Water cooled packaged Air conditioner

YBW Series

Office Locations
Australia (Melbourne) Indonesia Malaysia (Kuala Lumpur)
Tel : +61 (3) 9751 5000 Tel : +61 (21) 5633 8500 Tel : +60 (3) 7628 4300
Fax : +61 (3) 9755 7566 Fax : +61 (21) 5366 8300 Fax : +60 (3) 7874 1180

China (Shanghai) Japan New Zealand


Tel : +86 (21) 6276 6509 Tel : +81 (3) 5738 6100 Tel : +64 (9) 444 6434
Fax : +86 (21) 6277 3543 Fax : +81 (3) 5738 6298 Fax : +64 (9) 444 2092

Hong Kong Korea Singapore


Tel : +852 2590 0012 Tel : +822 554 5935 Tel : +65 6748 0202
Fax : +852 2516 5648 Fax : +822 554 5739 Fax : +65 6743 4420

India (Mumbai) Macau Thailand (Bangkok)


Tel : +91 (22) 6683 7000 Tel : +853 2875 1820 Tel : +66 (2) 717 1260-80
Fax : +91 (22) 6683 7002 Fax : +853 2875 1825 Fax : +66 (2) 717 1325-8
Product nomenclature

Y B W 90 B 0 0 L 1 B E

E: Export-oriented; when missing or

Water cooled packaged


Y: YORK absent, it means that the product is
for the domestic market.
B: Beyond series
Design series number,
W: Water-cooled cabinet A-First design,

air-conditioners
B-Second design

Model number
Service code, 0 -No modification,
1- First modification
A: Generation A;
B: Generation B
The YORK YBW water-cooled packaged air-conditioners are designed for B: Connection is feasible on
both sides; L: Left connection;
indoor installation free-blow or ducted air-conditioning system. There are Backup, default, no option R: Right connection.

two series and 11 models available. Series A includes one model while Backup, default, no option

Series B encompasses ten models, with a cooling capacity of 30kW to Note: YBW 33A 50B can be connected on both sides; for YBW 66-180B, the connection differs from right to left.
180kW. Perfect choice for ballrooms, restaurants, shopping malls, offices,
and premium facilities
Unit characteristics
Wide Scope of Application High Efficiency
All kinds of needs in the industrial and YBW33A/50B uses a high efficiency tube-in-tube counter
commercial industries can be satisfied. flow condenser; the refrigerant and water are circulated in
It is belt-driven and the external static opposite direction, which removes the heating quicker and
pressure is adjustable. more efficiently.
YBW66 ~ 180B uses a high-efficiency shell and tube heat
The blower and motor installation exchanger. Water goes through the tube. Long-term
is of suspension design maintenance of a high energy efficiency ratio and stability
The blower and motor are of the latest can be accomplished.
suspension design to greatly reduce the Individual components are optimized before assembly to
operating noise and make maintenance guarantee the maximum performance. The air flow structure
easy. is optimized to maximize heat exchange performance.

Quiet Operation Durable in use


The unit uses hermetic Scroll The casing of unit is coated with epoxy to guarantee
compressors; it operates quietly and absence of rust. YBW33A/50B has a large-diameter tube-
generates minimal noises. The blower in-tube condenser not susceptible to scaling; it is long-
and motor are of the suspension design lasting and durable. YBW66~180B has a shell-tube
to guarantee minimal vibration and condenser that can be cleaned artificially; it is easy to
noises generated by the unit. Factory clean and durable.
standard offering includes rubber
cushion to reduce operation noise.
Easy to Install
The unit is of packaged design, has a compact structure,
Safe and Reliable and takes up less space. Free return air. YBW33A/50B
The product is of multiple refrigeration condenser water can be connectted on both sides
circuits design. When one fails, the other freely,YBW66-180B condenser water connection is on the
refrigeration circuits are not affected. right or on the left. Hanging rings are installed on the top
The unit is equipped with compressor of the unit (excluding YBW160B/180B) to facilitate
overload protection, motor over-heating suspension for installation. There are two blowers. The
protection, external interlock protection, small volume and light weight make installation easy.
and high/low pressure protection.
Control failure codes are detailed and Easy to Repair
explicit, making determination and The unit has an access panel; it is easy to repair. The front
clearance of failures easy. panel of the unit consists of four pieces that are easy to
remove and facilitate repairs.
Specification table
Total Rated Range of Compressor Blower Dimension (mm)
power external external Cooling Water
Cooling consumed Air static static Capacity water pressure
Motor Width Depth Height Weight
capacity volume adjustment Power input Rated flow rate drop
Model No. (kW) for cooling (m3/h) pressure pressure range (%) Quantity power (W) (D) (H) (kg)
(kW) (Pa) (Pa) (kW) current (A) (m3/h) (kPa)
(kW)

