Академический Документы
Профессиональный Документы
Культура Документы
Applied Energy
journal homepage: www.elsevier.com/locate/apenergy
h i g h l i g h t s
a r t i c l e i n f o a b s t r a c t
Article history: The present study attempts to reduce the supply of outdoor air in conditioning building spaces for energy
Received 12 January 2017 saving while improving the indoor air quality. A hybrid air treatment system incorporating a cooling sys-
Received in revised form 28 February 2017 tem is introduced for tropical climates. The air treatment system (ATS) comprises an ozone-based oxida-
Accepted 14 March 2017
tion process and an air scrubbing device. The air purification process has been experimentally
Available online xxxx
investigated. Experimental results demonstrated the feasibility of the proposed ATS to provide improved
indoor air quality. A validated mathematical model has been employed to study the air cooling and dehu-
Keywords:
midification process through the cooling coil. The reduced outdoor air intake facilitates a higher chilled
Air-conditioning
Cooling load
water supply temperature resulting in an improved chiller performance and reduction of cooling load.
Mathematical model The energy consumption performance of the proposed hybrid ATS air-conditioning system has been eval-
Indoor air quality uated for an office building experiencing tropical climatic conditions. The cooling load on a design day has
Energy consumption demonstrated that the reduction of outdoor air intake enabled marked energy savings potential in terms
of the cooling demand. By analysing the building performance based on tropical climatic data, an annual
energy consumption saving of up to 64.6 kW h/m2 can be achieved via the hybrid ATS air-conditioning
system.
2017 Elsevier Ltd. All rights reserved.
1. Introduction with sick building syndrome (SBS) symptoms [5,6]. Research works
have been carried out to develop improved ACMV systems [711].
One of the key concerns in air-conditioning system is to supply Rackes et al. [12] generated guidelines for improving the design of
a comfortable and healthy indoor environment for building occu- natural ventilation for commercial buildings in warm and hot cli-
pants. In a normal air-conditioning mechanical ventilation (ACMV) mates. Tong et al. [13] investigated the potential of energy savings
system, extensive outdoor air is employed to dilute and remove on the natural ventilation with the influence of outdoor air pollu-
indoor air contaminants [1,2]. tion. They pointed out that a reduction of 878% of the energy con-
The design of ventilation system is an important issue affecting sumed by cooling can be potentially achieved due to the utilization
the energy performance [3,4]. In addition, building ventilation of natural ventilation subjecting to ambient air quality. Hughes
impacts the indoor pollutant removal process which is associated et al. [14] studied an energy recovery system for natural ventila-
tion based on heat pipe technology. The simulation results demon-
strated the ability of the system to reduce the energy consumption
Corresponding author at: Department of Mechanical Engineering, National
loads in domestic buildings. Ben-David and Waring [15] compared
University of Singapore, 9 Engineering Drive 1, Singapore 117576, Singapore.
the influence of natural ventilation and mechanical ventilation on
E-mail address: mpeckje@nus.edu.sg (K.J. Chua).
http://dx.doi.org/10.1016/j.apenergy.2017.03.067
0306-2619/ 2017 Elsevier Ltd. All rights reserved.
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
2 X. Cui et al. / Applied Energy xxx (2017) xxxxxx
Nomenclature
the concentration of indoor pollutants such as carbon dioxide and treatment. Waring and Wells [35] found that the ozone and the
formaldehyde. The energy consumption simulation was conducted hydroxyl radical influenced the total VOC conversion. Gallego
for a typical office building in United States. Abou Hweij et al. [16] et al. [36] investigated the performance of activated carbon filter
employed a computational fluid dynamics model to optimize a for VOCs removal. The removal efficiencies of the commercially
chair-fan integrated displacement ventilation system for improv- available activated carbon were useful in terms of future ventila-
ing the indoor air quality. Li et al. [17] presented the characteristics tion design. Sidheswaran et al. [37] indicated that the activated
of space cooling load for residences in the subtropics. They have carbon filter has a long adsorption lifespan and was a promising
analyzed the indoor humidity control considering the mismatching method for air cleaning.
