3, JULY 2007
AbstractAn analysis of the voltages induced on a 1-km pipeline uniform. When the imbalance of the three-phase electromag-
by a parallel overhead transmission line has been carried out when netic field and the higher magnitudes of fault current flows are
the transmission line is carrying power frequency (50 Hz) current considered, it becomes obvious that much higher pipeline volt-
and when it is subject to the propagation of a lightning or switching
transient. A frequency-based circuit modeling technique coupled ages can be produced.
with forward and inverse Fourier transforms is used to carry Capacitive coupling only affects pipelines located above
out this analysis. The relative severity of the induced voltages ground since these have both a capacitance to the transmission
from power frequency current or transient (lightning/switching) line and to earth. They therefore effectively act as a potential
overvoltages is illustrated using the simulation results. The results divider. In this case, there is no variation of induced voltage
demonstrate the high relative magnitude of induced pipeline
voltages that result from the propagation of lightning transients with length. Generally, capacitive coupling is a secondary
down overhead lines. The need to model the full overhead line for effect in terms of the total voltage induced on a pipeline with
such an analysis is investigated as is the variation of the level of any significant amount of parallelism to an overhead line.
transmission line/pipeline coupling as a function of the local soil Pipelines buried below ground are shielded from the electric
resistivity. Analysis of the level of induced voltage as a function of field produced by the transmission line and cannot be affected
length of parallelism is also carried out.
by capacitive coupling.
Index TermsLightning, pipelines, switching transients, trans- Resistive coupling between a transmission line and a pipeline
mission lines. is only relevant during ground faults when significant levels of
current flow into the earth. For example, if a phase-to-earth fault
takes place at an overhead line tower close to the pipeline, the
I. INTRODUCTION
potential at the base of the tower will rise as will that of the
surrounding ground. This, in conjunction with the high level of
T IS common practice to consider the electromagnetic inductive coupling that will take place in this situation, puts the
I coupling of parallel transmission lines and pipelines during
steady-state and faulted operation of the power system to ensure
pipeline at severe risk.
There are three main reasons for being concerned about the
unsafe or damaging voltages are not present on the pipeline. rise in the potential of a pipeline. First, any person touching a
All pipelines or other metallic structures running parallel to pipeline that is subject to the influence of a high-voltage trans-
ac transmission lines are subject to interference arising from mission line may be at risk from electric shock. For this reason,
inductive, capacitive, and resistive coupling. maximum allowable levels of steady-state induced voltage are
Inductive coupling arises when the pipeline is placed in a generally imposed on pipelines. These maximum levels vary
time-varying magnetic field. The voltage found at the pipeline from country to country but typically are in the order of 50
ends will vary linearly as a function of length of parallelism for V (although values as low as 10 V exist). Similar restrictions
cases where the pipeline is well coated (i.e., has a high resistance exist concerning the maximum voltage that can be present on
to earth) and will vary according to soil resistivity. Pipelines a pipeline during a power system fault. The allowable voltage
during the flow of power system frequency fault current is typ-
above and below ground are both affected by inductive coupling.
When the transmission line is operating in a normal condition, ically between 300 V and 1500 V [1].
the electromagnetic fields produced by the three overhead line These values of voltage are based on safe levels of current
phases generally balance each other and significantly reduce the that can be tolerated by the human body and the impedance
of the current path. Higher voltages would be tolerable when
net field seen by the pipeline. This is not the case when an asym-
metrical fault is present on the power system and flows are not making contact with coated pipelines as the coating will it-
self present an impedance and will therefore serve to limit
the current. Footwear and ground resistivity will also alter
Manuscript received May 21, 2006; revised October 5, 2006. Paper no.
TPWRD-00127-2006.
the impedance of any current path involving the feet. When
The authors are with the School of Electrical and Electronic Engineering, applying such criteria, the possibility of coming into contact
University of Manchester, Manchester, U.K. (e-mail: ian.cotton@man- with an uncoated portion of pipeline (either due to touching a
chester.ac.uk). large coating defect or a pipeline valve) usually ensures that
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. the pipeline coating resistance cannot be considered in any
Digital Object Identifier 10.1109/TPWRD.2006.886771 calculation.
