Академический Документы
Профессиональный Документы
Культура Документы
1. GENERAL
ELECTRICAL SYSTEMS
the motion of free electrons through
a solid conductor.
STORAGE BATTERIES
GENERATORS
STORAGE BATTERIES
GENERATORS
1
8/11/2016
UNIT OF QUANTITY
OHM The resistance which will
COULOMB a coulomb of electricity allow one ampere of current to flow
comprises approximately 6.25 x 10 18 when one volt is impressed upon it.
electrons.
as required.
SOURCE
factor of time is
VOLTAGE
LEADS
2
8/11/2016
from a source of electricity to and through same equal current and the total
some electrical device or load and back to the 10 amp
10 amp
resistance, R, is the sum of the
resistances around the circuit.
R5 R4
1
PARALLEL CIRCUIT
R= circuit. With this system, the total current
1/R1 + 1/R2 + 1/R3
flowing through the circuit is the sum of
the current flowing through each outlet.
Appliance Circuit
A branch circuit that supplies
current in one or more outlets
specifically intended for
appliances
C3
C3
20 amp
C2
small appliance outlets in the kitchen, amp circuit loads and on 15 and 20
pantry, dining and family room. amp overcurrent devices respectively.
3
8/11/2016
2.2 SINGLE PHASE ELECTRICAL SYSTEMS 2.2 THREE PHASE ELECTRICAL SYSTEMS
For homes and small commercial buildings For industries and large commercial buildings
The Three Phase AC electricity is a Triple
A single phase electrical system can Circuit. The lighting and outlet loads are
either be 2-wire or 3-wire and connected between any phase leg and a
composes two hot legs and a neutral A B C
neutral line. While machineries and other
wire. bigger loads are connected to the phase leg
SWITCH FUSE
A
only.
B
Three-Wire Three Phase AC
A-B 220V A-C 220V
MOTOR
110 V
Service
The supplying of utilities required
4
8/11/2016
Fuse
A device containing a strip or
wire of fusible metal that melts
under the heat produced by
Service Switch excess current thereby
electrical symbols
OR 13,200 VOLTS
BLOCK DIAGRAM
are used
A horizontal single line MAIN DISTRIBUTION
in lieu of the
SECONDARY SERVICE
a one line or a
120/208 OR BOARD MOTOR
VAULT
incoming service to the
PANELS
single line
120/240 OR
SWITCHES 227/480 VOLTS
utilization items at the end
LARGE
LIGHTING/
diagram.
TRANSFORMER APPLIANCE
MOTOR
of the system where the
FUSES PANELS SMALL
major electrical
BRANCH MOTORS &
CIRCUIT CONTROL
5
8/11/2016
LP
5A 5B
5C
electrical system
LOBBY
presented
showing the
SPARE M.C.C.
spatial relations
MACHINE ROOM
FIRE ALARM
between Standby Systems provide power to
FA PANEL components. selected loads not directly involved with
STAIR AND EXIT
life safety, such as, water and sewage
LPSE
PANEL
M METERING treatment plants and industrial machines
for manufacturing processes.
6
8/11/2016
CONDUCTOR SIZES
AWG/MCM STANDARD CONDUCTOR AMPACITY
All conductor sizes from No. 16 to
No. 0000 (also designated 4/0) are
expressed in AWG.
Beyond AWG No. 4/0, a different Conductor current carrying capacity or
designation, MCM (or thousand circular mil) ampacity is the maximum operating
is used. In this designation, the smallest temperature that its insulation can stand
MCM size is 250 MCM or and the continuously. Heat is generated as a
biggest is 500 MCM. result of the current flowing and the
A circular MIL is an artificial area conductor resistance. When conductors
measurement, representing the square of are placed in an enclosed conduit, the
the cable diameter (diam2) when the heat generated is not as easily
diameter is expressed in mils (thousands of dissipated as it would be if the conductor
an inch). Thus a solid conductor inch in were free in the air. Thus, the current
diameter is 500 mils in diameter, or rating of a conductor in free air is much
250,000 circular mils in area, (500)2 or higher than that for the same were it in
250 MCM; thus; a conduit.
CM/1000 = diam2 = (500)2/1000 =
250,000/1000 = 250 MCM
In the metric system, conductor sizes are
given simply as the diameter in millimeters
(mm).
