lter
Received in revised form 5 July 2013 by using the nonlinear modal series method. Firstly, the mathematical model and the corresponding
Accepted 15 July 2013
second order modal series model of the system are described. And then, the simulation results and the
Available online 17 August 2013
theoretical analysis manifest that there are abundant modal interactions, particularly the stronger second
order modal interaction, in the LVRT transient process. The revised expressions considering the nonlin-
Keywords:
ear terms for the state variables are subsequently obtained. By selecting the appropriate parameters to
Transient analysis
Low-voltage ride-through (LVRT)
weaken second order modal interaction, we can effectively reduce the amplitude and the duration of the
Three-phase grid-connected converter oscillation to satisfy the requirements of the system tolerance during LVRT process. Additionally, the dom-
Nonlinear modal series method inant oscillation modes of each state variable are also studied. Finally, the second order quasi-resonance
Modal interaction. boundaries are dened to facilitate the selection of practical parameters for maintaining normal transient
behavior.
2013 Elsevier B.V. All rights reserved.

1. Introduction voltage and the grid current are much uctuated in comparison
with the normal operation state during voltage dip [12], which has
The three-phase power electronic converters with LCL lter an important effect on the transient stability and applications in
are now used in many renewable energy generation systems as a many areas of these power generations.
grid-connected interface (e.g., wind energy, solar etc.) [1,2]. Power For the issues of LVRT, the previous work is mainly focused
regeneration, adjustable power factor and signicantly less line on a suitable ride-through control method or an additional hard-
current harmonic distortion are the most important advantages of ware circuit to enhance the LVRT capability of the grid-connected
this converter with respect to other types of converters [3]. As the converter in the power generation system, which will allow the
scale of renewable energy generations becomes larger and larger operation of the renewable energy generation system to meet
nowadays [4,5], the huge penetration of these new power to the the requirement of the set of grid codes [1316]. Unfortunately,
grid has led the grid codes to require the low-voltage ride-through since power system faults are often characterized by a momentary
(LVRT) capability of the grid-connected converter in these gener- decrease in the RMS voltage magnitude [17], these works ignore
ation systems during the grid disturbances to avoid the shutdown the various transient phenomenon existing in the LVRT process and
phenomenon of large renewable energy generations [6,7]. As an does not further analyze the transient behavior of the LVRT which
example, a diagram of the LVRT requirements, in which wind tur- might be of a powerful impact on the grid and or even destroy the
bines should be still connected for voltage sags, is shown in Fig. 1 system circuit. The investigation into transient behavior allows an
[8,9]. Practically speaking, these renewable energy generation sys- essential understanding of the system dynamical operations and
tems has been faced with serious problems during the LVRT process may give some useful information for practical design and control
and the grid code requirements about LVRT present a signicant applications [18,19].
challenge to the well-established renewable energy technologies Recently, some works detailing the transient state of volt-
[10,11]. In the power system where the renewable energy gener- age sags on the grid-connected converter in the renewable
ation is of a major portion, the system variables such as the grid energy generation system have appeared, and the transient phe-
nomenon has been used to assess the oscillations at external
grid voltage sag [20]. For example, Muyeen et al. have carried
Corresponding author. Tel.: +86 13572243436. out extensive time-domain simulation analyses on the transient
E-mail addresses: weiwang.eec@gmail.com, 240216@163.com (W. Wang). behavior of wind turbine system considering both symmetrical and

0378-7796/$ see front matter 2013 Elsevier B.V. All rights reserved.
http://dx.doi.org/10.1016/j.epsr.2013.07.007
40 W. Wang, X. Ma / Electric Power Systems Research 105 (2013) 3950

Fig. 1. National grid codes.

