EX. 10
10,000 .
Estimated loads DF
Lighting load 30 va./ sq.m. = 30X10,000 = 300 kva X 100% = 300 kva
Receptacle load 10 va./sq.m. = 10X10,000 = 100 kva X 50% = 50 kva
Air condition load 70 va./sq.m. = 70X10,000 = 700 kva X 65% = 455
kva
Mechanical load (pumps) 30 kva = 30 kva X 65% = 20 kva
Other = 50 kva X 50% = 25 kva
Transformer sizing
The size of transformer = total estimated demand load = 850 kva
Selected standard transformer size = 1000 kva, 22 kv 380/220 v, 3 PH, 4
W
MDB sizing
Since transformer secondary full load current = 1519 A
Selected standard MDB size = CU 1600 A, 380/220v, 3Ph, 4W half neutral
Main CB sizing
Selected standard size air circuit breaker 1600 A, 3P, 380V with GFI