Вы находитесь на странице: 1из 6

ICSET 2008

Fault Ride-Through of Doubly-Fed Induction Generator with


Converter Protection Schemes
Jin Yang, David G. Dorrell, Senior Member, IEEE, and John E. Fletcher, Senior Member, IEEE

AbstractThis paper from the point view of wind farm fault system was disconnected directly. This is called passive
ride-through (FRT) capability, discusses the performance of crowbar protection, which does not need complex control.
converter protection schemes to it. Different resistor protection As fault ride-through requirements have developed, an active
methods are summarized and then a new combined protection crowbar control scheme has emerged. This connects the
with crowbar (CB) and series dynamic resistor (SDR) is crowbar resistance when necessary and disables it to resume
proposed. With the analysis of rotor current during fault, DFIG control. The essence of this control is to limit the rotor
resistance values are calculated for practical application. The
current and to supply reactive power.
rotor high current reduction performance is simulated with
MATLAB/Simulink. Fault ride-through performance including For active crowbar control schemes, the control signals are
the reactive power supply, torque fluctuation and rotor speed activated by the rotor-side converter devices (which are usually
with crowbar and series dynamic resistor are compared. The IGBTs). These have voltage and current limits that must not be
proposed method is an alternative for further protection and exceeded. Therefore the rotor-side converter voltages and
requirements of wind farm riding-through grid disturbances. currents are the critical regulation reference [1][2]. The
Index Terms-Fault ride-through (FRT), Doubly-fed induction DC-link bus voltage can increase rapidly under these
generator (DFIG), converter protection, wind generation. conditions, so it is also used for crowbar triggering [3][4].
Some researchers have assumed that the crowbar was
NOMENCLATURE uneconomic and have avoided the use of crowbar control. They
G G G developed a new fault control strategy [5] and converter
v, i , Voltage, current and flux vector.
topology [6]. However, this makes the control system very
Rs, Rr, Ls, Lr Stator, rotor resistances and self-inductances.
Lm Magnetizing inductance. complex and increases the issues with control coordination
s, , r Synchronous, rotor and slip angular between normal and fault operation.
frequency. In addition to the triggering and control issues, the blocking
Ps, Qs Stator side active and reactive power. of the rotor-side converter by the switching-on crowbar is of
s, r Stator and rotor subscripts. concern. In a traditional system, the rotor-side converter is
n Nominal value subscripts. disconnected from the rotor when the crowbar is switched on.
However, some studies have proposed keeping converter
I. INTRODUCTION connected [1][7]. With this kind of control, the resumption of

F AULT Ride-Through (FRT) capability is one of the basic normal operation can be immediate after fault clearance.
requirements for wind farms. There are two aspects to fault Another kind of power-electronic-controlled external
ride-through: to continue power supply without breaking resistor, which is connected to the rotor windings of the
any part of the system and to resume normal operation after generator, is used to limit the rotor acceleration during a fault.
clearance of the fault. The doubly-fed induction generator This is called a braking resistor [8]. The purpose of the braking
(DFIG) is presently the most popular wind turbine system for resistor is to balance the active power then improve generator
large-scale generation. However, a significant disadvantage of stability during a fault. The advantages of a series dynamic
the DFIG is its vulnerability to grid disturbances and braking resistor, when connected to the generation circuit, were
fluctuations because the stator windings are connected directly studied by [9]. It was found that this enhanced the fault
to the grid through a transformer and switchgear; the rotor-side ride-through of a fixed speed wind turbine. Vestas (Denmark)
is buffered from the grid via a partially-rated converter. use pitch-regulated variable rotor resistance to realize a
To protect the wind farm from interruptions due to onshore quasi-variable-speed wind turbine (the OptiSlip technology
grid faults and wind farm faults, crowbar protection has [10]). In [4], a braking resistor was inserted into the DC-link
emerged as a protection method. A crowbar is a resistor that is between the converters of DFIG; this acts as a dump load (or
connected in parallel with the rotor winding on occurrence of DC-chopper) to smooth the DC-link voltage during heavy
an interruption, bypassing the rotor-side converter (RSC). imbalance of active power through the rotor-side and the
They were originally used with small wind farms. No fault grid-side converter. A similar resistor was proposed in [11] to
ride-through requirement was required and the wind turbine enhance the fault ride-through capability of a permanent
magnet synchronous generator with fully rated converter.
J. Yang is with the Department of Electronics and Electrical Engineering,
However, there has been no study into the use of a series
University of Glasgow, G12 8LT, UK (e-mail: j.yang@elec.gla.ac.uk). dynamic resistor in a DFIG system.
D. G. Dorrell is with the Mechatronics and Intelligent Systems Group, In this paper, a new topology and control strategy for the
Engineering, University of Technology, Sydney, NSW, Australia (e-mail: protection of the converter in a DFIG system is proposed. In
david.dorrell@uts.edu.au).
J. E. Fletcher is with the Department of Electronic and Electrical Engineering,
Section II, rotor voltage and current transients are discussed in
University of Strathclyde, G1 1XW, UK (e-mail: john.fletcher@eee.strath.ac.uk). detail. A new protection scheme for the rotor-side converter is