unsymmetrical faults occurring at several locations to analyze the state variable and the appropriate formulations of the main state
LVRT characteristics of the system [21]. And the simulation waves variables are presented by selecting the stronger modal interaction.
of PV converter in LVRT process are also investigated in relative The relationship between the nonlinear modal interactions and the
literatures [22]. Although the traditional time-domain simulation system parameters are newly performed to assess the parameters
method can get some nonlinear transient information by observing impacts on the LVRT transient behavior. Subsequently, the domi-
the time-domain simulation phenomena, it is difcult to identify nant oscillation modal of the system state variables are also studied.
the nature of system oscillations, and the relationship between In order to avoid the occurrence of resonance, the second order
the interactive modes and the state variables, as well as system quasi-resonance boundaries are given in this subsection. Finally,
parameters and disturbances. Essentially, the existing works have Section 5 concludes the paper.
not dealt with the effects of nonlinear modal interactions on the
dynamic behavior of the grid-connected converter in LVRT process, 2. System modeling
and the consequent relationship between the system behavior and
the control strategies. Moreover, traditional modeling methods use 2.1. Description and mathematical model
a linear model and the validity of linear analysis method such as
RouthHurwitz stability criterion is restricted to a small neighbor- The grid-connected converter is commonly based on a voltage
hood of the operating point which is not suitable to the case of large source inverter (VSI) connected to the supply network [25]. These
disturbance [23], so that the mechanism of LVRT transient behav- converters are always used to maintain a constant DC-link voltage
ior can not be accurately revealed. Therefore, an analysis of LVRT and to control the power factor of the generation system. The DC-
transient behavior for the grid-connected converter with LCL lter link is created by a capacitor which isolates the operation of the
in renewable energy generation system is absent from a theoretical grid-connected converter from renewable energy sources, so that
perspective. the control and the operation of the converter allow being indi-
In this paper, the nonlinear modal series method, by which vidual. In practice, the renewable energy generation system only
the linear system theory concepts can be extended to facilitate needs to take countermeasures for the grid-connected converter
the understanding and analysis of nonlinear system [24] through and the DC-link in the case of LVRT process which will not affect
considering the nonlinear high-order polynomial in high-order the normal operations of the renewable energy source. In order to
modes space, is used to investigate the LVRT transient dynamic deeply investigate the transient behavior, these generation systems
characteristics of the grid-connected converter with LCL lter should be simplied. Here, the equivalent circuit of the system is
during voltage sag so as to transfer the transient characteristics shown in Fig. 2. In this paper, a grid-connected interface system
research from the qualitative analysis to the quantitative analy- constituted by a three-phase converter with LCL lter as a research
sis. The intrinsic mechanism of the way by which the nonlinear model will be discussed.
modal interaction affects the LVRT transient behavior is revealed, In most of these studies, the power source of the system is
and more appropriate functions for representing system behav- considered as a DC voltage source [26]. However, this equivalent
ior can be obtained. Based on the relationship between the modal treatment is not adaptable to the control principles of the grid-
interaction and the parameters, the oscillation amplitude and dura- connected converter in the renewable energy generation system
tion of the state variable during LVRT transient process can be such as PMSG-type wind turbine. In addition, the input current of
reduced to satisfy the requirements of the system tolerance by the converter is not predictable. In order to establish a reasonably
adjusting certain of the parameters. Furthermore, the second order alternative model, the basic principles of a simplied treatment
quasi-resonance boundaries with regard to some key parameters should ensure that both the voltage and the current characteristics
are analyzed, in order to facilitate the optimal design of the grid- of the simplied model are as same as the prototype, and the con-
connected converter with LCL lter. trol method of the grid-connected converter remains unchanged.
This paper is organized as follows. In Section 2, the mathe- Based on these preconditions, a controlled current source is used
matical model of a interface system constituted by grid-connected to replace the renewable energy source and its related power
converter with LCL lter and its control scheme are developed. In
Section 3, the second order modal approximate solution of the sys-
tem is established by using the nonlinear modal series method. In
Section 4, more nonlinear modes are found using the second order
modal method, and the simulation is also carried out to illustrate
the efciency of the nonlinear modal series method in the analy-
sis of the LVRT transient behavior. Then, a quantitative measure is
used to nd out the dominant nonlinear interactive modes for the Fig. 2. Equivalent circuit of grid-connected renewable energy generation system.
W. Wang, X. Ma / Electric Power Systems Research 105 (2013) 3950 41

Fig. 3. The grid-connected interface in the equivalent circuit.

electronic devices. The current of the controlled current source is control scheme requires the measurements of the DC-link voltage,
determined by the system power and the voltage of the DC-link. the grid voltage and the grid current. The converter is controlled in
And the control method of the DC-link voltage is the same as the the grid voltage oriented reference frame, with its d-axis oriented
original renewable energy generation system. As a result, the grid- along the grid voltage vector position [27].
connected interface in the equivalent circuit is shown in Fig. 3, and Since the treatment of controller input is carried out by per unit,
here iccs = Pt /uDC . the reference value of the per unit and the transformation rela-
Here, let the direction of the current owing into the grid be tionships between the actual value and the per unit are given by
positive. Under a dq reference frame rotating at grid speed, the dif-
ferential equations for the grid-connected converter with LCL lter
2SB
can be written as IB dq = (7)
3UB
di1d R1 1 1
= i1d + i1q + u u (1)
dt L1 L1 d L1 0d Id/q Id/q
Id/q = = (8)
IB dq 2S
B
di1q R1 1 1 3UB
= i1d i1q + uq u0q (2)
dt L1 L1 L1
where SB , UB , and IB dq are the base value of the system power, the
grid voltage and the grid current, respectively. Id/q and I*d/q are the
di2d R2 1 1
= i2d + i2q + u u (3) nominal value and per unit of d-axis and q-axis current under dq
dt L2 L2 0d L2 sd
reference frame, respectively.
Usually, the feed-forward compensation does not affect the
di2q R2 1 1
= i2d i2q + u0q usq (4) accuracy of the system. On account of this fact, we use the PI
dt L2 L2 L2
controller only and ignore the feed-forward compensation in the
inner current control loop for converter control. Accordingly, the
du0d R1 RC 1 R2 RC 1 1 1
= ( + )i1d + ( )i2d RC ( + )u differential equations regarding the control of the converter are
dt L1 C L2 C L1 L2 0d expressed as follows:
RC RC
+ u0q + u + u (5) dud 1 di2dref 3UB di2d 3UB
L1 d L2 sd = (K2p K2p + K2i (i2dref i2d ))
dt 0.67uDC dt 2SB dt 2SB
(9)
du0q R1 RC 1 R2 RC 1
= ( + )i1q + ( )i2q u0d
dt L1 C L2 C

1 1 RC RC duq 1 3UB di2q 3UB
RC ( + )u0q + uq + usq (6) = (K2p + K2i (i2qref i2q )) (10)
L1 L2 L1 L2 dt 0.67uDC 2SB dt 2SB
where iL1 = i1d + ji1q , iL2 = i2d + ji2q are the L1 and L2 current vectors,
di2dref duDC
respectively; uo = uod + juoq is the voltage vectors of capacitor C; R1 , = K1p + K1i (uDCref uDC ) (11)
R2 and RC are the resistance of L1 , L2 and C, respectively; is the dt dt
grid voltage angular frequency. where u = ud + juq is the converter output voltage vector;
The generic control scheme of the grid-connected converter in i2 = i2d + ji2q and i2ref = i2dref + ji2qref are the grid current vector and
renewable energy generation system is illustrated in Fig. 4. The its reference, respectively; uDC is the DC-link voltage; K1p and K1i

Fig. 4. Control scheme of the grid-connected converter.


