Model WMA-1 Water Motor Alarm


Hydraulically Operated
Mechanical Sprinkler Alarm
General Technical
Description Data
The Model WMA-1 Water Motor Alarm Approvals
is a hydraulically operated outdoor UL and ULC Listed.
alarm designed for use with fire protec- FM, LPCB, and VdS Approved.
tion system waterflow detection
valves. It is lightweight yet rugged, and Gong Finish
it can be used in conjunction with Red or Aluminum
alarm check, dry pipe, deluge, and Working Water Pressure Range
preaction valves to sound a local 7 to 300 psi (0,5 to 20,7 bar)
alarm.
Nozzle K-Factor
The Water Motor Alarm is suitable for 0.7 GPM/psi1/2 (10,1 LPM/bar 1/2)
mounting to any type of rigid wall and
can accommodate a wall thickness Y-Strainer
range of 2 to 18 inches (50 to 450 mm). 3/4 inch, cast iron, 20 mesh screen positioned such that it can be drained
It is provided with a listed and ap- Trim Components back to the water flow detection valve
proved Model WM-1 Y-Strainer for use Galvanized steel nipples and cast iron trim.
in the alarm line. fittings. Item 6. The Clean-Out Sump Plug is to
The WMA-1 utilizes a lightweight, im- be located vertically below the Inlet to
peller design which can produce a very
high sound pressure level. The Gong, Design the Water Motor.
Item 7. Piping from the Water Motor
Gong Mount, and Water Motor Hous-
ing are fabricated from corrosion resis- Data Drain must be a minimum of 1 inch in
size throughout and directed to an
tant aluminum alloys. The polymer
drive bearings do not require lubrica- The Model WMA-1 Water Motor Alarm open drain, in order to ensure proper
tion, and the Gong is closely fitted to must be used in accordance with the drainage for obtaining the maximum
the Gong Mount to eliminate the need following design criteria: sound pressure level.
for a separate cover. Item 1. The Y-Strainer is to be located
The Model WMA-1 Water Motor Alarm at the alarm outlet of the waterflow
NOTE
is a redesignation for the Central detection valve trim. The Water Motor Alarm Drain may be
Model F-2, Gem Model F630, and Star connected to the main drain of a water
Model S450. Item 2. The Water Motor Alarm must flow detection valve if a non-spring
only be mounted to a rigid wall surface, loaded swing type check valve is in-
WARNING which will not permit the Striker/Gong stalled in a horizontal portion of the
The Model WMA-1 Water Motor Alarm Mount to loosen and fall out of align- water motor alarm drain piping (before
described herein must be installed and ment. its connection to the main drain).
maintained in compliance with this Item 3. In order to obtain the highest
document, as well as with the applica- possible sound level, the Water Motor Item 8. In order to minimize any wall
ble standards of the National Fire Pro- Alarm should be located as close as staining that can be created by drain
tection Association, in addition to the possible to the waterflow detecting water, it is recommended that the drain
standards of any other authorities hav- valve. (Refer to NFPA 13 for guidance.) piping from the Water Motor be galva-
ing jurisdiction. Failure to do so may nized steel, brass, or other suitable
impair the performance of this de- Item 4. The alarm line piping from the
corrosion resistant material.
vice. alarm outlet of the waterflow detection
valve trim to the Water Motor Alarm Item 9. Drain water must be directed
The owner is responsible for maintain- must be 3/4 inch size throughout and such that there will be no accidental
ing their fire protection system and de- it must be galvanized steel, brass, or damage to property or danger to per-
vices in proper operating condition. other suitable corrosion resistant ma- sons when the alarm is operating or
The installing contractor or sprinkler terial. thereafter.
manufacturer should be contacted
with any questions. Item 5. The alarm line piping must be Item 10. The alarm line drain (at the

Page 1 of 4 JULY, 2004 TFP921


Page 2 of 4 TFP921

NO. DESCRIPTION QTY. P/N

1 Water Motor 1 92-630-1-012


2 Support Washer 1 NR
3 Drive Shaft Sleeve 1 NR
4 Drive Shaft 1 NR
5 Gong Mount 1 NR
6 Striker 1 See (a)
7 Gong 1 See (a)
8 Cap Nut 1 See (a)
(a) Repair Parts Kit
Includes Items
6, 7 (red), and 8 1 92-630-1-025
(a) Repair Parts Kit
Includes Items
6, 7 (alum.), and 8 1 92-630-2-025