0885-8977/$25.00 2007 IEEE
COTTON et al.: COMPARISON OF TRANSIENT AND POWER FREQUENCY-INDUCED VOLTAGES 1707
The second reason for being concerned in regards to induced lightning or switching surges damaging the pipeline coating/
voltages relates to the pipeline integrity. A pipeline under the equipment or causing risk to human life.
influence of a high-voltage transmission line will have voltages Pipeline voltages resulting from the propagation of such tran-
established between the outer coating layer and the metallic sients on the transmission line may have the ability to damage
pipeline. If this voltage becomes too high, coating damage may the pipeline coating and/or equipment. Anecdotal evidence
take place, giving rise to the risk of subsequent corrosion. This exists of impressed current cathodic protection systems being
corrosion risk can be due to the development of a continuous damaged during lightning storms. One utility in the U.K. has
flow of alternating current (ac) through the coating defect site also reported anecdotal evidence of impressed current cathodic
or due to the increased requirement placed on the pipeline ca- protection systems failing at the same time as switching has
thodic protection system. It is recognized that higher ac current been carried out on a parallel overhead line. It is more difficult
flows will result in an increased need for cathodic protection to assign lightning as the cause of coating damage as such
[2]. Typical coatings have electrical strengths varying from 20 damage can exist for a number of different reasons. However,
kV for a fusion bonded epoxy material to 85 kV for a three-layer should voltages rise to the levels described above in the discus-
coating [33]. These voltages will not usually be seen across the sion of coating strength, it is likely that coating damage can be
coatings. However, the electrical strengths given are for perfect caused by lightning and/or switching.
coatings, defects in the coating will significantly reduce the di- Their ability to cause electric shock to a person is more
electric strength figure quoted. questionable. IEC 604794 deals with the risk of electric
Finally, if a pipeline rises in voltage with respect to the soil shock from lightning but only gives general guidance on the
surrounding it, equipment that is connected to the pipeline may comparison of such shocks to those from voltages of a standard
be damaged. Of particular importance in this regard are im- power frequency [6]. Significantly though, IEC 604794 does
pressed current cathodic protection systems that rectify low- state The interaction of a lightning stroke with the victims
voltage ac to provide pipeline protection. These must be pro- body is quite different from the usual experience with electric
tected against the overvoltages that can be induced on pipelines. shock derived from electrical systems. Even very short single
It is therefore clearly important to assess the voltages induced impulses of lightning can cause cardio-pulmonary arrest.
onto a pipeline by an overhead transmission line. These studies Further information is found in other members of the IEC
are routine and can be carried out using specialist software. 60479 family. IEC 604791 states that for shock durations
Much of the difficulty in carrying out such studies will only below 0.1 s, ventricular fibrillation may occur for current
relate to the gathering of accurate input data, soil resistivity data magnitudes above 500 mA and is likely to occur for current
being particularly time consuming to collect in an accurate magnitudes in the order of several amperes, only if the shock
manner. However, a factor not commonly assessed during falls within the vulnerable period [7]. It also states that body
pipelinetransmission-line interference studies is the impact impedance typically lies between 500 and 1000 for
of switching and lightning surges on the pipeline. In well- voltages above 1000 V. This assumes that the skin impedance
maintained transmission-line circuits, particularly those in areas is not significant as for high voltages that it has usually broken
of high lightning activity, the propagation of lightning surges down.
down an overhead line will be a reasonably regular event. IEC 60479-2 deals with the effects of short duration currents
Switching surges will also pass up and down the overhead (a minimum duration of 100 ) [8]. At this minimum duration,
line whenever switching is carried out locally on the power it states that there is a risk of death associated with a current
system. flow of around 8 A, at the higher end of that discussed by IEC
There is minimal literature on this topic. In the NACE stan- 60479-1.
dard recommended practice Mitigation of Alternating Current Assuming a worst-case body resistance of 500 , 8-A current
And Lightning Effects On Metallic Structures And Corrosion would need to be driven by 4-kV voltage. This would not cause
Control Systems, lightning is described in regards to direct death in every case as the shock would need to be at the vul-
strikes and its ability to cause phase-to-earth faults on the over- nerable period of the heartbeat and factors, such as coating re-
head line. Switching surges and other transients are simply said sistance, could decrease the current flow as described for power
to cause a momentary increase in inductive and capacitive cou- frequency currents earlier. However, this magnitude of voltage
pling on the affected structures [4]. No quantification of the rel- seems appropriate to use as a reasonable estimate of the safety
ative severity of lightning is performed nor is guidance given on level.
how such quantification could be performed. A paper by Licht-
enstein [5] also deals with the hazards posed by alternating volt-
II. SYSTEM MODELING
ages and lightning on transmission lines to pipelines but has the
same limitations as the NACE document.
