Вы находитесь на странице: 1из 17

8/11/2016

1. GENERAL

1.1 DEFINITION OF ELECTRICITY

a form of energy generated by


friction, induction or chemical
change, having magnetic, chemical
and radiant effect.

ELECTRICAL SYSTEMS
the motion of free electrons through
a solid conductor.

1.2 SOURCES OF ELECTRICITY

STORAGE BATTERIES

GENERATORS

STORAGE BATTERIES
GENERATORS

for generating electric current

Alternating Current Generators or


Alternators The bulk of electrical energy
utilized today is in the form of alternating
current, including energy for power and
lighting.

are used to supply emergency


lighting circuits for hallways, Direct Current Generators These
stairways, exits and to energize furnish electrical energy for elevators,
police and fire alarm systems escalators, intercommunicating telephone
and certain types of signal systems, control of signal systems, and
systems. clock systems.

1.4 TYPES OF CURRENT


1.3 OTHER DYNAMO ELECTRIC
MACHINES
ALTERNATING CURRENT a DIRECT CURRENT a current
current which is periodically which flows at a constant time rate
varying in time rate and in and in the same direction.
direction. It rises from zero to
maximum, falls to zero, reverses
its direction and again returns to
zero.

MOTORS for converting


electrical energy to mechanical
energy.
TRANSFORMERS for
converting one voltage to
another, from lower to higher
or from higher to lower
ROTARY CONVERTERS
for changing alternating
current to direct current and
vice versa.

1
8/11/2016

1.5 UNITS OF ELECTRICITY UNIT OF RESISTANCE

UNIT OF QUANTITY
OHM The resistance which will
COULOMB a coulomb of electricity allow one ampere of current to flow
comprises approximately 6.25 x 10 18 when one volt is impressed upon it.
electrons.

AMPERE An ampere of current UNIT OF ELECTRIC POWER


represents a rate of flow of one
coulomb or 6.25 x 10 18 WATT the unit of electric
electrons/second through a given power or the rate of doing
cross section. electrical work.

UNIT OF ELECTRIC POTENTIAL


UNIT OF ENERGY

VOLT is the electromotive force


or potential difference between two WATT-HOURS the unit of
points in an electric field which will energy or the capacity for doing
move a charge of one coulomb work.
between these points.

1.7 ELECTRIC LOAD CONTROL


1.6 OHMS LAW is the effective utilization of available
energy by reducing peak loads and
lowering demand charge. The control
I (amp) = V (Volts) / R (Ohms) devices and systems are referred to as
load shedding control, peak demand
control, peak load regulation, and power
use control.
LOAD SCHEDULING AND DUTY-
The current, I, that will flow in a CYCLE CONTROL the installations
d-c circuit is directly proportional to electric loads are analyzed and scheduled
the voltage ,V, and inversely to restrict demand by shifting large loads
proportional to the resistance , R, to off-peak hours and controlled to avoid
coincident operation.
of the circuit.

DEMAND METERING ALARM in


conjunction with a duty cycle controller,
demand is continuously metered and an
alarm is set on when a predetermined
demand level is exceeded.

AUTOMATIC INSTANTANEOUS 1.8 MEASURING ELECTRIC CONSUMPTION


DEMAND CONTROL also called rate
control, it is an automated version of the
CURRENT
LEADS

demand metering alarm system, where it


automatically disconnects or reconnects loads KWH METERS To
LOAD
POWER

as required.
SOURCE

measure energy, the


WM

factor of time is
VOLTAGE
LEADS

introduced, such that;


WATTMETER

IDEALCURVE CONTROL This controller energy = power x


operates by comparing the actual rate of time. A-C electric
energy usage to the ideal rate, and controls meters are basically
KW demand by controlling the total energy small motors, whose
used within a metering interval. speed is proportional
to the power being
used. The number of
rotations is counted on
FORECASTING SYSTEMS are the dials which are
computerized systems which continuously calibrated directly in
forecast the amount of energy remaining in kilowatt-hours.
the demand interval, then examine the status
and priority of each of the connected loads
and decide on the proper course of action.

2
8/11/2016

2. BUILDING ELECTRICAL SYSTEMS


R1 R2
10 amp 10 amp

2.1 BRANCH CIRCUITS SERIES CIRCUIT is one in which the


components are connected in tandem. All
An electrical circuit may be defined as a
separate loads of the circuit carry the
R3
ELEC
complete conducting path carrying current SOURCE

from a source of electricity to and through same equal current and the total
some electrical device or load and back to the 10 amp
10 amp
resistance, R, is the sum of the
resistances around the circuit.
R5 R4

source. The two wire circuit, which is the CIRCUIT IN SERIES

most elementary of all wiring systems, R = R1 + R2 + R3 + R4 + R5

consists of a live wire carrying the current to


the various power consuming devices in the PARALLEL CIRCUIT (or Multiple
circuit and a neutral or grounded wire which Circuit) is one in which the
is the return wire carrying the circuit back to
3 amp

components or loads are so arranged


the source of supply.
1 amp 1 amp 1 amp

that the current divides between them.


+

Each outlet has a live wire connected to


ELECTRICAL R1 R2 R3
SOURCE

the current carrying wire of the circuit


SERIES CIRCUIT and also a neutral wire or grounded wire
connected to the return wire of the
CIRCUIT IN PARALLEL

1
PARALLEL CIRCUIT
R= circuit. With this system, the total current
1/R1 + 1/R2 + 1/R3
flowing through the circuit is the sum of
the current flowing through each outlet.

CLASSIFICATIONS OF BRANCH CIRCUITS Branch Circuit


The portion of an electrical
system extending from the final

General Purpose Branch Circuit -


overcurrent device protecting a
circuit to the outlets served by
GENERALLY LTG A supplies outlets for lighting and the circuit General Purpose Circuit
A branch circuit that supplies
appliances, including convenience
15, 20A
current in a number of outlets for
receptacles. lighting and appliances

Appliance Circuit
A branch circuit that supplies
current in one or more outlets
specifically intended for
appliances

Appliance Branch Circuit - supplies Individual Circuit


outlets intended for feeding appliances.
15, 20, 30, A A A branch circuit that supplies
or 50A

Fixed lighting is not supplied.


current only to a single piece of
electrical equipment
Distribution Panel
A panel for distributing
power to other panels or to
motors and other heavy
power-consuming loads.
Controls, distributes and
Individual Branch Circuit - is protects a number of similar
Low-Voltage
designed to supply a single specific item,
branch circuits in an
SIZE RE QUIRED electrical system Of or pertaining to a circuit in which alternating
SINGLE ITEM

such as a motor load or a unit air-


FOR ITEM FED current below 50 volts is supplied by a step-down
transformer form the normal line voltage used in
conditioner. residential systems to control doorbells,
intercoms, heating and cooling systems and
remote lighting fixtures. Low-voltage circuits do
not require a protective raceway

GENERAL CIRCUITING GUIDELINES


3. Convenience receptacles in an area
shall be wired to at least two
different circuits so that in case of
failure in any one of the circuits, the
1. General: Branch circuits shall be
sufficient to supply a load of 30 entire area will not be deprived of
power.
watts per square meter (3 watts per
square foot) in buildings excluding
porches, garages and basements.
4. General purpose branch circuits shall
be rated at 20 amperes wired with
No. 12 AWG minimum. Switch legs
20 amp
C3

C3

C3

may be No. 14 AWG if the lighting


2. In all but the smallest installations, load permits.
connect lighting, convenience
receptacles, and appliances in
DINE

separate circuits. The Code requires a


KIT

20 amp

minimum of 2 - 20 amperes 5. Limit the circuit load for lighting and


C1
Range Ref

appliance branch circuit to feed all small appliances on 15 amp and 20


C4

C2

small appliance outlets in the kitchen, amp circuit loads and on 15 and 20
pantry, dining and family room. amp overcurrent devices respectively.