YBW33A 30 10 6500 100 60~130 50, 100 2 3.6 2 6.6 x 2 1.5 6.5 30 1374 995 1595 455

YBW50B 49 14.9 9000 150 110~190 33, 67, 100 3 3.8 3 7.2 3 3 10.5 36 1660 981 1646 562

YBW66B 65 17.5 12000 150 120~170 50, 100 2 6.6 2 11.8 x 2 3 14 35 1972 1125 1748 800

YBW80B 77 21.5 15000 200 160~230 50, 100 2 7.4 2 14.8 2 5.5 16.6 40 1972 1125 1748 885

YBW90B 86 24.5 16000 100 90~200 50, 100 2 8.5 x 2 16.6 x 2 5.5 18.5 51 1972 1125 1848 895

8.5 + 16.6 +
YBW100B 95 27.3 16500 100 90~230 45, 60, 85, 100 3 5.5 20.4 67 1972 1125 1848 970
7.4 + 3.8 14.8 + 7.2

Specifications YBW110B

YBW130B
105

130
30.0

35
17000

20000
100

150
70~230

100~260
33, 67, 100

33, 67, 100


3

3
6.6 x 3

7.6 x 3
11.8x3

15.2 x 3
5.5

7.5
22.6

28
70

80
1872

2172
1394

1394
1948

1948
1040

1180

22000 150 80~260 30, 40, 60, 3 7.6 x 2+ 15.2 x 2 + 7.5 29 82 2172 1394 1948 1220
YBW135B 135 36.5
70, 100 10 20

YBW160B 160 45.5 25200 250 240~350 25, 50, 75, 100 4 7.4 x 3 + 14.8 x 3 + 11 34.4 90 2270 1381 2030 1450
8.5 16.6

YBW180B 180 49.0 28000 400 270~410 25, 50, 75, 100 4 8.5 x 4 16.6 4 11 38.7 90 2520 1381 2030 1540

Note: 1. Operating conditions: Indoor 27C DB/19CWB; cooling water inlet is 30C.
2. Scroll compressors are adopted; the unit power is 400V 3N~50Hz.
3. YBW33A 50B condenser is of the large-diameter tube-in-tube while 66B~180B is of the shell-tube type; the blower is belt-driven.
5. In case of any change to the specifications, no individual notice will be sent.
6. For specific air volume and external static pressure requirements, please contact the manufacturer to select and confirm the right model.

Steady operation range


Inlet Air Temperature of
Voltage Condenser
Evaporating Coil

Cooling water
Dry Bulb Wet Bulb
Outlet Water Pressure Temperature Temperature
Minimum Maximum Temperature( C) (Mpa) (C) (C)
(V) (V)
Minimum Maximum Minimum Maximum Minimum Maximum Minimum Maximum

376 440 19 45 0.14 1 18 32 13 24


Unit dimension and specification table Control illustration

53
E
Dimension of Window

YBW33A 50B unit

53
F

DI
Condensate drain outlet Power connection port

H
Rc 1
Cooling water outlet, J C
Emergency drain pipe Cooling water inlet, J
Rc 1
75
W

Outlet water temperature of condenser Air outlet Air inlet Cooling


Evaporator return
dimension dimension water
air condition
26.7C 35C 43.3C mm mm inlet/outlet
External
Nominal
static Dry bulb Wet bulb Total Sensible Total Sensible Total Sensible
air flow
Model No. pressure temperature temperature cooling cooling cooling cooling cooling cooling C DI E F J Quantity
m3/h
Pa C C capacity kW capacity kW capacity kW capacity kW capacity kW capacity kW
30.0 22.2 35.2 21.5 33.4 20.8 31.2 20.3
YBW33A 6500 100 27.0 19.0 31.8 22.1 30.0 21.4 27.9 20.4 395 341 1100 762 Rc11/4 2
23.3 16.7 29.1 20.1 27.6 19.1 25.4 18.2
30.0 22.2 57.9 35.4 54.9 34.2 51.3 33.3
YBW50B 9000 150 27.0 19.0 52.2 36.3 49.0 35.1 45.9 33.6 471 404 1384 911 Rc2 2
23.3 16.7 47.9 33.0 45.4 31.5 41.8 30.0