of the sensible heat ratio (SHR). Chua et al. [18] compared different A review of previous works pointed out existing limitations and
strategies for indoor humidity control. A mathematical model was research gaps. Conventional ACMV systems depend on the outdoor
developed to study the part-load performance. Wang et al. [19] air to sustain an acceptable indoor air quality. However, outdoor
proposed an index named normalized concentration in the target air may sometimes contain high levels of pollutants. Conventional
zone (NC-TZ) which was capable of evaluating the impact of local ventilation process using unhealthy outdoor air can cause indoor
ventilation on the indoor air quality. Stabile et al. [20] suggested air quality to deteriorate. In addition, few attempts have been
that a better airing effect can be produced by employing passive made to investigate the helpful means to minimize the outdoor
ventilation grilles with automatically controlled opening section. air intake with the integration of an efficient air-treatment tech-
Lee et al. [21] proposed to combine the dedicated outdoor air ven- nique. These issues motivated the present work to develop and
tilation (DV) with dry cooling (DC) air-conditioning system. The study a novel ACMV system. The originality of this work is to intro-
DCDV system was able to achieve desirable indoor conditions with duce an air treatment system (ATS) that is capable of reducing the
an annual energy saving by 54% over CAV system with reheat. Fong polluted outdoor air intake while promoting improved energy
et al. [22] presented experimental study on three ventilation efficiency.
strategies with six exhaust configurations. It was concluded that The present study aims to (1) introduce an air treatment system
the stratum ventilation with rear-middle-level-exhaust can pro- (ATS) with air purification devices, (2) evaluate the performance of
vide satisfied comfort indoor condition while consuming the least primary components in the ATS, and (3) investigate the annual
value of energy. Martins [23] pointed out that the energy saving of energy consumption performance of the hybrid ATS air-
2580% on the air-conditioning system can be achieved when the conditioning system for an office building in tropical climates.
outdoor air condition was favorable in California. In tropical cli-
mates, however, the energy required to condition the outdoor air
constitutes a considerable portion of the total space-conditioning 2. System descriptions
load [2426]. Indeed, it is a real challenge to design and engineer
an energy-efficient ACMV system without sacrificing indoor air The air treatment system (ATS) is proposed to improve air qual-
quality [27,28]. ity of conditioned spaces and to reduce energy consumption of
People spend substantial portion of their time in rooms. The chiller systems. Fig. 1 shows an overview of the schematic diagram
indoor air pollutants can be emitted from building material, fur- of hybrid ATS air conditioning system. The plug-and-play ATS
nishings, occupancy, unvented combustion and other processes consists of two major components, namely, an ozone-based oxida-
[29,30]. Volatile organic compounds (VOCs) is one of the major tion treatment unit and an air scrubbing unit. The return air is first
concerns for indoor air quality since some VOCs may have adverse purified through the ozone-based oxidation treatment process
health effects on human [31,32]. Zhang and Xu [33] developed an which is an effective approach of cleaning air. After the oxidation
improved mass transfer model to analyze VOC emissions from treatment process, the excess ozone can be removed by using a
building materials. Correlations were provided as a function of commercially available ozone destruction unit. The ozone can be
mass transfer Biot number and mass transfer Fourier number. catalyzed into oxygen immediately in order to maintain the ozone
The comparison of building materials was conducted by Cheng concentration to below 0.05 ppm levels. Thereafter, the air scrub-
et al. [34] to study the VOCs emissions and the impact due to ozone ber unit reduces the concentration of CO2 and further remove other
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 3
unwanted air contaminants such as VOCs, dusts and smokes. The Table 1
purified air is finally cooled and dehumidified to the required sup- The specification of measuring instruments.
ply condition by the air handling unit using chilled water. The Parameter Measurement Accuracy
hybrid ATS air-conditioning system is able to reduce the ranges
outdoor-air intake due to the air purification procedure. In addi- VOC concentration 0.11000 ppm 2% of reading
tion, the reduced outdoor air supply will contribute to marked Ozone concentration 010 ppm (0.01 ppm + 7.5% of reading)
energy savings potential in terms of the cooling demand due to CO2 concentration 02000 ppm (1.5% of range + 2% of reading)
Air velocity 08 m/s 5% of reading
the decrease of cooling load and the improvement of chiller
efficiency.
blower with variable speed drive, the air was circulated and trea-
3. Methodology
ted through the scrubber canister. The canister was packed with
activated carbon for air scrubbing. The specifications of sensors
3.1. Experimental setups
are given in Table 1. The measuring instruments were inserted at
various locations to monitor the air scrubbing performance.