42 W. Wang, X. Ma / Electric Power Systems Research 105 (2013) 3950

are the proportional gain and the integral gain of the DC-link con- variables yields:
troller, respectively; K2p and K2i are the proportional gain and the
integral gain of the grid current controller, respectively.
The equation describing the energy balance of the DC-link
capacitor can be written as
J11 J12 0 0 J15 0 J17 0 0 0
duDC
= Po Pt = 1.5(ud i1d + uq i1q ) Pt
CDC uDC (12) J21 J22 0 0 0 J26 0 J28 0 0
dt

0 0 J33 J34 J35 0 0 0 0 0
where Po and Pt are the power supplied to the grid and generated
by the renewable energy source, respectively. 0 0 J43 J44 0 J46 0 0 0 0

Noting Eq. (12), then, Eqs. (911) can be rewritten as
J51 0 J53 0 J55 J56 J57 0 0 0
X =

X

dud 2.25K1p K2p i1d ud 2.25K1p K2p i1q uq
= 0 J62 0 J64 J65 J66 0 J68 0 0
dt CDC u2DC CDC u2DC

J71 J72 J73 J74 J75 0 J77 J78 J79 J710
3UB R2 K2p 3UB L2 K2i i2d 3UB K2p i2q
+ 0 0 J83 J84 0 J86 0 0 0 J810
u 0.67 2SB uDC
0.67 2SB L2 DC
J91 J92 0 0 0 0 J97 J98 0 J910
3UB K2p u0d K i2dref K1p K2p Pt 1
+ 2i + J101 J102 0 0 0 0 J107 J108 0 J1010
0.67 2SB L2 uDC 0.67 uDC 0.67CDC u2

DC

0
K1i K2p uDCref 1 3UB K2p usd 1 K1i K2p
+ + (13) 0
0.67 uDC 0.67 2SB L2 uDC 0.67
0

0

2
3UB K2p 2 3U L K
3UB R2 K2p 0
1
duq i2d B 2 2i i2q
= + + 0 + (17)
dt 0.67 2SB DCu 0.67 2SB L2 uDC 2
X T H7 X
2 2 u
3UB K2p u0q 3UB K2p sq 1 K2i i2qref 1 T
+ + (14) X H8 X
0.67 2SB L2 uDC 0.67 2SB L2 uDC 0.67 uDC
T
X H9 X
di2dref 1.5K1p i1d ud 1.5K1p i1q uq K1p Pt 1 X T H10 X
= + K1i uDC
dt CDC uDC CDC uDC CDC uDC
+ K1i uDCref (15)

where X belongs to the convergence domain of the Taylor series


From Eq. (1) to Eq. (15), we can obtain a set of differential equa- v RN , the coefcient matrix of X is the Jacobian matrix which rep-
tions to present the model of the grid-connected converter with resents the linear part of the vector eld and equals [fi /X]X=X0 , J
LCL lter, rewritten in a compact form as are the nonzero elements of the Jacobian matrix, Hi is the Hessian
Matrix for the state variable xi , where i = 7, 8, 9, 10.
X = f (X) (16) In order to get the standard form of the nonlinear modal series
processing method, denote the (complex) Jordan form of A by  and
where X = [i1d , i1q , i2d , i2q , uod , uoq , ud , uq , i2dref , uDC ]T is the vectors the matrices of the right and left eigenvectors by U and V, respec-
containing the system state variables, and F : RN RN is a smooth tively. Then, using the transformation X = UY yields the following
vector eld. equivalent system for (17)

2.2. Nonlinear modal series

As a powerful tool, nonlinear modal series theory can yield a



1
good deal of theoretical perspective into the dynamic analysis of
nonlinear systems. Particularly, the method of solution has the 2

great conceptual advantage of presenting a nonlinear system as
3
a rather straightforward generalization of the linear case, although
4
it may be much more involved [24]. The basic idea of modal series
approach is that a Taylor-series expansion is made for the nonlin-
5
ear system dynamics equations around a stable operating point. Y =

Y

The order of the series expansion is closely related to the nature 6

of the nonlinearities in the original dynamical system. As a result,
this method provides a closed-form approximate solution to the 7

differential equation, as well as the resonance condition. 8

Suppose f is a continuous and expansible function, and the order
of the system (16) is N. Expanding (16) as a Taylor-series around 9
a stable equilibrium point X0 and using again X as the new state 10
W. Wang, X. Ma / Electric Power Systems Research 105 (2013) 3950 43

Table 1
0
System parameters used in simulations.
0

0 Parameters Descriptions Values

0 R1 , L1 Inverter-side resistance and inductance of 0.004 , 1.6 mH
the LCL lter
0
1 R2 , L2 Grid-side resistance and inductance of the 0.004 , 1.6 mH
+ V 0 + (18) LCL lter
2
Y T U T H7 UY RC , C Resistance and capacitance of the LCL lter 1 , 0.05 mF
Pt Total input power of the system 100 kW
T T CDC DC-link capacitance 1.5 mF
Y U H8 UY
us Grid phase-phase voltage 480 V
T T Grid angular frequency 314 rad/s
Y U H9 UY uDCref DC-link voltage reference 900 V
i2qref Q-component reference of the grid-side 0A
Y T U T H10 UY
inductor current
K1p , 1i PI controller parameters of voltage control 0.01, 0.0033
loop
fswitch Switching frequency of the inverter 10 kHz
From the above analysis, the equivalent set of the system Eq.
(18) can be rewritten as