TYPES OF CABLES
Armored Cable (Type AC) a fabricated Shielded Non-Metallic Sheathed Cable
assembly of insulated conductors (Type SNM) a factory assembly of two
enclosed in flexible metal sheath. or more insulated conductors in an
extruded core of moisture resistant and
Metal Clad Cable (Type MC) a factory flame retardant material covered within
assembled cable of one or more an overlapping spiral metal tape.
conductors each individually insulated
Underground Feeder and Branch Circuit
and enclosed in a metallic sheath of
interlocking tape of a smooth or Cable (Type UF) a moisture resistant
corrugated tube. cable used for underground connections
including direct burial in the ground as
Mineral Insulated Cable (Type MI) a feeder or branch circuit.
factory assembled conductor/s insulated Service Entrance Cable (Type SE or
with a highly compressed refractory USE) a single or multi-conductor
mineral insulation enclosed in a liquid and assembly provided with or without an
gas tight continuous copper sheath.
overall covering primarily used for service
Non-Metallic Sheathed Cable (Type NM wire.
or NMC) also known by the trade Power and Control Tray Cable (Type TC) a
name ROMEX, is a factory assembly of factory assembled two or more insulated
two or more insulated conductors having conductors with or without associated bare
a moisture resistant, flame retardant, or covered grounding under a metallic sheath
and non-metallic material outer sheath. and is used for installation in cable trays,
raceways, or where supported by wire.
7
8/11/2016
8
8/11/2016
9
8/11/2016
10
8/11/2016
ELECTRICAL SYMBOLS
CEILING RACEWAY SYSTEMS
under-the-ceiling raceways composed of
FEEDER L LAMP HOLDER PUSH BUTTON
where required. WP
T TRANSFORMER
LIGHTING OUTLET WALL OUTLET AND SWITCH
S
J JUNCTION BOX
RANGE OUTLET
R
FLUORESCENT LAMP SPECIAL PURPOSE OUTLET
GROUND
REFRIGERATOR OUTLET
ref
2.2 Poles and transformer supports shall be located not more than
500mm inside from the road right-of-way or property line, and
1. General Locational Requirements in Towns, shall not obstruct the sidewalk, pedestrian path and/or the road
Subdivisions, Human Settlements, Industrial Estates drainage canal or structure, existing or proposed.
and the like.
11
8/11/2016
5 m
150 mm
2.4 Secondary, neutral and service lines shall have a minimum vertical
clearance of 7.5 m from the crown of the road pavement when
crossing the highway and from the top of the shoulder or sidewalk
when installed along the side of the highway or street in highly
urbanized area.
4.4 Clearance of wires from building surface shall be not less than
those required Table II. 5. Conductors Passing By or Over Buildings
12
8/11/2016
V
Span and guy wires 75 mm 150 mm 150 mm 150 mm 10 mm
attached to same
pole: general
Span and guy wires 75 mm 150 mm 300 mm 300 mm 10 mm
attached to same
pole: when parallel
to line
Lightning protection 75 mm 75 mm 75 mm 75 mm 5 mm
wires parallel to line:
surfaces of cross
arms
Lightning protection 75 mm 125 mm 75 mm 125 mm 5 mm
wires parallel to line:
surfaces of poles
Exception No. 2. Service drop conductors of 300 volts or less which do not pass 6.2 Clearance from the Ground. Conductors shall have a clearance of not less
over other than a maximum of 1.2m of the overhang portion of the roof for the than 3m from the ground or from any platform or projection from which they
purpose of terminating at a through-the-roof service raceway or approved might be reached.
conductor
support may be maintained at a minimum of 500mm from any portion of the
roof over which they pass. 3m platform
500mm
6.3 Clearance from Building Openings. Conductors shall have a horizontal
Service Drop Conductor clearance of not less than 1m from windows, doors, porches, fire escapes, or
300 volts similar locations and shall be run at least 500mm above the top level of a
1.2 m
window or opening.
Highest point
500mm
wi
window
1m
13
8/11/2016
6.5 No parts of swimming and wading pools shall be placed under existing service
6.4 Service Drop of communication lines, when crossing a street, shall have a drop conductors or any other over-head wiring; nor shall such wiring be
clearance of not less than 5.5 m from the crown of the street or sidewalk installed above the following:
over which it passes. Service drop of communication line
a. Swimming and wading pools and the area extending 3m
outward horizontally from the inside of the walls of the pool.