A. Description of Transmission Line and Pipeline
Given the current gaps in the understanding of the effect of
fast transmission-line transients on pipelines, this paper intends The system modeled consists of a 132-kV overhead line and
to establish whether such transients are likely to expose the a parallel pipeline. The 132-kV overhead line is a double-cir-
pipeline to a significant risk of damage in comparison to that cuit three-phase line with the lowest conductors placed 20.85 m
resulting from power frequency faults. To carry out this task, a above the earth. Single ACSR Hawk conductors are used for
pipelinetransmission-line parallelism is modeled over a 1-km the phases and the shield wire. The phase rotation is as shown
distance. This work is carried out to examine the likelihood of in the diagram of Fig. 1.
1708 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007
The pipeline has a 0.6096-m outer diameter and a wall being raised in potential will be limited to the local area of the
thickness of 7.9 mm. It is a steel pipeline with the steel having pipeline and not to a significant section. Conductive coupling
a resistivity of 0.22 and a relative permeability of 100. has been taken to be outside the scope of this paper. This is
A 2.5-mm anticorrosion coating is placed on the outside of the due to the simulation of an above ground pipeline. A hazard
pipeline. The coating has a conductivity of 200 and a to human life and to pipeline equipment due to conductive cou-
relative permittivity of 3. The pipeline is placed 1 m above the pling would only occur if either were in close proximity to a
ground to ensure it is subject to both inductive and capacitive struck tower at the time of the strike.
coupling. The lightning surge that has been modeled has 650 kV peak.
Three distinct situations have been modeled. The first is a In an identical way to the switching surge, a voltage source
reference case where power frequency current flows along the is used to inject this surge, the peak current of which can be
overhead line conductor to simulate the inductive coupling ex- found by dividing the peak current with the overhead line surge
pected during the passage of both load and fault current. This impedance. Capacitive and inductive coupling are therefore also
analysis is performed without the use of a voltage source on both modeled in this case.
the line as capacitive coupling is not considered significant in
most cases, especially when load/fault currents are flowing on B. Simulation Techniques
the system. This simulation is performed with the assumption A circuit modeling technique is used to perform the analysis.
that the fault is remote from the pipeline/transmission line par- This technique is established for lower frequency studies [9] of
allelism and conductive coupling is therefore neither modeled transmission-line interference and has been shown to be valid
nor discussed. A further simplification is made where the mag- for studies with higher frequencies within the constraints of this
netic field reducing effect of return current flowing through the work. Use of a circuit-based technique is preferable to the use
shield wire is not modeled. For the 132-kV transmission line of a field-based technique in terms of the time taken per sim-
modeled, a typical load current would be in the order of 200 A ulation. A field based approach takes around 24 h to simulate
root mean square (rms) while the phase-to-earth fault current the response of the pipeline to a single surge against around 30
would be 2 kA rms. min for a circuit model. A field-based approach does have an
Switching surges are reasonably straightforward to model advantage in that it could be used to examine conductive cou-
as they will be generated at a location where some form of pling accurately but this is not in the scope of this paper.
switching can take place, such as a substation or a generation In the circuit model, the self and mutual impedances of all the
plant. The rated switching impulse level of a 132-kV overhead conductors within the system are computed and used to deter-
line is around 3 p.u. or 325 kV peak (phase to earth). In the mine voltage/current distributions for a specific frequency. To
simulations, a voltage source injects an impulse of the appro- analyze the response of the pipeline to a transmission-line tran-
priate shape into the overhead line. The overhead line has a sient, time-domain computation results are generated using re-
given surge impedance and, in accordance with traveling-wave sults from the simulations carried out at multiple values of fre-
theory, the voltage impulse can be described as being equal to quency and Fourier transforms. The lumped parameter model
a current magnitude determined by the division of the peak of ensures that the behavior of traveling waves on both the pipeline
the injected voltage with the overhead line surge impedance. and the overhead line are accurately represented.
