Multilin UR & UR Plus

Proven, State-of-the-Art Protection & Control Systems Protection and Control


From the power plant to the power consumer, the Multilin UR & UR family of advanced protection
Plus Fast, segregated line current differential &
and control relays provides one integrated platform that delivers leading edge protection, control, distance protection functionality in one device
monitoring & metering solutions for critical power system applications. Featuring proven protection Phase distance (5 zones) with independent
algorithms, expandable I/O, integrated monitoring & high accuracy metering capabilities with the settings for compensation
latest in communications technologies, the Multilin UR & URPlus family of devices provides the situational
Single-pole tripping, breaker-and-a-half with
awareness needed for a reliable, secure and efficient modern grid.
independent current source support
Comprehensive generator protection with
Key Benefits 100% stator and field ground fault detection
Modular construction: common hardware, reduced stock of pare parts, plug & play modules for
maintenance cost savings and simplification (Multilin UR)
Proven flexibility and customization capabilities make the Multilin UR/URPlus devices suitable to retrofit
Communications
almost any kind of legacy P&C scheme 3 independent Ethernet ports for simultaneous
& dedicated network connections with
Large HMI and annunciator panels provide local monitoring & control capabilities, and backup the
IEEE1588 support
substation HMI (Multilin URPlus)
Supported industry protocols: IEC 61850 Ed.2,
Phase measurement Unit (synchrophasors) according to IEEE C37.118 (2011) and IEC 61850-90-5
SFTP, MMS File Transfer Service, DNP 3.0,
directly streamed from your protective device
Modbus Serial/TCP, IEEE 1588, IEC 60870-5-104
Embedded IEEE 1588 Time Synchronization Protocol support eliminates dedicated IRIG-B wiring and 103, PRP, SNTP, HTTP, TFTP
requirements for P&C devices (Multilin UR)
Advanced IEC 61850 Ed. 2 certified implementation, complete settings via SCL files and
IEC 61850-9-2 process bus solution enable resource and platform managing optimization and reduce Cyber Security
cost of ownership (Multilin UR) CyberSentry provides high-end cyber security
Routable GOOSE (R-GOOSE) enables customer to send GOOSE messages beyond the substation, which aligned to industry standards and services
enables WAPC and more cost effective communication architectures for wide area applications (NERC CIP, AAA, Radius, RBAC, Syslog)

Increased network availability via failover time reduced to zero through IEC 62439-3 PRP support Setting for security audit trails, tracking
changes to device configurations
CyberSentry provides high-end cyber security aligned to industry standards and services including
NERC CIP, AAA, Radius, RBAC and Syslog (Multilin UR)
Advanced fault and disturbance recording, including internal relay operating signals, eliminating the Monitoring & Metering
need for external recording devices
Advanced recording capabilities, configurable
Supports IEEE C37.111-1999/2013, IEC 60255-24 Ed 2.0 COMTRADE standard & extended waveform capture and data logger
Fault locator fault reports & programmable
Applications Breaker condition monitoring including
Protection, control, monitoring and supervision of power assets across generation, transmission, breaker arcing current (I2t), breaker re-strike
distribution, substation and industrial systems and breaker flashover
Utility substation and industrial plant automation Metering: current, voltage, power factor,
frequency, voltage & current harmonics,
Digital fault recording and Sequence of Event (SOE) recording
energy, demand, phasors, etc.
Predictive maintenance through data analysis and trending
Supports IEEE C37.111-1999/2013, IEC 60255-
Synchrophasors based monitoring and control system with specialized PMU devices that support 24 Ed 2.0 COMTRADE standard
multiple feeders providing P&M class synchrophasors of voltage, current, and sequence components
Complex protection & control and wide area monitoring solutions with complete diagnostic and
automation capabilities (Multilin URPlus)
UR & URPlus Family

UR & URPlus Market Offerings


Family Overview

Generation Transmission & Distribution


G60 D90Plus L60
Medium to Large Generators Sub-Cycle Distance Protection Line Phase Comparison Protection
The G60 provides comprehensive primary The D90 is ideally suited for application on
Plus
The L60 is an extremely fast line phase
and backup protection for medium and transmission lines where fast fault detection comparison system, suitable for two or three
large generators, including large steam and small breaker failure margin are required. terminal transmission lines. This system is able
and combustion turbines, combined-cycle The D90Plus allows transmission limits to be to operate using power line carrier or fiber optic
generators and multi-circuit hydro units. maintained or even increased while respecting communications.
The G60 includes advanced automation and the transient stability limits of the power system.
communication capabilities, extensive I/O L30
options, and powerful fault recording features D60 Sub-Transmission Line Current Differential
that simplify postmortem analysis and minimize
Fully Featured Distance Protection Protection
generator downtime.
The D60 is the ideal solution for providing The L30 is a cost-effective phase-segregated
G30 reliable and secure primary and backup line current differential system intended to
protection of transmission lines supporting: provide primary protection for MV cables and
Combined Generator & Transformer Protection
series compensation, teleprotection schemes, two/three-terminal sub-transmission lines or
The G30 is a flexible system that can be used five mho or quad distance zones, single backup protection to transmission lines.
on small and medium generators, generator or three-pole tripping, breaker-and-half
and step-up transformer arrangements or with independent current inputs, phasor B90
backup protection of large generators. Similar measurement units (PMUs), and more.
Low Impedance Busbar Protection
to the G60, the G30 also offers comprehensive
protection and monitoring elements. D30 The B90 is an advanced low-impedance
differential protection system that is intended to
Backup Distance Protection
cover applications ranging from small to large
The D30 is the cost-effective choice for the substations, having either single or complex-
primary protection of sub-transmission split busbar schemes. It is able to support
systems or backup protection of transmission busbars with up to 24 breakers, and 4 single
systems. Using FlexLogic elements, basic phase differential zones.
pilot schemes can be programmed. The
D30 has complementary protection, control, B30
communication, monitoring and metering
Low Impedance Busbar Protection
functions that meet the toughest requirements
of the market. The B30 is a cost-effective, advanced protection
system that fits busbars with up to 6 circuits
L90 and two protection zones. The B30 provides
advanced elements like CT trouble, directional
Complete Line Protection
and CT saturation, breaker failure and voltage
The L90 is a fast and powerful high-end supervision that make the B30 an extremely fast
phase-segregated line current differential and secure busbar protection system.
and complete distance protection system,
suitable for MV cables, two or three terminal B95Plus
transmission lines having breaker-and-half and
Distributed Busbar Protection System
single or three-pole tripping schemes.
The B95Plus is GEs distributed busbar solution
that can be applied to any kind of busbar
configuration and uses standard IEC 61850
protocol to connect to the bay units. The B95Plus
delivers comprehensive and reliable protection
for busbar applications with up to 24 feeders.

2 GEDigitalEnergy.com
UR & URPlus Family

Family Overview
Transmission & Distribution (Continued) Industrial & Network
F60 T35 M60
Feeder Protection with Hi-Z Fault Detection Basic Transformer Protection, Multiple CTs Motor Protection
The F60 provides comprehensive feeder The T35 is a basic transformer protection The M60 offers comprehensive protection and
protection, control, advanced communications, system capable of protecting combined main control solutions for large-sized three-phase
monitoring and metering in an integrated, power transformers and up to five feeders motors. The M60 provides superior protection,
economical, and compact package and more. downstream. The T35 provides automatic or control, and diagnostics that includes thermal
user-definable magnitude reference winding model with RTD and current unbalance biasing,
F35 selection for CT ratio matching, automatic stator differential, reverse and low forward
phase shift compensation and allows users to power, external RRTD module, two-speed
Multiple Feeder Protection
enable removal of the zero-sequence current motors, reduced voltage starting, broken rotor
The F35 is a cost-effective device for primary even for delta connected transformer windings. bar detection, and more.
feeder protection. F35s modular design allows
customers to protect groups of feeders as C90Plus N60
follows: independent current and voltage inputs,
Breaker Automation and Controller Network Stability and Synchrophasor
independent current and common voltage
Measurement
inputs or independent current inputs only. The C90 Plus is a powerful logic controller
designed to be used in substation environments The N60 is intended to be used on load shedding,
C70 and for the unique automation requirements remedial action, special protection and wide
of industrial and utility power systems. The area monitoring and control schemes. Like no
Capacitor Bank Protection
C90Plus provides unmatched logic processing one device before, the N60 shares real-time
The C70 is an integrated protection, control, and ability combined with a powerful math engine operational data to remote N60s so the system
monitoring device for shunt capacitor banks. with deterministic execution of logic equations can generate intelligent decisions to maintain
The current and voltage-based protection regardless of the configuration of the number of power system operation.
functions are designed to provide sensitive lines of logic.
protection for grounded, ungrounded single and
parallel capacitor banks and banks with taps. C60
Breaker Controller
T60
The C60 is a substation hardened controller that
Medium to Large Transformers
provides a complete integrated package for the
The T60 is a fully featured transformer protection protection, control, and monitoring of circuit
system suitable for power transformers of any breakers, supporting dual-breaker busbar
size that require current differential function. configurations, such as breaker-and-half or ring
The T60 provides automatic or user-definable bus schemes.
magnitude reference winding selection for CT
ratio matching, and performs automatic phase C30
shift compensation for all types of transformer
I/O Logic Controller
winding connections.
The C30 is designed to perform substation
control logic that can also expand the I/O
capability of protection devices and replace
existing Sequence of Events (SOE) recorders.

GEDigitalEnergy.com 3
UR & URPlus Family

Overview UR - Protection, Metering, Monitoring and Control


The Universal Relay (UR) is a family of leading
edge protection and control products built
on a common modular platform. All UR
products feature high-performance protection,
expandable I/O options, integrated monitoring
and metering, high-speed communications,
and extensive programming and configuration
Family Overview

capabilities. The UR forms the basis of simplified


power management for the protection of critical
assets, either as a stand-alone device or within
an overall power automation system.