Note:
1. All the vent dimensions are inside diameters, excluding the flange edge.
2. The flange edge of the air outlet is 40 mm wide; the flange edge of the air inlet is 30 mm wide.
45

Dimension of E

YBW66A~180B unit

53
F
H

DI
D
Emergency 1 Time setup key Can be used to set timed on/off mode and When an alarm goes off, check the failure code listed in
drain pipe
Condensate drain outlet
time, calibrate the date, clock, and address. the following table:
Rc1
C M C 2 Temperature setup key Will show the temperature value when
Cooling water inlet/outlet(K)
W pressed and held for three seconds. No. Failure Code

Outlet water temperature of condenser Air outlet Air inlet Cooling 3 Switch OFF key To turn off all units within the network when 1 Blower, power, external interlock failure 01
Evaporator return
dimension dimension water pressed.
air condition
26.7C 35C 43.3C mm mm inlet/outlet
External 2 Compressor 1 is overloaded or experiences high pressure failure. 02
Nominal 4 Display Selection key Is used to display the temperature and for
static Dry bulb Wet bulb Total Sensible Total Sensible Total Sensible
air flow failure inquiry.
Model No. pressure temperature temperature cooling cooling cooling cooling cooling cooling C DI M E F K Quantity
m3/h 3 Compressor 2 is overloaded or experiences high pressure failure 03
Pa C C capacity kW capacity kW capacity kW capacity kW capacity kW capacity kW
5 key Is used to adjust and set the room
30.0 22.2 76.8 46.9 72.8 45.4 68.0 44.1 temperature at increments of 1C. This key, 4 Compressor 3 is overloaded or experiences high pressure failure. 04
YBW66B 12000 150 27.0 19.0 69.2 48.1 65.0 46.6 60.8 44.5 373 404 294 1698 864 Rc2 2 however, is invalid in an YBW model.
23.3 16.7 63.5 43.8 60.2 41.7 55.4 39.8 5 Compressor 1 experiences low pressure failure. 05
6 key Is used to change the default or individual
30.0 22.2 91.0 55.6 86.2 53.7 80.6 52.3 status values at display (together with the
YBW80B 15000 200 27.0 19.0 82.0 57.0 77.0 55.2 72.1 52.8 373 404 294 1384 1143 Rc21/2 2 number pad keys 1, 2, and 4). 6 Compressor 2 experiences low pressure failure. 06
23.3 16.7 75.2 51.9 71.3 49.4 65.7 47.1
7 Shift key Is used to change the operating status of the 7 Heater fails 07
30.0 22.2 101.7 62.1 96.3 61.6 80.5 58.9
system; it changes among the three states,
YBW90B 16000 100 27.0 19.0 91.6 63.6 86.0 61.6 80.5 58.9 373 404 294 1698 1270 Rc21/2 2 cooling, heating, and circulating.
8 Water flow and water pump fail 08
23.3 16.7 84.0 57.9 79.7 55.2 73.3 52.6
8 Air speed key Is used to select the high, medium, low
30.0 22.2 112.3 68.6 106.4 66.3 99.4 64.5
speeds of the indoor blower; the air speed 9 Compressor 3 experiences low pressure failure 09
YBW100B 16500 100 27.0 19.0 101.2 70.3 95.0 68.1 88.9 65.1 373 404 294 1698 1270 Rc21/2 2 key is invalid for an YBW model.
23.3 16.7 92.8 64.0 88.0 61.0 81.0 58.1 10 Return air temperature sensor fails 10
30.0 22.2 124.1 75.8 117.6 73.3 109.9 71.3 9 Defrost key Is used to perform compulsory defrosting. An
YBW110B 17000 150 373 404 294 1698 1372 Rc21/2 2 YBW model is not equipped with the
27.0 19.0 111.9 77.7 105.0 75.3 98.3 72.0
defrosting feature.
23.3 16.7 102.6 70.7 97.3 67.4 89.5 64.2
30.0 22.2 153.7 93.9 145.6 90.7 136.0 88.3 10 Reset/Shift key Is used to reset the unit in a failure or after
YBW130B 20000 150 27.0 19.0 138.5 96.2 130.0 93.2 121.7 89.1 471 404 384 1698 1372 Rc21/2 2 the filter is cleaned.
23.3 16.7 127.0 87.6 120.4 83.5 110.8 79.5
11 ON/OFF key can turn on or off this unit (in the room).
30.0 22.2 159.6 97.5 151.2 94.2 141.3 91.7 After the running key is pressed, the LED
YBW135B 22000 150 27.0 19.0 143.8 99.9 134.0 96.8 126.3 92.5 471 404 384 1598 1473 Rc21/2 2 indicator turns green, indicating that the
23.3 16.7 131.9 90.9 125.1 86.7 115.1 82.6 system is operating; after it is pressed
again, the LED indicator turns red, indicating
30.0 22.2 189.1 115.5 179.2 111.7 167.4 108.6
that the system has stopped.
YBW160B 25200 250 27.0 19.0 170.4 118.4 160.0 114.7 149.7 109.6 708 708 384 1898 1604 Rc3 2
23.3 16.7 156.3 107.8 148.2 102.7 136.4 97.9 12 Function 1 key Extension Function 1.
30.0 22.2 212.8 130.0 201.6 125.6 188.3 122.2
YBW180B 28000 400 27.0 19.0 191.7 133.2 180.0 129.0 168.4 123.3 708 708 384 1898 1604 Rc3 2 13 Function 2 key Extension Function 2.
23.3 16.7 175.8 121.3 166.7 115.6 153.5 110.1
14 Air circulating key Invalid
Note:
1. All the vent dimensions are inside diameters, excluding the flange edge.
2. The flange edge of the air outlet is 40 mm wide; the flange edge of the air inlet is 30 mm wide.
4. The default water pipe connection is left.Face to the return air side, the water pipe connection is on the left.
Blower performance
YBW33A YBW66B / 80B /
YBW33A 90B / 100B / 110B YBW66B/80B/90B/100B/110B