Capacitive coupling and inductive coupling are therefore both In accordance with the flowchart shown in Fig. 2, a transient
modeled using the single injection of voltage. surge (either switching or lightning) is transformed into its fre-
For lightning surges, there are a number of types of study quency components by forward fast Fourier transform (FFT) op-
that could be performed. Lightning can hit the phase conductors eration. A double exponential waveform of the form given as 1)
of an overhead line (an event known as shielding failure) and, is to used to simulate the lightning/switching surge and this will
depending on the magnitude of the overhead line voltage rise, have the resulting frequency spectrum detailed in (2). A finite
flashover the overhead line insulation to the tower. The shield number of frequencies constituting a representative sample of
wire of the overhead line can also be hit, and below a certain cur- the frequency spectrum of the surge are selected and the voltage
rent level, this current will simply propagate in both directions induced on the pipeline is then evaluated for each frequency
along the shield wire and down any tower in the propagation
path. When the current rises above a given level, the voltage of (1)
a nearby/struck tower will rise enough to flashover the line insu- (2)
lation resulting in a so-called backflashover. This will therefore
result in the propagation of a lightning transient down the con-
ductor to which the flashover has taken place. It will also result This leads to the production of a frequency spectrum giving
in the passage of 50-Hz phase-to-earth fault current. the response of the pipeline to 1 p.u. (i.e., 1 V) energization on
For all of these cases, surges propagate down shield wires/ the overhead line. The frequency spectrum will inevitably con-
phase conductors. These surges can propagate considerable dis- tain resonances at various frequencies and the software auto-
tances. An overhead line may therefore be hit by lightning away matically detects such areas in the frequency spectrum where
from any parallelism but the surge can then propagate toward an the pipeline response is not fully detailed. Further computa-
area where parallelism exists. For the cases where conductive tions at additional frequencies are carried out until the frequency
coupling, (the flow of lightning current into the tower grounding spectrum is accurately described by a number of discrete sim-
system) is involved, the impact of that tower earthing system ulation results. By using the forward FFT of the originally se-
COTTON et al.: COMPARISON OF TRANSIENT AND POWER FREQUENCY-INDUCED VOLTAGES 1709
TABLE I
SURGE IMPEDANCE AND TRAVELING-WAVE
VELOCITY OF PIPELINE AND OVERHEAD LINE
III. RESULTS
Fig. 1. Phase positioning and dimensions of the 132-kV overhead line. The
lowest conductors are 20.85 m from the surface of the ground. A. Calculation of Transmission-Line and Pipeline Surge
Impedance
In the simulations carried out to determine the magnitude
of induced voltages from transients, surge impedance termina-
tions are used on the overhead line and the pipeline. To deter-
mine the transmission-line and pipeline surge impedances and,
thus, stipulate the value of these within the final model, simula-
tions were carried out where a single conductor is modeled. A
1-V surge was injected into one end of the conductor with the
other end being left open circuit. The resulting current wave-
form at the surge injection point can be used to determine the
surge impedance and the traveling-wave velocity (by examina-
tion of the reflections from the open-circuit point). The results
are shown in Table I and describe the surge impedance of the
pipeline and the lowest overhead line phase conductor. All other
overhead line conductors have similar surge impedances.
Fig. 4. Frequency spectrum of lightning surge and switching surge. Fig. 7. Time-domain voltage induced at end of the pipeline by a switching
surge.
result for this particular simulation task. For this simulation, TABLE II
the overhead line was also not elevated in voltage as during a RESPONSE OF PIPELINE TO POWER FREQUENCY CURRENT, LIGHTNING SURGE
AND SWITCHING SURGE PROPAGATING DOWN THE OVERHEAD LINE
fault; it would be usual for the voltage to significantly reduce
on the power system. This means that inductive coupling is the
only significant interference mechanism in this simulation.
In Table II, a comparison of the results are shown. The max-
imum voltages that are induced on the pipeline are presented.
These are calculated using the values in Table II and scaling
them using the typical values for a 132-kV transmission line
presented in Section II-A. In the case of the 50-Hz current, the
fault current level is used as the scaling factor. Load current will
normally result in a very low induced voltage owing to its low
magnitude and balanced three-phase nature.
