Академический Документы
Профессиональный Документы
Культура Документы
Business-Critical Continuity
Liebert PDX
15-33 kW Indoor Room Cooling Units with Modulating Capacity
A/W/F/D/H Version - 50 Hz
USER MANUAL
English Cod. 265075 Rev. 26.11.2015
Refrigerant R410A
Use proper tools
IMPORTANT SAFETY INSTRUCTIONS
Conventions
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION indicates a hazardous situation that, if not avoided, may result in minor or moderate injury.
NOTICE indicates a property damage message.
NOTICE
The manual is retained for the entire service life of the machine;
The user reads the manual carefully before carrying out any operations on the machine;
The unit control must be used exclusively for the purpose which it is intended for; the manufacturer
takes no liability in case of an incorrect use or a modification of the unit control
WARNING
This manual was prepared to enable the end user to carry out only the operation that can be done with
the panels closed.
Only qualified personnel are allowed to carry out operations that require opening of the door or the
equipment panels. The panel key supplied with the unit must be kept by a person responsible for the
maintenance.
CAUTION
Before proceeding with installation, read all instructions, verify that all parts are included and check the
nameplate to make sure the voltage matches available utility power.
For identification of the unit (model and serial no.) in case of the necessity for assistance or spare parts,
locate the identification label on the outside of the unit.
WARNING
This unit operates and restarts automatically.
If the electrical connection is live, there are residual risks: electric shock, burns, moving parts, automatic
restarting from the remote control.
Before any operation that requires opening of the door or the equipment panels (mainte-
nance, cleaning, etc.), disconnect the unit from the power supply.
The ON/OFF switch on the control panel does not isolate the power from the unit, even in the unit off
mode. To cut off the power supply, open the insulation device (main switch) which is positioned on the
electrical panel cover, behind the door on the left:
MAIN SWITCH
CAUTION
If the unit door is open while the fans are operating, the airflow may suddenly slam the door closed.
There is a risk of being hit by the door and hands being crushed.
Before opening the door, switch off the unit using the local or remote control panel or the external
main switch (if installed).
If small objects are left loose in the fans bay after any maintenance operation, it may result in the object
ejection at the fans start-up.
There is a risk of being hit by small objects.
Install all protection panels or a grid before starting up the fans after any maintenance operation.
Position the floor panels also below the unit with the fans below the floor.
WARNING
If the internal compartments are open immediately after the machine has been switched off, there might
be some hazards related to:
Components still at high temperature: electrical heaters, humidifier and steam distributor, hot water
piping.
Rotating elements (fan impellers, they might continue to rotate for a while by inertia)
Sharp edges, splinters and exposed fasteners
Pay attention to the warning labels on the unit.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
Upflow Downflow Up
Downflow Frontal
6 KA Version
1.5 - Dual fluid, water cooled unit - H versions
The Dualfluid unit cools the air flow by means of the air-refrigerant
coil (5) in direct expansion rows [direct expansion mode: see re- 10
8
frigeration circuit] or, as an alternative, the air/ water coil (5) in the 5
Note 1: The water-cooled Dualfluid versions are filled with the com-
plete charge of the requested refrigerant (standard R410A). 1
4
7
9
Note 2: To complete the Dualfluid system it is necessary to connect
the chilled water coming from the external source to the air/water 3
6
KW Version
10
5
9
11
4
1
2 7
Cooling Water
Can cause personal injury! Only properly trained per- by-standing personnel are to be no GRAVITY
damage to unit. Lift unit
from this side only.
HEAVY SIDE!
sonnel wearing appropriate safety headgear, gloves, shoes and closer than 5 m to the lift point of
glasses should attempt to move, lift, remove packaging from the the unit.
unit or prepare the unit for installation. Always refer to the location of the Center of Gravity indicators
when lifting the unit from any other side.
CAUTION! Use the center of gravity indicators on the unit panels to deter-
Risk of overhead interference! Can cause unit and/or mine the position of the slings.
structure damage! The unit may be too tall to fit through Center of gravity varies per unit size and selected options.
a doorway while on the skid. Slings shall be equally spaced on either side of the center of
Measure the unit and doorway heights and refer to the installation gravity indicator, and with the widest allowable distance. Be
plans prior to moving the unit to verify clearances. sure that the distance between slings guaranties the unit sta-
bility.
NOTICE! Place the slings between the unit bottom rails and the skid.
NOTICE!
The conditioner must never be installed outdoor.
See drawings in Enclosure C.
Spreader
Piano Jacks Bars and 2. Remove the top cover, corner
Slings and side packaging planks
from the unit.
4 - Positioning
1. Acquire piano jacks and
place them into a position Depending on the unit air discharge configuration there are differ-
so one is at each end of ent kinds of positioning.
the unit. Before proceeding with the installation of all units see overall
dimensions and service area drawings in Enclosure C - In-
stallation Drawings
Make sure the floor can support the unit weight (see point 2.8
Unit weights)
If required, accessories are available to support the unit in the
final position, to help with water connection and the mainte-
2. Remove 4 bolts from the nance operation.
pallet, two on each side. See Enclosures E - Accessories
Bolts can be removed by
using a socket wrench, NOTICE: Ensure isolation between the air conditioner
openend wrench or pliers. and the floor to avoid vibration transmission.
ext. only for aesthetic reasons only for aesthetic reasons only for aesthetic reasons
int. absolutely not not necessary no (expose to cold underfloor air)
liq.
ext. only for aesthetic reasons only if exposed to sun only if exposed to sun
1% room unit
room unit
liquid
gas
1%
1%
(see **)
liquid
gas
liquid
(see *)
1%
6m
1%
1%
(*) Oil traps every 6 m of vertical
piping
(**) see Chap. 1, Tab. a.
Note: Create an oil trap on the horizontal discharge line before each lift.
Check the manufacturers indication for the non-return valve orientation and position.
