Вы находитесь на странице: 1из 13

Applied Energy xxx (2017) xxxxxx

Contents lists available at ScienceDirect

Applied Energy
journal homepage: www.elsevier.com/locate/apenergy

Energy performance evaluation and application of an air treatment


system for conditioning building spaces in tropics
X. Cui a, B. Mohan a, M.R. Islam a,b, S.K. Chou a, K.J. Chua a,b,
a
Department of Mechanical Engineering, National University of Singapore, 9 Engineering Drive 1, Singapore 117576, Singapore
b
Engineering Science Programme, National University of Singapore, 9 Engineering Drive 1, Singapore 117575, Singapore

h i g h l i g h t s

 A hybrid air treatment system (ATS) incorporating a cooling system is introduced.


 Experiments were conducted to study the performance of primary components.
 The ATS can reduce outdoor air intake due to the air-purification process.
 The reduced outdoor air fraction enables a higher chilled water supply temperature.
 The system could achieve marked energy savings in tropical climate.

a r t i c l e i n f o a b s t r a c t

Article history: The present study attempts to reduce the supply of outdoor air in conditioning building spaces for energy
Received 12 January 2017 saving while improving the indoor air quality. A hybrid air treatment system incorporating a cooling sys-
Received in revised form 28 February 2017 tem is introduced for tropical climates. The air treatment system (ATS) comprises an ozone-based oxida-
Accepted 14 March 2017
tion process and an air scrubbing device. The air purification process has been experimentally
Available online xxxx
investigated. Experimental results demonstrated the feasibility of the proposed ATS to provide improved
indoor air quality. A validated mathematical model has been employed to study the air cooling and dehu-
Keywords:
midification process through the cooling coil. The reduced outdoor air intake facilitates a higher chilled
Air-conditioning
Cooling load
water supply temperature resulting in an improved chiller performance and reduction of cooling load.
Mathematical model The energy consumption performance of the proposed hybrid ATS air-conditioning system has been eval-
Indoor air quality uated for an office building experiencing tropical climatic conditions. The cooling load on a design day has
Energy consumption demonstrated that the reduction of outdoor air intake enabled marked energy savings potential in terms
of the cooling demand. By analysing the building performance based on tropical climatic data, an annual
energy consumption saving of up to 64.6 kW h/m2 can be achieved via the hybrid ATS air-conditioning
system.
2017 Elsevier Ltd. All rights reserved.

1. Introduction with sick building syndrome (SBS) symptoms [5,6]. Research works
have been carried out to develop improved ACMV systems [711].
One of the key concerns in air-conditioning system is to supply Rackes et al. [12] generated guidelines for improving the design of
a comfortable and healthy indoor environment for building occu- natural ventilation for commercial buildings in warm and hot cli-
pants. In a normal air-conditioning mechanical ventilation (ACMV) mates. Tong et al. [13] investigated the potential of energy savings
system, extensive outdoor air is employed to dilute and remove on the natural ventilation with the influence of outdoor air pollu-
indoor air contaminants [1,2]. tion. They pointed out that a reduction of 878% of the energy con-
The design of ventilation system is an important issue affecting sumed by cooling can be potentially achieved due to the utilization
the energy performance [3,4]. In addition, building ventilation of natural ventilation subjecting to ambient air quality. Hughes
impacts the indoor pollutant removal process which is associated et al. [14] studied an energy recovery system for natural ventila-
tion based on heat pipe technology. The simulation results demon-
strated the ability of the system to reduce the energy consumption
Corresponding author at: Department of Mechanical Engineering, National
loads in domestic buildings. Ben-David and Waring [15] compared
University of Singapore, 9 Engineering Drive 1, Singapore 117576, Singapore.
the influence of natural ventilation and mechanical ventilation on
E-mail address: mpeckje@nus.edu.sg (K.J. Chua).

http://dx.doi.org/10.1016/j.apenergy.2017.03.067
0306-2619/ 2017 Elsevier Ltd. All rights reserved.

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
2 X. Cui et al. / Applied Energy xxx (2017) xxxxxx

Nomenclature

A surface area [m2] Sl tube spacing in air flow direction [m]


cp specific heat [kJ/(kgK)] St tube spacing normal to air flow [m]
D tube diameter [m] T temperature [C]
Ga air flow rate per square meter [kg/(sm2)] V volume flow rate of air [m3/s]
h convection heat transfer coefficient [kW/(m2K)] gs surface effectiveness
hfg latent heat of water evaporation [kJ/kg] x humidity ratio [kg/kg]
hm mass transfer coefficient [kg/(m2 s)]
i enthalpy [kJ/kg] Subscripts
L tube length [m] a air
Lef Lewis factor i inner surface
m mass flow rate [kg/s] in inlet of cooling coil
Nu Nusselt number lat latent
p pressure [kPa] m mean value
Pr Prandtl number o outer surface
Q heat transfer rate [kW] out outlet of cooling coil
Re Reynolds number s surface
RH relative humidity sen sensible
s fin spacing [m] w water

