Liebert Challenger
Unmatched Environmental Control To Match Many Applications
When It Comes To Precision Air Conditioning,
Liebert Doesnt Accept Almost
2
The Complete Solution
I need a cooling source I can control The Liebert Challenger is a self-contained system.The status and control panel is on the
that is totally independent of the front, and all control functions are menu-driven. You have complete control of your
building HVAC system. environment at all times.
My equipment will be running Designed to run 24 hours a day, 365 days a year. The inherently efficient scroll compressor
continuously, so the air conditioner has an EER of 11.3. Liebert Microprocessor-based controls intelligently determine
needs to be energy efficient. operational requirements and minimize wasteful operating patterns such as short cycling.
Optional GLYCOOL free-cooling system permits compressorless operation in cold climates.
That room is jammed to the rafters; Footprint is a mere 7.3 square feet, with front access to all interior components for
I need a cooling system that takes maintenance and service. Theres no need to keep the back or sides clear, so the Liebert
very little space. Challenger can fit into a corner or squeeze between existing installed equipment.
I want everything in one cabinet Liebert Challenger includes all environmental functionscooling, reheat, dehumidification,
from one supplier. humidification, and filtrationand an intelligent control system to make sure every
function works in harmony with the other. Installation is fast, and maintenance is easy.
All systems are factory tested.
There are a dozen sites here, Liebert Challenger is the most versatile system available. It can be placed inside the
all unique. I want to simplify room, or remotely. Conditioned air can move up into ducts or down into a raised
my selection process without floor plenum. Self-contained or split systems. Air, water, glycol, GLYCOOL, and chilled
compromising my site needs.
water configurations.
3
Regardless Of The Application, Liebert Challenger
Will Meet Your Critical Requirements.
Years of experience in the design and manufacture of precision environmental control systems and staying abreast of new
technological developments and requirements has helped us produce the Liebert Liebert Challenger. We know that all critical
electronic systems demand a high quality environment...but we also know that not all applications are created equal. Thats
why Liebert Challenger is configurable to meet the needs of a wide variety of site requirements.
Labs and Medical suites such as MRI and CATscan sites In Telecommunications sites, space is at a premium.
need to handle cooling loads precisely and quietly. And you need a system dependable to operate year
The Liebert Challenger offers such precision features as round in unattended sites. The Liebert Challenger
Intelligent, microprocessor based control systems, features a reliable scroll compressor, remote
SCR controlled reheats for infinite levels of response, communications capability, and a microprocessor
an A-Frame coil that reduces air turbulence and a quiet, that controls the system without supervision. And it
dependable scroll compressor. All in a compact package provides all this protection while consuming only
that fits easily into any setting. 7.3 square feet.
4
Industrial Process Automation Computer Room Applications Need:
Applications Need:
24 Hour Per Day/365 Days Per Year Operation
Potentially Corrosive Environments Underfloor Air Discharge
High Static Pressure Air High Sensible Heat Ratio
Discharge Requirements 1800-3000 C.F.M. Air Discharge
High Air Filtration Requirements High Energy Efficiency Requirements
On the factory floor, you need a cooling system thats On a square foot basis, computer rooms generate up
dependable and tough. Tough enough to withstand to five times the heat of normal office space. And they
the corrosive environments, and tough enough to require higher than normal air handling requirements
supply continuous air flow in ducted applications. to reduce hot spots. The Liebert Challenger is designed
The Liebert Challenger answers all this with a MIG to handle this load efficiently with a high sensible heat
welded steelframe surrounded by insulated heavy ratio and an air delivery system capable of 1800-3000
gauge steel panels. C.F.M. Because most computer rooms use a raised floor
for air circulation and cable management, the Liebert
Challenger can be specified with underfloor air
discharge. This reduces the turbulence created by
competing warm and cold air streams.
5
More Benefits And Higher Quality...
Trademarks Of A Liebert System
Front Access For Easy An Autoflush System reduces the Year-Round Dependability
Maintenance buildup of mineral solids and reduces And Energy Efficiency
All interior components are front maintenance time. If your application A rugged and quiet Scroll
accessible to simplify maintenance calls for a Steam-Generating Compressor is at the heart of the
and reduce the floorspace that must Humidifier, Liebert can respond. refrigeration system. It operates at
be kept open. The disposable canister makes one of the highest EERs in the
maintenance quick and easy. industry, 11.3.