5.50 m 5.50 m b. Diving Structures
c. Observation stands, towers or platforms
3m
3m 3m Swimming pool
protector
8. Transformers
7. Wiring Methods
8.1 Oil-insulated Transformers Installed Outdoors. Combustible material,
Service entrance conductors extending along the exterior or entering combustible buildings and parts of buildings, fire escapes, door and
buildings or other structures shall be installed in rigid steel conduit or window openings shall be safeguarded from fires originating in oil-
asbestos cement conduit or concrete encased plastic conduit from point of insulated transformers installed on, attached to, or adjacent to a building
service drop to meter socket and from meter socket to the disconnecting or combustible material. Space separations, fire-resistant barriers and
equipment. However, where the service entrance conductors are protected enclosures which confine the oil of a ruptured transformer tank are
by approved fuses or breakers at their outer ends (immediately after the recognized safeguards. One or more of these safeguards shall be applied
service drop or lateral) they may be installed in any of the recognized wiring according to the degree of hazard involved in cases where the transformer
methods. installation presents a fire hazard. Oil enclosures may consist of fire-
resistant dikes, curbed areas or basins, or trenches filled with coarse,
7.1 Abandoned Lines and/or portions of lines no longer required to provide crushed stone. Oil enclosures shall be provided with trapped drains in
shall be removed. cases where the exposure and the quantity of oil involved are such that
removal of oil is important.
7.2 Power or communication poles, lines, service drops and other line
equipment shall be free from any attachment for antennas, signs, Exterior Oil-insulated
streamers and the like. Transformer
Trench all
7.3 Metallic sheaths or jackets of overhead power or communication cables around
shall be grounded at a point as close as possible to ground level
whenever such cables change from overhead to underground
installations.
1.85 m
300mm
8.3 Askarel-Insulated Transformers Installed Indoors. Askarel-insulated
transformers rated in excess of 25 KVA shall be furnished with a pressure
relief vent. Where installed in a poorly ventilated place they shall be
furnished with a means for absorbing any gases generated by arcing inside
the case, or the pressure relief vent shall be connected to a chimney or flue
which will carry such gases outside the building. Askarel-insulated
transformers rated more than 35,000 volts shall be installed in a vault.
14
8/11/2016
9.4 Doorways. Any doorway leading from the vault into the building shall be
protected as follows: 2. ARRANGEMENT. Vaults ventilated by natural circulation of air may have
roughly half of the total area of openings required or ventilation in one or more
openings near the floor and the remainder in one or more openings in the roof
1. TYPE OF DOOR. Each doorway shall be provided with a tight-fitting
or in the sidewalls near the roof; or all of the area required for ventilation may
door of a type approved for openings in such locations by the authority
be provided in one or more openings in or near the roof.
enforcing this Code.
3. SIZE. In the case of vaults ventilated to an outdoor area without using ducts or
2. SILLS. A door sill or curb of sufficient height to confine within the
flues the combined net area of all ventilating openings after deducting the area
vault, the oil from the largest transformer shall be provided and in no
occupied by screens, grating, or louvers, shall be not less than 0.006 sqmm per
case shall the height be less than 100mm.
KVA of transformer capacity in service, except that the net area shall be not
less than 0.1 sqm for any capacity under 50 KVA.
3. LOCKS. Entrance doors shall be equipped with locks, and doors shall
be kept locked, access being allowed only to qualified persons. Locks
4. COVERING. Ventilation openings shall be covered with durable gratings,
and latches shall be so arranged that the door may be readily and
screens, or louvers, according to the treatment requirement required in order to
quickly opened from the inside.
avoid unsafe conditions.
10. Ventilation. Ventilation shall be adequate to prevent a transformer temperature 5. DAMPERS. Where automatic dampers are used in the ventilation openings of
in excess of the prescribed values. vaults containing oil-insulated transformers, the actuating device should be
made to function at a temperature resulting from fire and not a temperature
1. LOCATION. Ventilation openings shall be located as far away as which might prevail as a result of an overheated transformer or bank of
possible from doors, windows, fire escapes and combustible material. transformers. Automatic dampers should be designed and constructed to
minimize the possibility of accidental closing.
15
8/11/2016
11. Capacitors.
6. DUCTS. Ventilating ducts shall be constructed of fire resistant material.
1. Application. This section applies to installation of capacitors on electric
7. DRAINAGE. Where practicable, vaults containing more than 100KVA circuits in or on buildings.
transformer capacity shall be provided with a drain or other means which will Exception No. 1. Capacitors that are components of other apparatus shall
carry off any accumulation of oil or water in the vaults unless local conditions conform to the requirements for such apparatus.
make this impracticable. Exception No. 2. Capacitors in hazardous locations shall comply with
additional requirements in PEC Section 400-415.