10
According to xi (t) = uij yj (t), the second order approximate

10 
10
j=1
i
y i = i yi + Cpq yp yq + (19) response becomes:
p=1 q=1 10 10

10 
xi (t) = uij yj0 j
h2kl yk0 yl0 ej t


10 j=1 k=1 l=1 R 
(k,l,j)/
where, y i is the i-th element of Y , Cpq
i = 1
vTik [U T Hk U]. 10 10
2

10 
h2kl j yk0 yl0 e(k +l )t
k=7
+ uij
Considering the initial condition Y0 = [y10 , y20 , ,
y100 ]T , the solution of Eq. (19) can be decomposed into j=1 k=1 l=1 R 
(k,l,j)/
yj (t) = y1j (t)+ y2j (t) + y3j (t) + in the McLaughlin expansion domain 10 10

10

of convergence. Here, ymj (t) contains the terms that depend on + uij Ckl j yk0 yl0 tej t (22)
any m-states multiples of initial conditions. If the system state
j=1 k=1 l=1 (k,l,j) R
variables are considered as a signal, we can recognize that the
signal is constituted by a number of basic signals. From the Eq. Ckl j
where h2kl j = k +l j
, j, k, l = 1, 2, , 10.
(19), then we can get
 10
The term uij yj0 ej t in the second order approximate response
y 1j = j y1j j=1
is the general expression of linear modal analysis. Therefore, the

10 
10
second modal series method, which gives an explicit correction
y 2j = j y2j + Ckl j y1k y1l (20) term to the linear approximate solution, provides a more accurate
k=1 l=1 approximation of the system than the linear modal method.
..
.
3. Transient phenomena

In this section, we will present a series of simulations to study


Eq. (20) can be solved by one and two dimensions Laplace trans-
the LVRT transient behavior of the grid-connected converter with
form. Neglecting y3j (t) and the other higher order terms, the inverse
LCL lter. All the components of the simulation model are built with
Laplace transform of yj can then be written [24]:
the standard electrical component blocks from the SimPowerSys-
tems block set in Matlab/Simulink library. The parameters used in
the simulation are given in Table 1.

10 
10
The transient dynamic response of the system output current,
yj (t) = y1j (t) + y2j (t) = yj0 ei t + Ckl j yk0 yl0 Skl j (t) = yj0 ei t
the control system reference current and the DC-link voltage are
k=1 l=1 essential for assessing the operation of the system in LVRT pro-
10 10
 e(k +l )t ej t
cess. The results of both the second order modal and the linear
j modal approximation simulations, compared to the original non-
+ Ckl yk0 yl0
k + l j linear time-domain simulation results of the system ride-through
k=1 l=1 R 
(k,l,j)/
10 10 process when an event of three-phase voltage sags to 75% of the
 transmission grid voltage occurred in 0.2 s and ended in 0.7 s, are
+ Ckl j yk0 yl0 tej t (21) shown in Fig. 5. The results show that the modal series method
k=1 l=1 (k,l,j) R can manifest the system behavior more accurately and capture
the dynamic response characteristics more effectively compared
with the linear modal method, especially for the transient process.
where j = 1, 2, , 10. The set R cause the second order resonance Therefore, these simulation results demonstrate that the nonlinear
condition, i.e., satises the condition k + l = j . modal series method is appropriate for transient behavior analysis.
44 W. Wang, X. Ma / Electric Power Systems Research 105 (2013) 3950

Fig. 5. Second order modal series, linear and nonlinear simulation results: (a) Waveform of phase A of L2 current i2a ; (b) waveform of d-component of L2 reference Current
i2dref ; (c) waveform of DC-link voltage uDC .

4. Transient characteristics analysis of the grid-connected converter and the DC-link voltage, 1 ,2 and
3 ,4 have a high frequency, 7 ,8 and 9 ,10 have a high damping
In the foregoing section, we have observed that the second order ratio, and 5 ,6 have a low degree of participation for the corre-
modal response has maintained the transient operation trend of the sponding state variables. For ud and uq , the modes corresponding
system state variables in the nonlinear time domain simulation. to the state variables are signicantly increased in their own par-
In this section, we will give a formal theoretical analysis for the ticipation and the damping ratio are increased at the same time
transient phenomena. which determines the decay rate of the oscillation amplitude and
the attenuation characteristics. For uod and uoq , the damping ratio
4.1. Eigenvalue analysis is decreased.
In power systems, the analysis and design of the system usu-
Using the Jacobian matrix derived in Section 2, the eigenvalues ally follows from a linear systems analysis under neglecting the
of the system can be calculated by the standard method. In the sys- possible nonlinear interaction between modes. In fact, a disturb-
tem LVRT process, both the voltage dip and voltage recovery states ance can excite numerous oscillation modes in the system LVRT
have 10 eigenvalues that belong to oscillatory modes. The com- transient process, only a few of these modes are of primary inter-
plete system modes are listed in Table 2 during voltage dip and est to the system designer. The system modes distribution of
Table 3 during voltage recovery, respectively. It can be clearly seen both the linear method and the nonlinear second order modal
that the system eventually operates at a stable state in the whole series method in voltage dip state and voltage recovery state are
LVRT process. In Tables 2 and 3, 9 ,10 are related to PI controllers shown in Fig. 6 below, respectively. Since the modes distribution is

Table 2
Basic modes analysis during voltage dip.