Tab. f - Equivalent lengths (m) of: curves, shut-off and non-return valves
Nominal
diameter
(mm)
90 45 180 90
12 0.50 0.25 0.75 2.10 1.90
14 0.53 0.26 0.80 2.20 2.00
16 0.55 0.27 0.85 2.40 2.10
18 0.60 0.30 0.95 2.70 2.40
22 0.70 0.35 1.10 3.20 2.80
28 0.80 0.45 1.30 4.00 3.30
ing vacuum. 10
subcooling [K]
the system. 2
Air
6.1 - General warnings conditioner
ENSURE THAT THE TUBING DOES NOT OBSTRUCT THE
AIR FLOW (Downflow units only). 2 4 5
IF THE TUBING IS TO RUN OUTDOORS, ADD ETHYLENE
GLYCOL TO THE CIRCUIT AS DESCRIBED IN PAR. 6.5.
filling
HTC TS water
disconnect
after charge
pressure-operated
APPLIANCE
by-pass
Stand-by pump
(optional)
Stand-by pump
7 - Electrical connections If the unit must be installed in the IT System, contact Emerson
Technical department prior to installation.
remote on-off
(CLOSE = ON)
52
53 8 - Start-up
clogged filter (CF) 61
63
(CLOSE = OK) 8.1 - First start-up (or after long standstill)
105
(*) water leakage (LWD)
106 TO PREVENT COMPRESSOR DAMAGE THE CRANKCASE(S)
MUST BE PREHEATED FOR AT LEAST 4 HOURS BEFORE
CONDITIONER START-UP (FAILURE TO DO SO INVALIDATES
400 (NC)
GENERAL ALARM 401 (C)
(400, 401 NC = alarm or unit off) 402 (NO) THE GUARANTEE).
smokestat firestat (AAP) 51 Start the air conditioner as follows:
optional (CLOSE = OK) 53
1. Open all valves in the refrigeration circuit according to the in-
operating fan 70
struction label attached to the valve.
(CLOSE = ON) 71
2. W, F and H only: Open all valves in the water circuit according
operating compressor 1 72
(CLOSE = ON) 73 to the instruction label attached to the valve.
user alarm 1 61 3. Ensure that the refrigerant charge is correct (see Chap. 5).
(CLOSE = OK) 62
4. Using a leak detector, verify that there are no refrigerant
freecooling relay enabling, F/D/H only 580 leaks. If there are any, then repair the leak and recharge as
or AIR ECONOMIZER ON 369
described in Chap. 5.
chilled water thermostat enabling, 83 5. At least 4 hours before start-up, close the main switch and
D version only (CLOSE = compressor ON) 84
miniature circuit breaker for transformers protection on the
Liebert MC Condenser, common control signal 70C electrical panel.
Liebert MC Condenser, circuit 1 control signal 71C
In the iCOM control system factory setting the stand alone mode
Note: Connect 70C terminal with Liebert MC Condenser ter is standard. The stand alone mode gives the possibility of turning
minal 700, connect 71C terminal with Liebert MC Con on the unit simply rotating the main switch on the electric panel.
denser terminal 710.
The yellow LED on the iCOM case will light after turning the unit on,
showing the presence of the electric power.
7.4 - Protection degree IP2x check If the LED does not light up:
After whole of the connections and installation works, compris- check the electric panel power supply;
ing ceiling elements (plenum, ducting) and floor elements (base
check the protection devices (e.g.: thermal switches);
frame), check and verify the protection degree IP2x (protection
against finger access, std. IEC 60364-1) at the boundary of the air check the fuses.
conditioner. 6. Verify the operation of the crankcase heater.
7. With electronic expansion valve with digital compressor, the
battery is normally charged enough by the supplier to pass
CAUTION: All these tasks should be carried out only by an authorized and trained technician. We recommend the
Emerson Network Power Customer Service.
CAUTION: Sharp edges, splinters and exposed fasteners can cause personal injury! Only properly trained personnel, elec-
trically instructed, wearing appropriate safety headgear, gloves, shoes and glasses can carry out this operation!
DOWNFLOW UNITS UPFLOW UNITS
Filter Bracket
Filter Bracket
1) Switch off the unit and open the front panel with the key. 1) Switch off the unit and open the front panel with the key.
Note: Some components inside the unit can be still at high tem- Note: Some components inside the unit can be still at high tem-
perature, wait a few minutes before starting the maintenance op- perature, wait a few minutes before starting the maintenance op-
eration. eration.
2) Unscrew and remove the filter brackets. 2) Unscrew and remove the filter brackets.
3) Remove air filters. 3) Remove air filters.
b
a
A.2 - Installation
The humidifier is supplied already mounted within the air conditioner. The only necessary operations are the connections for the supply water and
drain water.
Supply Water.
Only use mains drinking water with:
pressure between 0.1 and 0.8 MPa (1 and 8 bars), temperature between 1 and 40C and an instant flow rate no higher than the rated flow of
the fill solenoid valve, the connection is R (ISO 7/1);
hardness no greater than 400 ppm of CaCO3 (40fH), conductivity range: 75-1250 S/cm;
no organic compounds. supply water normal water water with low salt content
unit of measure
characteristics min. max min. max.
Hydrogen ions (pH) 7 8.5 7 8.5
Specific conductivity at 20C(R, 20C) (R, 20C) S/cm 350 1250 75 350
Total dissolved solids(cR) mg/l (1) (1) (1) (1)
Dry residue at 180C(TH) mg/l (1) (1) (1) (1)
Total hardness mg/l CaCO3 100 (2) 400 50 (2) 160
Temporary hardness mg/l CaCO3 60 300 30 (3) 100
Iron + Manganese mg/l Fe+Mn = 0.2 = 0.2
Chlorides ppm Cl- = 30 = 20
Silica mg/l SiO2 = 20 = 20
Residual chlorine mg/l Cl2 = 0.2 = 0.2
Calcium sulphate mg/l CaSO4 = 100 = 60
Metallic Impurities mg/l 0 0 0 0
Solvents, thinners, detergents, lubricants mg/l 0 0 0 0
(1)= values depend on the specific conductivity; in general: CR 0.65 * R, 20C; R180 0,93 * R, 20C
(2) = not less than 200% of the chloride content in mg/l CL-
(3) = not less than 300% of the chloride content in mg/l CL-
There is not reliable relationship between hardness and conductivity of the water
Important:
do not treat the water with softeners, this may cause the entrainment of foam, affecting the operation of the unit;
do not add disinfectants or anticorrosive compounds to the water, as these are potential irritants;
the use of well water, industrial water or water from cooling circuits and, in general, any potentially chemically or bacteriologically
contaminated water is not recommended.