3
8/11/2016

2.2 SINGLE PHASE ELECTRICAL SYSTEMS 2.2 THREE PHASE ELECTRICAL SYSTEMS
For homes and small commercial buildings For industries and large commercial buildings
The Three Phase AC electricity is a Triple
A single phase electrical system can Circuit. The lighting and outlet loads are
either be 2-wire or 3-wire and connected between any phase leg and a
composes two hot legs and a neutral A B C
neutral line. While machineries and other
wire. bigger loads are connected to the phase leg
SWITCH FUSE
A
only.
B
Three-Wire Three Phase AC
A-B 220V A-C 220V

Two-Wire Single Phase DC or AC


C
B-C 220V

MOTOR

110 V

Three-Wire Single Phase DC


(EDISON SYSTEM) Four-Wire Three-Phase AC
F
220 V
A N B C

110 V Three-Wire Single Phase AC

220V 220V 110V


220V 11
0V
110V

Service
The supplying of utilities required

2.3 COMPONENTS OF THE BUILDING ELECTRICAL SYSTEM


or demanded by the public
Substation
An auxiliary power station
where electrical current is
converted or where voltage
is stepped up or down
Line Drop
The decrease in voltage between
two points on a power line,
usually caused by resistance or
leakage along the line

Service Entrance Conductor Service Drop


The portion of a service conductor extending The overhead portion of service
from a service drop or service lateral to the conductors extending from the
service equipment of a building nearest utility pole to a building
Service Lateral
Watt-Hour Meter
The underground portion of service
A meter for measuring and recording the
conductors extending from a main
quantity of electric power consumed with
power line or transformer to a
respect to time
building Feeder
Transformer Vault Switchgear Room Any of the conductors
A fire-rated room housing Contains the service extending from the
a transformer and equipment for a large service equipment to
auxiliary equipment for a building various distribution
large building points in a building
Service Equipment
Equipment necessary for
controlling, metering and
protecting the electric
Standby Generator
power supply to a builidng
For providing emergency power
during a power outage. Switchboard Unit Substation
One or a group of panels on A freestanding enclosure
Uninterruptible Power Supply which are mounted switches, housing a disconnect
An emergency system designed overcurrent devices, switch, a step-down
to provide pwer automatically and metering instruments and transformer and
instantaneously buses switchgear

Service Conductors extend from a main power


line or transformer to the service equipment of a
building
Servcie Drop
The overhead portion of service conductors extending
from the nearest utility pole to a building
Servcie Lateral
The underground portion of service conductors extending
Direct burial cable may be used for from a main power line or transformer to a building
residential service connections Servcie Entrance Conductor
Lightning Rod The portion of a service conductor extending from a service
drop or service lateral to the service equipment of a building
Any of several conducting rods installed at the A transformer is used by medium-sized and large buildings to step
top of a structure and grounded to divert down from a high supply voltage to the service voltage. To reduce
costs, maintenance and noise and heat problems, a transformer
lightning away from the structure. Also called air Watt-Hour Meter
may be placed on an outdoor pad. If located within a building, oil-
terminal filled transformers require a well-ventilated, fire-rated vault with
Measures and records the quantity of electric power
consumed with respect to time. Supplied by the public utility,
two exits and located on an exterior wall adjacent to the it is always placed ahead of the main disconnect switch so
Lightning Arrester switchgear room. Dry-type transformers used in small- and that it cannot be disconnected
A device for protecting electric equipment from medium-sized buildings may be replaced together with a
disconnect switch and switchgear in a unit substation For multiple-occupancy buildings, banks of meters are
damage by lightning or other high-voltage installed so that each unit can be metered
currents, using spark gaps to carry the current independently
to the ground without passing through the The service switch is the main
disconnect for the entire electrical
device Grounding Rod or Electrode
system of a building, except for any
Is firmly embedded in the earth to establish a ground
emergency power systems.
Spark Gap connection
A space between two terminals or electrodes The service equipment includes a main To panelboards
across which a discharge of electricity may pass disconnect switch and secondary
at a prescribed voltage switches, fuses and circuit breakers for
controlling and protecting the electric
power supply to a building. It is located
in a switchgear room near the entrance
of the service conductors

The main switchboard is a panel on


which are mounted switches,
overcurrent devices, metering
instruments and busbars for controlling,
distributing and protecting a number of
electric circuits

4
8/11/2016

FEEDER CIRCUITS A feeder circuit


SERVICE ENTRANCE the point of is a set of conductors which extends
delivery of electricity to a building by a from the main switchboard to a
public utility company. distributing center (panel board) with no
other circuits connected to it between
the source and the distributing center.

SUB-FEEDER CIRCUITS are line


MAIN SWITCHBOARD The service extensions of a feeder, fed through a
entrance conductors in the form of bus panel board or cut-out, or from one
bars terminates in the main switchboard distributing center to another and having
and connects to the distribution panel no other circuit connected to it between
boards by means of feeder circuits the two distributing centers. A sub-feeder
protected by circuit breakers. The main serves to distribute power from the main
switchboard serves for the control, feeders to smaller local panel boards,
protection and metering of the main called sub-panel boards.
feeders.

Fuse
A device containing a strip or
wire of fusible metal that melts
under the heat produced by
Service Switch excess current thereby

BRANCH CIRCUITS These are


The main disconnect for the entire interrupting the circuit
electrical system of a building
small capacity conductors which deliver except for any emergency power

energy to lamps, motors and other loads


systems

within the circuit.


Panel
A board on which are mounted
the switches, fuses and circuit
breakers for controlling and
protecting a number of similar

PANEL BOARDS AND SUB-PANEL


branch circuits installed in a
cabinet and accessible from
BOARDS (also called CUT-OUTS) These the front only. Also called a Circuit Breaker
serve to control and protect the sub
panelboard. A switch that automatically interrupts an electric
circuit to prevent excess current from damaging
feeders and branch circuits. Bus apparatus in the circuit or from causing a fire. A
A heavy conductor, usually in the form of a circuit breaker may be reclosed and reused without
solid copper bar, used for collecting, carrying replacement of any components. Also called a
and distributing large electric currents. Also breaker.
called a busbar

UTILIZATION EQUIPMENT These


Grounded Conductor
Any conductor of an electrical system
are the lighting, power and motor loads intentionally connected to a ground

and wiring devices which are directly


connection

handled and utilized by users. Grounding Electrode


A conductor, as a metal ground rod,
Ground Wire
A conductor connecting
ground plate or cold-water pipe, firmly
electric equipment or a
embedded in the earth to establish a circuit to a ground
gorund connection
connection. Also called a
grounding conductor

2.4 ILLUSTRATING THE COMPONENTS OF THE BUILDING


ELECTRICAL SYSTEM

HIGH-VOLTAGE SINGLE LINE


DIAGRAM When
PRIMARY FEEDERS
2,400, 4,160, 7,200

electrical symbols
OR 13,200 VOLTS

BLOCK DIAGRAM
are used
A horizontal single line MAIN DISTRIBUTION
in lieu of the
SECONDARY SERVICE

diagram of the buildings


FEEDERS PANELS
CONDUCTORS
blocks, it is called
MAIN RECEPTACLES
LIGHTING
electrical system from the TRANSFORMER SWIT
SWITCH

a one line or a
120/208 OR BOARD MOTOR
VAULT
incoming service to the
PANELS

single line
120/240 OR
SWITCHES 227/480 VOLTS
utilization items at the end
LARGE
LIGHTING/

diagram.
TRANSFORMER APPLIANCE
MOTOR
of the system where the
FUSES PANELS SMALL

major electrical
BRANCH MOTORS &
CIRCUIT CONTROL

components are shown as


blocks or rectangles.