The UR is managed and programmed through


EnerVista Launchpad. This powerful software
package, which is included with each relay,
not only allows the setpoints of the relay to be
programmed, but also provides the capability
to manage setpoint files, automatically access The UR is the single point for protection, control, metering, and monitoring in one integrated device
the latest versions of firmware/documentation that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint
and provide a window into the substation Monitoring as shown.
automation system.

The UR can be supplied in a variety of Digital I/O SCADA capabilities that far surpass what is found
configurations and is available as a 19-inch in the average protection relay. Each UR can be
Up to 96 contact inputs (with utility voltage
rack horizontal mount unit or a reduced size seamlessly integrated with other UR relays for
rating up to 250V), and up to 64 contact
() vertical mount unit . The UR consists of complete system protection and control.
outputs, are available and can be used to
the following modules: power supply, CPU,
monitor and control a wide range of auxiliary
CT/VT input, digital input/output, transducer FlexLogic
equipment found within a substation or other
input/output , inter-relay communications, FlexLogic is the powerful UR-platform
protection application. Types of digital I/O
communication switch and IEC Process Bus. All programming logic engine that provides the
cards include trip-rated Form-A, Form-C, Fast
hardware modules and software options can be ability to create customized protection and
Form-C, latching and Solid State Relay (SSR),
specified at the time of ordering. control schemes, minimizing the need and
with or without DC voltage, current monitoring
and isolated inputs (with auto burnish feature). associated costs of, auxiliary components and
Protection and Control Mechanically latching outputs can be used to wiring. With 1024 lines of FlexLogic, the UR
develop secure interlocking applications and can be programmed to provide the required
The UR incorporates the most complete and
replace mechanical switches and lockout relays. tripping logic along with custom scheme logic
unique protection algorithms to provide
Form-A digital outputs have activation speeds for breaker control (including interlocking
unparalleled security and system uptime. The
of less than 4ms and both wet and dry contacts with external synchronizers), transfer tripping
UR selector guide (in the following pages) lists
are supported. schemes for remote breakers and dynamic
all the protection elements found in each relay.
setting group changes.
Solid state output modules with high current
To support the protection and control functions
breaking capability, fast tripping and reset time Scalable Hardware
of the UR, various types and forms of I/O
are ideal for direct tripping applications.
are available (specific capabilities are model The UR is available with a multitude of I/O
dependent). Supported I/Os include: configurations to suit the most demanding
Transducer I/O
application needs. The expandable modular
CTs and VTs RTDs and DCmA cards are available to monitor design allows for easy configuration and future
system parameters, such as temperature, upgrades.
Up to 24 analog current transformer (CT)
vibration, pressure, wind speed, and flow. Analog
and voltage transformer (VT) signals can be Multiple CT/VT configurations allow for the
outputs can be used for hardwired connections
configured to monitor AC power lines. Both 1 implementation of many different schemes,
from the controller to a SCADA system, to a
A and 5 A CTs are supported. Special function including concurrent split-phase and
programmable logic controller (PLC), or to other
modules are available including: a CT module differential protection
user interface devices (eg. panel display).
with sensitive ground input to provide ground
Flexible, modular I/O covering a broad
fault protection on high-impedance grounded
range of input signals and tripping schemes
systems, and a high-impedance fault detection Advanced Automation with trip rated Form-A, SSR, Form-C and
module that provides fast and reliable detection mechanically latched relays
The UR incorporates advanced automation
of faults caused by downed conductors.
features including powerful FlexLogic Inter-relay communications module that
programmable logic, communication, and enables the sharing of digital status and

4 GEDigitalEnergy.com
UR & URPlus Family

Family Overview
Digital fault recorder summary with the latest information on the events, Control screen for the preconfigured bay with breaker & disconnect control in
faults, transients and disturbances. multiple pages using dedicated pushbuttons in the front panel.

analog values between UR relays for control, Data Logger and Disturbance Recording A special feature of the synchrophasor
fast tripping or teleprotection applications - 16 channels up to 1 sample/cycle/channel implementation is the ability to apply magnitude
Types of digital outputs include trip-rated Fault Reports and phase angle correction on a per-phase basis
Form-A and SSR mechanically latching, and - Powerful summary report of pre-fault and for known CT and PT magnitude and phase errors.
Form-C outputs fault values Selected UR devices can apply a phase correction
on each phase of up to 5 in increments of 0.05.
Form-A and SSR outputs available with The very high sampling rate and large amounts
They also provide the ability to adjust for delta-
optional circuit continuity monitoring and of storage space available for data recording in
current detection to verify continuity and wye phase angle shifts or polarity reversal in
the UR allows for the capture of complex events
health of the associated circuitry the synchrophasor reporting of the voltage and
and can eliminate the need for installing costly
current sequence components.
IEC 61850 Process Bus delivering advanced stand-alone recording equipment.
protection and control capabilities while UR devices can stream PMU data through any
providing significant savings on the total life Advanced Device Health Diagnostics of its three Ethernet ports using either IEEE
cost of electrical substations The UR performs comprehensive device health C37.118 or IEC 61850-90-5 data formats. When
RTDs and DCmA inputs are available to diagnostic tests at startup and continuously streaming PMU data through a single port, a
monitor equipment parameters such as during run-time to test its own major functions failover function can automatically switch the
temperature and pressure and critical hardware. These diagnostic tests transmission over another Ethernet port.
monitor for conditions that could impact security
Selected UR devices also support up to 16 user-
and availability of protection, and present device
Monitoring and Metering status via SCADA communications and front
definable command outputs via the command
The UR includes high accuracy metering frame defined in the IEEE C37.118 standard.
panel display. Providing continuous monitoring
and recording for all AC signals. Voltage, and early detection of possible issues help
PMU recording
current , and power metering are built into improve system uptime.
the relay as a standard feature. Current and UR devices include high accuracy metering and
Comprehensive device health diagnostic
voltage parameters are available as total RMS recording for all AC signals. Voltage, current,
performed at startup
magnitude, and as fundamental frequency frequency, power and energy and demand
magnitude and angle. Monitors the CT/VT input circuitry to validate metering are built into the relay as a standard
the integrity of all signals feature. Current and voltage parameters are
Fault and Disturbance Recording Monitors internal DC voltage levels that available as total RMS magnitude, and as
The advanced disturbance and event recording allows for proactive maintenance and fundamental frequency magnitude and angle.
increased uptime UR devices have 12MB of synchrophasor
features within the UR can significantly reduce
the time needed for postmortem analysis recording memory with multiple recording and
of power system events and the creation of PMU - Synchrophasors triggering options. The PMU recorder can be
regulatory reports. Recording functions include: triggered by an over/under frequency, over/
With the ability of having up to 6 PMU elements
under voltage, overcurrent, overpower, rate of
Sequence of Event (SOE) in one device, UR devices provide simultaneous
change of frequency condition, or by a user-
- 1024 time stamped events (UR Relays) data streams of up to four different clients.
specified condition, freely configured through
- 8192 time stamped events (URPlus) FlexLogic. The PMU status flag shows which of
UR devices exceed the IEEE C37.118 (2011)
Oscillography requirements for Total Vector Error (TVE) less those functions triggered the PMU recorder.
- Supports IEEE C37.111-1999/2013, IEC than 1% over a range of 40Hz to 70Hz, and are
60255-24 Ed 2.0 COMTRADE standard able to measure and report synchrophasors
- 64 digital & up to 40 analog channels over a frequency range from 30Hz to 90Hz with
- Events with up to 45s length little effect on TVE.

GEDigitalEnergy.com 5
UR & URPlus Family

Monitor Multiple Power Circuits


Selected UR devices can monitor from one up
to six three-phase power circuits and can be
configured to simultaneously provide as many
as 6 PMUs. Other configurations are: three power
circuits with independent currents and voltages,
four power circuits with independent currents
and two common voltages, five power circuits
Family Overview

with independent current and one common


voltage. UR devices provide metering of many
power system quantities including active,
reactive and apparent power on a per-phase,
and three-phase basis, true RMS value, phasors
and symmetrical components of currents, IEC 61850 protocol enables high-speed trip and control via the substation LAN without complex fixed
and voltages, power factor, and frequency. wiring to many auxiliary devices.
Frequency can be measured independently
and simultaneously from up to six different
signals including currents if needed. UR devices Precision Time Protocol - IEEE 1588 The UR Switch Module provides a simple way
allow for the creation and processing of virtual to add fully-managed Ethernet networking
UR devices support the IEEE 1588 v2 (2012)
sums of currents through its user configuration to your relays and devices without the need
time synchronization protocol that enables
mechanism of signal sources, and can also sum for additional hardware or a dedicated
time synchronization via the substation LAN
analog values through its FlexMath elements. communications cabinet.
with no sacrifice on time accuracy (1s). IEEE
1588 removes the dedicated IRIG-B wiring and The UR Switch Module includes all the
Communications repeaters used for time synchronization that are management and features that come with
traditionally used in substations. all MultiLink managed switches, and can be
The UR provides advanced communications
easily integrated into a network that has other
technologies for remote data and engineering
UR Switch Module Ethernet switches.
access, making it easy and flexible to use and
integrate into new and existing infrastructures. In addition to providing high-speed connectivity
When used in a ring topology with other UR switch
Direct support for fiber optic Ethernet provides directly to the UR, the UR Switch Module
modules or MultiLink switches, the UR Switch
high-bandwidth communications allowing provides an additional 4 fiber Ethernet ports,
Module can be configured to use MultiLinks
for low-latency controls and high-speed for connection to other relays in the system as
Smart RSTP feature to provide industry-leading
file transfers of relay fault and event record well as upstream connectivity. It also provides 2
network recovery for ring topologies, at a speed
information. The available redundant Ethernet RJ45 copper Ethernet ports which can be used
of less than 5ms per switch.
option provides the means to create fault to connect local devices such as PCs, meters, or
tolerant communication architectures in an virtually anything else in the system.
easy, cost-effective manner without the need
for intermediary communication hardware.