the concentration of indoor pollutants such as carbon dioxide and treatment. Waring and Wells [35] found that the ozone and the
formaldehyde. The energy consumption simulation was conducted hydroxyl radical influenced the total VOC conversion. Gallego
for a typical office building in United States. Abou Hweij et al. [16] et al. [36] investigated the performance of activated carbon filter
employed a computational fluid dynamics model to optimize a for VOCs removal. The removal efficiencies of the commercially
chair-fan integrated displacement ventilation system for improv- available activated carbon were useful in terms of future ventila-
ing the indoor air quality. Li et al. [17] presented the characteristics tion design. Sidheswaran et al. [37] indicated that the activated
of space cooling load for residences in the subtropics. They have carbon filter has a long adsorption lifespan and was a promising
analyzed the indoor humidity control considering the mismatching method for air cleaning.
of the sensible heat ratio (SHR). Chua et al. [18] compared different A review of previous works pointed out existing limitations and
strategies for indoor humidity control. A mathematical model was research gaps. Conventional ACMV systems depend on the outdoor
developed to study the part-load performance. Wang et al. [19] air to sustain an acceptable indoor air quality. However, outdoor
proposed an index named normalized concentration in the target air may sometimes contain high levels of pollutants. Conventional
zone (NC-TZ) which was capable of evaluating the impact of local ventilation process using unhealthy outdoor air can cause indoor
ventilation on the indoor air quality. Stabile et al. [20] suggested air quality to deteriorate. In addition, few attempts have been
that a better airing effect can be produced by employing passive made to investigate the helpful means to minimize the outdoor
ventilation grilles with automatically controlled opening section. air intake with the integration of an efficient air-treatment tech-
Lee et al. [21] proposed to combine the dedicated outdoor air ven- nique. These issues motivated the present work to develop and
tilation (DV) with dry cooling (DC) air-conditioning system. The study a novel ACMV system. The originality of this work is to intro-
DCDV system was able to achieve desirable indoor conditions with duce an air treatment system (ATS) that is capable of reducing the
an annual energy saving by 54% over CAV system with reheat. Fong polluted outdoor air intake while promoting improved energy
et al. [22] presented experimental study on three ventilation efficiency.
strategies with six exhaust configurations. It was concluded that The present study aims to (1) introduce an air treatment system
the stratum ventilation with rear-middle-level-exhaust can pro- (ATS) with air purification devices, (2) evaluate the performance of
vide satisfied comfort indoor condition while consuming the least primary components in the ATS, and (3) investigate the annual
value of energy. Martins [23] pointed out that the energy saving of energy consumption performance of the hybrid ATS air-
2580% on the air-conditioning system can be achieved when the conditioning system for an office building in tropical climates.
outdoor air condition was favorable in California. In tropical cli-
mates, however, the energy required to condition the outdoor air
constitutes a considerable portion of the total space-conditioning 2. System descriptions
load [2426]. Indeed, it is a real challenge to design and engineer
an energy-efficient ACMV system without sacrificing indoor air The air treatment system (ATS) is proposed to improve air qual-
quality [27,28]. ity of conditioned spaces and to reduce energy consumption of
People spend substantial portion of their time in rooms. The chiller systems. Fig. 1 shows an overview of the schematic diagram
indoor air pollutants can be emitted from building material, fur- of hybrid ATS air conditioning system. The plug-and-play ATS
nishings, occupancy, unvented combustion and other processes consists of two major components, namely, an ozone-based oxida-
[29,30]. Volatile organic compounds (VOCs) is one of the major tion treatment unit and an air scrubbing unit. The return air is first
concerns for indoor air quality since some VOCs may have adverse purified through the ozone-based oxidation treatment process
health effects on human [31,32]. Zhang and Xu [33] developed an which is an effective approach of cleaning air. After the oxidation
improved mass transfer model to analyze VOC emissions from treatment process, the excess ozone can be removed by using a
building materials. Correlations were provided as a function of commercially available ozone destruction unit. The ozone can be
mass transfer Biot number and mass transfer Fourier number. catalyzed into oxygen immediately in order to maintain the ozone
The comparison of building materials was conducted by Cheng concentration to below 0.05 ppm levels. Thereafter, the air scrub-
et al. [34] to study the VOCs emissions and the impact due to ozone ber unit reduces the concentration of CO2 and further remove other

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 3

Fig. 1. Schematic diagram of the hybrid ATS air-conditioning system.

unwanted air contaminants such as VOCs, dusts and smokes. The Table 1
purified air is finally cooled and dehumidified to the required sup- The specification of measuring instruments.

ply condition by the air handling unit using chilled water. The Parameter Measurement Accuracy
hybrid ATS air-conditioning system is able to reduce the ranges
outdoor-air intake due to the air purification procedure. In addi- VOC concentration 0.11000 ppm 2% of reading
tion, the reduced outdoor air supply will contribute to marked Ozone concentration 010 ppm (0.01 ppm + 7.5% of reading)
energy savings potential in terms of the cooling demand due to CO2 concentration 02000 ppm (1.5% of range + 2% of reading)
Air velocity 08 m/s 5% of reading
the decrease of cooling load and the improvement of chiller
efficiency.

blower with variable speed drive, the air was circulated and trea-
3. Methodology
ted through the scrubber canister. The canister was packed with
activated carbon for air scrubbing. The specifications of sensors
3.1. Experimental setups
are given in Table 1. The measuring instruments were inserted at
various locations to monitor the air scrubbing performance.
Fig. 2 depicts the experimental setup for the ozone-based oxida-
In addition, an experimental study was also conducted on a
tion treatment unit. An insulated air-tight chamber of size
water-cooled scroll chiller. Two water mixing chambers were used
1 m  1 m  1 m was fabricated as the air-ozone mixing chamber.
to produce required inlet water conditions for both the evaporator
The injection of ozone into the chamber was precisely regulated by
and the condenser. The chiller performance was investigated at
a mass flow controller. Table 1 indicates the specification of sen-
varying chilled water supply temperatures.
sors for measuring concentration of various gases such as VOC
Experimental setups of the major components used in the
and ozone. The experiments were conducted with building materi-
hybrid ATS air-conditioning system have been constructed sepa-
als in the chamber. Samples of building materials were placed
rately in order to investigate the air treatment performance indi-
inside the chamber for VOC emission until a required concentra-
vidually. Fig. 4 shows the photograph of the experimental setups.
tion of VOC was reached. After the removal of samples, a specific
quantity of ozone was introduced into the chamber. The oxidation
treatment was monitored and recorded to study the impact of the 3.2. Mathematical formulation on cooling coil unit
ozone on the purification of air.
Fig. 3 shows the experimental setup for the air scrubbing unit. The chilled water cooling coil in the air handling unit is able to
To simulate an indoor environment, a chamber was fabricated with cool and dehumidify the supply air in order to provide a desirable
a size of 750 mm  750 mm  750 mm. A fan was installed inside indoor thermal condition. A mathematical model is developed
the chamber for proper mixing of the air. CO2 gas or samples of based on a row-by-row method [38,39] to evaluate the perfor-
building material can be introduced into the chamber. By using a mance of the cooling coil under varying operating conditions.