Fig. 2 depicts the experimental setup for the ozone-based oxida-
In addition, an experimental study was also conducted on a
tion treatment unit. An insulated air-tight chamber of size
water-cooled scroll chiller. Two water mixing chambers were used
1 m 1 m 1 m was fabricated as the air-ozone mixing chamber.
to produce required inlet water conditions for both the evaporator
The injection of ozone into the chamber was precisely regulated by
and the condenser. The chiller performance was investigated at
a mass flow controller. Table 1 indicates the specification of sen-
varying chilled water supply temperatures.
sors for measuring concentration of various gases such as VOC
Experimental setups of the major components used in the
and ozone. The experiments were conducted with building materi-
hybrid ATS air-conditioning system have been constructed sepa-
als in the chamber. Samples of building materials were placed
rately in order to investigate the air treatment performance indi-
inside the chamber for VOC emission until a required concentra-
vidually. Fig. 4 shows the photograph of the experimental setups.
tion of VOC was reached. After the removal of samples, a specific
quantity of ozone was introduced into the chamber. The oxidation
treatment was monitored and recorded to study the impact of the 3.2. Mathematical formulation on cooling coil unit
ozone on the purification of air.
Fig. 3 shows the experimental setup for the air scrubbing unit. The chilled water cooling coil in the air handling unit is able to
To simulate an indoor environment, a chamber was fabricated with cool and dehumidify the supply air in order to provide a desirable
a size of 750 mm 750 mm 750 mm. A fan was installed inside indoor thermal condition. A mathematical model is developed
the chamber for proper mixing of the air. CO2 gas or samples of based on a row-by-row method [38,39] to evaluate the perfor-
building material can be introduced into the chamber. By using a mance of the cooling coil under varying operating conditions.
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
4 X. Cui et al. / Applied Energy xxx (2017) xxxxxx
Fig. 4. Photograph of the experimental setup. (a) Ozone-based oxidation treatment; (b) air scrubbing unit; (c) chiller.
In the coil, the heat transfer occurs between the chilled water
and the coil surface: Fig. 5. Schematic illustration of the computational domain for the cooling coil.
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 5
DQ i;j hi DAi T s;mi;j T w;mi;j 3
where
2
f 0:79 ln Rew 1:64 5
For the air stream, the total heat transfer consists of sensible
heat flow and latent heat flow [41]:
DQ i;j DQ seni;j DQ lati;j 6
DQ seni;j ho DAo gs T a;mi;j T s;mi;j 7
DQ lati;j hfg hm DAo gs xa;mi;j xs;mi;j 8
Considering the assumption that the Lewis factor for air-water
mixture is unity,
ho
Lef 1 9
hm cpa
The total heat transfer in the air side can be written as:
gs
DQ i;j ho DAo ia;mi;j is;mi;j 10
cpa
The correlation for determining the external heat transfer coef-
ficient is expressed as [42]:
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
6 X. Cui et al. / Applied Energy xxx (2017) xxxxxx
Fig. 7. (a) Visualization of the reference office building, and (b) Flowchart illustrating the building simulation procedure.
Table 3
Schedules for occupancy, lighting, and equipment load in fraction of design values.
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 7
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
8 X. Cui et al. / Applied Energy xxx (2017) xxxxxx
Table 4
Comparison between modeled results and experimental data.
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 9
Fig. 13. Outlet air temperature of the cooling coil under varying chilled water Fig. 16. Profiles of the total cooling load with varying outdoor air intake on design
supply temperature and outdoor-air fraction. day.
from 7:00 to 19:00. In general, the total cooling load shows a sim-
ilar trend for different levels of outdoor air flow rate. The peak
cooling load occurs at around 15:00 mainly due to the absorption
of solar energy by the building structure and the corresponding
delay in releasing the heat to the space. It is also found that the
outdoor air flow rate markedly impacts the total cooling load. For
example, the peak total cooling load decreases from 164.2 W/m2
to 83.7 W/m2 by reducing the outdoor air flow rate from 10 L/s
per person to 2 L/s per person. It can be attributed to the high out-
door air enthalpy of tropical climate that requires a larger cooling
demand for conditioning the outdoor airflow. The outdoor air sup-
ply of 0 L/s per person indicates an extreme condition with no out-
door air intake. It can be inferred from the figure that
approximately 60% of the total cooling load is used to treat the out-
door air when the outdoor air supply rate is 10 L/s per person on
design days. As a result, the reduction of outdoor air intake can
help in achieving remarkable energy savings for the air-
conditioning systems.