The UR supports the most popular industry


standard protocols enabling easy, direct
integration into DCS and SCADA systems.

IEC 61850 with 61850-90-5 support


DNP 3.0 (serial & TCP/IP)
Ethernet Global Data (EGD)
IEC 60870-5-103 and IEC 60870-5-104
Modbus RTU, Modbus TCP/IP
HTTP, TFTP
SNTP and IEEE 1588 for time synchronization
PRP as per IEC 62439-3
Supports Routable GOOSE (R-GOOSE)

Purpose Specific LAN


The available three independent Ethernet ports
enable users to segregate heavy traffic (eg.
synchrophasors) from mission critical services
(eg. GOOSE), as a way to eliminate potential The UR Switch Module is a fully-managed Ethernet switch with a modular form factor. It can be placed directly
latency effects. into a GE Multilin UR to provide Ethernet connectivity to the relay as well as other Ethernet-enabled devices.

6 GEDigitalEnergy.com
UR & URPlus Family

Interoperability with Embedded IEC 61850 LAN Redundancy Every substation is unique, making design
and drafting a one-off solution for every
Use the UR with integrated IEC 61850 to lower Substation LAN redundancy has been traditionally
station
costs associated with system protection, control accomplished by reconfiguring the active network
and automation. GE Digital Energys leadership topology in case of failure. Regardless of the type Miles of copper wires need to be pulled,
in IEC 61850 comes from thousands of installed of LAN architecture (tree, mesh, etc), reconfiguring spliced and terminated
devices and follows on extensive development the active LAN requires time to switchover, during Time-consuming testing and troubleshooting
experience with UCA 2.0. which the LAN is unavailable. UR devices deliver of thousands of connections must be
redundancy as specified by PRP-IEC 62439-3, performed by skilled personnel
Backup wired signals or replace expensive

Family Overview
which eliminates the dependency on LAN The HardFiber Process Bus System was designed
copper wiring between devices with direct
transfer of data from up to 64 remote device reconfiguration and the associated switchover to address these challenges and reduce the
using GOOSE messaging. time. The UR becomes a dual attached node overall labor associated with the tasks of
that transmits data packets over both main and designing, documenting, installing and testing
Configure GE systems based on IEC 61850
redundant networks simultaneously, so in case protection and control systems. By specifically
and also monitor and troubleshoot them in
of failure, one of the data packets will reach the targeting copper wiring and all of the labor it
real-time with EnerVista Viewpoint Engineer
receiving device with no time delay. requires, the HardFiber Process Bus System
Multicast IEEE C37.118 synchrophasor
allows for greater utilization and optimization of
data between PMU and PDC devices using Direct I/O Messaging
resources with the ultimate goal of reducing the
IEC61850-90-5
Direct I/O allows for the sharing of analog or total life cost (TLC) for protection and control.
R-GOOSE enable customer to send GOOSE high-speed digital information between multiple
messages beyond the substation, which UR relays via direct back-to-back connections or
enables WAPC and more cost effective multiplexed through a standard DS0 multiplexer
Cyber Security - CyberSentry UR
communication architectures for wide area CyberSentry enables UR devices to deliver full
channel bank. Regardless of the connection
applications cyber security features that help customers to
method, direct I/O provides continuous
real-time channel monitoring that supplies comply with NERC CIP and NIST IR 7628 cyber
diagnostics information on channel health. security requirements through supporting the
Direct I/O provides superior relay-to-relay following core features:
communications that can be used in advanced
interlocking, generation rejection and other Password Complexity
special protection schemes. Supporting up to 20 alpha- numeric or special
characters, UR passwords exceed NERC
Communication with up to 16 UR relays
in single or redundant rings rather than CIP requirements for password complexity.
strictly limited to simplistic point-to-point Individual passwords per role are available.
configurations between two devices
AAA Server Support (Radius)
Connect to standard DS0 channel banks
through standard RS422, G.703 or IEEE Enables integration with centrally managed
C37.94 interfaces or via direct fiber optic authentication and accounting of all user
connections activities and uses modern industry best
practices and standards that meet and exceed
No external or handheld tester required to
NERC CIP requirements for authentication and
provide channel diagnostic information
password management.
Multi-Language
Role Based Access Control (RBAC)
UR devices support multiple languages: English,
French, Russian, Chinese, Turkish and German. Efficiently administrate users and roles within
These language options are available on the UR devices. The new and advanced access
front panel, in the EnerVista setup software, and functions allow users to configure up to eight
in the product manuals. Easily switch between roles for up to eight configurable users with
English and an additional language on the local independent passwords. The standard Remote
displays without uploading new firmware. Authentication Dial In User Service (Radius) is
used for authentication.

HardFiber IEC 61850 Process Bus Event Recorder (Syslog for SEM)
The HardFiber Process Bus System represents Capture all cyber security related events within
a true breakthrough in the installation and a SOE element (login, logout, invalid password
ownership of protection and control systems, attempts, remote/local access, user in session,
by reducing the overall labor required for settings change, FW update, etc), and then
substation design, construction, and testing. serve and classify data by security level using
IEC 61850 protocol enables high-speed trip and This innovative solution addresses the three key
control via the substation LAN without complex standard Syslog data format . This enables
fixed wiring to many auxiliary devices. issues driving the labor required for protection
UR devices to integrate with established SEM
and control design, construction and testing:
(Security Event Management) systems.

GEDigitalEnergy.com 7
UR & URPlus Family

EnerVista Software Viewpoint Monitoring Settings Security Audit Report

The EnerVista suite is an industry-leading set Viewpoint Monitoring is a simple-to-use and Device Health Report
of software programs that simplifies every full-featured monitoring and data recording Single-Click Fault Data Retreival
aspect of using the UR. The EnerVista suite software package for small systems. Similar
provides all the tools to monitor the status of to small SCADA systems, Viewpoint Monitoring EnerVista Integrator
the protected asset, maintain the relay, and provides a complete HMI package with the EnerVista Integrator is a toolkit that allows
integrate information measured by the UR into following functionality: seamless integration of Multilin devices into
DCS or SCADA monitoring systems. Convenient new or existing automation systems. Included in
Family Overview

Plug-&-Play Device Monitoring


COMTRADE and SOE viewers are an integral part EnerVista Integrator is:
System Single-Line Monitoring & Control
of the UR setup software included with every UR
OPC/DDE Server
relay, to carry out postmortem event analysis Annunciator Alarm Screens
and ensure proper protection system operation. GE Multilin Drivers
Trending Reports
Automatic Event Retrieval
Automatic Event Retrieval
EnerVista Launchpad Automatic Waveform Retrieval
Automatic Waveform Retrieval
EnerVista Launchpad is a powerful software
package that provides users with all of the Viewpoint UR Engineer User Interface
setup and support tools needed for configuring
Viewpoint UR Engineer is a set of powerful The UR front panel provides extensive local
and maintaining GE Multilin products. The
tools that allows the configuration and testing HMI capabilities. The local display is used for
setup software within Launchpad allows for
of GE relays at a system level in an easy-to- monitoring, status messaging, fault diagnosis,
the configuration of devices in real-time by
use graphical drag-and-drop environment . and device configuration. User-configurable
communicating using serial, Ethernet , or
Viewpoint UR Engineer provides the following messages that combine text with live data can
modem connections, or offline by creating
configuration and commissioning utilities: be displayed when user-defined conditions are
setting files to be sent to devices at a later time.
Graphical Logic Designer (Substation) met. Configurable LEDs allows status and alarm
Included in Launchpad is a document archiving signaling (50 LEDs).
Graphical System Designer
and management system that ensures critical
documentation is up-to-date and available when Graphical Logic Monitor The URPlus has a colorful, graphical HMI that
needed. Documents made available include: allows users to have local monitoring of status,
Graphical System Monitor (Substation)
values and control functionality.
Manuals IEC 61850 Configurator
The alarm annunciator panel provides the
Application Notes and Support Documents
Viewpoint Maintenance configuration of up to 256 signals (alarms and
Guideform Specifications status) with full text description.
Viewpoint Maintenance provides tools that
Brochures will create reports on the operating status of
Wiring Diagrams the relay, simplify the steps to download fault
FAQs and event data, and reduce the work required
for cyber security compliance audits. Tools
Service Bulletins
available in Viewpoint Maintenance include:

Power System Troubleshooting


The UR contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events, increase uptime and
reduce loss of production.

Record the operation of the internal UR elements and external connected Analyze faults and disturbances using both analog and digital power
devices with 1ms time-stamped accuracy to identify the Sequence of system quantities.
Operation of station devices during faults and disturbances.