NR: Not Replaceable

FIGURE 1 MODEL WMA-1 WATER MOTOR ALARM

waterflow detection valve) must be alarm line will automatically drain back
maintained at a minimum temperature Operation through the orifice which is also pro-
of 40F/4C. vided in the trim of the waterflow de-
Upon operation of the alarm check, dry tection valve.
Item 11. A single Water Motor Alarm pipe, deluge, or preaction valve to
may be connected to the alarm lines which the Model WMA-1 Water Motor The Water Motor Alarm does not have
from a maximum of three separate fire Alarm is connected, water will flow to to be reset after an operation. How-
protection systems. However, when the Water Motor and through the Inlet ever, if the alarm was silenced during
two or three alarm lines are intercon- Nozzle. As water flows through the In- operation by closing of an alarm con-
nected, each alarm line must be pro- let Nozzle, a high velocity jet is formed trol valve, the alarm control valve must
vided with a 3/4 inch (P/N 52-271-1- which impinges on the Impeller, caus- be reopened after the fire protection
001) Model WM-1 Y-Strainer and a 3/4 ing the Impeller and the Striker to ro- system is restored to service.
inch (P/N 52-403-1-005) Check Valve tate. With each rotation, the free swing-
with 3/32 inch orifice. The strainers ing Striker Ring hits the Gong and
must be located at the alarm outlet in sounds the alarm. The spent water is
the trim of each of the waterflow detec- then drained through the 1 inch outlet.
tion valves. The check valves must be
located between each strainer and the The alarm will sound as long as water
interconnection with the alarm line is flowing into the system and flowing
from another system. to the Water Motor Alarm. Water in the
TFP921 Page 3 of 4

NOTES: STANDARD INLET TRIM OPTIONAL DRAIN TRIM


NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.
1. All installation dimensions are shown at nominal value.
2. All dimensions are in inches and (mm). 1 3/4" x 3" Nipple 2 A 1" 90 Elbow 1
3. Pipe shown in dotted lines is not included with the WMA-1. 2 3/4" 90 Elbow 1 B 1" 45 Elbow 1
4. Consult with the Authority Having Jurisdiction as to local 3 3/4" x 1/4" x 3/4" Tee C Wall Plate 1
w/ 1/4" Plug 1 D 1" x 1 - 6" Pipe,
requirements for isolating valves for local mechanical alarms.
4 3/4" Union 1 T.O.E. 1
5. All trim components are galvanized.

FIGURE 2 TYPICAL INSTALLATION OF MODEL WMA-1 WATER MOTOR ALARM

NOTE verify that the Body and Support


Installation Use thread sealant sparingly on male Washer sit square against the wall. If
threads only. not, adjust the alarm line and/or drain
The Model WMA-1 Water Motor Alarm piping to suit.
must be installed in accordance with Step 5. Prior to initiating installation of
the following instructions: Step 9. From the outside wall, insert
the Water Motor Alarm, mount the
Drain Trim (less the Wall Plate and 45 the Drive Shaft through the Sleeve and
Step 1. Mark the through-wall loca- Elbow), as well as the balance of alarm fully insert it into the Impeller. (When
tions for the centerlines of the Sleeve line piping (including other union half) fully inserted, the Shaft should pro-
and Drain Outlet. The Drain Outlet to the Water Motor. trude beyond the face of the wall by
must be located at least 10 inches (250 approximately 20" minus 2" minus wall
Step 6. Tighten the NPT threaded end thickness.)
mm) below the Sleeve per Figure 2. of the Sleeve into the Body hand tight Mark the Drive Shaft at a point of ap-
Step 2. Make 1-1/2 inch (38 mm) di- plus 1/8 turn. proximately 1/8 to 1/4 inch inside the
ameter holes straight through the wall Step 7. Slip the Support Washer over face of the wall; remove the Shaft; cut
at both locations. the Sleeve and place the assembly in the Shaft where previously marked; file
Step 3. Cut the non-threaded end of position against the wall. off burrs from the cut end of the Drive
the Sleeve to a length equal to that of Step 8. Tighten the 3/4 inch Union. Shaft; and, re-insert the Drive Shaft
the wall thickness plus 0 to 1/8 inch (0 Install the Wall Plate and tighten the through the Sleeve and fully insert it
to 3 mm). Thread the cut end to 3/4 45 Elbow. into the Impeller.
inch NPT per ANSI B1.20.1. Step 10. Hold the Gong Mount in posi-
Step 4. Install the alarm line piping up NOTE tion against the wall, engage the Cou-
to and including the union half, Item 4 Apply pressure against the outside pling with the Drive Shaft and then
- Fig. 2. edge of the Water Motor Body and carefully thread the Striker Shaft Bear-
Page 4 of 4 TFP921