Fig. 14. Effect of the chilled water supply temperature on the COP of the chiller. 4.5. Annual energy consumption evaluation
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
10 X. Cui et al. / Applied Energy xxx (2017) xxxxxx
Fig. 17. Profile of monthly weather condition in Singapore, Bangkok, and Kuala Lumpur. (a) Outdoor air dry bulb temperature, and (b) outdoor air relative humidity.
Fig. 18. Monthly electricity peak demand for cooling in (a) Singapore, (b) Bangkok, and (c) Kuala Lumpur.
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 11
Fig. 19. Annual energy consumption under varying outdoor air flow rate.
door air dry bulb temperature reaches 30.6 C. The lowest electric- platform. Results have demonstrated that the peak total cooling
ity demand appears in December (33.95 W/m2 in Singapore, load decreases from 164.2 W/m2 to 83.7 W/m2 when the outdoor
32.19 W/m2 in Bangkok, and 33.07 W/m2 in Kuala Lumpur, respec- air flow rate is reduced from 10 L/s per person to 2 L/s per person.
tively, for the outdoor air intake of 10 L/s per person) due to the In addition, the annual energy consumption analysis indicates that
decrease of outdoor air temperature. In addition, a lower outdoor the percentage of energy saving due to cooling can be significant
air intake effectively reduces the electricity peak demand for cool- up to 36.5%.
ing. For example, in Singapore, the electricity peak demand drops Buildings across the globe suffering from ambient air pollution
by 41% in January when the outdoor air supply is changed from is able to adopt the proposed ATS to realize improvement in air
10 to 2 L/s per person. quality and energy efficiency. The proposed ATS can be easily
Fig. 19 compares the annual consumption of different compo- incorporated to any new or existing air-conditioning system
nents under varying outdoor air intake rates. The ATS is switched worldwide. The air treatment equipment including the ozone oxi-
on when the supply of outdoor air is less than 10 L/s per person. dation device and the air-scrubbing unit should be installed along
The ATS consumes energy mainly for ozone generation and air cir- the return air duct in tandem with the air handling unit. However,
culation. The total energy consumption is estimated by considering compared with the conventional ACMV system, the proposed ATS
the electrical power consumed by the primary equipment. The requires a larger footprint area due to the additional air treatment
annual energy consumption per floor area decreases with a lower equipment. The additional space requirement leads to a potential
outdoor air intake. For example, in Singapore, comparing with limitation of the proposed ATS when incorporating the ATS to an
the energy consumption for cooling with outdoor air of 10 L/s existing air-conditioning system. A compact design with renew-
per person, the percentage of energy saving in cooling is 8.2%, able energy integrated system is highly recommended as a part
23.4%, and 36.5% for the outdoor air supply rate of 6 L/s, 2 L/s, of the future work.
and 0 L/s per person, respectively. The reduction in the energy con-
sumption for cooling can be attributed to the decrease of the total Acknowledgements
cooling load and the improvement of the chiller efficiency. The
total energy consumption in Singapore is the highest among these The authors gratefully acknowledge the generous funding from
three cities since Singapore has higher outdoor air cooling load. In the National Research Foundation (NRF) Singapore under the
general, by reducing the outdoor air flow rate from 10 to 0 L/s per Energy Innovation Research Programme (EIRP) Funding
person, the hybrid ATS air-conditioning system is able to achieve Scheme (R-265-000-515-279) managed on behalf by Building
an annual energy consumption saving up to 64.6 kW h/m2. and Construction Authority (BCA).
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
12 X. Cui et al. / Applied Energy xxx (2017) xxxxxx
The power consumption of fan is calculated based on the flow [20] Stabile L, DellIsola M, Frattolillo A, Massimo A, Russi A. Effect of natural
rate (V), pressure drop (Dp), blower efficiency (gb ), and motor effi- ventilation and manual airing on indoor air quality in naturally ventilated
Italian classrooms. Build Environ 2016;98:1809. http://dx.doi.org/10.1016/j.
ciency (gm ) as: buildenv.2016.01.009.