1211
978-1-4244-1888-6/08/$25.00 
c 2008 IEEE
proposed and simulated in Sections III-V. The method is Which is in the rotor reference frame. (9) is a linear
G
verified by simulations using MATLAB/Simulink. The differential equation for ir r in the time domain, which can be
protection schemes are compared with simulations. solved and the final expression is
Rr Rr
G 1 Lr t Lr t G L 1
II. ROTOR CURRENT OF INDUCTION GENERATOR DURING ir r = e e vrr (t )dt m sV2 e jr t
DISTURBANCES Lr Ls Rr / Lr + jr . (13)
The general Parks model of an induction generator is often Lm 1
+ (1 s )(V1 V2 ) e (1/ s + j )t
used for both normal operation and transient analysis [12]. Ls Rr / Lr 1/ s j
Using the motor convention in a static stator-oriented From the above equation we can see that the second and
reference frame, without saturation, the voltage equations are third bracketed terms have frequencies of r and
G G dG respectively. The maximum value of rotor current during
vs = Rs is + s (1) fault can be as serious as five to ten times of the rated value as
dt
G G dG G shown in the example in Fig. 2. The rotor current is related to
vr = Rr ir + r
j r (2) the voltage V1, V2, and the slip s and this will be concerned in
dt
G G
where vs is grid-imposed. The rotor voltage vr is inverter- the selection of resistance values in the Section IV.
_ , ,
10

controlled and performs the control. The flux equations:

Rotor currents (p.u.)


G G G 5

s = Ls is + Lm ir (3) 0
G G G
r = Lm is + Lr ir . (4) -5
G
From (3) and (4) we can eliminate is and obtain an expression -10
2.8 2.9 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7
G
to put into (2); further eliminating r gives Time (s)
Fig. 2. Rotor currents during a disturbance without protection.
G L d G L L L2m d G
vr = m j s + Rr + s r j ir . (5)
Ls dt L dt III. CONVERTER PROTECTION SCHEMES
s
2
With leakage factor = s r L L L m . (6) A. Existing Protection Methods
Ls Lr Existing protection systems use crowbars, DC-choppers (for
And then use a voltage source to represent the voltage due to DFIGs), and series braking resistors (for permanent magnetic
the stator flux produces synchronous generators). The traditional crowbar resistor
G L d G bypasses the rotor-side converter when switched on.
vr 0 = m j s . (7)
Bi-directional thyristors [13], GTOs [2][4] and IGBTs [3] are
Ls dt
normally used for the control of the crowbar switching. In [4]
So (5) becomes vG= vG + R + L d j iG. (8) [11] a braking resistor (DC-chopper) is connected in parallel
r r0 r r r
dt with the DC-link capacitor to limit the overcharge during low
The rotor voltage in (8) can be expressed in a rotor reference grid voltage. This protects the IGBTs from overvoltage and can
G
frame where vG Gr Gr dir r (9) dissipate energy, but this has no effect on the rotor current. In a
r
r
= v r0 + R r ir + Lr
dt similar way to the series braking resistor, a dynamic resistor
so that the rotor equivalent circuit in Fig. 1 is obtained. can be put in series with the rotor (series dynamic resistor) and
G
ir r Rr Lr this limits the rotor over-current. Its operation is different from
+ the crowbar. It can be controlled by a power-electronic switch.
Rotor
G
vrr + G
vrr0 In normal operation, the switch is on and the resistor is