Stable and Quiet Air cooled systems with outdoor
A MIG welded steel frame provides High Performance Cooling condenser can operate between -
a solid platform for the internal and Heating Components 30 and +120F (-34 and 49C).
components. Units incorporate a An A-Frame Evaporator Coil Water and glycol cooled systems
vibration-isolated fan deck which exposes more coil surface to the air feature a coaxial condenser and
reduces noise and vibration that passes through it. This not only regulating valves that can be
transmission to any connected provides a more rapid and precise adjusted to meet the capabilities
ductwork. The heavy gauge response to changing room of the site.
panels/heavy duty gaskets option conditions, but it reduces the
provides upgraded protection, horsepower requirements of the All Components From One
popular in industrial and/or high fan motor, saving energy. Manufacturer
static applications. Liebert is the only manufacturer in the
The 304/304 Stainless Steel, Finned computer support industry that builds
Corrosion Resistant Tube Reheat, like the evaporator coil, its own condensers and drycoolers.
The frame and exterior panels is designed to maximize surface area. They feature aluminum cabinets and
are powder coated and baked, a This allows lower sheath temperatures, copper-tube, aluminum-fin coils, and
solvent-free process that is not only reducing the likelihood of ionization are built to precisely match the heat
environmentally safe, but produces that could trip fire detection equipment, rejection requirements of the Liebert
an attractive, durable finish. and more precisely controlling room Challenger .
temperature during dehumidification.
Precise Humidity Control The reheat coils are constructed of NRTL-C Certified
The Infrared Humidifier has been stainless steel for corrosion resistance Standard 60Hz products are NRTL-C
a feature on Liebert environmental and long life. listed/certified. NRTL-C meets both
control systems for over 25 years. U.S. and Canadian government
Its rapid response and cleanliness An optional SCR-Controlled safety standards, providing fast,
has made it an industry standard in Reheat is available that provides hassle-free inspection and building
applications that demand precise, infinite response levels to changing code approval.
particle-free humidity control. room temperatures.
6
Corrosion-Resistant
Steel Frame
Vibration-Isolated
Fan Deck
Scroll
Compressor
7
Communicating With Your Precision Environmental System
Whether you use its local or remote monitoring and control capabilities, the Liebert Challenger is designed to provide the
widest range of monitoring options.
In the alarm mode, the control panel can The standard operations screen shows temperature
display any of up to 21 alarms. and humidity in large, easy-to-read type.
8
Liebert Remote Monitoring Solutions: When You Need To Know
IT Manager Network Data Center Facility Enterprise
Single Phase
Uninterruptible Liebert OpenComms Nform
Power System Liebert MultiLink
Liebert OpenComms Nform
You will find a full range of monitoring and control systems, Three Phase
Uninterruptible
Liebert OpenComms Nform
Power System Liebert SiteScan Web
communications modules designed to interface Liebert equipment
Power
with a variety of building management systems, plus stand-alone Management
Liebert OpenComms Nform
Liebert SiteScan Web
monitoring, control and leak detection devices. Environmental
Control
9
See For Yourself How The Liebert Challenger Can
Be Configured To Match Your Exact Cooling Needs
Direct Expansion Or
Chilled Water Models?
Direct Expansion includes
Air cooled, Water cooled,
Glycol cooled, and GLYCOOL.
Chilled Water Systems require
connection to a chilled water source. Glycol Cooled/GLYCOOL
Water-Cooled Self-Contained System
Self-Contained System
Self-Contained or
Split System?
Self-Contained Systems package all
refrigeration components within the
cabinet to minimize installation time.
Air Cooled models require field
connection to a remote condenser.
Water Cooled models require field
connection to a remote water source.
Glycol Cooled/GLYCOOL models
require field connection to a remote
drycooler and circulating pump.
All Chilled Water systems
are self-contained. Split- System
Split systems split the refrigeration
components between the room Air Cooled
unit and a condensing unit. Outdoor
Prop Fan
This locates the compressor and
condenser at a remote location,
and reduces noise levels within Air Cooled
the room unit. Indoor
Centrifugal
Air, Water, and Glycol Cooled
models connect to the room unit
with pre-charged refrigerant line Cooling
Water Tower
sets (up to 45 ft./14 meters), or Cooled
traditional piping techniques for
longer distances.
Glycol
Cooled
10
Upflow Air Discharge Downflow Air Discharge
3212
3212 (826 mm)
(826 mm)
3212
(826 mm)
*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72F (22C), 50% RH is the standard rating condition of ASHRAE 127-2001.
11
Ensuring The High Availability Of
Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, Liebert Corporation
1050 Dearborn Drive
ensures network resiliency and adaptability through a family of technologies P.O. Box 29186
Columbus, Ohio 43229
including Liebert power and cooling technologies that protect and support
800 877 9222 Phone (U.S. &
business-critical systems. Liebert solutions employ an adaptive architecture that Canada Only)
614 888 0246 Phone (Outside U.S.)
responds to changes in criticality, density and capacity. Enterprises benefit 614 841 6022 FAX
from greater IT system availability, operational flexibility, and reduced capital Via Leonardo Da Vinci 8
Zona Industriale Tognana
equipment and operating costs.
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
2006 Emerson Electric Co.