[21] Lee WL, Chen H, Leung YC, Zhang Y. Decoupling dehumidification and cooling
V Dp for energy saving and desirable space air conditions in hot and humid Hong
Wf A2
gb gm Kong. Energy Convers Manage 2012;53:2309. http://dx.doi.org/10.1016/j.
enconman.2011.08.018.
[22] Fong ML, Hanby V, Greenough R, Lin Z, Cheng Y. Acceptance of thermal
Similarly, the power consumption of pump is conditions and energy use of three ventilation strategies with six exhaust
configurations for the classroom. Build Environ 2015;94:60619. http://dx.doi.
V Dp org/10.1016/j.buildenv.2015.10.024.
Wp A3
gp gm [23] Martins NR, Carrilho da Graa G. Impact of outdoor PM2.5 on natural
ventilation usability in Californias nondomestic buildings. Appl Energy
2017;189:71124. http://dx.doi.org/10.1016/j.apenergy.2016.12.103.
where gp is the pump efficiency. [24] Vakiloroaya V, Samali B, Fakhar A, Pishghadam K. A review of different
strategies for HVAC energy saving. Energy Convers Manage 2014;77:73854.
http://dx.doi.org/10.1016/j.enconman.2013.10.023.
References [25] He Y, Liu M, Kvan T, Peng S. An enthalpy-based energy savings estimation
method targeting thermal comfort level in naturally ventilated buildings in
[1] Zhang T, Tan Y, Yang H, Zhang X. The application of air layers in building hot-humid summer zones. Appl Energy 2017;187:71731. http://dx.doi.org/
envelopes: a review. Appl Energy 2016;165:70734. http://dx.doi.org/ 10.1016/j.apenergy.2016.11.098.
10.1016/j.apenergy.2015.12.108. [26] Wong LT, Mui KW. A transient ventilation demand model for air-conditioned
[2] Cao G, Awbi H, Yao R, Fan Y, Sirn K, Kosonen R, et al. A review of the offices. Appl Energy 2008;85:54554. http://dx.doi.org/10.1016/j.
performance of different ventilation and airflow distribution systems in apenergy.2007.07.010.
buildings. Build Environ 2014;73:17186. http://dx.doi.org/10.1016/j. [27] Chua KJ, Chou SK, Yang WM, Yan J. Achieving better energy-efficient air
buildenv.2013.12.009. conditioning a review of technologies and strategies. Appl Energy
[3] Homod RZ, Sahari KSM, Almurib HaF. Energy saving by integrated control of 2013;104:87104. http://dx.doi.org/10.1016/j.apenergy.2012.10.037.
natural ventilation and HVAC systems using model guide for comparison. [28] Shahzad S, Brennan J, Theodossopoulos D, Hughes B, Calautit JK. Energy
Renewable Energy 2014;71:63950. http://dx.doi.org/10.1016/j. and comfort in contemporary open plan and traditional personal offices.
renene.2014.06.015. Appl Energy 2015;185:154255. http://dx.doi.org/10.1016/j.apenergy.
[4] Mardiana-Idayu A, Riffat SB. Review on heat recovery technologies for building 2016.02.100.
applications. Renew Sustain Energy Rev 2012;16:124155. http://dx.doi.org/ [29] Nath RK, Zain MFM, Jamil M. An environment-friendly solution for indoor air
10.1016/j.rser.2011.09.026. purification by using renewable photocatalysts in concrete: a review. Renew
[5] Sundell J, Levin H, Nazaroff WW, Cain WS, Fisk WJ, Grimsrud DT, et al. Sustain Energy Rev 2016;62:118494. http://dx.doi.org/10.1016/j.
Ventilation rates and health: multidisciplinary review of the scientific rser.2016.05.018.
literature. Indoor Air 2011;21:191204. http://dx.doi.org/10.1111/j.1600- [30] Mickal D, Bruno B, Valrie C, Murielle L, Ccile P, Jacques R, et al. Indoor air
0668.2010.00703.x. quality and comfort in seven newly built, energy-efficient houses in France.
[6] Faulkner D, Fisk WJ, Sullivan DP, Lee SM. Ventilation efficiencies and thermal Build Environ 2014;72:17387. http://dx.doi.org/10.1016/j.
comfort results of a desk-edge-mounted task ventilation system. Indoor Air buildenv.2013.10.017.