8 GEDigitalEnergy.com
UR & URPlus Family

URPlus Front Panel with Large Color Display and Annunciator Panel

Digital Alarm Annunciator Intuitive HMI Advanced Control


256 customizable alarms in Customizable bay diagrams for various Customizable bay diagrams for various
multiple pages applications applications

Eliminates the need for separate Local control and status indication of breakers Local control and status indication of breakers
& disconnect switches & disconnect switches
annunciator
Local/remote control Local/remote control
(20 programmable buttons)
Fault, event, disturbance and transient reports

Family Overview
Fault, event, disturbance and transient reports

Advanced Automation Advanced Communications Advanced Recorders Front USB Port


Controller Capabilities Eliminate the need for stand-alone High-speed local
Built-in programmable logic Up to three Ethernet ports disturbance recorders data transfer
engine
IEC 61850, DNP 3.0, Modbus TCP/IP, 128 samples/cycle, 1 min duration
Advanced math, Boolean and IEC 60870-5-104 protocols transient recorder
control operations
IEEE C37.118 synchrophasors over Seperate dynamic disturbance
Ethernet recorder for recording long term
events
Synchrophasors PMU recording

URPlus Dimensions

9.80
7.50 (249)
11.43
(190) (290)

18.31 (465)

18.86 (479)

4 x 0.28 Dia
(7.1)

18.37 (466.6)

GEDigitalEnergy.com 9
7.13 4.00
(81.1) (101.6)
UR & URPlus Family

UR Enhanced Front Panel with Large Display, Customizable LED Annunicator,


and User-Programmable Pushbuttons

Bright Annunciator Easy LED Labeling Large LCD Display & Complete Secure Locking
with 62 LEDs Keypad for Local Operation
Family Overview

Optional 16 User-Programmable Pushbuttons 3 User Pushbuttons Local RS232 Port

UR Horizontal Dimensions

10 GEDigitalEnergy.com
UR & URPlus Family

UR Enhanced Front Panel - Vertical Faceplate

Secure Locking

Large LCD Display

Family Overview
Bright, Easy Labeling, LED Annunciator

Complete Keypad and 3 User Pushbuttons

Local RS232 Port

Optional 6 User-Programmable Pushbuttons

UR Vertical Dimensions

7.482 7.482
(190) (190) 11.015 11.015
(279.781)
1.329 (279.781)
1.329
(33.76) (33.76)

15.00 15.00 14.025 14.025


(381) (381) (356.2) (356.2) 13.560 13.560
(344.4) (344.4)

4.00 4.00
(101.6) (101.6) 9.780 9.780
(248.4) (248.4)

GEDigitalEnergy.com 11
UR & URPlus Family

UR Family
Selector Guide
Features ANSI B30 B90 B95Plus C30 C60 C70 C90Plus D30 D60 D90Plus
Protection
Family Overview

Disturbance Detector
Mho Distance, Phase (No. of Zones) 21P 5 5 5
Mho Distance, Ground or Neutral Phase (No. of Zones) 21G/N 5 5 5
Quadrilateral Distance, Phase (No. of Zones) 21P 5 5 5
Quadrilateral Distance, Ground or Neutral (No. of Zones) 21G/N 5 5 5
Permissive Pilot Logic
Sub-Cycle Distance
Overexcitation Protection (V/Hz) 24
Synchronism Check or Synchronizing 25
Undervoltage, Phase 27P
Undervoltage, Auxiliary 27X
Stator Ground (3rd Harmonic) 27TN
Sensitive Directional Power 32S
Loss of Excitation Based on Reactive Power 40Q
Loss of Excitation Based on Impedance Element 40
Current Unbalance 46
Broken Conductor Detection 46BC
IOC, Negative Sequence 46/50
TOC, Negative Sequence 46/51
Current Directional, Negative Sequence 46/67
Reverse Phase Sequence Voltage 47
Thermal Model 49
Inadvertent/Accidental Energization 50/27
End of Fault Protection
Motor Mechanical Jam
Motor Start Supervision
Motor Acceleration Time
User Programmable Curves
Breaker Failure 50BF Logic
IOC, Phase 50P
IOC, Ground 50G
IOC, Neutral 50N
IOC, Sensitive Ground 50SG
High Impedance Fault Detection
TOC, Phase 51P
TOC, Ground 51G
TOC, Neutral 51N
TOC, Sensitive Ground 51SG
TOC, Voltage Restrained 51V
Overvoltage, Phase 59P
Overvoltage, Auxiliary 59A
Overvoltage, Neutral 59N
Negative Sequence Overvoltage 59-2
100% Stator Ground Protection 64TN
Current Directional, Phase 67P
Current Directional, Neutral 67N
Current Directional, Negative Sequence 46/67
Power Swing Blocking 68
Out-of-Step Tripping 78
AC Reclosing (No. of Shots) 79 4 4 4 4
Switch on to Fault (Line Pickup) SOTF
Voltage Transformer Fuse Failure VTFF
Current Transformer Supervision 50/74
Load Encroachment Logic
Underfrequency 81U
Overfrequency 810
Anti-Islanding Protection/Frequency Rate of Change 81R
Lockout Functionality 86
Bus Differential 87B 2 2 2
Line Current Differential 87L
Ground Differential 87G
Stator Differential 87S
Transformer Differential 87T
Line Phase Comparison 87PC
Voltage Differential
Capacitor Bank Overvoltage
Neutral Voltage Unbalance
Automatic Voltage Regulation
Time of Day Control
Instantaneous Differential 50/87
Split Phase Protection
Line Current Differential Trip Logic
CT Failure

12 GEDigitalEnergy.com
UR & URPlus Family

Features F35 F60 G30 G60 L30 L60 L90 M60 N60 T35 T60
Protection

Family Overview
Disturbance Detector
Mho Distance, Phase (No. of Zones) 3 3 5 5
Mho Distance, Ground or Neutral Phase (No. of Zones) 3 3 5
Quadrilateral Distance, Phase (No. of Zones) 3 3 5
Quadrilateral Distance, Ground or Neutral (No. of Zones) 3 3 5
Permissive Pilot Logic
Sub-Cycle Distance
Overexcitation Protection (V/Hz)
Synchronism Check or Synchronizing
Undervoltage, Phase
Undervoltage, Auxiliary
Stator Ground (3rd Harmonic)
Sensitive Directional Power
Loss of Excitation Based on Reactive Power
Loss of Excitation Based on Impedance Element
Current Unbalance
Broken Conductor Detection
IOC, Negative Sequence
TOC, Negative Sequence
Current Directional, Negative Sequence
Reverse Phase Sequence Voltage
Thermal Model
Inadvertent/Accidental Energization
End of Fault Protection
Motor Mechanical Jam
Motor Start Supervision
Motor Acceleration Time
User Programmable Curves
Breaker Failure Logic Logic Logic Logic Logic
IOC, Phase
IOC, Ground
IOC, Neutral
IOC, Sensitive Ground
High Impedance Fault Detection
TOC, Phase
TOC, Ground
TOC, Neutral
TOC, Sensitive Ground
TOC, Voltage Restrained
Overvoltage, Phase
Overvoltage, Auxiliary
Overvoltage, Neutral
Negative Sequence Overvoltage
100% Stator Ground Protection
Current Directional, Phase
Current Directional, Neutral
Current Directional, Negative Sequence
Power Swing Blocking
Out-of-Step Tripping
AC Reclosing (No. of Shots) 4 4 4 4 4
Switch on to Fault (Line Pickup)
Voltage Transformer Fuse Failure
Current Transformer Supervision
Load Encroachment Logic
Underfrequency
Overfrequency
Anti-Islanding Protection/Frequency Rate of Change
Lockout Functionality
Bus Differential
Line Current Differential
Ground Differential
Stator Differential
Transformer Differential
Line Phase Comparison
Voltage Differential
Capacitor Bank Overvoltage
Neutral Voltage Unbalance
Automatic Voltage Regulation
Time of Day Control
Instantaneous Differential
Split Phase Protection
Line Current Differential Trip Logic
CT Failure

GEDigitalEnergy.com 13
UR & URPlus Family

UR Technical Specifications
PROTECTION PROTECTION PROTECTION
100% STATOR GROUND BREAKER FAILURE Timing accuracy: 3% or 4 ms, whichever is greater
Operating quantity: V_neutral_3rd/(V_neutral_3rd + Mode: 1-pole, 3-pole Current supervision:
V_zero_3rd) Current supervision: phase, neutral current Level: neutral current (3I_0)
Pickup level: 0.000 to 0.250 pu in steps of 0.001 Current supv. 0.02 to 30.000 pu in steps of 0.001 Pickup: 0.050 to 30.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup pickup: Dropout: 97 to 98%
Level accuracy: 2% of reading from 1 to 120 V Current supv. 97 to 98% of pickup Memory duration: 5 to 25 cycles in steps of 1
Pickup delay: 0 to 600.00 s in steps of 0.01 dropout: Voltage supervision 0 to 5.000 pu in steps of 0.001
3rd harmonic 0.0010 to 0.1000 pu in steps of 0.0001 Current supv. accuracy: pickup (series
supervision level: 0.1 to 2.0 CT 0.75% of reading or 2% of rated compensation
Family Overview

Time accuracy: 3% or 20 ms, whichever is greater rating: (whichever is greater) applications):


Operate time: < 30 ms at 1.10 Pickup at 60 Hz above 2 CT rating: 2.5% of reading Operation time: 1 to 1.5 cycles (typical)
ACCELERATION TIME BREAKER FLASHOVER Reset time: 1 power cycle (typical)
Acceleration 1.00 to 10.00 FLA in steps of 0.01 Operating quantity: Phase current, voltage and voltage GROUND DISTANCE OPERATING TIME CURVES
current: difference The operating times are response times of a microprocessor
Acceleration time: 0.00 to 180.00 s in steps of 0.01 Pickup level voltage: 0.02 to 1.500 pu in steps of 0.001 part of the relay. See output contacts specifications for
Operating mode: Definite Time, Adaptive Dropout level 97 to 98% of pickup estimation of the total response time for a particular
ACCIDENTAL ENERGIZATION voltage: application. The operating times are average times including
Operating condition: Overcurrent Pickup level current: 0.004 to 1.500 pu in steps of 0.001 variables such as fault inception angle or type of a voltage
Arming condition: Undervoltage and/or Machine Offline Dropout level 97 to 98% of pickup source (magnetic VTs and CVTs).
Overcurrent: current: 30

Pickup level: 0.02 to 3.000 pu in steps of 0.001 Level accuracy: 0.5% or 0.1% of rated, whichever 29

Dropout level: 97 to 98% of pickup is greater 28


27

Level accuracy: 0.5% of reading from 0.1 to 2.0 Pickup delay: 0 to 65.535 s in steps of 0.001 26

Time accuracy: 3% or 42 ms, whichever is greater


25
CT rating 24

Undervoltage: Operate time: <42 ms at 1.10 pickup at 60 Hz 23

BUS DIFFERENTIAL (87B)