bypassed; during fault conditions, the switch is off and the

resistor is connected in series to the rotor winding. Fig. 3 shows
Fig. 1. Equivalent circuit of rotor circuit during faults.
the protection schemes for a DFIG converter connected to the
We can now get the relationship between rotor voltage and rotor. G
current from (9). When there is a disturbance on the stator DC-link ir r Rr Lr
side, assume that there is a sharp voltage change from V1 to + G
G Shunt- Shunt- vrr0
V2. In [12] it was shown that v rr0 can exceed the maximum Resistor Resistor
Rotor
G
vrr Series-Resistor +

voltage that the rotor-side converter can generate, so that Thyristors

current control is lost. In the same reference frame, the Bypass Switch
voltage is DC-Chopper RSC Crowbar Series Dynamic Resistor
Fig. 3. Per-phase DFIG rotor equivalent circuit with protections.
G L L 1 V V
vrr0 = V2 m se jst m + j 1 2 e t / s . (10)
Ls Ls s j s B. Proposed Protection Scheme
This can be simplified by omitting 1/s, which is very small: The difference between the series dynamic resistor and the
G L L V V crowbar or DC-link braking resistor is its topology. The latter
vrr0 V2 m se jst m j 1 2 e t / s . (11)
Ls Ls j s are shunt-connected and control the voltage while the series
or G L
[ ]
vrr0 m sV2 e jr t (1 s )(V1 V2 )e jt e t / s
Ls
(12) dynamic resistor has the distinct advantage of controlling the
current magnitude directly. Therefore it not only controls the

1212
rotor overvoltage which could cause the rotor-side converter fault deteriorates, or during the voltage recovery transient the
to lose control, but, more significantly, limit high rotor rotor current goes high again, the crowbar can be switched on
current. In addition, the limited current can reduce the once more as further protection in conjunction with the series
charging current to the DC-link capacitor, hence avoiding dynamic resistor, i.e., during a serious fault, the process is:
DC-link overvoltage. So with the proposed series dynamic (a)(b)(c)(d)(c)(d)(a) as shown in Fig. 5.
resistor, the rotor-side converter does not need to be stopped. DC-link
G
ir r Rr Lr DC-link
G
ir r Rr Lr
Two functions of a traditional crowbar are to bypass the + +
G G G G
converter and limit the current in the rotor windings. The first Rotor vrr vrr0 +

Rotor vrr vrr0 +

function is to protect for converter, while the second to protect the


RSC CB SDR RSC CB SDR
rotor windings. The obvious disadvantage of the bypassing (a) (b)
G G
function is that it turns the DFIG into a normal asynchronous DC-link ir r Rr Lr DC-link ir r Rr Lr

machine. These need reactive power for excitation, so it will G


+
G
+
G G
Rotor vrr vrr0 + Rotor vrr vrr0 +
absorb reactive power from the grid that will exacerbate the


voltage dip. RSC CB SDR RSC CB SDR
Using a series dynamic resistor, a new rotor-side converter (c) (d)

protection scheme is proposed by dividing the two functions of Fig. 4. Switching sequence of converter protection scheme.
crowbar. The shunt crowbar keeps its bypass function while the Vs (a) (b) (c) (d) (c) (d) (a)

