OMICRON PTL
User Manual
V1.000
Content
1. General ............................................................................................................................................ 3
1.1 Supported Relays........................................................................................................................... 3
2. Software and Hardware Requirements........................................................................................... 3
3. Hardware ......................................................................................................................................... 3
4. Functional Range ............................................................................................................................ 5
5. XRIO Converter ............................................................................................................................... 5
5.1 Specialties of the Additional Information Block ................................................................................ 5
6. Specific Protection Tests ................................................................................................................ 5
6.1 Differential Protection ..................................................................................................................... 5
6.2 Thermal Overload Protection .......................................................................................................... 6
1. General
This user manual describes details of testing ABB RET630 relays with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.
3. Hardware
There are multiple possibilities of wiring a RET630 relay to a CMC test set. The advised connections are
shown in Figure 1. These connections are the default settings in the Hardware Configuration of the PTT
and have to be used to get the correct test results, even if the relay is connected in another way to the
real CTs.
IA HV
IB HV
IC HV
N HV
Trip HV
CB aux. HV (52a)
CB aux. LV (52a)
Start
Trip LV
IA LV
IB LV
IC LV
N LV
CB aux. HV (52a)
CB aux. LV (52a)
Start
Trip LV
Trip HV
I0 HV
I0_N HV
Figure 2: Connection Diagram for ABB RET630 for Earth-Fault Protection HV Side
CB aux. HV (52a)
CB aux. LV (52a)
Start
Trip LV
Trip HV
IA LV
IB LV
IC LV
N LV
Figure 3: Connection Diagram for ABB RET630 for Earth-Fault Protection LV Side
4. Functional Range
Supported functions:
Transformer differential protection for two winding transformers TR2PTDF
Three-phase thermal overload protection for power transformers, two time constants T2PTTR
Three-phase non-directional overcurrent PHxPTOC
Non-directional earth-fault EFxPTOC
Although the functions listed above are not supported by the Protection Test Template, the Relay
Parameter Section of the XRIO Converter includes all protection parameters of the relay.
5. XRIO Converter
The Test Object already contains the ABB RET630 XRIO Converter, which includes settings parameters
of the modelled protection relay. The settings parameters are built as an image of the ABB PCM600 V2.7
software.
The Standard Filter for XRIO Files can be used for importing settings into the Relay Parameter
Section.
The configuration test for L-N and L-L fault types is not supported for Clock number settings of 2, 4, 8 or
10. The correspondent test module is deactivated in any of these cases.
Internal Fault - Diff Operating Characteristic Test
The operating characteristic test for L-N and L-L fault types is not supported for Clock number settings of
2, 4, 8 or 10. The correspondent test modules are deactivated in any of these cases.
Before each test shot the thermal memory of the relay has to be reset in order to set up a defined test
case. In this case the relay uses the Initial temperature parameter to initiate the temperature calculation.
As the converter uses the Env temperature Set parameter to initiate the calculation of the temperature
rise, the Initial temperature in the relay has to be set to the same value as the Env temperature Set to
perform the test (in C). Otherwise the relay would have a different start point for the temperature
calculation than the converter and the test fails.