22

Operate Time (ms)


Pickup level: 0.004 to 3.000 pu in steps of 0.001 21
SIR=0.1
SIR=1
Dropout level: 102 to 103% of pickup Pickup level: 0.050 to 6.000 pu in steps of 0.001 20
SIR=10

Low slope: 15 to 100% in steps of 1


19
Level accuracy: 0.5% of reading 10 to 208 V 18
SIR=20

Operate Time: < 30 ms at 1.10 Pickup at 60 Hz High slope: 50 to 100% in steps of 1 17


16
SIR=30
SIR=60
AUTORECLOSURE C60/D60/L90/L60 Low breakpoint: 1.00 to 30.00 pu in steps of 0.01 15

Two breakers applications High breakpoint: 1.00 to 30.00 pu in steps of 0.01 14


13
Single- and three-pole tripping schemes High set level: 0.10 to 99.99 pu in steps of 0.01 12

Up to 4 reclose attempts before lockout Dropout level: 97 to 98% of Pickup 11


10
Selectable reclosing mode and breaker sequence Level accuracy: 0 20 40 60 70 80

0.1 to 2.0 CT 0.5% of reading or 1% of rated


Fault Location (%)
AUTORECLOSURE F60/F35/D30
Single breaker applications, 3-pole tripping schemes rating: (whichever is greater) LINE CURRENT DIFFERENTIAL (87L)
Up to 4 reclose attempts before lockout >2.0 CT rating 1.5% of reading Application: 2 or 3 terminal line, series
Independent dead time setting before each shot Operating time: one power system cycle (typical) compensated line, tapped line, with
Possibility of changing protection settings after each shot with CT TROUBLE charging current compensation
FlexLogic. Responding to: Differential current Pickup current level: 0.20 to 4.00 pu in steps of 0.01
AMP UNBALANCE Pickup level: 0.020 to 2.000 pu in steps of 0.001 CT Tap (CT mismatch 0.20 to 5.00 in steps of 0.01
Avg and Full Load RMS Pickup delay: 1.0 to 60.0 sec. in steps of 0.1 factor):
amps: Time Accuracy: 3% or 40ms, whichever is greater Slope # 1: 1 to 50%
I_1 and 1_2 amps: Phasor Availability: 1 per zone of protection (B90) Slope # 2: 1 to 70%
Pickup level: 0.0 to 100.0% in steps of 0.1 GENERATOR UNBALANCE Breakpoint between 0.0 to 20.0 pu in steps of 0.1
Dropout level: 97 to 98% of pickup Gen. nominal 0.000 to 1.250 pu in steps of 0.001 slopes:
Level accuracy: 0.1 current: DTT: Direct Transfer Trip (1 and 3 pole)
Pickup delay: 0.00 to 600.00 s in steps of 0.01 Stages: 2 (I2t with linear reset and definite time) remote L90
Reset delay: 0.00 to 600.00 s in steps of 0.01 Pickup level: 0.00 to 100.00% in steps of 0.01 Operating Time: 1.0 to 1.5 power cycles duration
Operate time: < 20 ms at 1.10 pickup at 60 Hz Dropout level: 97 to 98% of pickup Asymmetrical channel asymmetry up to 10ms
Timing accuracy: 3% or 20 ms, whichever is greater Level accuracy: delay compensation
AUXILIARY OVERVOLTAGE 0.1 to 2 x CT rating: 0.5% of reading or 1% of rated using GPS:
Pickup level: 0.004 to 3.000 pu in steps of 0.001 (whichever is greater) LINE CURRENT DIFFERENTIAL TRIP LOGIC
Dropout level: 97 to 98% of Pickup > 2.0 x CT rating: 1.5% of reading 87L trip: Adds security for trip decision;
Level accuracy: 0.5% of reading from 10 to 208 V Time dial (K-value): 0.00 to 100.00 in steps of 0.01 creates 1 and 3 pole trip logic
Pickup delay: 0 to 600.00 s in steps of 0.01 Pickup delay: 0.0 to 1000.0 s in steps of 0.1 DTT: Engaged Direct Transfer Trip (1 and 3
Reset delay: 0 to 600.00 s in steps of 0.01 Reset delay: 0.0 to 1000.0 s in steps of 0.1 pole) from remote L90
Timing accuracy: 3% of operate time or 4 ms Time accuracy: 3% or 20 ms, whichever is greater DD: Sensitive Disturbance Detector to
(whichever is greater) Operate time: < 50 ms at 60 Hz detect fault occurrence
Operate time: < 30 ms at 1.10 pickup at 60 Hz GROUND DISTANCE Stub bus protection: Security for ring bus and 1 breaker
AUXILIARY UNDERVOLTAGE Characteristic: Mho (memory polarized or offset) configurations
Pickup level: 0.004 to 3.000 pu in steps of 0.001 or Quad (memory polarized or non- Open pole detector: Security for sequential and evolving
Dropout level: 102 to 103% of pickup directional), selectable individually faults
Level accuracy: 0.5% of reading from 10 to 208 V per zone LINE PICKUP
Curve shapes: GE IAV Inverse, Definite Time Reactance negative-sequence or zero-sequence Phase IOC: 0.02 to 30.000 pu
Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01 polarization: current Undervoltage pickup: 0.004 to 3.000 pu
Timing accuracy: 3% of operate time or 4 ms Non-homogeneity -40 to 40 in steps of 1 Overvoltage delay: 0.000 to 65.535 s
(whichever is greater) angle: LOAD ENCROACHMENT
BREAKER ARCING CURRENT Number of zones: 5 Responds to: Positive-sequence quantities
Principle: Accumulates breaker duty (I2t) and Directionality: Forward, Reverse, or Non-Directional Minimum voltage: 0.004 to 3.000 pu in steps of 0.001
measures fault duration per zone Reach (sec. W): 0.02 to 250.00 in steps of 0.01
Initiation: Programmable per phase from any Reach (secondary 0.02 to 250.00 in steps of 0.01 Impedance accuracy: 5%
FlexLogic operand W): Angle: 5 to 50 in steps of 1
Compensation for 0 to 65.535 s in steps of 0.001 Reach accuracy: 5% including the effect of CVT Angle accuracy: 2
auxiliary relays: transients up to an SIR of 30 Pickup delay: 0 to 65.535 s in steps of 0.001
Alarm threshold: 0 to 50000 kA2-cycle in steps of 1 Distance 30 to 90 in steps of 1 Reset delay: 0 to 65.535 s in steps of 0.001
Fault duration 0.25 of a power cycle characteristic angle: Time accuracy: 3% or 4 ms, whichever is greater
accuracy: Distance 30 to 90 in steps of 1 Operate time: < 30 ms at 60 Hz
Availability: 1 per CT bank with a minimum of 2 comparator limit LOSS OF EXCITATION
angle: Operating condition: Positive-sequence impedance
Directional supervision Characteristic: 2 independent offset mho circles
Characteristic angle: 30 to 90 in steps of 1 Center: 0.10 to 300.0 (sec.) in steps of 0.01
Limit angle: 30 to 90 in steps of 1 Radius: 0.10 to 300.0. (sec.) in steps of 0.01
Zero-sequence compensation Reach accuracy: 3%
Z0/Z1 magnitude: 0.00 to 10.00 in steps of 0.01 Undervoltage supervision
Z0/Z1 angle: -90 to 90 in steps of 1 Level: 0.000 to 1.250 pu in steps of 0.001
Zero-sequence mutual compensation Accuracy: 0.5% of reading from 10 to 208V
Z0M/Z1 magnitude: 0.00 to 7.00 in steps of 0.01 Pickup delay: 0 to 65.535 s in steps of 0.001
Z0M/Z1 angle: -90 to 90 in steps of 1 Timing accuracy: 3% or 20 ms, whichever is greater
Right blinder (Quad only): Operate time: <50 ms
Reach: 0.02 to 500 in steps of 0.01
Characteristic angle: 60 to 90 in steps of 1
Left blinder (Quad only):
Reach: 0.02 to 500 in steps of 0.01
Characteristic angle: 60 to 90 in steps of 1
Time delay: 0.000 to 65.535 s in steps of 0.001

14 GEDigitalEnergy.com
UR & URPlus Family

UR Technical Specifications
PROTECTION PROTECTION PROTECTION
MECHANICAL JAM OPEN POLE DETECTOR Memory duration: 5 to 25 cycles in steps of 1
Operating condition: Phase overcurrent Detects an open pole condition, monitoring breaker auxiliary VT location: all delta-wye and wye-delta
Arming condition: Motor not starting contacts, the current in each phase and optional voltages on transformers
Pickup level: 1.00 to 10.00 FLA in steps of 0.01 the line CT location: all delta-wye and wye-delta
Dropout level: 97 to 98% of pickup Current pickup level: 0.02 to 30.000 pu in steps of 0.001 transformers
Level accuracy: at 0.1 to 2.0 CT: 0.5% of reading Line capacitive 300.0 to 9999.9 sec. W in steps of 0.1 Voltage supervision 0 to 5.000 pu in steps of 0.001
at > 2.0 CT rating: 1.5% of reading reactances (XC1, pickup (series
Pickup delay: 0.10 to 600.00 s in steps of 0.01 XC0): compensation
Reset delay: 0.00 to 600.00 s in steps of 0.01 Remote current 0.02 to 30.000 pu in steps of 0.001 applications):
pickup level: PHASE DISTANCE OPERATING TIME CURVES