It is clear that a lightning surge gives by far the highest voltage
on the pipeline at 18.3 kV. This could realistically cause damage TABLE III
to a pipeline coating or to any impressed current cathodic pro- INDUCED PIPELINE VOLTAGE FOR A LIGHTNING SURGE
PROPAGATING DOWN A PARTICULAR OVERHEAD LINE PHASE
tection system used by the pipeline. The 50/60-Hz values are WITH/WITHOUT THE OTHER CONDUCTORS MODELED
significantly lower although they would exist on the pipeline for
a longer period of time.
A limitation of these results worthy of note relates to the non-
linear effects of overhead line corona that are not easily modeled
in lumped parameter software operating in the frequency do-
main. When an overhead line is raised in voltage, the increased
electric field around the conductor will cause corona to form.
This has a resulting effect of increasing the apparent diameter
of the conductor and this would raise the mutual capacitance be-
tween the overhead line and the pipeline. Energy losses would
also take place from the overhead line due to the corona.
TABLE IV
INDUCED PIPELINE VOLTAGE AND INDUCED VOLTAGE
PER METER AS A FUNCTION OF PARALLELISM LENGTH
REFERENCES
[1] P. Kouteynikoff, Results of an international survey of the rules lim-
iting interference coupled into metallic pipelines by high voltage power
systems, Electra, no. 110, pp. 5566, 1987.
Fig. 13. Per-unit induced time domain voltage for a 100-m and 1000-m trans- [2] J. S. Smart, D. L. van Oostendorp, and W. A. Wood, Induced ac creates
mission linepipeline parallelism. problems for pipelines in utility corridors, Pipeline Gas Ind., vol. 82,
no. 6, pp. 2525, 1999.
[3] P. Andrews, Private Communication, National Grid, U.K., 2006.
to earth than the overhead line and a significant inductance due [4] Mitigation of Alternating Current and Lightning Effects on Metallic
to the high steel permeability. Structures and Corrosion Control Systems. Houston, TX: NACE Int.,
2000.
Fig. 13 shows the significant effect that the shift in the reso- [5] J. Lichtenstein, AC and lightning hazards on pipelines, Mater. Per-
nant frequency has on the shape of the induced voltage when a form. , vol. 31, no. 12, pp. 1921, 1992.
shorter parallelism exists. The time-domain waveform is much [6] Effects of Current on Human Beings and LivestockPart 4: Effects of
Lightning Strokes on Human Beings and Livestock 2004, IEC Tech.
richer in high frequencies in comparison to a longer parallelism Rep. 60479-4.
and the waveform is therefore significantly shorter in duration. [7] Effects of Current on Human Beings and LivestockPart 1: General
The results indicate that transients voltages are likely to be Aspects 2005, IEC 60479-1.
[8] Effects of Current Passing Through the Human BodyPart 2: Special
more significant for pipelines with shorter parallelisms. That is, Aspects 1987, IEC 60479-2.
as for these cases, the transient coupling will be dominant. As [9] F. P. Dawalibi and R. D. Southey, Analysis of electrical interference
the parallelism gets longer, the level of inductive coupling at the from power lines to gas pipelines: II. Parametric analysis, IEEE Trans.
Power Del., vol. 5, no. 1, pp. 415421, Jan. 1990.
low-power system frequencies will continue to increase linearly [10] F. P. Dawalibi, W. Xiong, and J. Ma, Transient performance of sub-
with distance while the amount of coupling due to transient volt- station structures and associated grounding systems, IEEE Trans. Ind.
ages will rise more slowly. Appl., vol. 31, no. 3, pp. 520527, May/Jun. 1995.
Konstantinos Kopsidas was born in Lefkas, Greece, Yang Zhang (Elton) was born in Chengdu, China,
in 1977. He received the Higher Technological Edu- in 1984. He is currently pursuing the B.Eng. (Hons.)
cation degree in electrical engineering from Institute degree in electrical and electronic engineering at the
of Piraeus, Athens, Greece, in 2002 and the Class University of Manchester, Manchester, U.K.
I B.Eng. (Hons.) in electrical and electronic engi-
neering from the University of Manchester Institute
of Technology (UMIST), Manchester, U.K., in 2004.
In 2006, he received the M.Sc. degree in electrical
power engineering at the University of Manchester,
Manchester, U.K.