State variables Participation factor Eigenvalue/103 Frequency/kHz Damping ratio/%

i1d , i1q 0.1265, 0.1253 0.5998 5.2795i 0.8403 0.11288


i2d , i2q 0.1253, 0.0404 0.5973 4.6515i 0.7403 0.12736
uod , uoq 0.000224, 0.0001 0.0602 0.3635i 0.05785 0.16339
ud , uq 0.4326, 0.0170 0.0285 0.0559i 0.008897 0.45421
i2dref , uDC 0.5311, 0.0301 0.0040 0.0002i 0.000032 0.99875
W. Wang, X. Ma / Electric Power Systems Research 105 (2013) 3950 45

Table 3
Basic modes analysis during voltage recovery.

State variables Participation factor Eigenvalue/103 Frequency/kHz Damping ratio/%

i1d , i1q 0.1270, 0.1248 0.5995 5.2804i 0.8404 0.11281


i2d , i2q 0.1247, 0.1270 0.5976 4.6526i 0.7405 0.12740
uod , uoq 0.000473, 0.000039 0.0347 0.3872i 0.06162 0.08926
ud , uq 0.5021, 0.6069 0.0473 0.0469i 0.007464 0.71010
i2dref , uDC 0.5248, 0.0269 0.0040 0.0002i 0.000032 0.99875

Fig. 6. (a) Linear modes distribution and second order modes distribution during grid voltage dip; (b) Linear modes distribution and second order modes distribution during
grid voltage recovery.

conjugate-symmetric, a zoom-in sub-gure for half parts of the dis- simulation illustrate that the nonlinear system response contains
tribution space is added to show the difference between the linear a number of nonlinear interactive modes compared with the lin-
method and the nonlinear second order modal series method in ear modal simulation. In the nonlinear system response, except for
more detail. It is clear that the modes in the modal series method the foregoing 10 detectable eigenvalues from linear model, much
are much more than in the linear method, as well as the distribu- more interaction modes, like i,j = i + j , also exist. Some of the
tion range is wider than in the linear method. According to Eq. (22), results are shown in Figs. 7 and 8. Based on the modal interac-
the coupling degree of the system will increase due to system has tion indicator I2ikl , these gures show the effects of k,l on the state
a large number interactive mode. Moreover, we can nd out that variables. Where k=5,6,7,8, l=9,10 and k=9,10, l=5,6,7,8 are the dominant
some modes of the system move to the imaginary axis and the oscil- nonlinear interactive modes for the state variable i2d , k=7,8, l=9,10
lation frequency increases in the LVRT process. Therefore, power and k=9,10, l=7,8 the dominant nonlinear interactive modes for the
systems exhibit a complicated dynamic behavior when subjected state variable i2q , i2dref and uDC . The dominant nonlinear interac-
to disturbances, and a linear theoretical analysis of this behavior is tive modes will play a major role in the system transient behavior
not feasible in the grid-connected converter with LCL lter. of the process. According to the denition of I2ikl , the amplitude
and the duration of the transient behavior will be lager and longer
4.2. Nonlinear interaction between two modals when the indicator value of these dominant nonlinear interactive
modes is greater. Here, k=5,6,7,8, l=9 and k=9, l=5,6,7,8 are correspon-
Using Eq. (22), the second order modal time response term dence to the interaction between the AC circuit and the control

10
j
system, k=5,6,7,8, l=10 and k=10, l=5,6,7,8 to the interaction between
uij h2kl yk0 yl0 e(k +l )t is determined by two parameters of the
j=1

10
j
absolute value of the constant uij h2kl yk0 yl0 and the time con-
j=1
stant  kl = 1/real(k + l ). Therefore, I2ikl is dened as an indicator
for the effects of the modal interaction in the time response to cap-
ture both the amplitude and the duration effects of the interactive
modes [24] and expressed as
 10 
 
 
 uij h2kl yk0 yl0 
j
 
 j=1 
I2ikl =   (23)
 real(k + l ) 
 
 
 
It can be seen from the established equation that indicators
can quantify the strength of each modal interaction and provides
Fig. 7. Effects of modal interaction on the d-component of the L2 current i2d , the
a convenient for investigating the dominant nonlinear interactive q-component of the L2 current i2q , the d-component of the L2 reference current i2dref
modes. In addition, the results of the second order modal series and the DC-Link voltage uDC during grid voltage dip.
46 W. Wang, X. Ma / Electric Power Systems Research 105 (2013) 3950

grid-side inductance L2 become larger, respectively. Also shown


in Fig. 10(ad) are the plots of the modal interaction indices vari-
ation of the system state variable in voltage recovery period. It
can be seen from Figs. 9(a and b) and 10(a and b) that the modal
interaction decreases as C and CDC increases. The increases of L1
and L2 result in an increase in the modal interaction as shown in
Figs. 9(c and d) and 10(c and d).
Additionally, it can be observed that the system modal interac-
tions differ greatly in their sensitivities to different parameters and
different operating period. The system parameters CDC , L1 and L2
have the stronger effects on the modal interactions in voltage recov-
ery period, but the effect of C is very little. This observation implies
that the system will get a steady state as quickly as possible by
adjusting the parameters CDC , L1 and L2 . Moreover, the interaction
sensitivities of parameters are also changed in the LVRT process.
In summary, some practical results can be reached for the non-
Fig. 8. Effects of modal interaction on the d-component of the L2 current i2d , the linear modal interactions:
q-component of the L2 current i2q , the d-component of the L2 reference current i2dref
and the DC-Link voltage uDC during grid voltage recovery.
1) Decreasing L1 and L2 or increasing C and CDC is a feasible method
to reduce the modal interaction. For transient process of specic
the AC circuit and the DC-link. These stronger modal interactions state variables, we should consider the modal interactions in
enhance the coupling degree of the system which will lead to the detail.
analysis of system transient process more difcult and therefore, 2) Ignoring the feeble effect of parameter C, it will be able to quickly
the nonlinear modal interaction between the DC side and AC side increase or decrease the modal interaction by adjusting the
of the system, as well as the main circuit and control system, makes parameters CDC , L1 and L2 during voltage recovery.
the system LVRT transient dynamic behavior complicated. In addi- 3) Opposite the voltage dip period, we should increase the regu-
tion, two period analysis of the entire process also shows that the lated degree of the parameters L1 and L2 which helps the system
modal interaction between the grid current and the DC-link voltage to achieve convergence in voltage recovery period.
are weakened when the grid voltage turning to recovery.
Since most of the modal interactions are not particularly evi- 4.3. Dominant oscillation mode
dent in engineering practice, we can get the approximate describing
function by selecting the main modal of interaction which is suit- The dominant oscillation mode is of the greatest impact on both
able for the main state variable. Here, we give the expression of the the system dynamics and the stability of oscillation modal. In lin-
main state variables of the system as ear theory, the stability of the system is independently dominated