2004;14(Suppl. 8):927. http://dx.doi.org/10.1111/j.1600-0668.2004.00295.x. [31] Zhang LZ, Niu JL. Modeling VOCs emissions in a room with a single-zone multi-
[7] Yassine B, Ghali K, Ghaddar N, Srour I, Chehab G. A numerical modeling component multi-layer technique. Build Environ 2004;39:52331. http://dx.
approach to evaluate energy-efficient mechanical ventilation strategies. doi.org/10.1016/j.buildenv.2003.10.005.
Energy Build 2012;55:61830. http://dx.doi.org/10.1016/j. [32] Yu BF, Hu ZB, Liu M, Yang HL, Kong QX, Liu YH. Review of research on air-
enbuild.2012.08.042. conditioning systems and indoor air quality control for human health. Int J
[8] Oropeza-Perez I, stergaard PA. Potential of natural ventilation in temperate Refrig 2009;32:320. http://dx.doi.org/10.1016/j.ijrefrig.2008.05.004.
countries - a case study of Denmark. Appl Energy 2014;114:52030. http://dx. [33] Zhang Y, Xu Y. Characteristics and correlations of VOC emissions from building
doi.org/10.1016/j.apenergy.2013.10.008. materials. Int J Heat Mass Transf 2003;46:487783. http://dx.doi.org/10.1016/
[9] Cho W, Song D, Hwang S, Yun S. Energy-efficient ventilation with air-cleaning S0017-9310(03)00352-1.
mode and demand control in a multi-residential building. Energy Build. [34] Cheng Y-H, Lin C-C, Hsu S-C. Comparison of conventional and green building
2015;90:614. http://dx.doi.org/10.1016/j.enbuild.2015.01.002. materials in respect of VOC emissions and ozone impact on secondary
[10] Calautit JK, Hughes BR, Nasir DSNM. Climatic analysis of a passive cooling carbonyl emissions. Build Environ 2015;87:27482. http://dx.doi.org/10.1016/
technology for the built environment in hot countries. Appl Energy j.buildenv.2014.12.025.
2016;186:32135. http://dx.doi.org/10.1016/j.apenergy.2016.05.096. [35] Waring MS, Wells JR. Volatile organic compound conversion by ozone,
[11] Mrz TM, Dutka A. Exergyeconomic evaluation of heat recovery device in hydroxyl radicals, and nitrate radicals in residential indoor air: magnitudes
mechanical ventilation system. Energy Build. 2015;86:296304. http://dx.doi. and impacts of oxidant sources. Atmos Environ 2014;106:38291. http://dx.
org/10.1016/j.enbuild.2014.10.026. doi.org/10.1016/j.atmosenv.2014.06.062.
[12] Rackes A, Melo AP, Lamberts R. Naturally comfortable and sustainable: [36] Gallego E, Roca FJ, Perales JF, Guardino X. Experimental evaluation of VOC
informed design guidance and performance labeling for passive commercial removal efficiency of a coconut shell activated carbon filter for indoor air
buildings in hot climates. Appl Energy 2016;174:25674. http://dx.doi.org/ quality enhancement. Build Environ 2013;67:1425. http://dx.doi.org/
10.1016/j.apenergy.2016.04.081. 10.1016/j.buildenv.2013.05.003.
[13] Tong Z, Chen Y, Malkawi A, Liu Z, Freeman RB. Energy saving potential of [37] Sidheswaran MA, Destaillats H, Sullivan DP, Cohn S, Fisk WJ. Energy efficient
natural ventilation in China: the impact of ambient air pollution. Appl Energy indoor VOC air cleaning with activated carbon fiber (ACF) filters. Build Environ
2016;179:6608. http://dx.doi.org/10.1016/j.apenergy.2016.07.019. 2012;47:35767. http://dx.doi.org/10.1016/j.buildenv.2011.07.002.
[14] Hughes BR, Chaudhry HN, Calautit JK. Passive energy recovery from natural [38] Khamis Mansour M, Hassab M. Thermal design of cooling and dehumidifying
ventilation air streams. Appl Energy 2014;113:12740. http://dx.doi.org/ coils. InTech; 2012. http://dx.doi.org/10.5772/32536.