Connection:
For the supply water connection see the details in Fig. 1 (point 11-14)
Drain Water.
This contains the same substances dissolved in the supply water, however in larger quantities;
It may reach a temperature of 100C;
It is not toxic and can be drained into the sewerage system, category 3, EN 1717.
Important:
For drain water connection see details in Fig. 1:
Use a drain hose 32mm, maximum length 10m with minimum 5% gradient, dont make siphon on this hose to avoid back pressures
in the drain piping. For configuration with bigger length or high head consider the PDX option with condensate pump.
Supply limit
A.4 - Maintenance
Important: the cylinder may be hot. Let it cool down before touching it or use protective gloves.
A.4.1 - Cylinder replacement
Completely drain the water contained in the cylinder;
Turn the appliance off and open the disconnect switch on the mains power line (safety procedure);
Remove the steam hose from the cylinder;
Disconnect the electrical connections from the top of the cylinder;
Release the cylinder from the fastening device and lift it up to remove it;
Fit the new cylinder in the humidifier by performing the previous operations in reverse.
A.4.2 - Cylinder maintenance (see cylinder instruction sheet)
The life of the cylinder depends on several factors, including: the complete filling with lime scale and/or the partial or complete corrosion
of the electrodes, the correct use and sizing of the humidifier, the output and the quality of the water, as well as careful and regular main-
tenance. Due to the aging of the plastic and the consumption of the electrodes, even an operable steam cylinder has a limited life and it
is, therefore, recommended to replace it after 5 years or 10,000 operating hours.
Important: the humidifier and its cylinder contain live electrical components and hot surfaces, and therefore all service and/or mainte-
nance operations must be performed by expert and qualified personnel, who are aware of the necessary precautions.
Before performing any operations on the cylinder, check that the humidifier is disconnected from the power supply; carefully read and
follow the instructions contained in the humidifier manual. Remove the cylinder from the humidifier only after having drained it completely.
Check that the model and the power supply voltage of the new cylinder correspond to the one being replaced.
A.4.3 - Periodical checks
After one hour of operation: for both disposable and openable cylinders, check that there are no significant water leaks.
Every fifteen days or no more than 300 operating hours: for both disposable and openable cylinders check operation, that there are
no significant water leaks and the general condition of the casing. Check that during operation there are no arcs or sparks between
the electrodes.
Every three months or no more than 1000 operating hours: for disposable cylinders, check operation, that there are no significant
water leaks and, if necessary, replace the cylinder; for openable cylinders, check that there are no markedly blackened parts on the
casing: if this is the case, check the condition of the electrodes and, if necessary, replace them together with the O-rings and the
cover gasket.
Annually or no more than 2500 operating hours: for disposable cylinders, replace the cylinder; for openable cylinders check opera-
tion, that there are no significant water leaks, the general conditions of the container, check that there are no markedly blackened
parts on the casing; replace the electrodes together with the O-rings and the cover gasket.
After five years or no more than 10,000 operating hours: for both disposable and openable cylinders, replace the cylinder.
After extended use or alternatively when using water with a high salt content, the solid deposits that naturally form on the electrodes
may reach the stage where they also stick to the inside wall of the cylinder; in the event of especially conductive deposits, the con-
sequent heat produced may overheat the plastic and melt it, and, in more severe cases, puncture the cylinder, allowing water to leak
back into the tank.
As a precaution, check, at the frequency recommended further on, for deposits and the blackening of the wall of the cylinder, and replace
the cylinder if necessary.
Nominal power*
Nominal power*
Nominal power*
Power factor
Power factor
Power factor
Model
cos
cos
cos
OA* FLA LRA OA* FLA LRA OA* FLA LRA
[kW]
[kW]
[kW]
[A] [A] [A] [A] [A] [A] [A] [A] [A]
PX015 A/W 0.8 3.1 0.1 0.37 0.87 0.78 3.1 0.1 0.35 0.86 0.91 3.1 0.1 0.45 0.87
version with basic fan module
PX021 A/W 1.62 3.1 0.1 0.97 0.89 1.57 3.1 0.1 0.93 0.88 1.79 3.1 0.1 1.08 0.90
PX025 A/W 2.02 3.1 0.1 1.25 0.91 1.96 3.1 0.1 1.2 0.91 2.22 3.1 0.1 1.38 0.91
PX031 A/W 2.66 3.1 0.1 1.68 0.91 2.57 3.1 0.1 1.62 0.91 2.74 3.1 0.1 1.73 0.91
PX033 A/W 2.66 3.1 0.1 1.68 0.83 2.57 3.1 0.1 1.62 0.82 2.74 3.1 0.1 1.73 0.86
PX015 F/D/H 1.39 3.1 0.1 0.8 0.87 1.31 3.1 0.1 0.74 0.86 1.56 3.1 0.1 0.93 0.89
PX021 F/D/H 1.68 3.1 0.1 1.01 0.9 1.63 3.1 0.1 0.97 0.89 1.89 3.1 0.1 1.16 0.91
PX025 F/D/H 2.15 3.1 0.1 1.34 0.92 2.09 3.1 0.1 1.29 0.91 2.42 3.1 0.1 1.52 0.92
PX031 F/D/H 2.74 3.1 0.1 1.74 0.75 2.67 3.1 0.1 1.68 0.74 2.73 3.1 0.1 1.73 0.78
PX015 A/W 0.87 5.6 0.1 0.45 0.85 0.84 5.6 0.1 0.43 0.84 0.98 5.6 0.1 0.53 0.87
PX021 A/W 1.37 5.6 0.1 0.81 0.92 1.32 5.6 0.1 0.77 0.91 1.47 5.6 0.1 0.88 0.92
version with premium fan
PX025 A/W 2.1 5.6 0.1 1.33 0.94 2.03 5.6 0.1 1.28 0.94 2.26 5.6 0.1 1.44 0.94
PX031 A/W 2.89 5.6 0.1 1.88 0.94 2.97 5.6 0.1 1.81 0.94 3.1 5.6 0.1 2.02 0.94
module
PX033 A/W 3.28 5.6 0.1 2.13 0.87 3.16 5.6 0.1 2.06 0.86 3.51 5.6 0.1 2.29 0.89
PX015 F/D/H 1.53 5.6 0.1 0.92 0.9 1.43 5.6 0.1 0.85 0.89 1.68 5.6 0.1 1.04 0.91
PX021 F/D/H 1.81 5.6 0.1 1.13 0.93 1.69 5.6 0.1 1.04 0.93 1.99 5.6 0.1 1.25 0.94
PX025 F/D/H 2.77 5.6 0.1 1.79 0.94 2.68 5.6 0.1 1.73 0.94 3.04 5.6 0.1 1.97 0.89
PX031 F/D/H 3.56 5.6 0.1 2.32 0.94 3.45 5.6 0.1 2.25 0.94 3.89 5.6 0.1 2.39 0.89
(*) At standard operating conditions, Filters class F5, ESP: Upflow 50Pa; Downflow Up 20Pa; Downflow Frontal 0Pa.