10

10 

10 10 
n

j t j j t by every single modal, the response xi (t) = uij yj0 ej t (i = 1, 2,


xi=3 (t) = uij yj0 e uij h2kl yk0 yl0 e
j=1
j=1 j=1 k=1 l=1
 , n) manifests the effects of each modes for the state variable xi ,

10 
8

10 uij uj0  the maximum amplitude of the jth mode at the zero-time,
+ uij h2kl j yk0 yl0 e(k +l )t and Tj = 1/real(j ) the attenuation
 speed of the mode. So the jth
j=1 k=5 l=9 mode, which is of max(uij  /real(j )), is called the dominant oscil-
lation mode due to its biggest inuence on the system dynamics and

10 
10

8
stability. However, the dominant oscillation mode in nonlinear sys-
+ uij h2kl j yk0 yl0 e(k +l )t (24) tem may be different from that in linear system since the nonlinear
j=1 k=9 l=5 oscillation mode is related not only to the fundamental modes, but
also the nonlinear interaction between the modals. Since the loca-

10
 
10 10 10 tion, the type and the duration of the disturbance may be different,
xi=4,9,10 (t) = uij yj0 ej t uij h2kl j yk0 yl0 ej t the motivation level of each oscillation modal will also be different.
j=1 j=1 k=1 l=1
The corresponding strongest incentive and nonlinear interaction
modal is the dominant oscillation mode. Developing the denition

10 
8

10 of the linear dominant oscillation mode into the nonlinear system
+ uij h2kl j yk0 yl0 e(k +l )t analysis theory, the indices of the dominant modal considered in
j=1 k=7 l=9 the nonlinear modal interaction would be dened by analyzing the
second-order analytical solution of the system response. Therefore,

10 
10

8
according to Eq. (22), I(j) is dened as a measure for the response of
+ uij h2kl j yk0 yl0 e(k +l )t (25)
the jth mode and the interaction between the jth mode and other
j=1 k=9 l=7 modes, and we obtain
 
It has been stated in the preceding discussion that the LVRT  maxuji h2j yk0 yl0 maxuji Ckl yk0 yl0 maxuji h2kl yk0 yl0 
j j
 k,l kl
I(j) =  
k,l k,l
transient characteristics is mainly related to the modal interac- +2e1 +
real(j ) real(j ) real(i + j ) 
tions. From a practical standpoint, it is necessary to acquire a  
better understanding of the relation between the modal interac- (27)
tion and the system parameters to make transient process shorter.
Fig. 9(ad) shows the modal interaction indices variation of the
system state variable during voltage dip when DC-link capaci- The maximum modulus value of I(j) indicates that j has the
tance CDC , lter capacitance C, inverter-side inductance L1 and strongest nonlinear interaction, the corresponding modal will be
W. Wang, X. Ma / Electric Power Systems Research 105 (2013) 3950 47

Fig. 9. Nonlinear interaction variation during voltage dip: (a) The CDC increasing from 1300 F to 2000 F; (b) The C increasing from 45 F to 59 F; (c) The L1 increasing
from 1300 H to 2000 H; (d) The L2 increasing from 1300 H to 2000 H.

Fig. 10. Nonlinear interaction variation during voltage recovery: (a) The CDC increasing from 1300 F to 2000 F; (b) The C increasing from 45 F to 59 F; (c) The L1 increasing
from 1300 H to 2000 H; (d) The L2 increasing from 1300 H to 2000 H.
48 W. Wang, X. Ma / Electric Power Systems Research 105 (2013) 3950

Fig. 11. Dominant oscillation mode of each state variable.