Family Overview
Time accuracy: 3% or 20 ms, whichever is greater
MOTOR START SUPERVISION Current dropout Pickup + 3%, not less than 0.05 pu The operating times are response times of a microprocessor
Maximum no. of 1 to 16 in steps of 1 level: part of the relay. See output contacts specifications for
starts: OVERFREQUENCY estimation of the total response time for a particular
Monitored time 1 to 300 minutes in steps of 1 Pickup level: 20.00 to 65.00 Hz in steps of 0.01 application. The operating times are average times including
interval: Dropout level: Pickup - 0.03 Hz variables such as fault inception angle or type of a voltage
Time between starts: 0 to 300 minutes in steps of 1 Level accuracy: 0.01 Hz source (magnetic VTs and CVTs).
Restart delay: 0 to 50000seconds in steps of 1 Time delay: 0 to 65.535 s in steps of 0.001 30
NEGATIVE SEQUENCE DIRECTIONAL OC Timer accuracy: 3% or 4 ms, whichever is greater 29

Directionality: Co-existing forward and reverse PHASE COMPARISON PROTECTION (87PC) 28

Polarizing: Voltage Signal Selection: Mixed I_2 - K x I_1 (K=0.00 to 0.25 in 27


26
Polarizing voltage: V_2 steps of 0.01, or3I_0) 25

Operating current: I_2 or I_0 Angle Reference: 0 to 360 leading in steps of 1 24


23
Level sensing: Fault detector low:

Operate Time (ms)


22 SIR=0.1
Zero-sequence: |I_0| - K |I_1| Instantaneous 0.02 to 15.00 pu in steps of 0.01 21
SIR=1

Negative-sequence: |I_2| - K |I_1| Overcurrent: 20


19
SIR=10

Restraint, K: 0.000 to 0.500 in steps of 0.001 I2 x Z - V2: 0.005 to 15.00 pu in steps of 0.01 18
SIR=20

Characteristic angle: 0 to 90 in steps of 1 dI2 / dt: 0.01 to 5.00 pu in steps of 0.01 17 SIR=30
SIR=60
dI1 / dt: 0.01 to 5.00 pu in steps of 0.01
16
Limit angle: 40 to 90 in steps of 1, independent for 15

forward and reverse Fault detector High: 14

Angle accuracy: 2 Instantaneous 0.10 to 15.00 pu in steps of 0.01 13


12
Offset impedance: 0.00 to 250.00W in steps of 0.01 Overcurrent: 11

Pickup level: 0.05 to 30.00 pu in steps of 0.01 I2 x Z - V2: 0.005 to 15.00 pu in steps of 0.01 10
0 20 40 60 70 80
Dropout level: 97 to 98% dI2 / dt: 0.01 to 5.00 pu in steps of 0.01 Fault Location (%)

Operation time: < 16 ms at 3 Pickup at 60 Hz dI1 / dt: 0.01 to 5.00 pu in steps of 0.01
NEGATIVE SEQUENCE IOC Signal Symmetry PHASE/NEUTRAL/GROUND IOC
Current: Phasor Adjustment: -0.5 to 5.0 ms in steps of 0.1 Pickup level: 0.02 to 30.000 pu in steps of 0.001
Pickup level: 0.02 to 30.000 pu in steps of 0.001 Channel Delay 0.000 to 30.00 ms in steps of 0.001 Dropout level: 97 to 98% of pickup
Dropout level: 97 to 98% of Pickup Adjustment: Level accuracy:
Level accuracy: Channel channel delay and signal symmetry 0.1 to 2.0 CT 0.5% of reading or 1% of rated
0.1 to 2.0 CT 0.5% of reading or 1% of rated Adjustments: compensation rating: (whichever is greater)
rating: (whichever is greater)> 2.0 CT rating: Operate Time 3/4 cycle for single phase comparison > 2.0 CT rating: 1.5% of reading
1.5% of reading (Typical): Overreach: <2%
Overreach: < 2% Trip Security: First coincidence or enhanced Pickup delay: 0.00 to 600.00 s in steps of 0.01
Pickup delay: 0.00 to 600.00 s in steps of 0.01 Second Coincidence 10 to 200 ms in steps of 1 Reset delay: 0.00 to 600.00 s in steps of 0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01 Timer: Operate time: <16ms at 3 pickup at 60Hz (Phase/
Operate time: < 20 ms at 3 Pickup at 60 Hz Enhanced Stability 40 to 180 in steps of 1 Ground IOC) <20ms at 3 pickup at
Timing accuracy: Operate at 1.5 Pickup 3% or 4 ms Angle: 60Hz (Neutral IOC)
(whichever is greater) PHASE DIRECTIONAL OVERCURRENT Timing accuracy: Operate at 1.5 Pickup 3% or 4 ms
NEGATIVE SEQUENCE OVERVOLTAGE Relay connection: 90 (quadrature) (whichever is greater)
Pickup level: 0.004 to 1.250 pu in steps of 0.001 Quadrature voltage: PHASE/NEUTRAL/GROUND TOC
Dropout level: 97 to 98% of Pickup ABC phase seq.: phase A (VBC), phase B (VCA), Current: Phasor or RMS
Level accuracy: 0.5% of reading from 10 to 208 V phase C (VAB) Pickup level: 0.02 to 30.000 pu in steps of 0.001
Pickup delay: 0 to 600.00 s in steps of 0.01 ACB phase seq.: phase A (VCB), phase B (VAC), Dropout level: 97% to 98% of Pickup
Reset delay: 0 to 600.00 s in steps of 0.01 phase C (VBA) Level accuracy: for 0.1 to 2.0 CT: 0.5% of reading
Time accuracy: 3% or 20 ms, whichever is greater Polarizing voltage 0.004 to 3.000 pu in steps of 0.001 or 1% of rated (whichever is greater)
Operate time: < 30 ms at 1.10 Pickup at 60 Hz threshold: for > 2.0 CT: 1.5% of reading > 2.0
NEGATIVE SEQUENCE TOC Current sensitivity 0.05 pu CT rating
Current: Phasor threshold: Curve shapes: IEEE Moderately/Very/Extremely
Pickup level: 0.02 to 30.000 pu in steps of 0.001 Characteristic angle: 0 to 359 in steps of 1 Inverse; IEC (and BS) A/B/C and Short
Dropout level: 97% to 98% of Pickup Angle accuracy: 2 Inverse; GE IAC Inverse, Short/Very/
Operation time: (FlexLogic elements): Extremely Inverse; I2t; FlexCurves.
Level accuracy: 0.5% of reading or 1% of rated (programmable); Definite Time (0.01 s
(whichever is greater from 0.1 to 2.0 Tripping (reverse < 12 ms, typically
load, forward fault): base curve)
x CT rating 1.5% of reading > 2.0 x
CT rating Blocking (forward < 8 ms, typically Curve multiplier: Time Dial = 0.00 to 600.00 in steps
load, reverse fault): of 0.01
Curve shapes: IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short PHASE DISTANCE Reset type: Instantaneous/Timed (per IEEE)
Inverse; GE IAC Inverse, Short/Very/ Characteristic: Mho (memory polarized or offset) Timing accuracy: Operate at > 1.03 actual Pickup
Extremely Inverse; I2t; FlexCurves. or Quad (memory polarized or non- 3.5% of operate time or cycle
(programmable); Definite Time (0.01 s directional), selectable individually (whichever is greater)
base curve) per zone PHASE OVERVOLTAGE
Curve multiplier 0.00 to 600.00 in steps of 0.01 Number of zones: Up to 5 Voltage: Phasor only
(Time dial): Directionality: Forward, Reverse, or Non-Directional Pickup level: 0.004 to 3.000 pu in steps of 0.001
Reset type: Instantaneous/Timed (per IEEE) and per zone Dropout level: 97 to 98% of Pickup
L ear Reach (secondary W): 0.02 to 250.00 in steps of 0.01 Level accuracy: 0.5% of reading from 10 to 208V
Timing accuracy: Operate at > 1.03 Actual Pickup Reach accuracy: 5% including the effect of CVT Pickup delay: 0.00 to 600.00 in steps of 0.01 s
3.5% of operate time or cycle transients up to an SIR of 30 Operate time: < 30 ms at 1.10 Pickup at 60 Hz
(whichever is greater) Distance: Timing accuracy: 3% or 4 ms (whichever is greater)
NEUTRAL DIRECTIONAL OVERCURRENT Characteristic angle: 30 to 90 in steps of 1 PHASE UNDERVOLTAGE
Directionality: Co-existing forward and reverse Comparator limit 30 to 90 in steps of 1 Voltage: Phasor only
Polarizing: Voltage, Current, Dual, Dual-I, Dual-V angle: Pickup level: 0.004 to 3.000 pu in steps of 0.001
Polarizing voltage: V_0 or VX Directional supervision: Dropout level: 102 to 103% of Pickup
Polarizing current: IG Characteristic angle: 30 to 90 in steps of 1 Level accuracy: 0.5% of reading from 10 to 208V
Operating current: I_0 Limit angle: 30 to 90 in steps of 1 Curve shapes: GE IAV Inverse; Definite Time (0.1s
Level sensing: 3 (|I_0| - K |I_1|), IG Right blinder (Quad only): base curve)
Restraint, K: 0.000 to 0.500 in steps of 0.001 Reach: 0.02 to 500 in steps of 0.01 Curve multiplier: Time Dial = 0.00 to 600.00 in steps
Characteristic angle: -90 to 90 in steps of 1 Characteristic angle: 60 to 90 in steps of 1 of 0.01
Limit angle: 40 to 90 in steps of 1, independent for Left Blinder (Quad only): Timing accuracy: Operate at < 0.90 Pickup 3.5% of
forward and reverse Reach: 0.02 to 500 in steps of 0.01 operate time or 4 ms (whichever is
Angle accuracy: 2 Characteristic angle: 60 to 90 in steps of 1 greater)
Offset impedance: 0.00 to 250.00W in steps of 0.01 Time delay: 0.000 to 65.535 s in steps of 0.001 PILOT-AIDED SCHEMES
Pickup level: 0.05 to 30.00 pu in steps of 0.01 Timing accuracy: 3% or 4 ms, whichever is greater Direct Underreaching Transfer Trip (DUTT)
Dropout level: 97 to 98% Current supervision: Permissive Underreaching Transfer Trip (PUTT)
Operation time: < 16 ms at 3 Pickup at 60 Hz Level: line-to-line current Permissive Overreaching Transfer Trip (POTT)
NEUTRAL OVERVOLTAGE Pickup: 0.050 to 30.000 pu in steps of 0.001 Hybrid POTT Scheme
Pickup level: 0.004 to 3.000 pu in steps of 0.001 Dropout: 97 to 98% Directional Comparison Blocking Scheme
Polarizing: Voltage, Current, Dual, Dual-I, Dual-V Customizable version of the POTT and DCB schemes (POTT1
Level accuracy: 0.5% of reading from 10 to 208 V and DCB1)
Pickup delay: 0.00 to 600.00 s in steps of 0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01
Timing accuracy: 3% or 20 ms (whichever is greater)
Operate time: < 30 ms at 1.10 Pickup at 60 Hz