(**)At nominal operating conditions: Condensing temperature 45C - Room conditions 24C / 50% RH
Digital
Digital
Digital
Digital
Digital
Digital
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
PX015 A/W 4.52 4.68 0.83 0.82 8 6.9 43 46 2.6 2.67
version with basic fan module
PX021 A/W 6.89 7.37 0.79 0.8 11.8 11.9 64 64 3.79 4.07
PX025 A/W 10.1 10.03 0.74 0.79 15 16.5 101 101 5.19 5.47
PX031 A/W 12.17 13.63 0.75 0.68 21 21 111 111 6.33 6.42
PX033 A/W 13.98 14.15 0.75 0.77 22 22 118 118 7.27 7.54
PX015 F/D/H 4.51 4.68 0.83 0.82 8 6.9 43 46 2.59 2.66
PX021 F/D/H 6.89 7.37 0.79 0.8 11.8 11.8 64 64 3.79 4.07
PX025 F/D/H 10.07 10.03 0.74 0.79 15 16.5 101 101 5.17 5.47
PX031 F/D/H 12.16 12.6 0.75 0.73 21 21 111 111 6.32 6.4
PX015 A/W 4.5 4.68 0.83 0.81 8 6.9 43 46 2.59 2.64
PX021 A/W 6.84 7.38 0.79 0.8 11.8 11.8 64 64 3.76 4.09
version with premium fan
PX025 A/W 10.11 10.03 0.74 0.79 15 16.5 101 101 5.2 5.46
PX031 A/W 12.17 12.65 0.75 0.74 21 21 111 111 6.33 6.44
module
PX033 A/W 13.98 14.15 0.75 0.77 22 22 119 118 7.27 7.55
PX015 F/D/H 4.51 4.68 0.83 0.82 8 6.9 43 46 2.59 2.65
PX021 F/D/H 6.88 7.37 0.79 0.8 11.8 11.8 64 64 3.78 4.08
PX025 F/D/H 10.08 10.03 0.74 0.79 15 16.5 101 101 5.18 5.47
PX031 F/D/H 12.16 12.61 0.75 0.73 21 21 111 111 6.32 6.41
(*) At standard operating conditions, Filters class F5, ESP: Upflow 50Pa; Downflow Up 20Pa; Downflow Frontal 0Pa.
(**)At nominal operating conditions: Condensing temperature 45C - Room conditions 24C / 50% RH
Digital
Digital
Digital
Digital
Digital
Digital
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
PX015 A/W 4.52 4.68 0.83 0.82 8 6.9 43 46 2.6 2.67
version with basic fan module
PX021 A/W 6.89 7.37 0.79 0.8 11.8 11.9 64 64 3.79 4.07
PX025 A/W 10.1 10.03 0.74 0.79 15 16.5 101 101 5.19 5.47
PX031 A/W 12.17 13.63 0.75 0.68 21 21 111 111 6.33 6.42
PX033 A/W 13.98 14.15 0.75 0.77 22 22 118 118 7.27 7.54
PX015 F/D/H 4.51 4.68 0.83 0.82 8 6.9 43 46 2.59 2.66
PX021 F/D/H 6.89 7.37 0.79 0.8 11.8 11.8 64 64 3.79 4.07
PX025 F/D/H 15 10.03 0.74 0.79 15 16.5 101 101 5.17 5.47
PX031 F/D/H 12.16 12.6 0.75 0.73 21 21 111 111 6.32 6.4
PX015 A/W 4.5 4.68 0.83 0.81 8 6.9 43 46 2.59 2.64
PX021 A/W 6.84 7.38 0.79 0.8 11.8 11.8 64 64 3.76 4.09
version with premium fan
PX025 A/W 10.11 10.03 0.74 0.79 15 16.5 101 101 5.2 5.46
PX031 A/W 12.17 12.65 0.75 0.74 21 21 111 111 6.33 6.44
module
PX033 A/W 13.98 14.15 0.75 0.77 22 22 119 118 7.27 7.55
PX015 F/D/H 4.51 4.68 0.83 0.82 8 6.9 43 46 2.59 2.65
PX021 F/D/H 6.88 7.37 0.79 0.8 11.8 11.8 64 64 3.78 4.08
PX025 F/D/H 10.08 10.03 0.74 0.79 15 16.5 101 101 5.18 5.47
PX031 F/D/H 12.16 12.61 0.75 0.73 21 21 111 111 6.32 6.41
(*) At standard operating conditions, Filters class F5, ESP: Upflow 50Pa; Downflow Up 20Pa; Downflow Frontal 0Pa.