considered as the dominant oscillation mode. This quantitative oscillation modes are signicantly weakened, especially for the
approach makes the discrimination of dominant oscillation mode i2dref , and uDC .
easier.
We use the index I(j) to denote the jth oscillation mode of each
state variable in the time response and plot it in three-dimensional 4.4. Second order quasi-resonance boundary
coordinates. Since the system experiences a voltage sag and recov-
ery period in the process of LVRT, there may be a certain change for Eq. (22) represents the second order resonance responses
dominant oscillation mode and also the signicance correspond- of the system model in domain R . When the term
ing to the state variables. As shown in Fig. 11(a and b), X and Y 
n 
n

n
coordinates are used to denote the eigenvalue and the state vari- uij Ckl j yk0 yl0 tej t is added to the linear modal approx-
able, and Z is used to show I(j), respectively. It is clearly seen that j=1 k=1 l=1
the effects of 5 and 6 are the dominant oscillation mode for the imate solution, it will increase both the amplitude and the
state variables i1d , i1q , i2d and i2q in the whole process. For uod and duration of the nonlinear simulation result with respect to
uoq , the corresponding mode 7 is the dominant oscillation mode the nonlinear modal simulation in which resonances have not
during voltage dip and 10 is the dominant oscillation mode dur- occur. Therefore, it is often possible that the system resonance
ing voltage recovery. 7 is also relevant to the dominant oscillation occurs when the relation k + l = j is satised. Lets call the
mode for ud , uq , i2dref and uDC in the whole LVRT process. In addi- requirement |k + l j | |j | the condition of the second order
tion, we nd out that the conspicuousness of the system dominant quasi-resonance and denote the set of all three tuples (k, l, j) by
oscillation mode has changed throughout the process. The signif- R . Here, the coefcient must be a much smaller constant. This
icance of the dominant oscillation mode of the state variables i1d , quasi-resonance will produce an exponentially decaying sinusoid
i1q , i2d and i2q is enhanced obviously, and some other dominant signal with a frequency of inter-area oscillation.

Fig. 12. Normal transient phenomenon: (a) waveform of phase A of the L2 current i2a ; (b) waveform of d-component of the L2 reference current i2dref ; (c) waveform of the
DC-link voltage uDC . The second order resonance transient phenomenon; (d) waveform of phase A of the L2 current i2a ; (e) waveform of d-component of the L2 reference
current i2dref ; (f) waveform of the DC-link voltage uDC .
W. Wang, X. Ma / Electric Power Systems Research 105 (2013) 3950 49

Fig. 13. Second order quasi-resonance boundary in the parameter space of K2p versus  i : (a) DC-link capacitance CDC ; (b) capacitance of LCL lter C; (c) inverter-side inductance
L1 ; (d) gird-side inductance L2 .

Fig. 12(ac) shows the time-domain simulation waveforms of L2 parameters are located in the normal operation region. Otherwise,
current of phase A i2a , d-component reference of the current i2dref if the parameters cross the boundary and enter into the second
in L2 , and the DC-link voltage uDC when the control parameters are order resonance region, both the amplitude and the duration of
set to K2p = 0.5 and i = 0.15. The duration of the transient process transient process will persist larger and longer due to the resonance
is seen to be very short, and the overshoot relatively small. But occurring. Therefore, the selection of the control parameters should
when the control parameter is above a critical value, the resonance be always located in the normal operation region so that each state
behaviors occur in transient process. Fig. 12(df) shows the corre- variable will quickly convergence due to avoiding the occurrence of
sponding time-domain waveforms resulting from a step increase second order resonance in the LVRT process. Additionally, the val-
of 2 in K2p . It is shown that the transient responses of i2a , i2dref and ues of L1 and L2 cannot be made too small since these two second
uDC are no longer vanished quickly and the amplitude of the tran- order quasi-resonance boundary of the parameters will intersect
sient response is much bigger. The preceding analysis about the so that there is only the resonance region.
essence of such behavior is expounded from a second order reso-
nance perspective, and the simulated transient phenomenons also 5. Conclusion
match the earlier resonance analysis. The simulation results illus-
trate that the second order resonance has a great inuence on the This paper studies the LVRT transient behavior of a grid-
transient process. connected converter with LCL-lter using nonlinear modal series
Usually, we always want the system to operate in a fast tran- method so as to transfer the transient characteristics research from
sient over-process and restrain resonance. Hence, how to dene the qualitative analysis to quantitative analysis. The obtained sim-
the boundary of the second order resonance is the principal focus ulation results indicate that the nonlinear modal series method
of our study to avoid resonance in practical applications. From the can manifest the system behavior more accurately and capture
previous analysis, we consider that the system resonance occurs the dynamic response characteristics more effectively. It have been
when the parameters match the condition |k + l j |0.0005|j |. shown that except for the fundamental modes, the LVRT transient
Therefore, the system quasi-resonance boundaries corresponding behavior of the system is signicantly inuenced by the inter-
to resonance are given to delineate the scope of the practical param- active modes, particularly by the stronger second order modal
eter value for ensuring system operation in the normal state. These interaction which will make higher coupling degree and exacerbate
boundaries can be readily obtained by using the analytical means transient behavior. Subsequently, the more appropriate functions
described above. Fig. 13 laid out the system parameters boundaries which include the higher order nonlinear terms can be obtained
in the parameter space of K2p ,  2i , and clearly illustrates the effect of by selecting the more strong interactive modes. On the other hand,
the main system parameters on the second order quasi-resonance the results also indicate that the oscillation amplitude and duration
in the space of K2p  i . In Fig. 13, the boundaries divide the param- of the LVRT transient process can be reduced by adjusting certain
eter space into three parts in which one is the normal operation of the parameters so as to weaken the second order modal inter-
region and other two are the second order resonance regions. action. Additionally, the dominant oscillation mode of the system
The system works in the stable operation when the controller is changed in the LVRT process. Finally, the relationships between
50 W. Wang, X. Ma / Electric Power Systems Research 105 (2013) 3950