rotor current limit function is partially taken over by a series


dynamic resistor. Hence, the crowbar limits the rotor winding
over-current and the series dynamic resistor limits the converter 0.00
1.50 2.00 2.50 3.00 3.50 4.00 4.50
over-current. Therefore the series dynamic resistor is the primary Fig. 5 An example of the protection switching sequence
protection, and the crowbar resistor can further bypass the
It is estimated that the first peak of the three-phase rotor
rotor-side converter during a deteriorating fault. While the
combination of the two resistors can protect the converter current happens during the first cycle of oscillating term in
system, a DC-link bus overvoltage may still occur due to the (13). Hence crowbar is switched on for t_Pre = T = 2/ =
fault. 2/(1-s) s, where s is of the synchronous frequency.
The DC-chopper across DC-link is not essential for fault For a gradual or moderate fault, the series dynamic resistor
ride-through operation but it smoothes the DC-link voltage and is switched on first and the crowbar can be turned on when
increases the normal range of the DFIG operation during heavy necessary depending on the fault development.
imbalances of active power between the converters [4]. For a D. Protection Switching Strategy
recovering of fault, the grid-side converter current may have
To coordinate with the above protection arrangement, a
transients that can charge the capacitor so that the chopper can
switching strategy, which includes converter protection, is
function. In this paper, the series dynamic resistor and crowbar
proposed in Fig. 6. Both the rotor current ir and voltage vr are
are combined and used for rotor-side converter protection.
monitored and compared with preset threshold values Ith_pre, Ith,
C. Triggering-on/-off Sequence of CB and SDR Vth_pre and Vth. If either exceeds the threshold value, the output of
In a time sequence, the series dynamic resistor should be the comparator is 1, else it is 0. A single 1 triggers the protection.
switched on first. If the rotor current still increases the The timer for pre-crowbar is switched on to enable the converter.
crowbar offers further protection. However, for a serious fault, At the same time, another timer is triggered for a period whilst
the most important feature of the rotor current during the the series dynamic resistor on. If during this period either the
disturbance is its abrupt change immediately after the fault as current ir or voltage vr with a series dynamic resistor exceeds
shown in Fig. 2. Because of the rotor winding impedance the the new threshold values Ith and Vth, the crowbar protection is
current will decrease if the fault does not deteriorate so it is switched on and the rotor-side converter IGBTs can be turned
critical to protect the converter from the first peak. However, off for further protection. Ith and Vth are less than Ith and Vth
for the series dynamic resistor and crowbar, there are because the IGBTs have been in a fault condition for a period so
switching delays in the protection triggering. In a serious fault, that the safe operating area has to be reduced.
the series dynamic resistor is first triggered but it cannot limit With the timer and piecewise protection, the system can cope
the high current, however it may be that there is insufficient with the piecewise grid code requirements for fault ride-through.
time to switch-in the crowbar to protect it from the first-peak. The rotor-side converter can continue to work and control the
To deal with this, a switching sequence strategy has to be active and reactive power through the fault. The reference
used which includes the pre-crowbar protection as shown in threshold values of Ith_pre, Ith, Ith, Vth_pre, Vth and Vth need to be set
Fig. 4. or obtained by a control calculation scheme.
If the current goes beyond the extreme limit, the crowbar is For switch-off control, the opposite procedure is followed.
switched in the first instance. At almost the same time, the And the rotor current RMS or average value is monitored to
series dynamic resistor is triggered. After a drop in avoid unnecessary frequent switching due to the high frequency
over-current the crowbar can be switched off with only the current fluctuation. If the value decreases to below the second
series dynamic resistor in operation. The process from (a) to threshold Ith, then crowbar is switched off. The series dynamic
(d) is utilized over the first cycle of a large rotor over-current. resistor is switched out when the rotor current falls to below the
After this period the system is in a new steady state. If the rated value.