Fig. 2. Experimental setup for the ozone-based oxidation treatment.

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
4 X. Cui et al. / Applied Energy xxx (2017) xxxxxx

Fig. 3. Experimental setup for air scrubbing unit.

Fig. 4. Photograph of the experimental setup. (a) Ozone-based oxidation treatment; (b) air scrubbing unit; (c) chiller.

The mathematical model of the cooling coil is employed to deter-


mine the potential for increasing the chilled water supply temper-
ature due to the reduction of the outdoor air intake. In addition, the
developed mathematical model is necessary to analyze the
improvement of chiller performance. The computational domain
for a four-row cooling coil is shown in Fig. 5. The computational
domain in each tube is meshed into several segments.
The governing equations are established within each computa-
tional element to investigate the heat and mass transfer process
between the chilled water and the supply air. As shown in Fig. 5,
the computation element is associated with its chilled water tem-
perature (T wi;j ), mass flow rate (mw ), air temperature (T ai;j ), air
enthalpy (iai;j ), and air flow rate (ma ). ia;mi;j , is;mi;j T a;mi;j , T s;mi;j ,
and T w;mi;j are the mean values between adjacent grid points.
The coil surface is considered as wet unless the coil surface tem-
perature is higher than the dew-point temperature of the air
stream.
Considering the conservation principle of energy for the chilled
water, we obtain:
 
DQ i;j mw cpw T wi;j1  T wi;j 1
Similarly, the conservation of energy for the air stream can be
evaluated by the change of enthalpy:
 
DQ i;j ma iai;j  iai1;j 2

In the coil, the heat transfer occurs between the chilled water
and the coil surface: Fig. 5. Schematic illustration of the computational domain for the cooling coil.

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 5

 
DQ i;j hi DAi T s;mi;j  T w;mi;j 3

The correlation for determining the inner heat transfer coeffi-


cient is given by [40]:
 "
f
Rew  1000Pr w  23 #
8 Di
Nui  0:5  2  1 4
f L
1 12:7 8 Prw  1
3

where
2
f 0:79 ln Rew  1:64 5
For the air stream, the total heat transfer consists of sensible
heat flow and latent heat flow [41]:
DQ i;j DQ seni;j DQ lati;j 6
 
DQ seni;j ho DAo gs T a;mi;j  T s;mi;j 7
 
DQ lati;j hfg hm DAo gs xa;mi;j  xs;mi;j 8
Considering the assumption that the Lewis factor for air-water
mixture is unity,
ho
Lef 1 9
hm  cpa
The total heat transfer in the air side can be written as:
gs  
DQ i;j ho DAo ia;mi;j  is;mi;j 10
cpa
The correlation for determining the external heat transfer coef-
ficient is expressed as [42]:

ho jGa cpa Pr 2=3 11


where
 0:502  0:0312
St s
j 0:14Re0:328
a 12
Sl Do
The mathematical model traces the fluid conditions in every
computational segment with reference to the adjacent segment.
The simulation begins with an initial estimated coils chilled water Fig. 6. Flowchart illustrating the calculation procedure of the cooling coil model.
outlet temperature. The relevant equations are applied to compute
the tube surface temperature (T s;mi;j ), air temperature (T ai;j ), and
Table 3 shows the daily schedules of occupancy, lighting and
chilled water temperature (T wi;j ). The calculation is performed
equipment. The building is generally occupied during office hours.
consecutively in the subsequent segments until it approaches the
The schedules in Table 3 illustrate the fraction of their design val-
inlet of chilled water. This procedure is repeated in order to
ues. During workdays, the design occupancy in the office room is
achieve a desired convergence. Fig. 6 illustrates the flowchart to
0.3 person/m2. The design lighting load is 10.66 W/m2 due to the
clarify the calculation process.
typical overhead fluorescent lighting. Computers and printers are
used in the office. The design equipment load of 7.64 W/m2 is to
3.3. Building characteristics in tropical climate
be accommodated by the cooling system.
As recommended by ASHRAE [45], the dry bulb temperature of
In order to evaluate the energy consumption of the proposed
24 C and a maximum of 5065% relative humidity are considered
hybrid ATS air-conditioning system in tropical climates, a hypo-
as the design values of typical indoor conditions for thermal com-
thetical five-story office building was designed to perform the sim-
fort. To analyze the building energy performance, three typical
ulation. Fig. 7 illustrates the office building simulation procedure.
tropical climate cities (namely Singapore, Bangkok, and Kuala Lum-
The calculation was performed using the building energy simula-
pur) were chosen as representatives in the present study. The out-
tion program EnergyPlus [43,44], which is able to evaluate the
door weather conditions in these selected cities were employed in
cooling load and energy consumption in buildings. The building
the EnergyPlus for cooling load calculation.
geometry was created using SketchUp program. The software
OpenStudio then converted all the operation details to the Energy-
Plus input file for the cooling load and energy consumption 4. Results and discussion
calculation.
Table 2 presents key construction information of the office Fig. 8 illustrates the framework and objectives of the present
building in the present study. The 5-storey office building includes work. The experimental results of the air purification performance
a total conditioned space area of 3000 m2. The floor to floor height are first presented in order to illustrate the ability of the ATS to
is 3 m. The window to wall ratio is assumed to be 0.4. Overhangs purify the return air and improve the indoor air quality. As a result,
are attached to the windows. the hybrid ATS air-conditioning system is able to reduce the out-

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
6 X. Cui et al. / Applied Energy xxx (2017) xxxxxx

Fig. 7. (a) Visualization of the reference office building, and (b) Flowchart illustrating the building simulation procedure.