(**)At nominal operating conditions: Condensing temperature 45C - Room conditions 24C / 50% RH
Digital
Digital
Digital
Digital
Digital
Digital
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
PX015 A/W 4.53 4.68 0.83 0.82 8 6.9 43 46 2.6 2.67
version with basic fan module
PX021 A/W 6.92 7.37 0.79 0.8 11.8 11.9 64 64 3.79 4.07
PX025 A/W 10.09 10.03 0.74 0.79 15 16.5 101 101 5.19 5.47
PX031 A/W 12.17 13.63 0.75 0.68 21 21 111 111 6.33 6.42
PX033 A/W 13.98 14.15 0.75 0.77 22 22 118 118 7.27 7.54
PX015 F/D/H 4.52 4.68 0.83 0.82 8 6.9 43 46 2.59 2.66
PX021 F/D/H 6.9 7.37 0.79 0.8 11.8 11.8 64 64 3.79 4.07
PX025 F/D/H 10.06 10.03 0.74 0.79 15 16.5 101 101 5.17 5.47
PX031 F/D/H 12.16 12.6 0.75 0.73 21 21 111 111 6.32 6.4
PX015 A/W 4.5 4.68 0.83 0.81 8 6.9 43 46 2.59 2.64
PX021 A/W 6.85 7.38 0.79 0.8 11.8 11.8 64 64 3.76 4.09
version with premium fan
PX025 A/W 10.1 10.03 0.74 0.79 15 16.5 101 101 5.2 5.46
PX031 A/W 12.17 12.65 0.75 0.74 21 21 111 111 6.33 6.44
module
PX033 A/W 13.98 14.15 0.75 0.77 22 22 119 118 7.27 7.55
PX015 F/D/H 4.51 4.68 0.83 0.82 8 6.9 43 46 2.59 2.65
PX021 F/D/H 6.89 7.37 0.79 0.8 11.8 11.8 64 64 3.78 4.08
PX025 F/D/H 10.08 10.03 0.74 0.79 15 16.5 101 101 5.18 5.47
PX031 F/D/H 12.16 12.61 0.75 0.73 21 21 111 111 6.32 6.41
(*) At standard operating conditions, Filters class F5, ESP: Upflow 50Pa; Downflow Up 20Pa; Downflow Frontal 0Pa.
(**)At nominal operating conditions: Condensing temperature 45C - Room conditions 24C / 50% RH
Digital
Digital
Digital
Digital
Digital
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
(*) At standard operating conditions, Filters class F5, ESP: Upflow 50Pa; Downflow Up 20Pa; Downflow Frontal 0Pa.
(**)At nominal operating conditions: Condensing temperature 45C - Room conditions 24C / 50% RH
PX015-021-025-031
F/D/H Siemens VXP45.25-10
2-way chilled water valve Modulating action
all PDX water cooled VXP45.32-16
(W/F/H)
PX015-021-025-031
F/D/H Siemens VXP45.25-10
3-way chilled water valve Modulating action
all PDX water cooled VXP45.32-16
(W/F/H)
ON-OFF
All versions
action
Siemens VXI 469.25
3-way hot water valve
1
COND
CDT
(Distance) D = a + b + c
CDT = Conditioner a
COND = Condenser
G
D
D
A
A*
Floor
Level
C
F
MAX
800
200
PX015
Base Module
300
PX021
(Base
Module with
500-600-
bottom air
PX025 844 1970* 700-800- 600-900 600-900 600 850
intake)
900
600
PX031
(Base
Module with
rear air
PX033
intake)
F (free space between unit bottom and basement): max. 800 mm (base frame/legs kit availability)
min. 600mm (to get declared performances)
min. 300mm (minimum working conditions)
G (free space between ceiling and unit top or plenum top if installed):
min. 600mm (to get declared performances)
min. 300mm (minimum working conditions)
* In Downflow Up and Downflow Frontal units with predisposition for damper, economizer and plenum installation the unit is shipped with
a connecting flange 50 mm high fixed on the unit top, so the unit is 50 mm higher. If required, the flange can be removed by unscrewing
the fixing screws (removing the side panel to access the screws head) and repositioned later (see E.10).
Downflow Up
* Connection size only. The connecting pipe diameter depends on unit model, see Tab. d in par. 5.1.2
*** Optional. Threaded union on request
215.0
CD
83.0
OHW
IHW IL1 / OWC1
87.0
578.0
OG1 / IWC1
HF1
387.0
EC
319.0
HD1 HD2/HF2
223.0
213.0
153.0
155.0
EC aux
118.0
109.5
84.5 68.5
115.5
184.5
Fig. 2 Refrigerant, water and electrical connections PX015 - 021 - 025 - 031 - 033 A-W Upflow, top view
215.0
CD
125.0
70.0
OHW IL1 / OWC1
87.0
578.0
HD1 HD2/HF2
213.0
223.0
153.0
155.0
118.0
EC aux
109.5
84.5 68.5
115.5
184.5
215.0
CD
83.0