GEDigitalEnergy.com 15
UR & URPlus Family

UR Technical Specifications
PROTECTION PROTECTION PROTECTION
POWER SWING DETECT THERMAL MODEL TRIP OUTPUT
Functions: Power swing block, Out-of-step trip Thermal overload Standard curve, FlexCurve, Collects trip and reclose input requests and issues outputs to
Characteristic: Mho or Quad curves: voltage dependent curve control tripping and reclosing.
Measured impedance: Positive-sequence Standard Curve Time 0.00 to 600.00 in steps of 0.01 Communications timer 0 to 65535 s in steps of 0.001
Blocking / tripping 2-step or 3-step Multiplier: delay:
mozes: Thermal Overload pu = overload factor x FLA Evolving fault timer: 0.000 to 65.535 s in steps of 0.001
Tripping mode: Early or Delayed Pickup: Timing accuracy: 3% or 4 ms, whichever is greater
Current supervision: Overload (OF): 1.00 to 1.50 in steps of 0.001 UNDERFREQUENCY
Pickup level: 0.050 to 30.000 pu in steps of 0.001 Standard Overload Minimum signal: 0.10 to 1.25 pu in steps of 0.01
Family Overview

Dropout level: 97 to 98% of Pickup Curve: Pickup level: 20.00 to 65.00 Hz in steps of 0.01
Fwd / reverse reach 0.10 to 500.00W in steps of 0.01 trip time = Dropout level: Pickup + 0.03 Hz
(sec. W): TD x 2.2116623 Level accuracy: 0.01 Hz
Left and right blinders 0.10 to 500.00W in steps of 0.01 Time delay: 0 to 65.535 s in steps of 0.001
(sec. W): 2 Timer accuracy: 3% or 4 ms, whichever is greater
( )
Imotor Imotor
Impedance accuracy: 5% 0.02530337 x + 0.05054758 x VOLTS PER HERTZ
Fwd / reverse angle 40 to 90 in steps of 1 OF x FLA OF x FLA Voltage: Phasor only
impedances: Pickup level: 0.80 to 4.00 in steps of 0.01 pu V/Hz
Angle accuracy: 2 Motor Rated Voltage: 1 to 50000 V in steps of 1 Dropout level: 97 to 98% of Pickup
Characteristic limit 40 to 140 in steps of 1 Thermal Motor Current unbalance, RTDs Level accuracy: 0.02 pu
angles: Biasing: Timing curves: Definite Time; Inverse A, B, and C,
Timers: 0.000 to 65.535 s in steps of 0.001 Thermal Model 1 power cycle FlexCurves. A, B, C, and D
Timing accuracy: 3% or 4 ms, whichever is greater Update Rate: TD Multiplier: 0.05 to 600.00 s in steps of 0.01
RATE OF CHANGE OF FREQUENCY Stopped/Running 1 to 65000 min. in steps of 1 Reset delay: 0.0 to 1000.0 s in steps of 0.1
df/dt trend: increasing, decreasing, Time Cool Constants: Timing accuracy: 3% or 4 ms (whichever is greater)
bi-directional Stopped/Running Exponential VT FUSE FAIL
df/dt pickup level: 0.10 to 15.00 Hz/s in steps of 0.01 Time Cool Constants Monitored parameters: V_2, V_1, I_1
df/dt dropout level: 96% of pickup Decay: WATTMETRIC ZERO-SEQUENCE DIRECTIONAL
df/dt level accuracy: 80 mHz/s or 3.5%, whichever is greater Hot/Cold Safe Stall 0.01 to 1.00 in steps of 0.01 Measured Power Zero-Sequence
Overvoltage supv.: 0.02 to 3.000 pu in steps of 0.001 Ratio: Number of Elements: 2
Overcurrent supv.: 0.000 to 30.000 pu in steps of 0.001 Current Accuracy: Per phase current inputs Characteristic Angle: 0 to 360 in steps of 1
Pickup delay: 0 to 65.535 s in steps of 0.001 Current Source: True RMS Minimum Power: 0.001 to 1.20pu in steps of 0.001
Reset delay: 0 to 65.535 s in steps of 0.001 Timing Accuracy 100 ms or 2% whichever is greater Pickup Level Accuracy: 1% or 0.0025 pu, whichever is
Time accuracy: 3% or 4 ms, whichever is greater Timing Accuracy for 100 ms or 4%, whichever is greater greater
95% settling time for < 24 cycles Voltage Dependent Pickup Delay: Definite time (0 to 600.00 s in steps
df/dt: Overload: of 0.01), inverse time, or FlexCurve
Operate time: THIRD HARMONIC NEUTRAL UNDERVOLTAGE Inverse Time Multiplier: 0.01 to 2.00 s in steps of 0.01
at 2 pickup: 12 cycles Operating quantity: 3rd harmonic of auxiliary undervoltage Time Accuracy: 3% or 8 ms, whichever is greater
at 3 pickup: 8 cycles Undervoltage: Operate Time: <30 ms at 60 Hz
at 5 pickup: 6 cycles Pickup level: 0.001 to 3.000 pu in steps of 0.001
RESTRICTED GROUND FAULT Dropout level: 102 to 103% of pickup
Pickup: 0.000 to 30.000 pu in steps of 0.001 Accuracy: 2% of reading from 1 to 120V
Dropout: 97 to 98% of Pickup Power: MONITORING
Slope: 0 to 100% in steps of 1% Pickup level: 0.000 to 1.200 pu in steps of 0.001 DATA LOGGER
Pickup delay: 0 to 600.00 s in steps of 0.01 Dropout level: 97 to 98% of pickup Number of channels: 1 to 16
Dropout delay: 0 to 600.00 s in steps of 0.01 Accuracy: 5% or 0.01 pu, whichever is greater Parameters: Any available analog actual value
Operate time: < 1power system cycle Undervoltage Inhibit Sampling rate: 15 to 3600000 ms in steps of 1
SENSITIVE DIRECTIONAL POWER Level: 0.000 to 3.000 pu in steps of 0.001 pu Trigger: Any FlexLogic operand
Measured power: 3-phase, true RMS Accuracy: 0.5% of reading from 10 to 208V Mode: Continuous or Triggered
Number of stages: 2 Pickup delay: 0 to 600.00 s in steps of 0.01 Storage capacity: (NN is dependent on memory)
Characteristic angle: 0 to 359 in steps of 1 Time accuracy: 3% or 20 ms, whichever is greater 1-second rate: 01 channel for NN days
Calibration angle: 0.00 to 0.95 in steps of 0.05 Operate time: < 30 ms at 1.10 pickup at 60 Hz 16 channels for NN days
Minimum power: -1.200 to 1.200 pu in steps of 0.001 TRANSFORMER AGING FACTOR 60-minute rate: 01 channel for NN days
Pickup level accuracy: 1% or 0.001 pu, whichever is greater Operating quantity: computed aging accelaration factor 16 channels for NN days
Hysteresis: 2% or 0.001 pu, whichever is greater (pu) EVENT RECORDER
Pickup delay: 0 to 600.00 s in steps of 0.01 Pickup level: 1 to 10 pu in steps of 0.1 Capacity: 1024 events
Time accuracy: 3% or 4 ms, whichever is greater Pickup delay: 0 to 30000 min. in steps of 1 Time-tag: to 1 microsecond
Operate time: 50 ms TRANSFORMERINSTANTANEOUS DIFFERENTIAL Triggers: Any element pickup, dropout or
SPLIT PHASE PROTECTION Pickup level: 2.00 to 30.00 pu in steps of 0.01 operate Digital input change of state
Operating quantity: split phast CT current biased by Dropout level: 97 to 98% of pickup Digital output change of state Self-
generator load current test events
Level accuracy: 0.5% of reading or 1% of rated
Pickup level: 0.000 to 1.500 pu in steps of 0.001 (whichever is greater) Data storage: In non-volatile memory
Dropout level: 97 to 98% of pickup Operate time: < 20 ms at 3 pickup at 60 Hz FAULT LOCATOR
Level accuracy: 0.5% of reading or 1% of rated TRANSFORMER HOTTEST-SPOT TEMPERATURE Method: Single-ended
Pickup delay: 0.000 to 65.535 s in steps of 0.001 Operating quantity: computed temperature in C Maximum accuracy if: Fault resistance is zero or fault
Time accuracy: 3% of cycles, whichever is greater Pickup level: 50 to 300C in steps of 1 currents from all line terminals are
Operate time: < 5 cycles at 1.10 x pickup at 60Hz in phase
Dropout level: 1C below pickup
STATOR DIFFERENTIAL Relay accuracy: 1.5% (V > 10 V, I > 0.1 pu)
Pickup delay: 0 to 30000 min. in steps of 1
Pickup: 0.050 to 1.00 pu in steps of 0.01 Worst-case accuracy:
TRANSFORMER LOSS OF LIFE
Slope 1/2: 1 to 100% in steps of 1 VT%error + (user data)
Operating quantity: computed accumulated transformer
Break 1: 1.00 to 1.50 pu in steps of 0.01 loss of life, in hours CT%error + (user data)
Break 2: 1.50 to 30.00 pu in steps of 0.01 Pickup level: 0 to 500000 hours in steps of 1 ZLine%error + (user data)
Level accuracy: 2% TRANSFORMER PERCENT DIFFERENTIAL METHOD%error + (Chapter 6)
SYNCHROCHECK Characteristic: Differential Restraint pre-set RELAY ACCURACY%error + (1.5%)
Max voltage 0 to 400000 V in steps of 1 Number of zones: 2 HIGH-IMPEDANCE FAULT DETECTION (HIZ)
difference: Minimum pickup: 0.05 to 1.00 pu in steps of 0.001 Detections: Arc Suspected, Arc Detected, Downed
Max angle difference: 0 to 100 in steps of 1 Conductor, Phase Identification
Slope 1 range: 15 to 100% in steps of 1%
Max freq. difference: 0.00 to 2.00 Hz in steps of 0.01 OSCILLOGRAPHY
Slope 2 range: 50 to 100% in steps of 1%
Hysteresis for max. 0.00 to 0.10 Hz in steps of 0.01 Maximum records: 64
Kneepoint 1: 1.0 to 2.0 pu in steps of 0.0001
freq. diff.: Sampling rate: 64 samples per power cycle
Kneepoint 2: 2.0 to 30.0 pu in steps of 0.0001
Dead source function: None, LV1 & DV2, DV1 & LV2, DV1 or Triggers: Any element pickup, dropout or
2nd harmonic inhibit 1.0 to 40.0% in steps of 0.1 operate
DV2, DV1 xor DV2, DV1 & DV2 (L = Live, level:
D = Dead) Digital input change of state
2nd harmonic inhibit Adaptive, Traditional, Disabled
Freq. Slip Maximun dF: 0.10 to 2.00 in steps of 0.01 Hz function: Digital output change of state
Freq. Slip Minimun dF: 0.01 to 1.00 in steps of 0.01 Hz 2nd harmonic inhibit Per-phase, 2-out-of-3, Average Any FlexLogic Operand
Freq. Slip Close 0.010 to 0.500 in steps of 0.001 s mode: FlexLogic Equation
Breaker Time: 5th harmonic inhibit 1.0 to 40.0% in steps of 0.1 Data: AC input channels
range: Element state
Operate times: Digital input state
Harmonic inhibits 20 to 30 ms Digital output state
selected: Data storage: In non-volatile memory
No harmonic inhibits 5 to 20 ms USER-PROGRAMMABLE FAULT REPORT
selected: Number of elements: 2
Dropout level: 97 to 98% of pickup Pre-fault trigger: any FlexLogic. operand
Level accuracy: 0.5% of reading or 1% of rated Fault trigger: any FlexLogic. operand
(whichever is greater) Recorder quantities: 32 (any FlexAnalog value)