Table 2 Finally, by considering the reduced outdoor air fraction and


Construction details of the building. improved chillers COP, an energy consumption analysis is con-
Building element Description
ducted using EnergyPlus to estimate the energy saving potential
of the hybrid ATS air-conditioning system operating under tropical
Exterior walls 25 mm stucco, 200 mm concrete, 34 mm wall
insulation, 13 mm Gypsum
climatic conditions.
Exterior floors 100 mm concrete, carpet pad
Exterior roofs 10 mm roof membrane, 170 mm roof insulation, 2 mm
metal decking 4.1. Performance of air treatment in oxidation process
Exterior doors 0.8 mm metal surface, 25 mm insulation board
Exterior windows 3 mm thick glass We first studied the effect of ozone on air purification. The
Interior wall 19 mm gypsum board, wall air space resistance, 19 mm experiment was conducted with the circulating air treated by
gypsum board
Interior floor 19 mm acoustic tile, ceiling air space resistance,
ozone in the system. The ozone was supplied for the first 7 days.
100 mm concrete The ozone concentration was maintained within safety limit of
Interior ceiling 100 mm concrete, ceiling air space resistance, 19 mm 0.05 ppm [45]. Thereafter, the ozone supply was switched off for
acoustic tile the following 7 days. The variation of mold count of the circulating
Interior door 25 mm wood
air is shown in Fig. 9. The results indicate that the mold count in
Interior window 3 mm thick glass
the plate went up dramatically after the switch off of the ozone.
It demonstrates that the air quality can be significantly improved
when ozone is used to treat the circulating air.
door air intake which subsequently translates to a lower cooling In addition, the VOCs removal performance of the ozone-based
load. Modeling of the air handling cooling coil is then performed oxidation process has been evaluated. Building materials such as
to demonstrate the possibility of employing higher chilled water paint and glue are usually the sources of VOCs in the occupied
temperatures in the hybrid ATS air-conditioning system due to spaces. Experiments were carried out by treating the VOCs emitted
reducing the outdoor air intake. In addition, the experimental from samples of paint and glue. The ozone was injected into the
study performed on the chiller further illustrates that the chillers chamber with an initial concentration around 2 ppm. By using
COP is improved by increasing the chilled water temperature. the ozone destructor, the ozone concentration can be controlled

Table 3
Schedules for occupancy, lighting, and equipment load in fraction of design values.

Hours Occupancy Lighting Equipment


From To
Weekdays
0:00 5:00 0.00 0.05 0.40
5:00 6:00 0.00 0.10 0.40
6:00 7:00 0.10 0.10 0.40
7:00 8:00 0.20 0.30 0.40
8:00 12:00 0.85 0.90 0.90
12:00 13:00 0.50 0.90 0.80
13:00 17:00 0.85 0.90 0.90
17:00 18:00 0.70 0.70 0.80
18:00 20:00 0.40 0.50 0.60
20:00 22:00 0.10 0.30 0.50
22:00 23:00 0.05 0.10 0.40
23:00 24:00 0.05 0.05 0.40
Saturday
0:00 6:00 0.00 0.05 0.30
6:00 8:00 0.10 0.10 0.40
8:00 14:00 0.40 0.50 0.50
14:00 17:00 0.10 0.15 0.35
17:00 24:00 0.00 0.05 0.30
Sunday
0:00 24:00 0.00 0.05 0.03

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 7

Fig. 10. Performance of VOCs treatment in ozone-based oxidation process.

Fig. 8. Framework and objectives of the proposed hybrid ATS air-conditioning


system.

Fig. 11. Experimental results on the performance of CO2 scrubbing.

tration percentage in the chamber decreases faster with a higher


air flow rate. For example, it took around 130 min and 40 min for
air flow rate of 0.22 L/s and 1.08 L/s, respectively, to obtain 20%
Fig. 9. Effect of ozone on air cleaning performance.
reduction of the CO2 concentration.
The ozone-based oxidation treatment process may produce
to safe level after the oxidation treatment process. Fig. 10 illus- some unwanted reaction products. The second stage (namely, the
trates the variation of VOCs concentration inside the chamber. It air scrubbing device containing activated carbon) is able to further
can be seen that the VOC for paint and glue are decreased by remove unwanted air contaminants, such as sulfuric acid, VOCs,
10.2% and 22.9%, respectively. The experimental result indicates and dusts. Fig. 12 further illustrates the VOCs removal performance
that the reduction of VOCs can be achieved by using the ozone- through the air scrubbing unit containing activated carbon. Paint
based oxidation treatment. samples were placed in the chamber for VOCs emission until the
initial VOCs concentration reached around 30 ppm. After the
removal of samples, the VOCs scrubbing performance has been
4.2. Performance of air scrubbing unit tested. The flow rate of 0.431.73 L/s corresponds to the ACR of
3.614.7. It can be seen that the activated carbon is able to remove
Experiments were also conducted to study the performance of VOCs effectively. For example, the removal of 80% VOCs can be
air scrubbing unit. Fig. 11 presents the impact of return air flow obtained within 45 min under the air flow rate of 0.43 L/s. A higher
rate on the air scrubbing performance. In the chamber, the CO2 air flow rate improves the VOCs adsorption due to the increased air
concentration was initially maintained at 1200 ppm. The return circulation frequency. At present, the performance of ATS was pre-
air from the chamber flowed through the canister with a flow rate liminarily evaluated in laboratory. The experimental results con-
of 0.221.51 L/s. The corresponding air changes per hour spans tribute to a solid foundation for the integration in actual
1.812.8 [46]. It is observed from the figure that the CO2 concen- applications. Firstly, experimental results demonstrated the feasi-

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
8 X. Cui et al. / Applied Energy xxx (2017) xxxxxx