the second order quasi-resonance boundary and the parameters [13] M. Abbes, J. Belhadj, New control method of a robust NPC converter for renew-
are given, which can be used to perform the analysis of resonance able energy sources grid connection, Electric Power Systems Research 88
(2012) 5263.
and to design the controllers for the grid-connected converter. [14] I.D. Margaris, A.D. Hansen, P. Srensen, N.D. Hatziargyriou, Dynamic security
issues in autonomous power systems with increasing wind power penetration,
Electric Power Systems Research 81 (2011) 880887.
References [15] J.F. Conroy, R. Watson, Low-voltage ride-through of a full converter wind tur-
bine with permanent magnet generator, IET Renewable Power Generation 1
[1] M. Liserre, R. Teodorescu, F. Blaabjerg, Stability of photovoltaic and wind tur- (2007) 182189.
bine grid-connected inverters for a large set of grid impedance values, IEEE [16] C. Saniter, J. Janning, Test bench for grid code simulations for multi-MW wind
Transactions on Power Electronics 21 (2006) 263272. turbines, design and control, IEEE Transactions on Power Electronics 23 (2008)
[2] Y.M. Chen, Y.C. Liu, S.C. Hung, C.S. Cheng, Multi-input inverter for grid- 17071715.
connected hybrid pv/wind power system, IEEE Transactions on Power [17] A. Mullane, G. Lightbody, R. Yacamini, Wind-turbine fault ride-through
Electronics 22 (2007) 10701077. enhancement, IEEE Transactions on Power Systems 20 (2005) 19291937.
G. Majic,
[3] B. Terzic, A. Slutej, Stability analysis of three-phase PWM converter [18] T. Odun-Ayo, M.L. Crow, Structure-preserved power system transient stabil-
with LCL lter by means of nonlinear model, Automatika 51 (2010) 221232. ity using stochastic energy functions, IEEE Transactions on Power Systems 27
[4] J.E.G. Carrasco, J.M. Tena, D. Ugena, J. Alonso-Martinez, D. Santos-Martin, S. (2012) 14501458.
Arnaltes, Testing low voltage ride through capabilities of solar inverters, Elec- [19] M. Ouhrouche, Transient analysis of a grid connected wind driven induction
tric Power Systems Research 96 (2013) 111118. generator using a real-time simulation platform, Renewable Energy 34 (2009)
[5] S.M. Muyeen, R. Takahashi, J. Tamura, Electrolyzer switching strategy for hydro- 801806.
gen generation from variable speed wind generator, Electric Power Systems [20] C. Jauch, Transient and dynamic control of a variable speed wind turbine with
Research 81 (2011) 11711179. synchronous generator, Wind Energy 10 (2007) 247269.
[6] M. Garca-Gracia, M.P. Comech, J. Salln, D. Lpez-Anda, O. Alonso, Voltage [21] S.M. Muyeen, R. Takahashi, T. Murata, J. Tamura, Transient stability enhance-
dip generator for wind energy systems up to 5 MW, Applied Energy 86 (2009) ment of variable speed wind turbine driven PMSG with rectier-boost
565574. converter-inverter, in: Proceedings of The International Conference on Elec-
[7] A.H.M.A. Rahim, E.P. Nowicki, Performance of a grid-connected wind gener- trical Machine, Vilamoura, Portugal, 2008, pp. 400405.
ation system with a robust susceptance controller, Electric Power Systems [22] X. Jiao, Q. Gao, Integrated dynamic simulation of photovoltaic installations and
Research 81 (2011) 149157. its low voltage ride-through capability analysis, in: Proceedings of Australasian
[8] F. Iov, A.D. Hansen, P. Srensen, N.A. Cutululis, Mapping of Grid Faults and Grid Universities Power Engineering Conference, Bali, Indonesia, 2012.
Codes, Ris National Laboratory, Technical University of Denmark, Roskilde, [23] H. Geng, D. Xu, Stability analysis and improvements for variable-speed multi-
2007. pole permanent magnet synchronous generator-based wind energy conversion
[9] F. Tang, X.M. Jin, X. Zhou, X.Z. Wu, L. Ma, A novel LVRT strategy for direct- system, IEEE Transactions on Sustainable Energy 2 (2011) 459467.
drive wind turbines based on permanent magnet synchronous generator, in: [24] N. Pariz, H.M. Shanechi, E. Vaahedi, Explaining and validating stressed power
Proceedings of IEEE 7th International Power Electronics and Motion Control systems behavior using modal series, IEEE Transactions on Power Systems 18
Conference, Harbin, China, 2012, pp. 22282233. (2003) 778785.
[10] S.M. Muyeen, R. Takahashi, M.H. Ali, T. Murata, J. Tamura, Transient stabil- [25] J. Castell, J.M. Esp, R. Garca-Gil, Guidelines for the design and implementa-
ity augmentation of power system including wind farms by using ECS, IEEE tion of the ARPCC control applied to grid-connected converters, Electric Power
Transactions on Power Systems 23 (2008) 11791187. Systems Research 95 (2013) 284291.
[11] C.H. Benz, W.T. Franke, F.W. Fuchs, Low voltage ride through capability of a 5 kW [26] E. Twining, D.G. Holmes, Grid current regulation of a three-phase voltage source
grid-tied solar inverter, in: Proceedings of 14th International Power Electronics inverter with an LCL input lter, IEEE Transactions on Power Electronics 18
and Motion Control Conference, Ohrid, Macedonia, 2010, pp. 1320. (2003) 888895.
[12] K.H. Kim, Y.C. Jeung, D.C. Lee, H.G. Kim, LVRT scheme of PMSG wind power sys- [27] M. Chinchilla, S. Arnaltes, J.C. Burgos, Control of permanent-magnet generators
tems based on feedback linearization, IEEE Transactions on Power Electronics applied to variable-speed wind-energy systems connected to the grid, IEEE
27 (2012) 23762384. Transactions on Energy Conversion 21 (2006) 130135.

Вам также может понравиться