OHW
IHW IL1 / OWC1 87.0
578.0
IFC OG1 / IWC1
HF1
387.0
HD2/HF2
319.0
HD1
213.0
223.0
223.0
OFC 153.0
155.0
155.0
EC aux
118.0
109.5
EC
68.5
115.5
Fig. 4 Refrigerant, water and electrical connections PX015 - 021 - 025 - 031 F - D - H Upflow, top view
215.0
CD
125.0
70.0
IHW
OHW IL1 / OWC1 87.0
578.0
HD1 HD2/HF2
316.0
213.0
223.0
223.0
OFC
153.0
155.0
155.0
EC aux
109.5
118.0
EC
68.5
115.5
OG1 / IWC1
IL1 / OWC1
FRONT
135.7
105.7
FLOOR
Fig. 6 - Refrigerant and water connections PX015 - 021 - 025 - 031 - 033 A/W/F/D/H Downflow, side view
OG1 / IWC1
IL1 / OWC1
FRONT
642.0
612.0
FLOOR
FRONT
OFC
IFC
135.7
105.7
FLOOR
Fig. 8 - Refrigerant and water connections PX015 - 021 - 025 - 031 F/D/H Downflow, side view
FRONT
OFC
IFC
642.0
612.0
FLOOR
12
6 15 14
16
10
MC
1 11
SCROLL
COMPRESSOR
3
18
9 FG
6
7
6
8
6 18
5
13 13
SUPPLY LIMIT SUPPLY LIMIT
EXTERNAL TO PDX UNIT EXTERNAL TO PDX UNIT
12
4 CONDENSING UNIT
12
11
6 15 14
16 6
6 10
MC
1 SCROLL
COMPRESSOR 19
18
9 FG
6
7
6
6 18 8
5
13 13
12
4 CONDENSING UNIT
Cond. F
12
15 14
19
16 D
F F
10
MC
6
DIGITAL COMP
1
11
T
20
3
18 9 FG
6
7
6
6 19
21 5 8
13 13
A
SUPPLYING LIMIT
EXTERNAL TO PDX UNIT
12
Cond. F
12
15 14
E
T
6 11
19
16
MC
F F D
2
DIGITAL COMP
10
1
6
20
T
18
9 FG
7 6
A
6 8
6 19
5
21
C
13 13
SUPPLYING LIMIT
EXTERNAL TO PDX UNIT
12
12
6 15 14
16
10
MC
2 11
1 SCROLL
COMPRESSOR
3
9 FG
22
7 6
20
OPTION 8
12
2-WAY VALVE 6 6
5
18
OPTION
A AB 3-WAY VALVE
18 19
B
21
A AB WATER OUTLET
B
4
WATER INLET
12
11
15 14
16
MC
10
2
1 SCROLL
COMPRESSOR
23
22
9 FG
7 6
20
8
12
6
5
OPTION
2-WAY VALVE 6
18
OPTION
A AB 3-WAY VALVE 19
18
B
21
A AB WATER OUTLET
B
4
WATER INLET
Cond. F
12
6
6
23
15 14
F F
16
D
10
MC
DIGITAL COMP. 11
1
T
22
9 FG
23
3 A
B
7 6
10
20
8
12 6
6
5
OPT. 2-WAY VALVE C
18
10
13
A AB B OPT. 3-WAY VALVE 19
18
B
21
G A AB G H WATER OUTLET
B
4
G G H WATER INLET
Cond. F
12
T
11
E
6 6
15 14
23 6
F F
16
D
10
MC
1
DIGITAL COMP.
22
T
9 FG
23
3 B
7 6
10
20
A 8
12 6
5
OPT. 2-WAY VALVE 6 C
18 13
10
A AB B OPT. 3-WAY VALVE 19
18
B
21
G A AB G H WATER OUTLET
B
4
G G H WATER INLET
17
12
6
6
20 15 14
16
MC 10
1 SCROLL 11
COMPRESSOR
9 FG
3
25
6
7
6
24
12 21
8
6
5
18
19
A AB
4
B
23 T
17
12
11
6 6
20 15 14
16 6
MC
10
1 SCROLL
COMPRESSOR 26
3
9 FG
25
6
7
6 21
24
12 8
6
5
18
19
A AB
4
23 T
Compr. Suct. 6
17
6
Compr. Disch./VYTLAK KOMPRESORA Reh. Coil F
12
Cond. F
26
20 15 14
6
6
16 D
10
6
MC
F F 2
1
DIGITAL COMP. 11
T 25
26 9 FG
A B
6 21
10 7
24
12
6 6
5 8
C
13
10
B 19
18
A AB G
4
B
G
23 T
10
COOLING WATER OUTLET L I I I
I
Compr. Suct. 6
17
6
Compr. Disch./VYTLAK KOMPRESORA Reh. Coil F
12
Cond. F
E
T
11
6
20 15 14
26
16
6
6 D
MC
10
F F 2
1
DIGITAL COMP.
T
25
3
26
9 FG
6 21
10 7
6 24
12
6
5 8
13
10
B
19
A 18
A AB G
4
B
G
23 T
10 I
COOLING WATER OUTLET L I I
20
12
OPTION KIT
2-WAY CW VALVE
A 21
B
6 19 15 14 23 AB
B A
16 21
AB
22 T
MC 10
1 SCROLL 11
COMPRESSOR
3 NOT AVAILABLE
FOR MODEL:
18 PX015/021/025/031
9 FG
7
6
8
6 18
5
13 13
SUPPLY LIMIT SUPPLY LIMIT
EXTERNAL TO PDX UNIT EXTERNAL TO PDX UNIT
12
4 CONDENSING UNIT
12
20
OPTION KIT
2-WAY CW VALVE
A 21
B
6
T 23 AB
11
A
B 21
16 19 15 14
6
AB
6
22 T
MC
10
2
1 SCROLL
COMPRESSOR
24
3 NOT AVAILABLE
FOR MODEL:
PX015/021/025/031
18
7
6
8
6 18
5
13 13
SUPPLY LIMIT SUPPLY LIMIT
EXTERNAL TO PDX UNIT EXTERNAL TO PDX UNIT
12
4 CONDENSING UNIT
Cond. F
12
20
15 14
6
OPT. KIT 2-WAY CW VALVE
18
I
21
A
B
AB
6 19 25
6
D
21
16
A
B
F F 10 AB
MC T
22
DIGITAL COMP.
1
11
T
24
NOT AVAILABLE
3 FOR MODEL:
PX015/021/025/031
I
9 FG
23
B
7 6
6
L
26 6 18
5 8
A C
13 13 SUPPLYING LIMIT
COOLING WATER OUTLET
COOLING WATER INLET
Cond. F
12
20
15 14
E T
11
6 OPT. KIT 2-WAY CW VALVE
I
21
18
A
B
16 AB
6 19 25
6
MC 21
A
B
F F 2 D AB
T
10 22
1
DIGITAL COMP.