supply temperature, the reduction of the outdoor air intake results


in a lower outlet air temperature.
To maintain a specific outlet air temperature, it is possible to
increase the chilled water supply temperature by reducing the out-
door air fraction. For example, when the outdoor air fraction is reg-
ulated from 40% to 0%, the required chilled water supply
temperature can be increased from 7 C to 10 C while maintaining
a constant outlet air temperature of 15 C. Therefore, a higher
chilled water supply temperature can be adopted in the hybrid
ATS air-conditioning system due to a lower outdoor air fraction.
In addition, Fig. 14 illustrates the impact of the chilled water
supply temperature on the coefficient of performance (COP) of
the chiller. The cooling tower is operating at water flow rate of
5 gpm/ton, and the water temperature entering the condenser
was controlled at 29 C, 30 C, and 31 C, respectively. By raising
the chilled water supply temperature from 7 to 10 C, the average
COP spans 3.58 4.14. Generally, the efficiency of the chiller is
improved by around 3.7% for every 1 C increase of chilled water
supply temperature. Therefore, the energy consumption of chiller
Fig. 12. Experimental results on the performance of VOCs scrubbing.
system will be reduced remarkably due to the improvement of
chiller performance and the reduction of cooling load.
bility of using the proposed ATS to provide purified air for main-
taining a good indoor air quality under a required ventilation rate. 4.4. Cooling profiles on design day in tropical climate
Secondly, the capacity of air treatment equipment can be properly
scaled up based on the experimental data to fulfill the requirement The cooling load is impacted by the outdoor weather conditions,
of the actual room. Thirdly, the concentration of the ozone treat- building characteristics, and the indoor occupancies. In tropical cli-
ment and the air change rate in the experiments can be applied mates, the outdoor air temperature and humidity are usually high
to actual buildings. for all year round. Fig. 15 presents the hourly weather conditions
on a design day (21 June) for Singapore. The daily temperature in
Singapore varies little from hour to hour. On the design day, the
4.3. Performance of air handling cooling coil daily average humidity ratio is 0.019 kg/kg, and the highest out-
door air dry bulb temperature is around 33.2 C occurred at 2 pm.
The mathematical model is first validated to demonstrate the The building energy simulation has been conducted on the
capability of predicting the performance of the cooling coil. Exper- summer design day (21 June) using EnergyPlus. The outdoor
imental results acquired from literature were relied on to conduct weather conditions, characteristics of building and occupancies
the validation. Zhou and Braun [47] have conducted an experimen- result in a time-varying cooling load. An hour-by-hour analysis
tal study on the cooling and dehumidifying coils. The outlet air has been performed to identify the cooling load profile so that a
temperature readings produced by the mathematical model are properly sized cooling system can be selected.
compared with the experimental data as presented in Table 4. It The internal load characteristics are supposed to be the design
can be inferred from the table that the model predicts the perfor- values throughout the design days in order to determine the peak
mance of the cooling coil well to within a maximum 9.2% or maximum cooling load. The design values for occupancy, light-
discrepancy. ing load, and equipment load are considered as 0.3 person/m2,
The validated mathematical model has been employed to study 10.66 W/m2, and 7.64 W/m2, respectively. In office spaces, an out-
the impact of outdoor air fraction on the air cooling process door air flow rate of 10 L/s per person is usually considered as a
through the cooling coil. The outdoor air condition is selected requirement to provide acceptable indoor air quality. However,
based on the weather of summer design day with a dry bulb tem- during haze situations, the supply of outdoor air could be
perature of 33.2 C and a humidity ratio of 0.019 kg/kg. The cooling unhealthy due to the unacceptable levels of pollutants in the out-
coil has six rows and eight passes. The coil tube length is 1.2 m. The door air. Therefore, activating the proposed ATS while reducing the
longitudinal pitch and the transverse pitch of the coil is 0.033 m, outdoor air supply could be an attractive alternative option for
and 0.038 m, respectively. Fig. 13 illustrates the temperature of improving the indoor air quality.
air at the outlet of the cooling coil for varying chilled water supply Fig. 16 illustrates the profiles of a buildings hourly total cooling
temperature and outdoor air fraction. For a specific chilled water load with varying outdoor air intake on the design day for a period

Table 4
Comparison between modeled results and experimental data.

Test Coil Ta,in (C) RHa,in (%) ma (kg/s) mw (kg/s) Ta,out


Experiment Model Discrepancy
1 Four-Row 28.68 55.60 1.16 0.45 17.44 17.58 0.80%
2 Four-Row 28.68 55.60 0.72 0.45 14.69 14.34 -2.38%
3 Four-Row 25.99 70.22 1.20 0.46 17.17 16.91 -1.51%
4 Four-Row 25.99 54.13 1.20 0.46 15.27 15.38 0.72%
5 Eight-Row 23.94 70.80 1.13 0.43 13.24 14.46 9.21%
6 Eight-Row 24.59 55.02 1.27 0.24 15.83 16.43 3.79%
7 Eight-Row 24.59 55.02 1.27 0.44 12.84 14.02 9.19%
8 Eight-Row 27.29 51.19 1.04 0.52 13.47 14.23 5.64%

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 9

Fig. 13. Outlet air temperature of the cooling coil under varying chilled water Fig. 16. Profiles of the total cooling load with varying outdoor air intake on design
supply temperature and outdoor-air fraction. day.

from 7:00 to 19:00. In general, the total cooling load shows a sim-
ilar trend for different levels of outdoor air flow rate. The peak
cooling load occurs at around 15:00 mainly due to the absorption
of solar energy by the building structure and the corresponding
delay in releasing the heat to the space. It is also found that the
outdoor air flow rate markedly impacts the total cooling load. For
example, the peak total cooling load decreases from 164.2 W/m2
to 83.7 W/m2 by reducing the outdoor air flow rate from 10 L/s
per person to 2 L/s per person. It can be attributed to the high out-
door air enthalpy of tropical climate that requires a larger cooling
demand for conditioning the outdoor airflow. The outdoor air sup-
ply of 0 L/s per person indicates an extreme condition with no out-
door air intake. It can be inferred from the figure that
approximately 60% of the total cooling load is used to treat the out-
door air when the outdoor air supply rate is 10 L/s per person on
design days. As a result, the reduction of outdoor air intake can
help in achieving remarkable energy savings for the air-
conditioning systems.

