in a given orifice flow meter (to change the range of flow rate measurement) required moving the dow
In 1991 ISO 5167 identified three standard pressure tap configurations for an orifice flow meter. The th
flange taps, and D - D/2 taps, as illustrated in the figure at the left. The advantage of the ISO 5167 pre
the pressure taps from the orifice plate is given as a fixed distance, or as a function of the pipe diame
Determination of Orifice Discharge Coefficient
ISO 5167 provides an equation (given below) for the orifice discharge coefficient, Cd, as a function of
Cd = 0.5959 + 0.0312 2.1 - 0.1840 8 + 0.0029 2.5(106/Re)0.75 + 0.0900(L1/D)[4/(1 - 4)] - 0.0337(L2/D
This equation can be used to find the orifice discharge coefficient for an orifice flow meter with any of
but not for any other arbitrary values of L1 and L2. The introduction of standard pressure tap configura
orifice flow meter to conveniently use different size orifice openings and cover a wide flow measureme
Note that an iterative (trial and error) calculation is needed to get a value for Cd, because the upstrea
A U.S Dept. of the Interior reference with information about ISO 5167 for determining the orifice disch
ONGC - CLAMPON RESTRICTION ORIFICE SIZING
DATA
m kg/s 0.50
C 0.60
k 1.38
k+1 2.38
k-1 0.38
kg/m3 22.77
P1 Pa 3000000
CALCULATION
0.336
A mm2 147.17
dia mm 13.6888
Choked flow
ONGC - CLAMPON RESTRICTION ORIFICE SIZING Choked flow
assumes d/s pressure is less than half u/s pr. !!
DATA
ONGC 8" closed 10 mm 2" valve
clamp-on drain vent RO
C 0.60 0.60 0.60 0.60
dia m ### 200.00 10.00 40.00
A m2 0.0001 0.0314 0.0001 0.0013
k 1.38 1.28 1.28 1.28
k+1 2.38 2.28 2.28 2.28
k-1 0.38 0.28 0.28 0.28
P1 bar abs 30 5 30 30
Mol
weight 23 23 23
HYSYS HYSYS HYSYS
kg/m3 22.77 5.13 30.80 30.80
0.336 0.344 0.344 0.344
CALCULATION