24 T
3
NOT AVAILABLE
FOR MODEL:
PX015/021/025/031
23
I
9 FG
6 6
7
26
L
6 18
5 8
A
C
13 13 SUPPLYING LIMIT
COOLING WATER OUTLET
COOLING WATER INLET
23
12
OPTION KIT
2-WAY CW VALVE
6
A 21
B
20 15 14 27 AB
6
6
A
B
21
16
AB
22 T
MC
10
2
SCROLL
1 COMPRESSOR
11
NOT AVAILABLE
3 FOR MODEL:
PX015/021/025/031
26 9 FG
7 6
24
12 8
OPTION 6
5
2-WAY VALVE
6
18
OPTION
3-WAY VALVE
A AB 19
18
B
25
A AB WATER OUTLET
4
WATER INLET
12 23
OPTION KIT
6 2-WAY CW VALVE
T A 21
B
11
27 AB
6 20 15 14
A
16 21
6
B
AB
22 T
MC 10
1 SCROLL
COMPRESSOR
28
NOT AVAILABLE
3 FOR MODEL:
PX015/021/025/031
26
9 FG
7 6
24
12 8
6
OPTION 5
2-WAY VALVE
6
18
OPTION
A AB 3-WAY VALVE 19
18
B
25
A AB WATER OUTLET
B
4
WATER INLET
Cond. F
12
23
E
OPT. KIT 2-WAY CW VALVE
I
6 21
A
B
27 AB
20 15 14 28
6
21
F F A
16 B
D AB
22
T
MC 10
DIGITAL COMP.
1 11
26
T
NOT AVAILABLE
FOR MODEL:
PX015/021/025/031
I
9 FG
3 27
B
6
10 7
A 24
12
L
6 6
5 8
OPT. 2-WAY VALVE
C
18
13
10
COOLING WATER OUTLET
COOLING WATER INLET
G G H WATER INLET
Cond./DO KONDENZATORA F
12
23
E T
6
11
OPT. KIT 2-WAY CW VALVE
I
27 21
A
B
16 AB
6 20 15 14 28
F F
MC 21
A
B
2 D AB
T
10 22
1
DIGITAL COMP.
26
T
NOT AVAILABLE
FOR MODEL:
3 PX015/021/025/031
27
I
9 FG
A
B
6
10 7
6 24
12
L
6 L
5 8
OPT. 2-WAY VALVE
13
C
18
VYSTUP CHLADIACEJ VODY
VSTUP CHLADIACEJ VODY
10
COOLING WATER OUTLET
COOLING WATER INLET
G G H WATER INLET
VSTUP VODY
12
20
6 15 14
19
6
16
10
MC
1 11
SCROLL
COMPRESSOR
3
18
9 FG
6
7
6
8
6 18
5
13 13
SUPPLY LIMIT SUPPLY LIMIT
EXTERNAL TO PDX UNIT EXTERNAL TO PDX UNIT
12
4 CONDENSING UNIT
12
13
6 15 14
23
16
10
MC
2
11
1
SCROLL
COMPRESSOR
3 9 FG
22
7 6
20
OPTION 8
12
2-WAY VALVE 6
5
18
OPTION
A AB 3-WAY VALVE
18 19
B
21
A AB WATER OUTLET
B
4
WATER INLET
A base frame can be supplied on request to support Li- A 200 mm high base module can be supplied on request
ebert PDX when installed with a raised floor. The frame to support Liebert PDX Upflow and at the same time al-
could be regulated with a height from 120mm to 800mm low pipework to enter the base of the unit when a raised
and the unit is fixed on it. floor is not installed.
Upflow Downflow
The fresh air kit, optional, has a G3 class filter installed As the fresh air intake is positioned close to the fan suc-
on the intake side of the fan and is connected to the PDX tion, it will easily mix with the recirculation air.
unit with a 100 mm diameter plastic duct.
An extension hood can be supplied on request and can Optional high efficiency filters, filtration class F6, F7 and
be installed on top of the unit. It is available with different F9 in accordance with the CEN EN 779 standard, are
height: 500mm; 600mm; 700mm; 800mm; 900 mm. It has made of fiberglass filter media.
the same design as the unit and consists of sandwich The filters are placed in V sections with a solid external
panels lined with non-flammable insulation material of frame in polypropylene and can withstand remarkable
class 0 (ISO 1182.2), density 30 kg/m3. pressure and flow variations. These filters will be installed
within an additional duct on the unit top.
E.7 Plenum with silencing cartridges E.8 Horizontal hood with grill
These are special cartridges made of self-extinguishing A supply plenum with horizontal air flow can be installed
material with a high noise attenuation capacity. They are on top of the unit. The 600 mm high plenum has the same
guaranteed against disintegration and release of parti- design as the unit; it consists of sandwich panels lined
cles do to friction of the air. with non-flammable insulation material of class 0 (ISO
Despite a small additional pressure drop, these cartridg- 1182.2), density 30 kg/m3. It is equipped with a double
es provide a remarkable sound power level reduction. deflection grill.
The Air Economizer comprises an extension hood 860mm To use the Air Economizer the building has to be equipped
height with a dampers system installable on top of the with suitable air ducts and the dampers system modulat-
Downflow units. This system allows the freecooling taking ing permits to use different channel configurations.
advantage of cool outdoor air to condition indoor space. Note: It is required a flange 50 mm high to connect the air
The Air Economizer system delivers high energy savings economizer to the unit (see E.10).
reducing or eliminating the cost for refrigerant pumping.
In Downflow Up and Downflow Frontal units with predis- If required, the flange can be removed by unscrewing
position for damper, economizer and plenum installation the fixing screws (removing the side panel to access the
the unit is shipped with a connecting flange 50 mm high screws head) and repositioned later.
fixed on the unit top, so the unit is 50 mm higher.
F. 2 - Installation
The infrared humidifier is supplied already mounted within the air conditioner. The only necessary operations are the connections for the
supply water and drain water.
Supply Water.
Maximum water pressure 200 kPa
Size humidifier supply line for 3.8 l/min, with a minimum water pressure of 138 kPa
Do not supply de-ionized water to the humidifier
Drain Water.
This contains the same substances dissolved in the supply water, however in larger quantities;
It may reach a temperature of 100 C;
It is not toxic and can be drained into the sewerage system, category 3, EN 1717.