Fig. 14. Effect of the chilled water supply temperature on the COP of the chiller. 4.5. Annual energy consumption evaluation

The annual building energy consumption performance has been


analyzed under tropical climatic conditions. Singapore, Bangkok
(Thailand), and Kuala Lumpur (Malaysia) are chosen as representa-
tive cities in tropical climate for this study. A large number of
parameters influence the building energy consumption [4851].
In the present study, we confine our study to the influence of
weather condition and outdoor air intake.
The monthly outdoor air dry bulb temperature and relative
humidity are shown in Fig. 17. The weather condition in Singapore
and Kuala Lumpur presents a small month-to-month variation
with a lowest average monthly temperature in December and a
highest average temperature in June. The relative humidity in Sin-
gapore is normally high throughout the year ranging from 82% to
89%, while Bangkok has a dryer climate with relative humidity
spanning 5877%.
Fig. 18 presents the monthly electricity peak demand for cool-
ing under varying outdoor air intake rates. In tropical climates,
space cooling is required throughout the year. The profile of the
cooling demand is generally consistent with the variation of out-
door weather conditions. For example, in Bangkok, the highest
electricity peak demand for cooling occurs in April (51.98 W/m2
Fig. 15. Outdoor air condition variation on design day in Singapore. for the outdoor air intake of 10 L/s per person) as the average out-

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
10 X. Cui et al. / Applied Energy xxx (2017) xxxxxx

Fig. 17. Profile of monthly weather condition in Singapore, Bangkok, and Kuala Lumpur. (a) Outdoor air dry bulb temperature, and (b) outdoor air relative humidity.

Fig. 18. Monthly electricity peak demand for cooling in (a) Singapore, (b) Bangkok, and (c) Kuala Lumpur.

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 11

Fig. 19. Annual energy consumption under varying outdoor air flow rate.

door air dry bulb temperature reaches 30.6 C. The lowest electric- platform. Results have demonstrated that the peak total cooling
ity demand appears in December (33.95 W/m2 in Singapore, load decreases from 164.2 W/m2 to 83.7 W/m2 when the outdoor
32.19 W/m2 in Bangkok, and 33.07 W/m2 in Kuala Lumpur, respec- air flow rate is reduced from 10 L/s per person to 2 L/s per person.
tively, for the outdoor air intake of 10 L/s per person) due to the In addition, the annual energy consumption analysis indicates that
decrease of outdoor air temperature. In addition, a lower outdoor the percentage of energy saving due to cooling can be significant
air intake effectively reduces the electricity peak demand for cool- up to 36.5%.
ing. For example, in Singapore, the electricity peak demand drops Buildings across the globe suffering from ambient air pollution
by 41% in January when the outdoor air supply is changed from is able to adopt the proposed ATS to realize improvement in air
10 to 2 L/s per person. quality and energy efficiency. The proposed ATS can be easily
Fig. 19 compares the annual consumption of different compo- incorporated to any new or existing air-conditioning system
nents under varying outdoor air intake rates. The ATS is switched worldwide. The air treatment equipment including the ozone oxi-
on when the supply of outdoor air is less than 10 L/s per person. dation device and the air-scrubbing unit should be installed along
The ATS consumes energy mainly for ozone generation and air cir- the return air duct in tandem with the air handling unit. However,
culation. The total energy consumption is estimated by considering compared with the conventional ACMV system, the proposed ATS
the electrical power consumed by the primary equipment. The requires a larger footprint area due to the additional air treatment
annual energy consumption per floor area decreases with a lower equipment. The additional space requirement leads to a potential
outdoor air intake. For example, in Singapore, comparing with limitation of the proposed ATS when incorporating the ATS to an
the energy consumption for cooling with outdoor air of 10 L/s existing air-conditioning system. A compact design with renew-
per person, the percentage of energy saving in cooling is 8.2%, able energy integrated system is highly recommended as a part
23.4%, and 36.5% for the outdoor air supply rate of 6 L/s, 2 L/s, of the future work.
and 0 L/s per person, respectively. The reduction in the energy con-
sumption for cooling can be attributed to the decrease of the total Acknowledgements
cooling load and the improvement of the chiller efficiency. The
total energy consumption in Singapore is the highest among these The authors gratefully acknowledge the generous funding from
three cities since Singapore has higher outdoor air cooling load. In the National Research Foundation (NRF) Singapore under the
general, by reducing the outdoor air flow rate from 10 to 0 L/s per Energy Innovation Research Programme (EIRP) Funding
person, the hybrid ATS air-conditioning system is able to achieve Scheme (R-265-000-515-279) managed on behalf by Building
an annual energy consumption saving up to 64.6 kW h/m2. and Construction Authority (BCA).

5. Conclusions Appendix A. Energy consumption calculation for primary


equipment
The proposed ATS is capable of reducing the intake of outdoor
air while realizing improved indoor air quality. Several experimen- The chiller consumes the electrical power:
tal systems have been designed, engineered and fabricated to
Qc
investigate the air purification process individually. The hybrid Chiller power A1
ATS air-conditioning system facilitates a higher chilled water sup- COP
ply temperature resulting in improved chiller energy efficiency. In the ATS, to produce ozone of 1 g/h, the ozone generator usu-
Building energy analysis has been conducted using the EnergyPlus ally consumes a power of 20 W.

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
12 X. Cui et al. / Applied Energy xxx (2017) xxxxxx