5
8/11/2016

2.5 EMERGENCY ELECTRIC SUPPLY


SYSTEM
ELEVATORS
PP MACHINE
MR ROOM ROO
ROOF

LP
5A 5B
5C

RISER Emergency Systems provide electric


DIAGRAM power and illumination essentially for life
4A 4B
4C

LEFT Is a vertical line safety and protection of property during


diagram of the an emergency, such as, electricity for exit
3A 3B 3C
RISER CENTRAL RISER SHAFT
2A 2B major electrical lighting, elevators, fire alarm systems,
fire pumps and the like.
2C
RIGHT RISER components of
the buildings
1A LP 1B
1C

electrical system
LOBBY

presented
showing the
SPARE M.C.C.

spatial relations
MACHINE ROOM

FIRE ALARM
between Standby Systems provide power to
FA PANEL components. selected loads not directly involved with
STAIR AND EXIT
life safety, such as, water and sewage
LPSE
PANEL
M METERING treatment plants and industrial machines
for manufacturing processes.

EMERGENCY POWER EQUIPMENT EMERGENCY WIRING SYSTEMS


USING THE BATTERY

Small emergency appliance connected


Battery Equipment Central storage direct to a storage battery
batteries are mounted in individual racks
and always provided with automatic
charging equipment.
Groups of emergency loads
connected to central storage battery
through automatic device

Engine-Generator Sets are machines Emergency equipment loads are


intended to produce electricity and entirely separate from normal loads
composed of three components: the and are generally de-energized. The
machine and its housing (if any), fuel contactor is activated when it senses
storage tank and the exhaust facilities. power loss.

EMERGENCY WIRING SYSTEMS 3. ELECTRICAL MATERIALS AND EQUIPMENT


USING THE GENERATOR
3.1 CONDUCTORS
are materials which allow the free
Emergency system handled by a flow of electrons through them.
single transfer switch which
automatically turns on when it senses Wires are single insulated
power loss at its downstream location. conductors No. 8 AWG (American Wire
Gauge or smaller; for the English
Emergency system handled by System, it is the B & S Gauge or
multiple switches Browne and Sharpe Gauge. The
smallest size of wire permitted is No.
14.
Emergency service totally separated
Cables are single insulated
from normal through its own emergency
conductors No. 6 AWG or larger; or
service entrance, coming from different they may be several conductors of
transformers or feeders.
any size assembled into a single unit.

Bus Bars large conductors which


Same as above, but both service are not circular in cross section and
entrances supply normal loads and usually found only to supply the main
each act as standby for each other. switch boards.

6
8/11/2016

CONDUCTOR SIZES
AWG/MCM STANDARD CONDUCTOR AMPACITY
All conductor sizes from No. 16 to
No. 0000 (also designated 4/0) are
expressed in AWG.
Beyond AWG No. 4/0, a different Conductor current carrying capacity or
designation, MCM (or thousand circular mil) ampacity is the maximum operating
is used. In this designation, the smallest temperature that its insulation can stand
MCM size is 250 MCM or and the continuously. Heat is generated as a
biggest is 500 MCM. result of the current flowing and the
A circular MIL is an artificial area conductor resistance. When conductors
measurement, representing the square of are placed in an enclosed conduit, the
the cable diameter (diam2) when the heat generated is not as easily
diameter is expressed in mils (thousands of dissipated as it would be if the conductor
an inch). Thus a solid conductor inch in were free in the air. Thus, the current
diameter is 500 mils in diameter, or rating of a conductor in free air is much
250,000 circular mils in area, (500)2 or higher than that for the same were it in
250 MCM; thus; a conduit.
CM/1000 = diam2 = (500)2/1000 =
250,000/1000 = 250 MCM
In the metric system, conductor sizes are
given simply as the diameter in millimeters
(mm).

TYPES OF CABLES
Armored Cable (Type AC) a fabricated Shielded Non-Metallic Sheathed Cable
assembly of insulated conductors (Type SNM) a factory assembly of two
enclosed in flexible metal sheath. or more insulated conductors in an
extruded core of moisture resistant and
Metal Clad Cable (Type MC) a factory flame retardant material covered within
assembled cable of one or more an overlapping spiral metal tape.
conductors each individually insulated
Underground Feeder and Branch Circuit
and enclosed in a metallic sheath of
interlocking tape of a smooth or Cable (Type UF) a moisture resistant
corrugated tube. cable used for underground connections
including direct burial in the ground as
Mineral Insulated Cable (Type MI) a feeder or branch circuit.
factory assembled conductor/s insulated Service Entrance Cable (Type SE or
with a highly compressed refractory USE) a single or multi-conductor
mineral insulation enclosed in a liquid and assembly provided with or without an
gas tight continuous copper sheath.
overall covering primarily used for service
Non-Metallic Sheathed Cable (Type NM wire.
or NMC) also known by the trade Power and Control Tray Cable (Type TC) a
name ROMEX, is a factory assembly of factory assembled two or more insulated
two or more insulated conductors having conductors with or without associated bare
a moisture resistant, flame retardant, or covered grounding under a metallic sheath
and non-metallic material outer sheath. and is used for installation in cable trays,
raceways, or where supported by wire.

Flat Cable Assemblies (Type FC) an 3.2 INSULATORS


assembly of parallel conductors formed
integrally with an insulating material web INSULATORS are materials which
designed specially for field installation in prevent the flow of electrons through
square structural channels. them.

Flat Conductor Cable (Type FCC)


consists of three or more flat copper
conductors placed edge to edge
separated and enclosed within a
insulating assembly. This type of cable
is used for appliance or individual
branch circuits installed inside floor
surfaces.

Medium Voltage Cable (MV) a


single or multi-conductor solid dielectric
insulated cable rated at 2,000 to
35,000 volts. Trade name is Medium
Voltage Solid Dielectric.

7
8/11/2016

TYPES OF INSULATORS 3.3 CONDUITS


General Wiring
CONDUITS are circular raceways used
to enclose wires and cables and are of
metal or plastic (PVC).
Trade name Type Maximum Application
Letter Operating Provisions
Temperatur
e
To protect the enclosed conductors
Moisture-& heat-resistant RHW 75O C Dry and wet
from mechanical injury and chemical
damage.
rubber 167O F Locations
Thermoplastic T 60OC Dry locations
140O F
Moisture-resistant TW 60O C Dry and wet
To protect people from shock hazards
by providing a grounded enclosure.
thermoplastic 140O F Locations
Heat-resistant THHN 90O C Dry locations
thermoplastic 194O F

To provide a system ground path.


Moisture-& heat-resistant THW 75O C Dry and wet
thermoplastic 167O F Locations
Moisture-& heat-resistant THW N 75O C Dry and wet
thermoplastic 167O F Locations
Moisture-& heat resistant XHHW 90O C Dry locations To protect the surroundings against fire
hazard as a result of overheating or short
cross-linked 194O F Wet
thermosetting 75O C locations
polyethelene 167O C circuiting of the enclosed conductors.
Silicone-asbestos SA 90O C Dry locations

To support the conductors.


