USER MANUAL
Models
ISP416 220
ISP416 110
ISP416 48
ISP416 24
1
Safety Warnings
The warning symbol shown at left denotes an important safety consideration. Please read this manual Carefully before performing any
of the procedures contained herein. Failure to follow these instructions may result severe injury.
Have a qualified electrical maintenance technician install, adjust and service this equipment. Follow the National Electrical Code and
all other applicable electrical and safety codes, including the provisions of the Occupational Safety and Health, when installing
equipment.
Reduce the chance of an electrical fire, shock, or explosion by proper grounding, over-current protection, thermal protection, and
enclosure. Follow sound maintenance procedures.
Circuit potentials can be max 220VDC . Avoid direct contact with the printed circuit board or with circuit elements to prevent the risk of
serious injury or fatality.
2
1- Features & Benefits
The ISP416 Series alarm annunciators that functional, flexible and reliable device
are designed to fulfill all the requirements of Alarm condiditons.
Horn or Bell output selection can be easily configurable with pushbuttons for each
channels.
Each ISP Series annunciator is equipped with low power, long life LEDs. Each
alarm point uses a bicolor LEDs providing illumination in all light conditions
Horn/Bell selections and other status.
High Interference Immunity. All alarm inputs are provided with fully isolated inputs
using optical couplers and a transient hardware and software filters.
Common Outputs As standard, each unit is fitted with three common relays:
Critical Audible Relay (HORN), Non-Critical Audible Relay (BELL), Watchdog Relay
3
2- Connections
All connections are made on the rear of the unit using two-part quick disconnect plug in
terminals accepting up to 12 AWG (2.5mm2) wires.
Figure 1
( GND and SURGE must be seperatly Grounded )
Figure 2
( Wrong Conncetion - Do not use any jumper between GND and SURGE terminals)
4
2-2- A Terminals ( Input Cahnnels 1-8 )
Figure 3
(Supply is optional 24Vdc 48Vdc 110Vdc 220Vdc)
Figure 4
( Wrong Conncetion - Do not use any jumper between GND and SURGE terminals)
5
2-3- B Terminals ( Input Cahnnels 9-16 )
Figure 5
(Supply is optional 24Vdc 48Vdc 110Vdc 220Vdc)
Figure 6
( Wrong Conncetion - Do not use any jumper between GND and SURGE terminals)
Figure 7
(Required 250ohm termination resistor for master and slave ports, both side of Rs485 comm. line)
6
3- Configure Relay Outputs (Horn or Bell ) for All Channels
V- Press Test Button firstly (all input channel leds solid red and buzzer turn on)
VI- Press Horn Button secondly (for a while 3 Secs) (buzzer turn off) when
pressing the test Button.
VIII- Press Horn Button to setup alarm output type (Horn or Bell ) for input
channel 1 while led's is blink red in this step. When the pressed Horn Button channel 1
led's color change to blink green. (Blink Red Horn Output / Blink green Bell Output)
Figure 8
IX- Press Test Button to change input channel. When the pressed test button next
channel led's blink red.
X- Press Ack Button to save input ch. settings or Press Reset Button to
cancel configuration settings. When the pressed Ack Button will ISP416 save your
configuration and start up itself.
! If wasn't pressed any button for 60 sec in config mode then ISP return the regular
7
Process Mode.
8
4-Output Relay and Led Status
Example
For Channel 1
Initial Test Test Fail Process Normal Process Abnormal
Horn / Bell Relay Open / Open Open / Open Open / Open Open / Closed
Watch Dog Relay Open Open Closed Closed
Channel 1 Led Solid Red/Grn Off Off Blink Green 4Hz
Horn / Silent Led Solid Red/Grn Off
Safe / Fail Led Solid Red/Grn Blink Red Solid Green Solid Green
For Channel 2
Initial Test Test Fail Process Normal Process Abnormal
Horn / Bell Relay Open / Open Open / Open Open / Open Open / Closed
Watch Dog Relay Open Open Closed Closed
Channel 1 Led Solid Red/Grn Off Off Blink Red 4Hz
Horn / Silent Led Solid Red/Grn Off
Safe / Fail Led Solid Red/Grn Blink Red Solid Green Solid Green
9
4-1 Horn / Silent Led Status
Horn / Bell Relays are Turned On Horn / Bell Relays are Turned Off
Horn or Bell Relay Outputs or both of them H/B Relay Outputs are (OPEN)Passive
are (CLOSED)Active
Horn / Bell Relays are Tuned On Horn / Bell Relays are Tuned Off
H/B Relay Outputs are (OPEN)Passive H/B Relay Outputs are (OPEN)Passive
10
4-2 Safe / Fail Led Status
11
4-3 Input Channels Led Status
There is no alarm
Cleared all alarms with Reset Button After Process can be Normal or Abnormal in
the acknowledged all alarms. this phase (leds are turned off).
12
5- Alarm Sequence ( Modified - ISA-S18.1 Code-M (Manual Reset) )
13
6- Technical Specification
INPUTS
OUTPUTS
POWER REQUIREMENTS
24V ISP416, Min 18Vdc Max 30Vdc,
48V ISP416, Min 36Vdc Max 60Vdc,
Supply Voltage
110V ISP416, Min 80Vdc Max 140Vdc,
220V ISP416, Min 165Vdc Max 275Vdc,
Supply Power 5W
14
USER INTERFACE
Test - Horn -
Pushbuttons
Ack - Reset -
ENVIRONMENTAL SPECIFICATION
Operating Temperature -20C to +60Degrees C
15
MECHANICAL
16
MECHANICAL
17
MODEL DESCRIPTION ORDER CODE
18