The power consumption of fan is calculated based on the flow [20] Stabile L, DellIsola M, Frattolillo A, Massimo A, Russi A. Effect of natural
rate (V), pressure drop (Dp), blower efficiency (gb ), and motor effi- ventilation and manual airing on indoor air quality in naturally ventilated
Italian classrooms. Build Environ 2016;98:1809. http://dx.doi.org/10.1016/j.
ciency (gm ) as: buildenv.2016.01.009.
[21] Lee WL, Chen H, Leung YC, Zhang Y. Decoupling dehumidification and cooling
V Dp for energy saving and desirable space air conditions in hot and humid Hong
Wf A2
gb gm Kong. Energy Convers Manage 2012;53:2309. http://dx.doi.org/10.1016/j.
enconman.2011.08.018.
[22] Fong ML, Hanby V, Greenough R, Lin Z, Cheng Y. Acceptance of thermal
Similarly, the power consumption of pump is conditions and energy use of three ventilation strategies with six exhaust
configurations for the classroom. Build Environ 2015;94:60619. http://dx.doi.
V Dp org/10.1016/j.buildenv.2015.10.024.
Wp A3
gp gm [23] Martins NR, Carrilho da Graa G. Impact of outdoor PM2.5 on natural
ventilation usability in Californias nondomestic buildings. Appl Energy
2017;189:71124. http://dx.doi.org/10.1016/j.apenergy.2016.12.103.
where gp is the pump efficiency. [24] Vakiloroaya V, Samali B, Fakhar A, Pishghadam K. A review of different
strategies for HVAC energy saving. Energy Convers Manage 2014;77:73854.
http://dx.doi.org/10.1016/j.enconman.2013.10.023.
References [25] He Y, Liu M, Kvan T, Peng S. An enthalpy-based energy savings estimation
method targeting thermal comfort level in naturally ventilated buildings in
[1] Zhang T, Tan Y, Yang H, Zhang X. The application of air layers in building hot-humid summer zones. Appl Energy 2017;187:71731. http://dx.doi.org/
envelopes: a review. Appl Energy 2016;165:70734. http://dx.doi.org/ 10.1016/j.apenergy.2016.11.098.
10.1016/j.apenergy.2015.12.108. [26] Wong LT, Mui KW. A transient ventilation demand model for air-conditioned
[2] Cao G, Awbi H, Yao R, Fan Y, Sirn K, Kosonen R, et al. A review of the offices. Appl Energy 2008;85:54554. http://dx.doi.org/10.1016/j.
performance of different ventilation and airflow distribution systems in apenergy.2007.07.010.
buildings. Build Environ 2014;73:17186. http://dx.doi.org/10.1016/j. [27] Chua KJ, Chou SK, Yang WM, Yan J. Achieving better energy-efficient air
buildenv.2013.12.009. conditioning a review of technologies and strategies. Appl Energy
[3] Homod RZ, Sahari KSM, Almurib HaF. Energy saving by integrated control of 2013;104:87104. http://dx.doi.org/10.1016/j.apenergy.2012.10.037.
natural ventilation and HVAC systems using model guide for comparison. [28] Shahzad S, Brennan J, Theodossopoulos D, Hughes B, Calautit JK. Energy
Renewable Energy 2014;71:63950. http://dx.doi.org/10.1016/j. and comfort in contemporary open plan and traditional personal offices.
renene.2014.06.015. Appl Energy 2015;185:154255. http://dx.doi.org/10.1016/j.apenergy.
[4] Mardiana-Idayu A, Riffat SB. Review on heat recovery technologies for building 2016.02.100.
applications. Renew Sustain Energy Rev 2012;16:124155. http://dx.doi.org/ [29] Nath RK, Zain MFM, Jamil M. An environment-friendly solution for indoor air
10.1016/j.rser.2011.09.026. purification by using renewable photocatalysts in concrete: a review. Renew
[5] Sundell J, Levin H, Nazaroff WW, Cain WS, Fisk WJ, Grimsrud DT, et al. Sustain Energy Rev 2016;62:118494. http://dx.doi.org/10.1016/j.
Ventilation rates and health: multidisciplinary review of the scientific rser.2016.05.018.
literature. Indoor Air 2011;21:191204. http://dx.doi.org/10.1111/j.1600- [30] Mickal D, Bruno B, Valrie C, Murielle L, Ccile P, Jacques R, et al. Indoor air
0668.2010.00703.x. quality and comfort in seven newly built, energy-efficient houses in France.
[6] Faulkner D, Fisk WJ, Sullivan DP, Lee SM. Ventilation efficiencies and thermal Build Environ 2014;72:17387. http://dx.doi.org/10.1016/j.
comfort results of a desk-edge-mounted task ventilation system. Indoor Air buildenv.2013.10.017.
2004;14(Suppl. 8):927. http://dx.doi.org/10.1111/j.1600-0668.2004.00295.x. [31] Zhang LZ, Niu JL. Modeling VOCs emissions in a room with a single-zone multi-
[7] Yassine B, Ghali K, Ghaddar N, Srour I, Chehab G. A numerical modeling component multi-layer technique. Build Environ 2004;39:52331. http://dx.
approach to evaluate energy-efficient mechanical ventilation strategies. doi.org/10.1016/j.buildenv.2003.10.005.
Energy Build 2012;55:61830. http://dx.doi.org/10.1016/j. [32] Yu BF, Hu ZB, Liu M, Yang HL, Kong QX, Liu YH. Review of research on air-
enbuild.2012.08.042. conditioning systems and indoor air quality control for human health. Int J
[8] Oropeza-Perez I, stergaard PA. Potential of natural ventilation in temperate Refrig 2009;32:320. http://dx.doi.org/10.1016/j.ijrefrig.2008.05.004.
countries - a case study of Denmark. Appl Energy 2014;114:52030. http://dx. [33] Zhang Y, Xu Y. Characteristics and correlations of VOC emissions from building
doi.org/10.1016/j.apenergy.2013.10.008. materials. Int J Heat Mass Transf 2003;46:487783. http://dx.doi.org/10.1016/
[9] Cho W, Song D, Hwang S, Yun S. Energy-efficient ventilation with air-cleaning S0017-9310(03)00352-1.
mode and demand control in a multi-residential building. Energy Build. [34] Cheng Y-H, Lin C-C, Hsu S-C. Comparison of conventional and green building
2015;90:614. http://dx.doi.org/10.1016/j.enbuild.2015.01.002. materials in respect of VOC emissions and ozone impact on secondary
[10] Calautit JK, Hughes BR, Nasir DSNM. Climatic analysis of a passive cooling carbonyl emissions. Build Environ 2015;87:27482. http://dx.doi.org/10.1016/
technology for the built environment in hot countries. Appl Energy j.buildenv.2014.12.025.
2016;186:32135. http://dx.doi.org/10.1016/j.apenergy.2016.05.096. [35] Waring MS, Wells JR. Volatile organic compound conversion by ozone,
[11] Mrz TM, Dutka A. Exergyeconomic evaluation of heat recovery device in hydroxyl radicals, and nitrate radicals in residential indoor air: magnitudes
mechanical ventilation system. Energy Build. 2015;86:296304. http://dx.doi. and impacts of oxidant sources. Atmos Environ 2014;106:38291. http://dx.
org/10.1016/j.enbuild.2014.10.026. doi.org/10.1016/j.atmosenv.2014.06.062.
[12] Rackes A, Melo AP, Lamberts R. Naturally comfortable and sustainable: [36] Gallego E, Roca FJ, Perales JF, Guardino X. Experimental evaluation of VOC
informed design guidance and performance labeling for passive commercial removal efficiency of a coconut shell activated carbon filter for indoor air
buildings in hot climates. Appl Energy 2016;174:25674. http://dx.doi.org/ quality enhancement. Build Environ 2013;67:1425. http://dx.doi.org/
10.1016/j.apenergy.2016.04.081. 10.1016/j.buildenv.2013.05.003.
[13] Tong Z, Chen Y, Malkawi A, Liu Z, Freeman RB. Energy saving potential of [37] Sidheswaran MA, Destaillats H, Sullivan DP, Cohn S, Fisk WJ. Energy efficient
natural ventilation in China: the impact of ambient air pollution. Appl Energy indoor VOC air cleaning with activated carbon fiber (ACF) filters. Build Environ
2016;179:6608. http://dx.doi.org/10.1016/j.apenergy.2016.07.019. 2012;47:35767. http://dx.doi.org/10.1016/j.buildenv.2011.07.002.
[14] Hughes BR, Chaudhry HN, Calautit JK. Passive energy recovery from natural [38] Khamis Mansour M, Hassab M. Thermal design of cooling and dehumidifying
ventilation air streams. Appl Energy 2014;113:12740. http://dx.doi.org/ coils. InTech; 2012. http://dx.doi.org/10.5772/32536.
10.1016/j.apenergy.2013.07.019. [39] McQuiston FC, Parker JD, Spitler JD. Heating, ventilating, and air conditioning:
[15] Ben-David T, Waring MS. Impact of natural versus mechanical ventilation on analysis and design. 6th ed. John Wiley & Sons; 2005.
simulated indoor air quality and energy consumption in offices in fourteen U.S. [40] Petukhov BS. Heat transfer and friction in turbulent pipe flow with variable
cities. Build Environ 2016;104:32036. http://dx.doi.org/10.1016/j. physical properties. Adv Heat Transf 1970;6:50364. http://dx.doi.org/
buildenv.2016.05.007. 10.1016/S0065-2717(08)70153-9.
[16] Abou Hweij W, Ghaddar N, Ghali K, Habchi C. Optimized performance of [41] Xia L, Chan MY, Deng SM, Xu XG. Analytical solutions for evaluating the
displacement ventilation aided with chair fans for comfort and indoor air thermal performances of wet air cooling coils under both unit and non-unit
quality. Energy Build 2016;127:90719. http://dx.doi.org/10.1016/j. Lewis factors. Energy Convers Manage 2010;51:207986. http://dx.doi.org/
enbuild.2016.06.052. 10.1016/j.enconman.2010.02.041.
[17] Li Z, Chen W, Deng S, Lin Z. The characteristics of space cooling load and indoor [42] Chua KJ, Chou SK, Ho JC. A model to study the effects of different control
humidity control for residences in the subtropics. Build Environ strategies on space humidity during part-load conditions. Build Environ
2006;41:113747. http://dx.doi.org/10.1016/j.buildenv.2005.05.016. 2008;43:207489. http://dx.doi.org/10.1016/j.buildenv.2007.12.005.
[18] Chua KJ, Ho JC, Chou SK. A comparative study of different control strategies for [43] Fumo N, Mago P, Luck R. Methodology to estimate building energy
indoor air humidity. Energy Build 2007;39:53745. http://dx.doi.org/10.1016/ consumption using EnergyPlus benchmark models. Energy Build
j.enbuild.2006.09.008. 2010;42:23317. http://dx.doi.org/10.1016/j.enbuild.2010.07.027.
[19] Wang Y, Cao Y, Liu B, Liu J, Yang Y, Yu Q. An evaluation index for the control [44] Nguyen A-T, Reiter S, Rigo P. A review on simulation-based optimization
effect of the local ventilation systems on indoor air quality in industrial methods applied to building performance analysis. Appl Energy
buildings. Build Simul 2016;9:66976. http://dx.doi.org/10.1007/s12273-016- 2014;113:104358. http://dx.doi.org/10.1016/j.apenergy.2013.08.061.
0295-2. [45] ASHRAE. ASHRAE handbook-fundamentals. Atalanta (GA); 2009.