8. WATER PIPES AND ACCESSORIES. Any pipe or duct system foreign to the
electrical installation should not enter or pass through a transformer vault. 2. Location. An installation of capacitors in which any single unit contains
Where the presence of such foreign system cannot be avoided, appurtenances more than three gallons of combustible liquid shall be in a vault conforming
thereto which require maintenance at regular intervals shall not be located to part C of PEC Section 319.
inside the vault. Arrangements shall be made where necessary to avoid
possible trouble from compensation, leaks and breaks in such foreign system. 3. Mechanical Protection. Capacitors shall be protected from physical damage
by location or by suitable fences, barriers or other enclosures.
Piping or other facilities provided for fire protection or for water-cooled
transformers are not deemed to be foreign to the electrical installation.
4. Cases and Supports. Capacitors shall be protected from physical damage by
location or by suitable fences, barriers or other enclosures.
1. The provisions of this Section shall apply to the installation, operation and
maintenance of circuits, systems and equipment intended to supply 4. Tests and Maintenance
illumination and power in the event of failure of the normal supply or in the
event of accident to elements of a system supplying power and illumination a. The authority having jurisdiction shall conduct or witness a test on the
essential for safety to life and proper where such systems or circuits are complete system upon completion of installation, and periodically afterwards.
required by the Fire Code, or by any government agency having jurisdiction.
b. Systems shall be tested periodically in accordance with a schedule acceptable
Emergency systems are generally installed in places of assembly where to the authority having jurisdiction to assure that they are maintained in proper
artificial illumination is required, such as buildings subject to occupancy by operating condition.
large numbers of persons, hotels, theaters, sports arenas, hospitals and similar
institutions. Emergency systems provide power for such functions as c. Where the battery systems or unit equipment are involved, including
refrigeration, operation of mechanical breathing apparatus, ventilation batteries used for starting or ignition in auxiliary engines, the authority having
essential to maintain life, illumination and power for hospital room, fire alarm jurisdiction shall require periodic maintenance.
systems, fire pumps, industrial processes where current interruption would
produce serious hazards, public address systems and other similar functions. d. A written record shall be kept of such tests and maintenance.
5. Emergency systems shall have adequate capacity and rating for the emergency
2. All requirements of this Section shall apply to emergency systems. operation of all equipment connected to the system.
3. All equipment for use on emergency systems shall be properly approved.
6. Current supply shall be such that in the event of failure of the normal supply to
or within the building or group of buildings concerned, emergency lighting or 8. A generator set driven by some form of prime mover, with sufficient capacity
emergency power, will be immediately available. The supply system for and proper rating to supply circuits carrying emergency lighting or lighting and
emergency purposes may be composed one or more of the types of systems power, equipped with suitable means for automatically starting the prime mover
covered in Section 12.7 to Section 12.10 of this Rule. Unit equipment in on failure of the normal service shall be provided. For hospitals, the transition-
accordance with Section 12.21 shall satisfy the applicable requirements of this time from instant of failure of the normal power source to the emergency
Section. generator source shall not exceed ten seconds. (See Section 12.4)
Consideration must be given to the type of service to be rendered; whether for 9. There shall be two services, each in accordance with Section 200 of the PEC,
short duration, as for exit lights of a theater, or for long duration, as for widely separated electrically and physically to minimize the possibility of
supplying emergency power and lighting during long periods of current failure simultaneous interruption of power supply arising from an occurrence within
from trouble either inside or outside the buildings, as in the case of a hospital. the building or group of buildings served.
Assignment of degree of reliability of the recognized emergency supply system 10. Connections on the line side of the main service shall be sufficiently separated
depends upon the careful evaluation of the variables of each particular from said main service to prevent simultaneous interruption of supply through
installation. an occurrence within the building or group of buildings served.
7. A storage battery of suitable rating and capacity shall supply, by means of a 11. The requirements of Section 12.5 and Section 12.6 also apply to installations
service installed according to Section 200 of the PEC and maintained at not where the entire electrical load on a service or sub-service is arranged to be
more than 90 per cent of system voltage, the total load of the circuits supplying supplied from a second source. Current supply from a standby power plant
emergency lighting and emergency power for a period of at least hour. shall satisfy the requirements of availability in Section 12.6.