1213
ir example grid code for fault ride-through. When the stator
>
Ith_pre Pre-Crowbar ON voltage is below the curve, the wind turbine can be disconnected.
vr
OR Rotor Side Converter OFF In the example, the wind turbine should withstand a 0.85 to
>
Vth_pre Pre-Crowbar OFF 1.00p.u. voltage dip for 0.2s. When there is 0.50p.u. voltage,
t_Pre Timer
t0 Timer
Rotor Side Converter ON it is required that the wind turbine should provide reactive
power and be connected for 1.5s. In this case, RSDR is firstly
ir
> AND calculated by the criteria of 0.50p.u. for 0.2s. If the
Ith
OR Series Dynamic Resistor
ON
disturbance fault is more serious or is sustained for a longer
vr
Vth
> AND period, RCB is calculated for the further fault conditions.
t_SDR Timer Vs (p.u.)
ir 1.00
>
Ith Crowbar ON
OR 0.75
Rotor Side Converter OFF
vr
> 0.50
Vth
Fig. 6. Wind turbine system protection strategy with converter protection.
0.15
IV. RESISTANCE VALUE LIMITS OF SERIES DYNAMIC
RESISTOR AND CROWBAR 0.20 1.00 1.50 3.00 Time (s)
Time fault occured
A. Traditional Crowbar Resistance Fig. 7. A fault ride-through requirement example.
For single crowbar protection, the double function means For series dynamic resistor operation: RT = Rr + RSDR. The
the resistance has to have both a lower and an upper limit. The most serious condition can be obtained when s = 0.3 p.u.,
minimum value is related to the rotor winding over-current = 1.3 p.u., V1V2 = 0.5 p.u.. Hence the RSDR,min can be
limit, while the maximum is set by the over-voltage on the obtained. For the series dynamic resistor with crowbar
converter terminals [13]. operation: RT = Rr + RSDR + RCB. Again, the most serious
Here we use the approximated crowbar resistance
condition can be obtained when s = 0.3 p.u., = 1.3 p.u.,
calculation from [13]. The estimated maximal rotor current is
V1V2 = 1.0 p.u. so that minimum crowbar resistor RCB,min can
1.8Vs . (14)
ir ,max be obtained. The maximum value can be obtained in a similar
X s + RCB
2
way to the single crowbar resistor by adding RCB to RSDR in
The voltage across the bypass resistors, and thus across the (14):
rotor and converter is 2Vr RCB ir ,max . (15) 2
RCB ,max = 1.67 RSDR + 0.33 40 RSDR + 15 Ls 2 (20)
From (14) and (15) we obtain R 2Vr ,max s Ls (16)
CB ,max =
V. SIMULATION RESULTS AND DISCUSSION
3.2Vs2 2Vr2,max The proposed converter protection method is simulated in
where Lr Lm (17) MATLAB/Simulink. The generator parameters are listed in
Ls = Ls + TABLE I. RSDR and RCB are calculated as the example code
Lr + Lm
requirements in the above section. The threshold values are set as
Vs is the stator voltage RMS before a fault, Vr,max is the upper
limit RMS value of the rotor-side converter voltage. Both are Ith_pre=3Irn, Vth_pre=Vrn; Ith=2Irn, Vth=Vrn; Ith=0.9Ith, Vth=0.9Vth. The
chosen of rated value. So in a per-unit calculation slip is chosen as normal operation condition, i.e. s=0.1p.u. The
RCB,max = 1.29Ls. (18) calculated values are RSDR,min=0.059=0.098p.u., RCB,min=
0.029=0.048p.u.. From (20), RCB,max=0.26p.u.=0.156. In
B. Combined Protection Resistances simulations, 0.06 and 0.03 are chosen as the resistances. The
With the above transient analysis and from the switching faults simulated are based on the fault ride-through examples: 1) a
sequence of protection scheme, the resistance values for the serious three-phase grounding which begins at t=4.0 s and clears
series dynamic resistor RSDR and the crowbar RCB can be at t=4.2 s (Fig. 8) and 2) a 0.5p.u. voltage dip for 1.5s (Fig. 9 and
calculated from the equivalent circuit in Fig. 4, in terms of the Fig. 10 with series dynamic resistor and crowbar protection
stator voltage magnitude changes, slip and rotor speed. In (13), respectively).
substitute Rr with RT (which will be Rr + RSDR or Rr + RSDR + RCB Series dynamic resistor and single crowbar protection systems
G
depending on the fault level) and v rr with the constant limit are compared for the second fault condition. (18) is used in the
voltage Vth or Vth. Rr and Lr are known parameters. With the single crowbar RCB,max calculation with per-unit values, so
G
condition ir r I th or I th , RT can be expressed in terms of V1, V2, RCB,max = 0.105 p.u. = 0.063 . This is used in the crowbar
simulation.
and s. At t = 0, omitting 1/s in denominator of the third
component TABLE I GENERATOR PARAMETERS
Parameter Value Parameter Value
1 Rated power Pn 2 MW Ratio Ns/Nr 0.63
(1 s )(V1 V2 )
G Vth Lm RT / Lr j (19) Rated stator voltage Vsn 690 V Inertia constant H 3.5 s
ir r,max = I th = +
RT Lr Ls 1 Rated frequency fs 50 Hz Pole pair no. Pp 2
sV2 R / L + j Stator leakage inductance Lls 0.105 p.u. Stator resistance Rs 0.005 p.u.
T r r
Rotor leakage inductance Llr 0.11 p.u. Rotor resistance Rr 0.0055 p.u.
The fault ride-through specifications can be used to divide the
Magnetizing inductance Lm 3.953 p.u.
boundaries of V1, V2, and s for RSDR and RCB. Fig. 7 shows an

