Solution which maximize your storage criteria. (Examples: Capacitance continuous type,
This document details the selection criteria for the overfill Radar (working on time measurement TDR or GWR)
prevention sensors (OPS) and Honeywell solutions for the continuous sensors, High accuracy Radar type FMCW
automatic overfill prevention system (AOPS) for bulk petroleum principle non-contact continuous electronic sensors,
storage terminals and refinery tank farms. High accuracy Servo type continuous electronic sensors
The standards and the recommendation which are covered in etc.)
this note are: Automatic Tank Gauge (ATG) sensors- These are high
API MPMS 3.1B, Reaffirmed, Aug 2011 *1 accuracy continuous type sensors meeting specification
of API MPMS Ch. 3.1B recommendations. It is used in
API STANDARD 2350-2012, 4th Edition *2
category 2 and category 3 sites for tank gauging and
IEC 61508:2010 *3 alarm system. If used independently from ATG system,
IEC 61511:2004 *4 they can be considered for category 3 and AOPS tanks.
(Examples: High accuracy Radar type FMCW principle
OIML R85:2008 *5
non-contact continuous electronic sensors, High
accuracy Servo type continuous electronic sensors etc.)
Automatic Overfill Prevention System (AOPS)
Safety logic solver SIL2 certified safety logic solver.
This document covers the following category of sites while
guiding the selection of AOPS: Remote operated shut off valves
- Category 2 - Semi attended sites- These sites typically use auto Selection of Overfill Prevention Sensor (OPS)
tank gauging systems (ATG) for level monitoring and hi-hi alarms API STD 2350 excludes some storage applications (like pressure
in control center. vessels, underground tanks, tanks with capacity equal to or less
than 5000 liters etc.), however this document covers the sensors
- Category 3 Un-attended sites These sites uses both an ATG which could be considered for AOPS deployment in all petroleum
and an independent level alarm high-high sensor (LAHH). liquids/liquefied gas storage tanks as a recommended design
practice.
Basic components of the AOPS: Use of point level sensors is not covered in this document.
Overfill prevention sensors As per API STD 2350 The selection criterion refers to the below Honeywell electronic
there are three types of sensors which can be used: continuous type level sensors while discussing the AOPS
- Point level Sensor Level Switch only used for alarm solution, considering various practical scenarios and design
purposes and if used independently can be used in requirements:
AOPS if meeting other selection criteria. (Examples: TV certified SIL 3/2 servo instrument model Honeywell
Tuning fork type, Capacitance, Ultrasonic sensors etc.) Enraf Servo gauge 854 (High accuracy ATG type
-Continuous level sensors Sensors measuring the continuous electronic sensor)
product level continuously. It is used for level TV certified SIL 3/2 radar instrument model Honeywell
measurement in category 2 sites. (if ullage in tank is Enraf SmartRadar FlexLine (High accuracy ATG type
calculated by operator using strapping table). Used for continuous electronic sensor)
alarm purposes and if used independently can be used TV certified SIL 3/2 Guided-wave radar (GWR) type
in automatic overfill prevention if meeting other selection continuous sensor model Honeywell SLG 700.
Honeywell Automatic Overfill Prevention System 2
Benefits
Compliance with requirements of standards,
recommendations, guidelines on safety.
Automatic proof testing continuous type level
measurement OPS - No climbing on tank. Fig 2: The solution above shows an enhanced safety system
where the continuous type overfill prevention sensors are
2oo4D internal architecture gives redundancy and
connected to control center over wireless, ensuring additional
prevents spurious trips.
alarming and event recording possibility.
Industry best diagnostic cycle time, prevents
--------------------------------------------------------------------------------------
catastrophic accidents.
*1: Standard practice (SP) for level measurements of liquid hydrocarbons in
Reduce financial and environmental risks; Safety stationary tanks by auto tank gauging.
certified AOPS enhances safety with active guarding *2: Standard (STD) Overfill Protection for storage tanks in petroleum facilities
and alarming. *3
: Standard (STD) Internal Standard on Functional safety of electrical/ electronic/
Optimized use of storage capacity, plus optimized programmable electronic safety-related systems.
available storage capacity *4: International Standard (STD) on Functional safety Safety Instrumented
systems for process industry sector
Increase efficiency: Assures onsite accuracy and *5: International recommendation on automatic level gauges for measuring the level
product movement guidance, and improves resource in stationary storage tanks Requirements (Metrological & technical), Controls &
planning. tests (Metrological)
6: For detailed specifications refer product data sheets of Servo 854 ATG,
SmartRadar FlexLine ATG, SmartLine GWR SLG700 and HC900 controllers.
Honeywell Automatic Overfill Prevention System 4