194O F
Asbestos and Varnished AVA 110O C Dry locations
Cambric 230O F only

TYPES OF STEEL CONDUITS 3.4 RACEWAYS are channels or


wiring accessories so designed for
Heavy-wall steel conduits called Rigid holding wires, cables and bus bars that
Steel Conduits or RSC with an are either made of metal, plastic, or any
approximate thickness of 0.117 mm. insulating medium.

Intermediate Metal Conduit or IMC with


thickness of 0.071 mm.

Thin-wall steel conduits named Electric


Metal Tubing or EMT.

RSCs and IMCs use the same fitting, called


condulets, and are threaded alike at the
joints. EMTs are not threaded but use set
screw and pressure fitting and are not
recommended for embedding in concrete
nor permitted in hazardous areas. IMCs
yield a larger inside diameter (ID) for
easier wire pulling and is lighter than the
RSC.
Standard length of steel conduits is 3 M or
10 ft.

Lighting Outlet is an outlet intended


3.5 OUTLETS and RECEPTACLES for direct connection to a lamp holder,
An outlet is a point in the wiring system lighting fixture, or pendant cord
at which current is taken to supply terminating in a lamp holder.
utilization equipment. It refers only to
the box. A receptacle is the wiring
device in which the utilization
equipment (appliance) cord is plugged
into.

Convenience Outlet or Attachment


Cap - the complete set-up which Receptacle Outlet is an outlet where
establishes connection between the one or more receptacles are installed.
conductor of the flexible cord and the
conductors connected permanently to
the receptacle.

8
8/11/2016

3. Wiring Switches include all the


3.6 SWITCHES are devices for making,
relatively small switches that are
breaking, or changing conditions in an TYPE OF SWITCH - ACCORDING
employed in interior wiring
electrical circuit under the conditions of TO TYPE OF SERVICE
installations for the control of
load which they are rated.
branch circuits, individual lamps or
TYPE OF SWITCH ACCORDING 1. Service Switch intended to appliances.
disconnect all the electric service in
TO VOLTAGE a) Generalpurpose switches are
Switches are rated as 250V, 600V,or 5KV the building except emergency
equipment. This may comprise one to single-pole or double-pole switches
as required. for the general purpose use of
six properly rated switches that are
TYPE OF SWITCH ACCORDING assembled into a switchboard. connecting or cutting-off circuits for
TO INTENSITY OF USE the control of lamps or other loads
2. Power Switches from a single point.
1. Normal Duty (ND) intended for
normal use in light and power circuits a) General purpose switches are b) Three-way switches are used
as in general-purpose switches. intended for use in general where it is desired to control lamps
distribution and branch circuits. from two different points, as in a
2. Heavy Duty (HD) intended for stairwell.
frequent interrupting. b) Disconnecting or isolating switches
are intended for disconnecting or c) Four-way switches are used in
3. Light Duty (LD) intended to connect isolating circuits; used for circuits conjunction with two 3-wire switches
the loads occasionally, such as service rated at more than 600 volts. where it is desired to control lamps
switches. from three or more desired points.

TYPE OF SWITCH - ACCORDING TO


d) Electrolier or multi-circuit switches OPERATION MECHANISM
are used for the control of lights in SPECIAL SWITCHES
Wiring switches may also be classified
multi-lamp fixtures so that one
according to the operating mechanism 1. Time Controlled Switches This 5. Float Switch a switch controlled by
lamp or set of lamps may be turned as: device comprises a precision low a conductor floating in a liquid.
on alone or in combination with 1. Rotary switch speed miniature drive motor (timer)
other lamps. 2. Push-button switch to which some type of electric 6. Mercury Switch an especially quiet
3. Toggle or tumbler switch contact-making device is connected. switch that opens and closes an electric
e) Momentary contact switches are
circuit by shifting a sealed glass tube of
used where it is desired to connect TYPE OF SWITCH - ACCORDING TO 2. Remote Control (RC) Switches A mercury so as to uncover or cover the
or cut-off a circuit for only a short NUMBER OF POLES AND THROWS contactor[1], or more specifically, a contacts.
duration. The switch is provided
with a spring so that it will return to
relay[2], that latches after being
1. Poles that part of the switch which is operated wireless from a distance. 7. Key Switch a switch operated only
its original position as soon as the used for making or breaking of a by inserting a key or a card. Also called
handle or button is released. connection and which is electrically 3.Air Switch a switch in which the a card switch.
insulated from other contact making or interruption of a circuit occurs in air.
f) Dimmer switches a rheostat[1] or
breaking parts. 8. Automatic Transfer Switch (ATS)
similar device for regulating the
4. Knife Switch a form of air switch in This device, an essential part of an
intensity of an electric light without
2. Throws - a single throw switch is one which a hinged copper blade emergency or standby service, is
appreciably affecting spatial
which will make a closed circuit only is placed between two basically a double throw switch,
distribution. Also called a dimmer.
when the switch is thrown in one contact clips. generally 3-pole, so arranged that on
Wiring switches may either be the
position. A double throw switch will failure of normal power, emergency
flush type, surface type or the
make a closed circuit when thrown in service is automatically supplied.
pendant type.
either of two positions.

3.7 WALL PLATES OR FACEPLATES -


These are coverings for switches and wall 3.8 OVER-CURRENT CIRCUIT
outlets usually made of metal or of PROTECTIVE DEVICES are devices
phenollic compound (Bakelite). whose sole purpose is to protect
insulation, wiring, switches and other
apparatus from overheating or burning,
due to overloads, to faults or to short
circuits, by automatically cutting off the
circuit.

FUSE is a device consisting of an


alloy link of wire with a low melting
temperature which is inserted in the
circuit, in such a way, that all current
which passes through the circuit, must
also pass through this metal.

9
8/11/2016

PANELBOARDS popularly known as


panel or electrical panel, it is simply
the box wherein the protective devises are
housed from which the circuits and bus
CIRCUIT BREAKERS is an over- bars terminate.
current protective device designed to
function as a switch, or it can be
manually tripped and thus act as a
circuit switch. It breaks a circuit with an SWITCHBOARDS are free standing
automatic tripping device without injury assemblies of switches, fuses, and/or
to itself. circuit breakers whose function normally
is to provide switching and feeder
protection to a number of circuits
connected to a main source.

UNIT SUBSTATIONS (Transfer Load


GROUND FAULT CIRCUIT Centers) an assembly of primary switch-
INTERRUPTERS (GFCI or GFI) is fuse-breaker, step-down transformer,
an over current protective device that meters, controls, bus bars and secondary
will provide ground fault protection as switchboard. It is used to supply power
well as function as an ordinary circuit from a primary voltage line to any large
breaker. facility.