1214
A. Protection Performance Results advantages.
vs abc (p.u.)
The combined converter protection results are shown in Fig. 8. 1
As in Fig. 1, the total voltage dip results in about eight times the 0
-1
rated value of current. So the crowbar is switched on first for the
is abc (p.u.)
first cycle of the high frequency component, i.e. t_Pre = T = 2/ 2

= 2/1.1s = 0.0182 s. The series dynamic resistor is also 0


-2
switched on when fault occurs and remains connected until
ir abc (p.u.)
recovery. The big transients in the recovery period make the 2

crowbar switched on again for about t_Pre. With the combined 0


-2
protection, the rotor current is effectively restricted to within 2.0 i sdr (p.u.)
p.u. with the rotor-side converter disabled for only 0.0364 s. 0.5

Hence the time of the rotor-side converter operation is 0


-0.5
-1
effectively prolonged. Ps, Qs (p.u.)
vs,abc (p.u.) 2
2
1
0 0

-2 Te (p.u.)
is,abc (p.u.)
0
2
-1
0
-2
-2
w (p.u.)
ir,abc (p.u.)
2 1.2
0 1.1
-2 4 4.5 5 5.5 6
Time (s)
i sdr (p.u.)
2 Fig. 9. With series dynamic resistor protection, voltage dip of 0.5p.u. for 1.5s.
0
vs abc (p.u.)
-2 1
i cb (p.u.) 0
5 -1
0
is abc (p.u.)
-5 2
Ps/Qs (p.u.) 0
3
2
1 -2
0
-1 ir abc (p.u.)
2
Te (p.u.)
0
1
0
-1 -2
-2
-3 i cb (p.u.)
2
w (p.u.) 1
0
1.11 -1
1.1
1.09 Ps, Qs (p.u.)
3.8 4 4.2 4.4 4.6 4.8 5 2
Time (s) 1
Fig. 8. With combined converter protection, voltage dip of 1 p.u. for 0.2 s. 0

B. Fault Ride-Through Performance Comparison Te (p.u.)

The rotor current, reactive power, electrical torque and rotor 0


-1
speed of a DFIG, when series dynamic resistor and crowbar -2

protection systems are used, are simulated and compared in w (p.u.)