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067
X. Cui et al. / Applied Energy xxx (2017) xxxxxx 13

[46] Kreider JF, editor. Handbook of heating, ventilation, and air conditioning. CRC [49] Garcia Sanchez D, Lacarrire B, Musy M, Bourges B. Application of sensitivity
Press; 2000. analysis in building energy simulations: combining first- and second-order
[47] Zhou X, Braun J. A Simplified dynamic model for chilled-water elementary effects methods. Energy Build 2014;68:74150. http://dx.doi.org/
cooling and dehumidifying coilsPart 2: experimental validation (RP-1194). 10.1016/j.enbuild.2012.08.048.
HVAC&R Res 2007;13:80517. http://dx.doi.org/10.1080/10789669. [50] Wong SL, Wan KKW, Lam TNT. Artificial neural networks for energy analysis of
2007.10390987. office buildings with daylighting. Appl Energy 2010;87:5517. http://dx.doi.
[48] Calleja Rodrguez G, Carrillo Andrs A, Domnguez Muoz F, Cejudo Lpez JM, org/10.1016/j.apenergy.2009.06.028.
Zhang Y. Uncertainties and sensitivity analysis in building energy simulation [51] Pereira W, Bgl A, Natschlger T. Sensitivity analysis and validation of an
using macroparameters. Energy Build 2013;67:7987. http://dx.doi.org/ EnergyPlus model of a house in Upper Austria. Energy Proc 2014;62:47281.
10.1016/j.enbuild.2013.08.009. http://dx.doi.org/10.1016/j.egypro.2014.12.409.

Please cite this article in press as: Cui X et al. Energy performance evaluation and application of an air treatment system for conditioning building spaces in
tropics. Appl Energy (2017), http://dx.doi.org/10.1016/j.apenergy.2017.03.067

Вам также может понравиться