16
8/11/2016
c. To indicate when a battery charger is properly functioning. b. Two or more separate and complete systems with independent power
supply, each system providing sufficient current for emergency lighting
13. Only appliances and lamps specified as required for emergency use shall be purposes. Unless both systems are used for regular lighting purposes
supplied by emergency lighting circuits. and are both lighted, means shall be provided for automatically
energizing either system upon failure of the other. Either or both
14. Emergency illumination shall be provided for all required exit lights and all systems may be part of the general lighting system of the protected
other lights specified as necessary for sufficient illumination. occupancy if circuits supplying lights for emergency illumination are
Emergency lighting systems should be so designed and installed that the installed in accordance with other Section of this Rule.
failure of any individual lighting element, such as the burning out of a light
bulb, shall not leave any area in total darkness. 16. For branch circuits which supply equipment classed as emergency, there shall
be an emergency supply source to which the load will be transferred
automatically and immediately upon the failure of the normal supply.
17. Emergency circuit wiring shall be kept entirely independent of all other wiring and
equipment and shall not enter the same raceway, box or cabinet with other wiring 20. Lights on the exterior of the building which are not required for illumination
except: when there is sufficient daylight may be controlled by an automatic light
a. In transfer switches, or actuated device approved for the purpose.
b. In exit or emergency lighting fixtures supplied from two (2) sources.
21. In hospital corridors, switching arrangements to transfer corridor lighting in
18. The switches installed in emergency lighting circuits shall be so arranged that only patient areas of hospitals from overhead fixtures to fixtures designed to provide
authorized persons have control of emergency lighting, except: night lighting maybe permitted, provided that the switching system is so
a. Where two or more single throw switches are connected in parallel to designed that switches can only select between two sets of fixtures but cannot
control a single circuit, at least one of those switches shall be accessible extinguish both sets at the same time.
only to authorized persons.
b. Additional switches which act only to put emergency lights into operation 22. The branch circuits over current devices in emergency circuits shall be
but not to disconnect them may be permitted. accessible to authorized persons only.
Switches connected in series and three- and four-way switches shall not be 23. Where permitted by the authority having jurisdiction, in lieu of other methods
allowed.
specified elsewhere in this Section, individual unit equipment for emergency
illumination shall consist of:
19. All manual switches for controlling emergency circuits shall be located at the most
accessible place to authorized persons responsible for their actuation. In places of
assembly, such as theaters, a switch for controlling emergency lighting systems a. Battery
shall be located in the lobby or at a place conveniently accessible there from. In b. Battery charging means, when a storage battery is used
no case shall a control switch for emergency lighting in a theater for motion c. One or more lamps, and
picture projection be placed in the projection booth or on the stage. However, d. A relaying device arranged to energize the lamps automatically upon
where multiple switches are provided, one such switch may be installed in such failure of the normal supply to the building
locations and so arranged that it can energize but not disconnect for the circuit.
The batteries shall be of suitable rating and capacity to supply and maintain, at not
less than 90 per cent of rated lamp voltage, the total lamp load associated with the
unit for a period of at least hour. Storage batteries, whether of the acid or alkali
type, shall be designed and constructed to meet the requirements of emergency
service. Lead-acid type storage batteries shall have transparent jars.
Unit equipment shall be permanently fixed in place and shall have all wiring to each
unit installed in accordance with the requirements of any of the wiring methods
THANK YOU
discussed in Chapter II of the PEC. They shall not be connected by flexible cord. The
supply circuit between the unit equipment and the service, the feeders or the branch
circuit wiring shall be installed as required by Section 12.17. Emergency illumination
fixtures which obtain power from a unit equipment which are not part of the unit
equipment shall be wired to the unit equipment as required by Rule 5257 of the PEC
and in accordance with the one of the wiring methods described in Chapter II of the
PEC.
13. Effectivity
1. All primary and secondary supply lines already existing shall comply with the
provisions of this Rule within two (2) years from the effectivity of this Rule.
2. Transformers to be installed on, attached to, or in buildings shall comply with the
requirements of this Rule. Transformer installations already existing shall comply with
the requirements within two (2) years from the effectivity of this Rule.
3. Non-compliance with the provisions of this Rule shall be subject to the penal
provisions in Section 213 of PD 1096.
17