4. WIRING SYSTEMS FLEXIBLE METAL CONDUIT


WIRING Its installation is much
4.1 WIRING METHODS easier and quicker than that of rigid
metal conduits. Unlike the rigid conduits
KNOB AND TUBE WIRING an which come in short lengths of 10 ft. (3
obsolete wiring system consisting of
M), flexible metal conduit wiring comes
single insulated conductors secured to in length of 25 ft 250 ft (8 M 83 M)
and supported on porcelain knobs and depending on the size of the conduit.
tubes. When wires run through walls,
they are inserted into a nonmetallic fire- ARMORED CABLE WIRING (BX
resistant tubing called a loom. WIRING) consists of rubber or
thermoplastic covered wire protected
RIGID METAL CONDUIT WIRING
from injury to a certain extent from
is the best and most expensive among
dampness by one or two layers of flexible
the usual type of wiring. Its advantages steel armor.
are:
1. it is fireproof; SURFACE METAL RACEWAY
2. moisture proof; WIRING the wires are supported on a
3. it is mechanically strong so that nails thin sheet steel casing. The raceway is
cannot be driven through it and it is not installed exposed, being mounted on the
readily deformed by blows; walls or ceiling. Metal raceways must be
4. it resists the normal action of cement continuous from outlet to outlet or
when embedded in concrete or masonry. junction box, designed especially for use
with metal raceways.

FLOOR RACEWAYS The NEC


FLAT CABLE ASSEMBLIES a field recognizes three types of floor
installed rigidly mounted square raceways:
structural channel (1 5/8 standard)
designed to carry 2 to 4 conductors (No. 1. Underfloor Ducts (UF) installed beneath
10 AWG) and will act as light duty or flush with the floor. These underfloor
(branch circuit) plug-in busways. ducts usually requires a triple duct
system for power, telephone and
signal cabling.
LIGHTING TRACK a factory-
assembled channel with conductors for 2. Cellular Metal Floor Raceway Found
one to four circuits permanently usually in office landscaping, it is an
installed in the track that will act as integrated structural/electrical system
light duty (branch circuit) plug-in in a cellular metal floor.
busways.
3. Precast Cellular Concrete made of
concrete cells fed from header ducts,
CABLE TRAY / OPEN RACEWAY which are normally installed in concrete
is a continuous open support for fill above the hollow core structural slab
approved cables. When used as a or fed from the ceiling void below. The
general wiring system, the cables cells can be used for air distribution and
must be self-protected, jacketed for piping.
types, type TC.

10
8/11/2016

ELECTRICAL SYMBOLS
CEILING RACEWAY SYSTEMS
under-the-ceiling raceways composed of
FEEDER L LAMP HOLDER PUSH BUTTON

header ducts and distribution ducts BRANCH CIRCUIT-CEILING/WALL


separate for power and telephone cabling.
PS LAMP HOLDER WITH PULL SWITCH BELL

They permit very rapid changes in layouts


BRANCH CIRCUIT-FLOOR
C
CLOCK OUTLET
at low cost and are therefore particularly 3&4 WIRES CIRCUIT NO. BUZZER
MARK INDICATES 2 WIRES
desirable in stores where frequent display
D DROP CORD OUTLET
CH CHIME
transformations necessitate corresponding CROSSING WIRES
F FAN OUTLET
electrical facility adjustments. ANNUNCIATOR
CONNECTING WIRES
R RADIO OUTLET

LIGHTING OUTLET CEILING FLOOR OUTLET LIGHTING PANEL


POWER PANEL
PRE-WIRED CEILING DISTRIBUTION RECESSED CEILING OUTLET
DUPLEX CONVENIENCE OUTLET
FUSE
SYSTEMS are ceiling raceways that are DASH INDICATES SHAPE OF
CONVENIENCE OUTLET SPLIT-WIRED
pre-wired in the factory and plugged in FIXTURE
WEATHER PROOF OUTLET
WH WATT-HOUR METER

where required. WP
T TRANSFORMER
LIGHTING OUTLET WALL OUTLET AND SWITCH
S
J JUNCTION BOX
RANGE OUTLET
R
FLUORESCENT LAMP SPECIAL PURPOSE OUTLET
GROUND

REFRIGERATOR OUTLET
ref

LIGHTING LAYOUT PLAN POWER LAYOUT PLAN

2. Location of Poles and Clearances of Power Lines along Public Roads.


ELECTRICAL REGULATIONS
BY PD 1096
2.1 All poles erected on public roads shall be covered by Approved Pole
Location (APL) plan from the Municipal Engineer.

2.2 Poles and transformer supports shall be located not more than
500mm inside from the road right-of-way or property line, and
1. General Locational Requirements in Towns, shall not obstruct the sidewalk, pedestrian path and/or the road
Subdivisions, Human Settlements, Industrial Estates drainage canal or structure, existing or proposed.
and the like.

Overhead transmission and/or distribution


lines/systems including transformers, poles, towers and Pole
the like shall be located and installed following the
latest standards of design, construction and 500 mm
maintenance but so as not to cause visual pollution and
in the interest of public safety, convenience, good
viewing and aesthetics, these may be located along
Property line
alleys or back streets.

11
8/11/2016

2.5 Clearances of Supporting Structures such as Poles, Towers and


others and their guys and braces measured from the nearest
2.3 Primary lines shall have a minimum vertical clearance of 10 m parts of the objects concerned:
from the crown of the pavement when crossing the highway A. From Fire Hydrants, not less than 5 m.
and 7.5 m from the top of the shoulder or sidewalk when installed B. From the Street Corners, where hydrants are
along the side of the highway or street in a highly urbanized area. located at street corners, poles and towers shall
not be set so far from the corners as to make
necessary the use of flying taps which are
inaccessible from the poles.
C. From Curbs, not less than 150 mm measured from

7.5 m the curb away from the roadway.
10 m

5 m
150 mm

2.4 Secondary, neutral and service lines shall have a minimum vertical
clearance of 7.5 m from the crown of the road pavement when
crossing the highway and from the top of the shoulder or sidewalk
when installed along the side of the highway or street in highly
urbanized area.

4. Open Supply Conductors Attached to Buildings


3. Attachments on and Clearances from Buildings
Where the permanent attachment of open supply conductors of any class to
3.1 Attachments for support of power lines and cables, transformers and other
buildings is necessary for an entrance such conductors shall meet the following
equipment and/or communications lines installed on buildings shall be
requirements:
covered by an Approved Attachment Plan from the local Building Official.
4.1 Conductors of more than 300 volts to ground shall not be carried along or
3.2 Where buildings exceed 15 m in height, overhead lines shall be arranged
near the surface of the buildings unless they are guarded or made
where practicable so that a clear space or zone at least 2 m wide will be
inaccessible.
left, either adjacent to the building or beginning not over 2.5 m from the
building, to facilitate the raising of ladders where necessary for fire
4.2 To promote safety to the general public and to employees not authorized
fighting.
to approach conductors and other current-carrying parts of electric supply
lines, such parts shall be arranged so as to provide adequate clearance
from the ground or other space generally accessible, or shall be provided
2 - 2.5 m
with guards so as to isolate them effectively from accidental contact by
such persons.
15 m Pole
4.3 Undergrounded metal-sheathed service cables, service conduits, metal
fixtures and similar noncurrent-carrying parts, if located in urban districts
and where liable to become charged to more than 300 volts to ground,
shall be isolated or guarded so as not to be exposed to accidental contact
by unauthorized persons. As an alternative to isolation or guarding,
noncurrent-carrying parts shall be solidly or effectively grounded.

