Introduction
ADEPT offers Series 6200 : DC Signal Isolators, Resistance, Temperature and Transformer Tap Position
Transducers to provide galvanic isolation between field DC Signal or Process Parameter and control room
equipment, which utilises reliable optical isolation technique. Use of latest circuit techniques and quality
components ensure reliable operation over long periods.
The Loop Powered Isolator provides galvanically isolated 4 - 20 mA DC output current proportional to
4 - 20 mA DC input current. The Isolator utilises high frequency transformer isolation technique.
The power required for internal circuitry is derived from input current.
DC Current or Voltage Isolator isolates the incoming DC Current or Voltage parameter to provide
proportional DC Output. Unipolar as well as Bipolar Input can be connected to these Isolators.
The Temperature Transducer is used for galvanically isolated measurement of Temperature using a
PT - 100 Sensor or a Thermocouple. For Thermocouple input automatic cold junction compensation is
provided. Linearity of Sensor is taken care off in the Transducer. The Resistance Transducer measures
value of any resistive output from Process Parameter and converts to proportional DC Output.
The Transformer Tap Position Transducers measures the value of resistance on tap position changers,
typically used on high voltage transformers.
Operation :
The Input DC Current is chopped by the chopper circuit to convert it into high frequency AC signal. This signal
is fed to an isolating high frequency transformer. The AC output current from the transformer is rectified and
filtered to obtain load independent DC output current. As the transformation ratio is 1:1, the output current is
identical in value to the DC input current.
Specifications :
Input Range : 4 - 20 mA DC
Output Range : 4 - 20 mA DC
Response Time : Less than 100 mSec.
Accuracy : 0.2% of Span
Continuous Overload Capacity : 50 mA DC
Maximum Input Voltage : 15 V DC
Voltage Drop Across Isolator : 4 V DC (approx.)
Operating Temp. : 0 - 55 Deg C, 95% RH Non Condensing
Effect of Ambient Temp. per C
O
: Less than 0.01% of Span
Isolation Test Voltage : 2 KV AC, 50 Hz for 1 min.
Insulation Resistance : More than 100 MOhm at 500 V DC
Output Load Resistance (RL) : 550 Ohms Max.
Output Ripple : Less than 0.5% of Span (peak to peak)
Terminals : Suitable for 2.5 sq.mm wires
Mounting : 35 mm DIN Rail, Panel Wall
Enclosure : ABS Plastic Enclosure, IP 40
Operation :
The Input signal is filtered and processed to convert into a standard DC voltage. This voltage is fed to a linear
optocoupler which provides the required galvanic isolation. An optical feedback is used for improved linearity,
response time and temperature effects. The output from the linear optocoupler is further processed to provide
DC Voltage / Current Output. The Isolator with fast response time (10 mSec) typically used in feedback control
system can be provided.
Specifications :
DC Current Input Range : 0 - 1 mA DC, 0 - 10 mA DC, 0 - 20 mA DC, 4 - 20 mA DC
(Unipolar or Bipolar) : or any other special requirement
Note : For DC Current above 100 mA DC, use external shunt and connect the shunt output
(0 - 75/100 mV DC) to the DC Voltage Isolator.
Operation :
It is a precision grade Transducer is used for galvanically isolated measurement of Temperature using a PT - 100
Sensor or a Thermocouple.
A temperature Sensor gives a continuous output following the actual temperature in the system, making it
possible to have the process in tight control. The output signal from the sensor can be: RTD (Resistance
Temperature Detector): PT-100 is accurate, stable and covers a broad temperature range.
Thermocouples: Suited for very high temperatures and mechanically very stable.
Specifications :
Input Temperature Range : As per requirement
Sensor : PT-100 or Thermocouple (J, K, R, S or T Type)
No.of Outputs : One, Two
Output Range : 0 - 1 mA DC, 0 - 20 mA DC, 0 - 5 V DC,
(Unipolar / Bipolar) 0 - 10 mA DC, 4 - 20 mA DC, 0 - 10 V DC
Response Time : Less than 500 mSec.
Accuracy : 0.5% of Span
Auxiliary Supply : 110, 240 V AC 20%, 50 Hz
24, 48, 110, 220 V DC 20%
80 - 300 V AC/DC and 18 - 60 V DC
Operation :
It is a precision grade Transducer is used for galvanically isolated measurement of Transformer Tap and
Resistance (2 Wire or 3 Wire). It measures the value of resistance on tap position changers, typically used on
high voltage transformers. Each position on the selector has an equal value of resistance so that as the tap
position is increased or decreased the value of resistance increases or decrease respectively. The Input is in
the form of Resistance and provides a Stable, Ripple-Free and Optically Isolated DC load independent output in
the form of current or voltage.
Specifications :
Input Range Tap Input : 0 - 1.7 KOhm, 0 - 17 KOhm
Resistance Input : Please Specify the range (2 Wire or 3 Wire)
Output Range : 0 - 1 mA DC, 0 - 20 mA DC, 0 - 5 V DC,
(Unipolar / Bipolar) : 0 - 10 mA DC, 4 - 20 mA DC, 0 - 10 V DC
Response Time : Less than 500 mSec.
Accuracy : 0.5% of Span
Auxiliary Supply : 110, 240 V AC 20%, 50 Hz
24, 48, 110, 220 V DC 20%
80 - 300 V AC/DC and 18 - 60 V DC.
No.of Outputs : One, Two
Data Scanner 8000
Data Scanner 8000 replaces multiple analog DC Signal Transducers and combines 6 Programmable
Channels in to a single product. The Product features user selectable Inputs such as mV DC, mA DC, V DC.
The Inputs can be changed from Jumper Settings.
The parameters are available through a galvanically isolated RS 485 Half Duplex or RS 232 Communication Port
over Modbus RTU Protocol.
Specifications
Number Of Channels : 1(Minimum) - 6(Maximum)
Input Type : mV, mA and V DC
Input Range : (-)100 - (+) 100 mV DC, (-)20 - (+)20 mA DC and (-)30 - (+)30 V DC
Isolation Test Voltage between : 2 KV AC, 50 Hz for 1 min
Input, Output and Aux.Supply
Accuracy : (+/-) 0.2%
Auxiliary Supply : 80 - 300 V AC/DC and 18 - 60 V DC.
Wiring Details
INPUT
4 - 20 mA DC PT-100, 3 Wire Type
+ - DC INPUT AUX.
+ -
SUPPLY
01 03 01 02 01 0 2 03
15 16 INPUT
+ - AUX. + - + - + - + - + - + - AUX. + - + -
OUTPUT SUPPLY DC OUTPUTS DC INPUT DC OUTPUTS SUPPLY DC OUTPUTS
4 - 20 mA DC
Thermocouple (J,K,R,S,T) LO HI
3 Wire Type
+ -
CH. 1 CH. 2 CH. 3 CH. 4 CH. 5 CH. 6
01 02 0 01 0 2 0 3 01 02 03
INPUT INPUT INPUT 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
10 11 15 16 17 18 10 11 15 16 17 18
17 18 03 04 05 06 07 08 09 10 11 12 13 30 31 32
10 11 15 16 17 18
+ -
AUX. + - + - AUX. + - + - AUX. + - + - D+ D - G
SUPPLY DC OUTPUTS SUPPLY DC OUTPUTS SUPPLY DC OUTPUTS AUX. SUPPLY RS 485 Output
Dimensional Drawing
30 85
150
120
114
0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 09
01 02 0 3 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
70
75
04 05 0 6 10 11 12 13 14 15 16 17 18 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32