10.1016/j.apenergy.2013.07.019. [39] McQuiston FC, Parker JD, Spitler JD. Heating, ventilating, and air conditioning:
[15] Ben-David T, Waring MS. Impact of natural versus mechanical ventilation on analysis and design. 6th ed. John Wiley & Sons; 2005.
simulated indoor air quality and energy consumption in offices in fourteen U.S. [40] Petukhov BS. Heat transfer and friction in turbulent pipe flow with variable
cities. Build Environ 2016;104:32036. http://dx.doi.org/10.1016/j. physical properties. Adv Heat Transf 1970;6:50364. http://dx.doi.org/
buildenv.2016.05.007. 10.1016/S0065-2717(08)70153-9.
[16] Abou Hweij W, Ghaddar N, Ghali K, Habchi C. Optimized performance of [41] Xia L, Chan MY, Deng SM, Xu XG. Analytical solutions for evaluating the
displacement ventilation aided with chair fans for comfort and indoor air thermal performances of wet air cooling coils under both unit and non-unit
quality. Energy Build 2016;127:90719. http://dx.doi.org/10.1016/j. Lewis factors. Energy Convers Manage 2010;51:207986. http://dx.doi.org/
enbuild.2016.06.052. 10.1016/j.enconman.2010.02.041.
[17] Li Z, Chen W, Deng S, Lin Z. The characteristics of space cooling load and indoor [42] Chua KJ, Chou SK, Ho JC. A model to study the effects of different control
humidity control for residences in the subtropics. Build Environ strategies on space humidity during part-load conditions. Build Environ
2006;41:113747. http://dx.doi.org/10.1016/j.buildenv.2005.05.016. 2008;43:207489. http://dx.doi.org/10.1016/j.buildenv.2007.12.005.
[18] Chua KJ, Ho JC, Chou SK. A comparative study of different control strategies for [43] Fumo N, Mago P, Luck R. Methodology to estimate building energy
indoor air humidity. Energy Build 2007;39:53745. http://dx.doi.org/10.1016/ consumption using EnergyPlus benchmark models. Energy Build
j.enbuild.2006.09.008. 2010;42:23317. http://dx.doi.org/10.1016/j.enbuild.2010.07.027.
[19] Wang Y, Cao Y, Liu B, Liu J, Yang Y, Yu Q. An evaluation index for the control [44] Nguyen A-T, Reiter S, Rigo P. A review on simulation-based optimization
effect of the local ventilation systems on indoor air quality in industrial methods applied to building performance analysis. Appl Energy
buildings. Build Simul 2016;9:66976. http://dx.doi.org/10.1007/s12273-016- 2014;113:104358. http://dx.doi.org/10.1016/j.apenergy.2013.08.061.
0295-2. [45] ASHRAE. ASHRAE handbook-fundamentals. Atalanta (GA); 2009.
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 13
[46] Kreider JF, editor. Handbook of heating, ventilation, and air conditioning. CRC [49] Garcia Sanchez D, Lacarrire B, Musy M, Bourges B. Application of sensitivity
Press; 2000. analysis in building energy simulations: combining first- and second-order
[47] Zhou X, Braun J. A Simplified dynamic model for chilled-water elementary effects methods. Energy Build 2014;68:74150. http://dx.doi.org/
cooling and dehumidifying coilsPart 2: experimental validation (RP-1194). 10.1016/j.enbuild.2012.08.048.
HVAC&R Res 2007;13:80517. http://dx.doi.org/10.1080/10789669. [50] Wong SL, Wan KKW, Lam TNT. Artificial neural networks for energy analysis of
2007.10390987. office buildings with daylighting. Appl Energy 2010;87:5517. http://dx.doi.
[48] Calleja Rodrguez G, Carrillo Andrs A, Domnguez Muoz F, Cejudo Lpez JM, org/10.1016/j.apenergy.2009.06.028.
Zhang Y. Uncertainties and sensitivity analysis in building energy simulation [51] Pereira W, Bgl A, Natschlger T. Sensitivity analysis and validation of an
using macroparameters. Energy Build 2013;67:7987. http://dx.doi.org/ EnergyPlus model of a house in Upper Austria. Energy Proc 2014;62:47281.
10.1016/j.enbuild.2013.08.009. http://dx.doi.org/10.1016/j.egypro.2014.12.409.
Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067