4.4 Clearance of wires from building surface shall be not less than
those required Table II. 5. Conductors Passing By or Over Buildings

5.1 Minimum Clearances. Unguarded or accessible supply conductors


Voltage of Supply Horizontal Vertical Clearance carrying voltages in excess of 300 volts may be run either beside
Conductors Clearance in in Meters or over buildings. The vertical or horizontal clearance to any
Meters building or its attachments (balconies, platforms, etc.) shall be as
300 to 8,700 volts 1.0 2.5 listed below. The horizontal clearance governs above the roof
level to the point where the diagonal equals the vertical clearance
8,700 to 15,000 2.5 2.5 requirement. This rule should not be interpreted as restricting the
volts installation of a trolley contact conductor over the approximate
15,000 to 50,000 3.0 3.0 center line of the track it serves.
volts
5.2 Guarding of Supply Conductors/Supply of Conductors of 300 volts
> 50,000 volts 3.0 + 10 mm per Kv 3.0 + 10 mm per Kv
or more shall be properly guarded by grounded conduit, barriers,
in excess in excess or otherwise, under the following conditions:
1. Where the clearances set forth in Table II above cannot
be obtained.
4.5 Supports over buildings. Service-drop conductors passing over a 2. Where such supply conductors are placed near enough to
roof shall be securely supported by substantial structures. windows, verandas, fire escapes, or other ordinarily
Where practicable, such supports shall be independent of the accessible places within the reach of persons.
building.

12
8/11/2016

5.3 Where the required clearances cannot be obtained, supply


conductors shall be of Grounded Metallic Shield, Jacketed Primary Clearance of line Communication LInes Supply LInes

Cables grouped or bundled and supported by grounded messenger


conductors from -
In general On jointly used In general (0 to On jointly used Exceeding 8700
wires. poles 8700 volts) poles (0 to 8700 volts, add for each
volts) 1000 volts of excess
Vertical and lateral 75 mm 75 mm 75 mm 75 mm 6.25 mm
V- conductors of the
same circuit
Vertical and lateral 75 mm 75 mm 150 mm 150 mm 10 mm
conductors of other
circuits

V
Span and guy wires 75 mm 150 mm 150 mm 150 mm 10 mm
attached to same
pole: general
Span and guy wires 75 mm 150 mm 300 mm 300 mm 10 mm
attached to same
pole: when parallel
to line
Lightning protection 75 mm 75 mm 75 mm 75 mm 5 mm
wires parallel to line:
surfaces of cross
arms
Lightning protection 75 mm 125 mm 75 mm 125 mm 5 mm
wires parallel to line:
surfaces of poles

6. Clearance of Service Drops


Exception No. 1. Where the voltage between conductors does not exceed 300
6.1 Service drop conductors shall not be readily accessible and when not in volts and the roof has a slope of not less than 100mm in 300mm, the
excess of 600 volts, shall conform to the following: clearance may not be less than 1m.

a. Clearances over roof. Conductors shall have a clearance of not less


than 2.5m from the highest point of roofs over which they pass with Service Drop Conductor
the following exceptions: 1 m 300 volts
Service Drop Conductor
Highest point
2.5 m < 600 volts
Highest point
Slope 1:3

Exception No. 2. Service drop conductors of 300 volts or less which do not pass 6.2 Clearance from the Ground. Conductors shall have a clearance of not less
over other than a maximum of 1.2m of the overhang portion of the roof for the than 3m from the ground or from any platform or projection from which they
purpose of terminating at a through-the-roof service raceway or approved might be reached.
conductor
support may be maintained at a minimum of 500mm from any portion of the
roof over which they pass. 3m platform

500mm
6.3 Clearance from Building Openings. Conductors shall have a horizontal
Service Drop Conductor clearance of not less than 1m from windows, doors, porches, fire escapes, or
300 volts similar locations and shall be run at least 500mm above the top level of a
1.2 m
window or opening.
Highest point

500mm

wi
window
1m

13
8/11/2016

6.5 No parts of swimming and wading pools shall be placed under existing service
6.4 Service Drop of communication lines, when crossing a street, shall have a drop conductors or any other over-head wiring; nor shall such wiring be
clearance of not less than 5.5 m from the crown of the street or sidewalk installed above the following:
over which it passes. Service drop of communication line
a. Swimming and wading pools and the area extending 3m
outward horizontally from the inside of the walls of the pool.
5.50 m 5.50 m b. Diving Structures
c. Observation stands, towers or platforms
3m

Service Drop of communication lines shall have a minimum clearance of 3m


S
Service
above ground at its point of attachment to the building or pedestal.
drop
conductor
co

3m 3m Swimming pool
protector

8. Transformers
7. Wiring Methods
8.1 Oil-insulated Transformers Installed Outdoors. Combustible material,
Service entrance conductors extending along the exterior or entering combustible buildings and parts of buildings, fire escapes, door and
buildings or other structures shall be installed in rigid steel conduit or window openings shall be safeguarded from fires originating in oil-
asbestos cement conduit or concrete encased plastic conduit from point of insulated transformers installed on, attached to, or adjacent to a building
service drop to meter socket and from meter socket to the disconnecting or combustible material. Space separations, fire-resistant barriers and
equipment. However, where the service entrance conductors are protected enclosures which confine the oil of a ruptured transformer tank are
by approved fuses or breakers at their outer ends (immediately after the recognized safeguards. One or more of these safeguards shall be applied
service drop or lateral) they may be installed in any of the recognized wiring according to the degree of hazard involved in cases where the transformer
methods. installation presents a fire hazard. Oil enclosures may consist of fire-
resistant dikes, curbed areas or basins, or trenches filled with coarse,
7.1 Abandoned Lines and/or portions of lines no longer required to provide crushed stone. Oil enclosures shall be provided with trapped drains in
shall be removed. cases where the exposure and the quantity of oil involved are such that
removal of oil is important.
7.2 Power or communication poles, lines, service drops and other line
equipment shall be free from any attachment for antennas, signs, Exterior Oil-insulated
streamers and the like. Transformer
Trench all
7.3 Metallic sheaths or jackets of overhead power or communication cables around
shall be grounded at a point as close as possible to ground level
whenever such cables change from overhead to underground
installations.

Transformers of more than 112-1/2 KVA rating shall be installed in a transformer


8.2 Dry-Type Transformers Installed Indoors. Transformers rated 112-1/2 KVA room of fire-resistant construction unless they are constructed with Class B (80C
or less shall have separation of at least 300mm from combustible material rise) or Class H (150C rise) insulation, and are separated from combustible
unless separated there from by a fire-resistant heat-insulating barrier or material not less than 1.85m horizontally and 3.7m vertically or are separated
unless of a rating not exceeding 600 volts and completely enclosed except for there from by a fire-resistant heat-insulating barrier.
ventilating openings.
Transformers rated more than 35,000 volts shall be installed in a vault.
Combustible Wall vault
Combustible ceiling
Dry-type transformer Dry-type transformer Tra
Transformer more
112-1/2 Kva or less Combustible 112-1/2 Kva or less 3.70 m
than
tha 35,000 volts
Wall

1.85 m

300mm
8.3 Askarel-Insulated Transformers Installed Indoors. Askarel-insulated
transformers rated in excess of 25 KVA shall be furnished with a pressure
relief vent. Where installed in a poorly ventilated place they shall be
furnished with a means for absorbing any gases generated by arcing inside
the case, or the pressure relief vent shall be connected to a chimney or flue
which will carry such gases outside the building. Askarel-insulated
transformers rated more than 35,000 volts shall be installed in a vault.