ing onto the Sleeve. Securely tighten must be given to the owner and the fire IN NO EVENT SHALL TYCO FIRE
the Striker Shaft Bearing using a pair department, central control station, or PRODUCTS BE LIABLE, IN CON-
of channel locks on the 1-1/2 inch (38 other signal station to which the TRACT, TORT, STRICT LIABILITY OR
mm) hex end. alarms are connected. UNDER ANY OTHER LEGAL THE-
Step 11. Spin the Striker by hand and If the alarm was silenced during opera- ORY, FOR INCIDENTAL, INDIRECT,
verify that it spins freely (without any tion, the alarm control valve must be SPECIAL OR CONSEQUENTIAL
sign of binding). If not, make the nec- reopened immediately after the fire DAMAGES, INCLUDING BUT NOT
essary adjustments. protection system is restored to serv- LIMITED TO LABOR CHARGES, RE-
ice. GARDLESS OF WHETHER TYCO
Step 12. Install the gong and securely FIRE PRODUCTS WAS INFORMED
tighten the Cap Nut. The identification The Model WMA-1 Water Motor Alarm ABOUT THE POSSIBILITY OF SUCH
sign lettering must be orientated hori- must be maintained and serviced in DAMAGES, AND IN NO EVENT
zontally, accordance with the following instruc-
SHALL TYCO FIRE PRODUCTS LI-
Step 13. Test the Water Motor Alarm tions:
ABILITY EXCEED AN AMOUNT
by opening the alarm test valve in the Step 1. The Model WMA-1 Water Mo- EQUAL TO THE SALES PRICE.
trim of the water flow detection valve. tor Alarm does not require any regu-
The alarm must be clear and steady. If larly scheduled maintenance. Rotating THE FOREGOING WARRANTY IS
not, make the necessary adjustments. parts do not require lubrication. It is MADE IN LIEU OF ANY AND ALL
recommended, however, that fire OTHER WARRANTIES EXPRESS
NOTE alarms be periodically operated, i.e., OR IMPLIED, INCLUDING WARRAN-
Testing of the Water Motor Alarm may inspected, to verify that they generate TIES OF MERCHANTABILITY AND
result in operation of other associated a clear and steady sound. Any impair- FITNESS FOR A PARTICULAR PUR-
alarms. Consequently, notification ment must be be immediately cor- POSE.
must be given to the owner and the fire rected.
department, central control station, or
other signal station to which the
Step 2. The inspection should be
made quarterly or more frequently, as
Ordering
alarms are connected. may be necessary in the case of loca-
tions subject to vandalism. The Y-
Information
Strainer and Sump are to be cleaned
Care and out after each operation of the Water
Orders for the WMA-1, Optional Drain
Trim, and replacement parts must in-
Motor Alarm and after the alarm line
Maintenance piping has been drained.
clude the description and Part Number
(P/N).
The following procedures and inspec- The Complete Model WMA-1 Alarm
tions should be performed as indi-
cated, in addition to any specific re-
Limited Assembly includes the Model WMA-1
Water Motor Alarm, Model WM-1
quirements of the NFPA, and any
impairment must be immediately cor-
Warranty Strainer, and Standard Inlet Trim.
WMA-1 Alarm Assemblies:
rected. Products manufactured by Tyco Fire
Specify: Model WMA-1 Alarm Assem-
The owner is responsible for the in- Products are warranted solely to the
bly with Red Finish Gong,
spection, testing, and maintenance of original Buyer for ten (10) years P/N 52-630-1-001.
their fire protection system and de- against defects in material and work-
vices in compliance with this docu- manship when paid for and properly or
ment, as well as with the applicable installed and maintained under normal Specify: Model WMA-1 Alarm Assem-
standards of the National Fire Protec- use and service. This warranty will ex- bly with Aluminum Finish Gong,
tion Association (e.g., NFPA 25), in pire ten (10) years from date of ship- P/N 52-630-2-001
addition to the standards of any ment by Tyco Fire Products. No war- Optional Drain Trim:
authority having jurisdiction. The in- ranty is given for products or
stalling contractor or product manufac- components manufactured by compa- Specify: Optional Drain Trim for Model
turer should be contacted relative to nies not affiliated by ownership with WMA-1 Water Motor Alarm,
any questions. Tyco Fire Products or for products and P/N 52-630-2-002.
It is recommended that automatic components which have been subject Separately Ordered Alarm Control
sprinkler systems be inspected, to misuse, improper installation, corro- Valve:
tested, and maintained by a qualified sion, or which have not been installed, Specify: UL/FM 3/4 Inch Ball Valve,
Inspection Service in accordance with maintained, modified or repaired in ac- P/N 92-300-1-006.
local requirements and/or national cordance with applicable Standards of Separately Ordered Parts for
codes. the National Fire Protection Associa- Multiple Systems:
tion, and/or the standards of any other Specify: Model WM-1 Y-Strainer, P/N
NOTES Authorities Having Jurisdiction. Mate- 52-271-1-001. (1 required for two sys-
Before closing a fire protection system rials found by Tyco Fire Products to be tem, 2 required for 3 systems.)
main control valve for maintenance defective shall be either repaired or
replaced, at Tyco Fire Products sole Specify: 3/4 Inch Check valve with
work on the fire protection system that 3/32 Inch Orifice, P/N 52-403-1-005 (2
it controls, permission to shut down option. Tyco Fire Products neither as-
sumes, nor authorizes any person to required for two system, 3 required for
the affected fire protection systems 3 systems.)
must first be obtained from the proper assume for it, any other obligation in
authorities and all personnel who may connection with the sale of products or Replacement Parts for
be affected by this decision must be parts of products. Tyco Fire Products Water Motor Alarm:
notified. shall not be responsible for sprinkler (Specify description) for use with
system design errors or inaccurate or Model WMA-1 Water Motor Alarm,
Testing of the Water Motor Alarm may P/N (see Figure 1).
result in operation of other associated incomplete information supplied by
alarms. Consequently, notification Buyer or Buyers representatives.