Figs. 9 to 11. These show the DFIG performance under these 1.25
1.2
protection schemes. To clarify, only single protection 1.15
1.1
strategies are simulated instead of combined protection and 4 4.5 5 5.5 6
Time (s)
this allows the observation and comparison of the different Fig. 10. With crowbar protection, voltage dip of 0.5 p.u. for 1.5 s.
protection strategies when used individually.
The reactive power and electrical torque ripples are larger
Both of the two strategies experience big reactive power with series dynamic resistor protection compared to crowbar
and electrical torque fluctuations during the fault clearance. protection. This is probably due to the big resistance in rotor
This is related to sudden stator current changes. The second winding and DFIG control system performance during faults,
reactive power graph in Fig. 11 is zoomed to show the
which needs further detailed work. For rotor speed changes
reactive power supply. It can be seen that with the rotor-side they are virtually the same. This means the series dynamic
converter connected in series dynamic resistor protection, resistor avoids rotor over-speed as effectively as crowbar.
about 0.1 p.u. reactive power is provided. However, for
crowbar protection, the asynchronous machine absorbs C. Discussion
reactive power of about 0.1 p.u.. So in terms of grid voltage The switching times of the crowbar and series dynamic
recovery, series dynamic resistor protection has its resistor power-electronic switches are not considered in the

1215
analyses and simulations. In reality, this may be an issue, Fault ride-through code requirements were used to find the best
especially for the pre-crowbar phase when fast response is triggering times for the series dynamic resistor and crowbar to
required. In many practical applications, the crowbar thyristor maximize the operation time of the rotor-side converter. The
switches cannot interrupt the current before zero-crossing resistance calculations for the series dynamic resistor and
[14]. This can also influence the protection performance. crowbar were described for further application reference.
These values were calculated using an expression for rotor
1.5
current and code requirements.
Qs (p.u.)

1
0.5 The series dynamic resistor can be in operation with the
0
4 4.5 5 5.5 6 6.5
rotor-side converter control without bypassing it. For the
0.2
control of the grid-side converter to DC-link bus voltage, the
resumption time can be shorter than for a system with normal
Qs (p.u.)

0.1
0 CB SDR
active crowbar protection, which is helpful for resuming
-0.1 normal control which provides reactive power for grid voltage
4.2 4.4 4.6 4.8 5 5.2 5.4 support. During this process, inspection of the reactive power,
0
electrical torque, and rotor speed fluctuations show that the
proposed method enhances DFIG fault ride-through capability.
Te (p.u.)

-0.5
-1 SDR

-1.5
CB
REFERENCES
4 4.5 5 5.5 6 6.5
[1] J. Morren, and S.W.H. de Haan, Ridethrough of wind turbines with
CB
doubly-fed induction generator during a voltage dip, IEEE Trans.
1.2 Energy Convers., vol. 20, no. 2, pp. 435-441, Jun. 2005.
w (p.u.)