14
8/11/2016

8.4 Oil-Insulated Transformers Installed Indoors. Oil-insulated transformers shall


be installed in a vault constructed as specified in this Section except as follows: 3. FURNACE TRANSFORMERS. Electric furnace transformers of a total rating
not exceeding 75 KVA may be installed without a vault in a building or room
1. NOT OVER 112-1/2KVA TOTAL CAPACITY. The provisions for transformer of fire-resistant construction provided suitable arrangements are made to
prevent a transformer oil fire spreading to other combustible material.
vaults specified in Section 9.3 of this Rule apply except that the vault may
be constructed of reinforced concrete not less than 100mm thick. 4. DETACHED BUILDING. Transformers may be installed in a building which
does not conform with the provisions specified in this Code for transformer
2. NOT OVER 600 VOLTS. A vault is not required provided suitable vault, provided neither the building nor its contents present fire hazard to
arrangements are made where necessary to prevent a transformer oil fire any other building or property, and provided the building is used only in
igniting other materials, and the total transformer capacity in one location supplying electric service and the interior is accessible only to qualified
does not exceed 10 KVA in a section of the building classified as persons.
combustible, or 75 KVA where the surrounding structures is classified as 8.5 Guarding. Transformers shall be guarded as follows:
fire-resistant construction.
1. MECHANICAL PROTECTION. Appropriate provisions shall be made
> 100mm thick reinforced to minimize the possibility of damage to transformers from external
concrete vault
causes where the transformers are located exposed to physical
damage.
oil insulated transformer
2. CASE OR ENCLOSURE. Dry-type transformers shall be provided with
< 112-1/2 KVa
a non-combustible moisture resistant case or enclosure which will
provide reasonable protection against accidental insertion of foreign
objects.
3. EXPOSED LIVE PARTS. The transformer installation shall conform
with the provisions for guarding of live parts in PEC Rule 1056.
4. VOLTAGE WARNING. The operating voltage of exposed live parts of
transformer installations shall be indicated by signs or visible
markings on the equipment or structures.

9. Provisions for Transformer Vaults


9.2 Location. Transformer and transformer vaults shall be readily accessible to
9.1 New Building. New buildings requiring an expected load demand of qualified personnel for inspection and maintenance. Vaults shall be located
200KVA or above shall be provided with a transformer vault, except that where they can be ventilated to the outside air without using flues or ducts
transformers may be mounted on poles or structures within the property if
wherever such an arrangement is practicable.
enough space is available, provided that all clearances required can be
obtained and no troublesome contamination on insulators, bushings, etc.
can cause hazards and malfunctioning of the equipment.
9.3 Walls, Roof and Floor. The walls and roofs of vaults shall consist of reinforced
150 mm for R.C concrete not less than 150mm thick, masonry or brick not less than 200mm
200 mm for Brick
thick, or 300mm load bearing hollow concrete blocks. The inside wall and roof
300 mm for Load bearing CHB
surface of vaults constructed of hollow concrete blocks shall have a coating of
Wall: 200 Kva or more cement or gypsum plaster not less than 20mm thick. The vault shall have a
20 mm thick plaster
2-1/2 hours fire rating concrete floor not less than 100mm thick. Building walls and floor which meet
these requirements may serve for the floor, roof and one or more walls of the
vaults. Other forms of fire-resistive construction are also acceptable provided
they have adequate structural strength for the conditions and a minimum fire
resistance of two and one half hours according to the approved Fire Test
Floor: Standard. The quality of the material used in the construction of the vault shall
100mm thick be of the grade approved by the Building Official having jurisdiction.
2-1/2 hours fire rating

9.4 Doorways. Any doorway leading from the vault into the building shall be
protected as follows: 2. ARRANGEMENT. Vaults ventilated by natural circulation of air may have
roughly half of the total area of openings required or ventilation in one or more
openings near the floor and the remainder in one or more openings in the roof
1. TYPE OF DOOR. Each doorway shall be provided with a tight-fitting
or in the sidewalls near the roof; or all of the area required for ventilation may
door of a type approved for openings in such locations by the authority
be provided in one or more openings in or near the roof.
enforcing this Code.
3. SIZE. In the case of vaults ventilated to an outdoor area without using ducts or
2. SILLS. A door sill or curb of sufficient height to confine within the
flues the combined net area of all ventilating openings after deducting the area
vault, the oil from the largest transformer shall be provided and in no
occupied by screens, grating, or louvers, shall be not less than 0.006 sqmm per
case shall the height be less than 100mm.
KVA of transformer capacity in service, except that the net area shall be not
less than 0.1 sqm for any capacity under 50 KVA.
3. LOCKS. Entrance doors shall be equipped with locks, and doors shall
be kept locked, access being allowed only to qualified persons. Locks
4. COVERING. Ventilation openings shall be covered with durable gratings,
and latches shall be so arranged that the door may be readily and
screens, or louvers, according to the treatment requirement required in order to
quickly opened from the inside.
avoid unsafe conditions.

10. Ventilation. Ventilation shall be adequate to prevent a transformer temperature 5. DAMPERS. Where automatic dampers are used in the ventilation openings of
in excess of the prescribed values. vaults containing oil-insulated transformers, the actuating device should be
made to function at a temperature resulting from fire and not a temperature
1. LOCATION. Ventilation openings shall be located as far away as which might prevail as a result of an overheated transformer or bank of
possible from doors, windows, fire escapes and combustible material. transformers. Automatic dampers should be designed and constructed to
minimize the possibility of accidental closing.

15
8/11/2016

11. Capacitors.
6. DUCTS. Ventilating ducts shall be constructed of fire resistant material.
1. Application. This section applies to installation of capacitors on electric
7. DRAINAGE. Where practicable, vaults containing more than 100KVA circuits in or on buildings.
transformer capacity shall be provided with a drain or other means which will Exception No. 1. Capacitors that are components of other apparatus shall
carry off any accumulation of oil or water in the vaults unless local conditions conform to the requirements for such apparatus.
make this impracticable. Exception No. 2. Capacitors in hazardous locations shall comply with
additional requirements in PEC Section 400-415.
8. WATER PIPES AND ACCESSORIES. Any pipe or duct system foreign to the
electrical installation should not enter or pass through a transformer vault. 2. Location. An installation of capacitors in which any single unit contains
Where the presence of such foreign system cannot be avoided, appurtenances more than three gallons of combustible liquid shall be in a vault conforming
thereto which require maintenance at regular intervals shall not be located to part C of PEC Section 319.
inside the vault. Arrangements shall be made where necessary to avoid
possible trouble from compensation, leaks and breaks in such foreign system. 3. Mechanical Protection. Capacitors shall be protected from physical damage
by location or by suitable fences, barriers or other enclosures.
Piping or other facilities provided for fire protection or for water-cooled
transformers are not deemed to be foreign to the electrical installation.
4. Cases and Supports. Capacitors shall be protected from physical damage by
location or by suitable fences, barriers or other enclosures.

5. Transformers Used with Capacitors. Transformers which are components of


capacitor installations and are used for the purpose of connecting the
capacitor to a power circuit shall be installed in accordance with PEC Section
319. The KVA rating shall not be less than 135 per cent of the capacitor
rating in Kva.

12. Emergency Systems

1. The provisions of this Section shall apply to the installation, operation and
maintenance of circuits, systems and equipment intended to supply 4. Tests and Maintenance
illumination and power in the event of failure of the normal supply or in the
event of accident to elements of a system supplying power and illumination a. The authority having jurisdiction shall conduct or witness a test on the
essential for safety to life and proper where such systems or circuits are complete system upon completion of installation, and periodically afterwards.
required by the Fire Code, or by any government agency having jurisdiction.
b. Systems shall be tested periodically in accordance with a schedule acceptable
Emergency systems are generally installed in places of assembly where to the authority having jurisdiction to assure that they are maintained in proper
artificial illumination is required, such as buildings subject to occupancy by operating condition.
large numbers of persons, hotels, theaters, sports arenas, hospitals and similar
institutions. Emergency systems provide power for such functions as c. Where the battery systems or unit equipment are involved, including
refrigeration, operation of mechanical breathing apparatus, ventilation batteries used for starting or ignition in auxiliary engines, the authority having
essential to maintain life, illumination and power for hospital room, fire alarm jurisdiction shall require periodic maintenance.
systems, fire pumps, industrial processes where current interruption would
produce serious hazards, public address systems and other similar functions. d. A written record shall be kept of such tests and maintenance.