Dispose the drain hose into an ordinary drainage network. The drainage network should have a siphon and must be able to withstand
temperatures up to 100C
F. 2.1 - Infrared humidifier components
1. humidifier pan 6. discharge connection
2. humidifier standpipe 7. supply line
3. solenoid valve flow regulation 8. manual reset thermostat
4. float switch 9. infrared bulbs
5. junction block
F. 4 - Maintenance
WARNING: Optical radiation; the humidifier components may be hot. Let it cool down before touching it or use
protective gloves.
The infrared humidifier contains live electrical components and hot surfaces and therefore all service and/or maintenance operations must
be performed by expert and qualified personnel, who are aware of the necessary precautions.
Before performing any operations, check that the humidifier is disconnected from the power supply; carefully read and follow the instruc-
tions contained in the manual.
F. 4.1 - Cleaning Humidifier Pan and Float Switch
Before turning off unit:
1. With the unit operating, remove call for humidification at the Liebert iCOM control.
2. Let the blower operate 5 minutes to allow the humidifier and water to cool.
3. Turn the unit Off at the Liebert iCOM control.
4. Open the air conditioner door and remove safety panels, if installed.
5. Pull out the humidifier standpipe in pan.
6. Inspect the O-ring (replace if necessary).
7. Let the pan drain and the condensate pump operate (if applicable).
8. Disconnect power from the unit.
9. Disconnect the drain coupling from the bottom of the pan.
10. Remove the thermostat from the bottom of the pan and retaining screws from sides of pan.
11. Slide pan out.
12. Loosen scale on the side and bottom of the pan with a stiff nylon brush or plastic scraper.
13. Flush with water.
14. Carefully clean the scale from the float switch (make sure to reinstall correctly; see Figure 2).
15. Reinstall the pan, thermostat, standpipe, drain coupling, cover and screws into the humidifier.
16. Operate the humidifier and check for leaks.
CAUTION: Touching quartz lamps with bare hands will severely shorten bulb life. Skin oils create hot spots on lamp
surface. Wear clean cotton gloves when handling lamps.
1. Remove the humidifier pan (see F.4.1 - Cleaning Humidifier Pan and Float Switch, Steps 1 to 11).
2. Disconnect power from the unit.
3. At the humidifier, remove the screws and cover from the high-voltage compartment.
4. Disconnect one end of the purple jumper wires.
5. Using a continuity meter, locate the burned-out lamp.
6. Remove the lamp brackets under the lamps.
7. Loosen the two screws securing the lamp lead wires to the junction block.
8. Pull the bulb straight down and discard it.
9. Wrap the lead wires once around the new lamps metal ends. This will support the lamp and allow for thermal expansion. Insert the
lead wires into the junction block and torque the screws
10. Reassemble by reversing Steps 1 to 9.
F. 4.3 - Periodical checks
1. Check drain lines and trap for clogs
2. Check/clean pan for mineral deposits
3. Clean reflector
4. Check water make-up valve for leaks
5. Check humidifier lamps (replace if burnt out)
6. Check wire connections (inside humidifier box)
G. 2 - Installation
The Ultrasonic humidifier is supplied mounted within one base module 400 mm heigh.
The base module with humidifier is supplied stand alone and it will be installed and connected with the air conditioner on field.
The module can be installed on the raised floor, see Fig. 1, or in the raised floor, see Fig. 2 (front and bottom module opened, sides and
back module closed).
When installed in the raised floor it is necessary to remove the module frontal panel to have also frontal air delivery.
A base frame, available on request, is required to support ultrasonic humidifier module.
Ensure 1 meter of free space (without obstacles) on ultrasonic humidifier module outlet.
Connect humidifier electrical cable, coming from the air conditioner, to the ultrasonic humidifier.
Connect water supply, water drain, safety overflow and humidifier drain pan water drain.
The relevant piping connections shall be in material resistant to fully demineralized water.
Refer to HSU08RM000 manual for details.
Fig. 1 - Ultrasonic humidifier module on the raised floor, frontal and lateral views
Supply Water.
Supply fully demineralized water with conductivity < 5 S/cm. If demineralized water is not available, provide demineralizer (not
supplied);
Water pressure from 50 kPa to 500 kPa;
Water temperature from 8C to 40C;
Dust or dirt must not get into the water lines;
Refer to HSU08RM000 manual for details.
Drain Water.
The drain water contains the same substances dissolved in the supply water, however in larger quantities;
It is not toxic and can be drained into the sewerage system, category 3, EN 1717;
Dispose the drain hose into an ordinary drainage network (the drainage network should have a siphon).
Refer to HSU08RM000 manual for details.
G. 2.1 - Ultrasonic humidifier components
1. humidifier 10. safety overflow
2. fan case 11. mist guide pipe
3. mist guide cover 12. ring and nut
4. fan 13. humidifier drain pan
5. metal plug 14. air filter
6. cable 15. water supply connection
7. metal plug 16. check valve (to be provided by the Customer)
8. cable 17. damper
9. water drain 18. humidifier drain pan water drain
Fig. 3 - The Ultrasonic humidifier and its components
G. 4 - Maintenance
If the humidifier is not used for a long period, the water must be drained off.
NEVER operate the humidifier without air supply.
Before performing any operations, check that the humidifier is disconnected from the power supply; carefully read and follow the instruc-
tions contained in the manual.
G. 4.1 - Periodical checks
1. Check drain lines and trap for clogs
2. Check/clean pan for dust
3. Check wire connections (inside humidifier box)
4. Check status of humidifier air filters
Cooling.NetworkPower.Eu@Emerson.com
While every precaution has been taken to ensure accuracy and completeness
herein, Emerson assumes no responsibility and disclaims all liability for damages
resulting from use of this information or for any errors or omissions.
Specifications subject to change without notice.
EmersonNetworkPower.eu
Emerson, Business- Critical Continuity and Emerson Network Power are trademarks of Emerson Electric Co. or one of its affiliated companies. E2013 Emerson Electric Co.