SDR
1.15 [2] P. Zhou and Y. He, Control strategy of an active crowbar for DFIG
based wind turbine under grid voltage dips, in Proc. Int. Conf. Electrical
1.1
4 4.5 5 5.5 6 6.5 Machines and System. 2007, Seoul, Korea, Oct. 8-11, 2007.
Time (s) [3] M. Rodrguez, G. Abad, I. Sarasola, and A. Gilabert, Crowbar control
Fig. 11. Protection comparison, voltage dip of 0.5 p.u. for 1.5 s. algorithms for doubly fed induction generator during voltage dips, in
Proc. 11th Eur. Conf. Power Electronics and Applications, Dresden,
In the simulations, a simple star-connected resistor Germany, Sep. 11-14, 2005.
connection is used for the crowbar. The operation resistance [4] I. Erlich, J. Kretschmann, J. Fortmann, S. Mueller-Engelhardt, and H.
of the rotor-side converter is set to 0.0001 . This is even Wrede, Modeling of wind turbines based on doubly-fed induction
smaller than the calculated RCB, min so this leads to generators for power system stability studies, IEEE Trans. Power Syst.,
vol. 22, no. 3, pp. 909-919, Aug. 2007.
malfunction of the bypassing. To maintain rotor-side [5] D. Xiang, R. Li, P. J. Tavner, and S. Yang, Control of a doubly fed
converter connection (this is better for immediate control induction generator in a wind turbine during grid fault ride-through,
recovery), a switch is used to transfer between the rotor-side IEEE Trans. Energy Convers., vol. 21, no. 3, pp. 652-662, Sep. 2006.
converter and the crowbar to enable its function. Hence [6] A. Gaillard, S. Karimi, P. Poure, S. Saadate, and E. Gholipour, A fault
tolerant converter topology for wind energy conversion system with
crowbar and series dynamic resistor switching needs to be doubly fed induction generator, in Proc. 12th Eur. Conf. Power
studied to ensure fast and effective protection of the Electronics and Applications, Sep. 2-5, 2007.
converter. [7] A. Dittrich and A. Stoev, Comparison of fault ride-through strategies for
The calculated theoretical values of RSDR and RCB need to be wind turbines with dfim generators, in Proc. 11th Eur. Conf. Power
Electronics and Applications, Dresden, Germany, Sep. 11-14, 2005.
checked for both the temperature rise and physical [8] W. Freitas, A. Morelato, and W. Xu, Improvement of induction
dimensions for practical use. An IGBT-based switch should generator stability using braking resistors, IEEE Trans. Power Syst., vol.
be picked by rated voltage, current and also thermal 19, no. 2, pp. 1247-1249, May 2004.
temperature rise limitation. Power electronic switches for [9] A. Causebrook, D. J. Atkinson, and A. G. Jack, Fault ride-through of
large wind farms using series dynamic braking resistors (March 2007),
partially-rated converter are usually compact and suitable for IEEE Trans. Power Syst., vol. 22, no. 3, pp. 966-975, Aug. 2007.
placement in the wind turbine nacelle. [10] J. M. Carrasco, E. Galvn, R. Portillo, L.G. Franquelo, and J.T.
The grid-side converter can contribute as a reactive Bialasiewicz, Power electronic systems for the grid integration of wind
compensator with limited reactive power generation capacity turbines, in Proc. 32nd Annual Conf. IEEE Industrial Electronics
IECON 2006, pp. 4182-4188, Nov. 2006.
(about 0.3 p.u. of the converter rating). This is related to the [11] J. F. Conroy and R. Watson, Low-voltage ride-through of a full
grid-side converter current and DC-link capacitor charging. converter wind turbine with permanent magnet generator, IET Renew.
The series dynamic resistor is realized by power electronic Power Gener., vol. 1, no. 3, pp. 182-189, 2007.
switch. However, the bypass switch that is closed during [12] J. Lpez, P. Sanchis, X. Roboam, and L. Marroyo, Dyanmic behavior of
the doubly fed induction generator during three-phase voltage dips,
normal operation will produce additional losses, specifically IEEE Trans. Energy Convers., vol. 22, no. 3, pp. 709-717, Sep. 2007.
device on-state losses. But this is negligible in comparison [13] J. Morren and S. W. H. de Haan, Short-circuit current of wind turbines
with the MW rating of the wind turbine. The reliability of the with doubly fed induction generator, IEEE Trans. Energy Conversion.,
wind turbine might be reduced due to the possible vol. 22, no. 1, pp. 174-180, Mar. 2007.
[14] I. Erlich, H. Wrede, and C. Feltes, Dynamic behavior of DFIG-based
malfunction of the power electronic switches. wind turbines during grid faults, in Proc. Power Conversion Conf.,
Nagoya, Japan, Apr. 2-5, 2007.
VI. CONCLUSION
Converter protection is necessary for DFIG wind turbine
systems during faults. The method proposed in this paper is for
over-current and -voltage protection of devices in the rotor-side
converter. Various resistor protection schemes were reviewed.

1216

Вам также может понравиться