5. Emergency systems shall have adequate capacity and rating for the emergency
2. All requirements of this Section shall apply to emergency systems. operation of all equipment connected to the system.
3. All equipment for use on emergency systems shall be properly approved.

6. Current supply shall be such that in the event of failure of the normal supply to
or within the building or group of buildings concerned, emergency lighting or 8. A generator set driven by some form of prime mover, with sufficient capacity
emergency power, will be immediately available. The supply system for and proper rating to supply circuits carrying emergency lighting or lighting and
emergency purposes may be composed one or more of the types of systems power, equipped with suitable means for automatically starting the prime mover
covered in Section 12.7 to Section 12.10 of this Rule. Unit equipment in on failure of the normal service shall be provided. For hospitals, the transition-
accordance with Section 12.21 shall satisfy the applicable requirements of this time from instant of failure of the normal power source to the emergency
Section. generator source shall not exceed ten seconds. (See Section 12.4)

Consideration must be given to the type of service to be rendered; whether for 9. There shall be two services, each in accordance with Section 200 of the PEC,
short duration, as for exit lights of a theater, or for long duration, as for widely separated electrically and physically to minimize the possibility of
supplying emergency power and lighting during long periods of current failure simultaneous interruption of power supply arising from an occurrence within
from trouble either inside or outside the buildings, as in the case of a hospital. the building or group of buildings served.

Assignment of degree of reliability of the recognized emergency supply system 10. Connections on the line side of the main service shall be sufficiently separated
depends upon the careful evaluation of the variables of each particular from said main service to prevent simultaneous interruption of supply through
installation. an occurrence within the building or group of buildings served.

7. A storage battery of suitable rating and capacity shall supply, by means of a 11. The requirements of Section 12.5 and Section 12.6 also apply to installations
service installed according to Section 200 of the PEC and maintained at not where the entire electrical load on a service or sub-service is arranged to be
more than 90 per cent of system voltage, the total load of the circuits supplying supplied from a second source. Current supply from a standby power plant
emergency lighting and emergency power for a period of at least hour. shall satisfy the requirements of availability in Section 12.6.

16
8/11/2016

15. Branch circuits intended to supply emergency lighting shall be so installed as to


provide service immediately when the normal supply for lighting is interrupted.
12. Audible and visual signal devices shall be provided, where practicable, for the Such installations shall provide either one of the following:
following purposes:
a. An emergency lighting supply, independent of the general lighting
a. To give warning of dearrangement of the emergency or auxiliary source. system with provisions for automatically transferring to the emergency
lights by means of devices approved for the purpose upon the event of
b. To indicate that the battery or generator set is carrying a load. failure of the general lighting system supply.

c. To indicate when a battery charger is properly functioning. b. Two or more separate and complete systems with independent power
supply, each system providing sufficient current for emergency lighting
13. Only appliances and lamps specified as required for emergency use shall be purposes. Unless both systems are used for regular lighting purposes
supplied by emergency lighting circuits. and are both lighted, means shall be provided for automatically
energizing either system upon failure of the other. Either or both
14. Emergency illumination shall be provided for all required exit lights and all systems may be part of the general lighting system of the protected
other lights specified as necessary for sufficient illumination. occupancy if circuits supplying lights for emergency illumination are
Emergency lighting systems should be so designed and installed that the installed in accordance with other Section of this Rule.
failure of any individual lighting element, such as the burning out of a light
bulb, shall not leave any area in total darkness. 16. For branch circuits which supply equipment classed as emergency, there shall
be an emergency supply source to which the load will be transferred
automatically and immediately upon the failure of the normal supply.

17. Emergency circuit wiring shall be kept entirely independent of all other wiring and
equipment and shall not enter the same raceway, box or cabinet with other wiring 20. Lights on the exterior of the building which are not required for illumination
except: when there is sufficient daylight may be controlled by an automatic light
a. In transfer switches, or actuated device approved for the purpose.
b. In exit or emergency lighting fixtures supplied from two (2) sources.
21. In hospital corridors, switching arrangements to transfer corridor lighting in
18. The switches installed in emergency lighting circuits shall be so arranged that only patient areas of hospitals from overhead fixtures to fixtures designed to provide
authorized persons have control of emergency lighting, except: night lighting maybe permitted, provided that the switching system is so
a. Where two or more single throw switches are connected in parallel to designed that switches can only select between two sets of fixtures but cannot
control a single circuit, at least one of those switches shall be accessible extinguish both sets at the same time.
only to authorized persons.
b. Additional switches which act only to put emergency lights into operation 22. The branch circuits over current devices in emergency circuits shall be
but not to disconnect them may be permitted. accessible to authorized persons only.

Switches connected in series and three- and four-way switches shall not be 23. Where permitted by the authority having jurisdiction, in lieu of other methods
allowed.
specified elsewhere in this Section, individual unit equipment for emergency
illumination shall consist of:
19. All manual switches for controlling emergency circuits shall be located at the most
accessible place to authorized persons responsible for their actuation. In places of
assembly, such as theaters, a switch for controlling emergency lighting systems a. Battery
shall be located in the lobby or at a place conveniently accessible there from. In b. Battery charging means, when a storage battery is used
no case shall a control switch for emergency lighting in a theater for motion c. One or more lamps, and
picture projection be placed in the projection booth or on the stage. However, d. A relaying device arranged to energize the lamps automatically upon
where multiple switches are provided, one such switch may be installed in such failure of the normal supply to the building
locations and so arranged that it can energize but not disconnect for the circuit.

The batteries shall be of suitable rating and capacity to supply and maintain, at not
less than 90 per cent of rated lamp voltage, the total lamp load associated with the
unit for a period of at least hour. Storage batteries, whether of the acid or alkali
type, shall be designed and constructed to meet the requirements of emergency
service. Lead-acid type storage batteries shall have transparent jars.

Unit equipment shall be permanently fixed in place and shall have all wiring to each
unit installed in accordance with the requirements of any of the wiring methods

THANK YOU
discussed in Chapter II of the PEC. They shall not be connected by flexible cord. The
supply circuit between the unit equipment and the service, the feeders or the branch
circuit wiring shall be installed as required by Section 12.17. Emergency illumination
fixtures which obtain power from a unit equipment which are not part of the unit
equipment shall be wired to the unit equipment as required by Rule 5257 of the PEC
and in accordance with the one of the wiring methods described in Chapter II of the
PEC.

13. Effectivity

1. All primary and secondary supply lines already existing shall comply with the
provisions of this Rule within two (2) years from the effectivity of this Rule.
2. Transformers to be installed on, attached to, or in buildings shall comply with the
requirements of this Rule. Transformer installations already existing shall comply with
the requirements within two (2) years from the effectivity of this Rule.
3. Non-compliance with the provisions of this Rule shall be subject to the penal
provisions in Section 213 of PD 1096.

17

Вам также может понравиться