5 5

4 4

(kW WER
(kW WER
3 3

O
O

)
)

FT P
FT P

TOTAL PRESSURE IN INCH WATER GAUGE (in.wg)


TOTAL PRESSURE IN INCH WATER GAUGE (in.wg)

A
A

SH
SH
2 2

1 1

0.5 0.5

SOUND POWER LEVEL LWiA dB(A) SOUND POWER LEVEL LWiA dB(A)
LWiA A LWiA A
VOLUME FLOW RATE VOLUME FLOW RATE
Q1000m /h Q1000m /h

VOLUME FLOW RATE VOLUME FLOW RATE


0.6 1 2 3 4 5 10 Q1000CFM
0.6 1 2 3 4 5 10 Q1000CFM
DYNAMIC PRESSURE DYNAMIC PRESSURE
Pd10Pa Pd10Pa

OUTLET VELOCITY OUTLET VELOCITY


Cm/s Cm/s

YBW160B / 180B YBW50B / 130B / 135B


YBW160B/180B
YBW50B/130B/135B

7 4
R

(kW WER
6
(kW E
POW
)

O
)
5

FT P
AFT

TOTAL PRESSURE IN INCH WATER GAUGE (in.wg)


TOTAL PRESSURE IN INCH WATER GAUGE (in.wg)


SH

A
4

SH
2
3

1
0.5

0.5

SOUND POWER LEVEL LWiA dB(A) SOUND POWER LEVEL LWiA dB(A)
LWiA A LWiA A
VOLUME FLOW RATE
VOLUME FLOW RATE
Q1000m /h
Q1000m /h
VOLUME FLOW RATE VOLUME FLOW RATE
1 2 3 4 5 10
2 3 4 5 10 20 Q1000CFM Q1000CFM

DYNAMIC PRESSURE DYNAMIC PRESSURE


Pd10Pa Pd10Pa

OUTLET VELOCITY OUTLET VELOCITY


Cm/s Cm/s

Note: Under the same pressure, coupled double-blower model air volume x 2