16 GEDigitalEnergy.com
UR & URPlus Family

UR Technical Specifications
MONITORING USER-PROGRAMMABLE ELEMENTS INPUTS
PHASOR MEASUREMENT UNIT CONTROL PUSHBUTTONS AC CURRENT
Output format: per IEEE C37.118 standard Number of pushbuttons: 3 (standard) or 16 (optional) CT rated primary: 1 to 50000 A
Number of channels: 14 synchrophasors, 16 analogs, 16 Operation: drive FlexLogic. operands CT rated secondary: 1 A or 5 A by connection
digitals FLEXCURVES Nominal frequency: 20 to 65 Hz
TVE (total vector error): <1% Number: 4 (A through D) Relay burden: < 0.2 VA at rated secondary
Triggering: frequency, voltage, current, power, Reset points: 40 (0 through 1 of pickup) Conversion range:
rate of change of frequency, user- Operate points: 80 (1 through 20 of pickup) Standard CT: 0.02 to 46 CT rating RMS symmetrical
defined Time delay: 0 to 65535 ms in steps of 1 Sensitive Ground/HI-Z CT module:
Reporting rate: 1, 2, 5, 10, 12, 15, 20, 25, 30, 50, 60 or FLEXLOGIC 0.002 to 4.6 CT rating RMS
120 times per second symmetrical

Family Overview
Programming language: Reverse Polish Notation with
Number of clients: One over TCP/IP port, two over UDP/ graphical visualization (keypad Current withstand: 20 ms at 250 times rated
IP ports programmable) 1 sec. at 100 times rated
TAC ranges: As indicated in appropriate Lines of code: 1024 continuous at 3 times rated
specifications sections Internal variables: 64 continuous 4xInom; URs equipped
Network reporting 16-bit integer or 32-bit IEEE floating Supported operations: NOT, XOR, OR (2 to 16 inputs), with 24 CT inputs have a maximum
format: point numbers AND (2 operating temp. of 50C
Network reporting Rectangular (real and imaginary) to 16 inputs), NOR (2 to 16 AC VOLTAGE
style: or polar (magnitude and angle) inputs), VT rated secondary: 50.0 to 240.0 V
coordinates NAND (2 to 16 inputs), Latch VT ratio: 1.00 to 24000.00
Filtering: P and M class (Reset Dominant), Edge Nominal frequency: 20 to 65 Hz For the L90, the nominal
Calibration: Angle 5, magnitude +/-5% per Detectors, system frequency should be chosen as
phase Timers 50 Hz or 60 Hz only.
Compensation: -180 to 180 in steps of 30 (current Inputs: any logical variable, contact, or Relay burden: < 0.25 VA at 120 V
and voltage components) virtual input Conversion range: 1 to 275 V
Mode of operation: Normal and test Number of timers: 32 Voltage withstand: continuous at 260 V to neutral
PMU Recording: 46 configurable channels Pickup delay: 0 to 60000 (ms, sec., min.) in 1 min./hr at 420 V to neutral
(14 syncrophasor, 16 digital, steps of 1 CONTACT INPUTS
16 analogs) Dropout delay: 0 to 60000 (ms, sec., min.) in Dry contacts: 1000 W maximum
METERING steps of 1 Wet contacts: 300 V DC maximum
RMS CURRENT: PHASE, NEUTRAL, AND GROUND FLEXELEMENTS Selectable 17 V, 33 V, 84 V, 166 V
Accuracy at: Number of elements: 8 or 16 thresholds:
0.1 to 2.0 CT rating: 0.25% of reading or 0.1% of rated Operating signal: any analog actual value, or two Tolerance: 10%
(whichever is greater) values in Differential mode Contacts Per 4
> 2.0 CT rating: 1.0% of reading Operating signal mode: Signed or Absolute Value Common Return:
RMS VOLTAGE Operating mode: Level, Delta Recognition time: < 1 ms
Accuracy: 0.5% of reading from 10 to 208 V Comparator direction: Over, Under Debounce timer: 0.0 to 16.0 ms in steps of 0.5
REAL POWER (WATTS) Pickup Level: -30.000 to 30.000 pu in steps Continuous Current 3mA (when energized)
Accuracy: 1.0% of reading at -0.8 < PF < -1.0 of 0.001 Draw:
and 0.8 < PF < 1.0 Hysteresis: 0.1 to 50.0% in steps of 0.1 CONTACT INPUTS WITH AUTO-BURNISHING
REACTIVE POWER (VARS) Delta dt: 20 ms to 60 days Dry contacts: 1000 W maximum
Accuracy: 1.0% of reading at -0.2 < PF < 0.2 Pickup & dropout delay: 0.000 to 65.535 s in steps of Wet contacts: 300 V DC maximum
APPARENT POWER (VA) 0.001 Selectable 17 V, 33 V, 84 V, 166 V
Accuracy: 1.0% of reading FLEXSTATES thresholds:
WATT-HOURS (POSITIVE AND NEGATIVE) Number: up to 256 logical variables Tolerance: 10%
Accuracy: 2.0% of reading grouped Contacts Per 2
Range: 0 to 2 109 MWh under 16 Modbus addresses Common Return:
Parameters: 3-phase only Programmability: any logical variable, contact, or Recognition time: < 1 ms
Update rate: 50 ms virtual input Debounce timer: 0.0 to 16.0 ms in steps of 0.5
VAR-HOURS (POSITIVE AND NEGATIVE) LED TEST Continuous Current 3mA (when energized)
Accuracy: 2.0% of reading Initiation: from any digital input or user- Draw:
Range: 0 to 2 109 Mvarh programmable condition Auto-Burnish Impulse 50 to 70 mA
Parameters: 3-phase only Number of tests: 3, interruptible at any time Current:
Update rate: 50 ms Duration of full test: approximately 3 minutes Duration of Auto- 25 to 50 ms
CURRENT HARMONICS Test sequence 1: all LEDs on Burnish Impulse:
Harmonics: 2nd to 25th harmonic: per phase, Test sequence 2: all LEDs off, one LED at a time DCMA INPUTS
displayed as a % of f1 (fundamental on for 1 s Current input (mA 0 to -1, 0 to +1, -1 to +1, 0 to 5, 0 to 10,
frequency phasor) THD: per phase, Test sequence 3: all LEDs on, one LED at a time DC): 0 to 20, 4 to 20 (programmable)
displayed as a % of f1 off for 1 s Input impedance: 379 10%
Accuracy: NON-VOLATILE LATCHES Conversion range: -1 to + 20 mA DC
Harmonics: 1. f1 > 0.4pu: (0.20% + 0.035% / Type: Set-dominant or Reset- Accuracy: 0.2% of full scale
harmonic) of reading or 0.15% of dominant Type: Passive
100%, whichever is greater Number: 16 (individually programmed) DIRECT INPUTS
2. f1 < 0.4pu: as above plus %error Output: Stored in non-volatile memory Number of input 32
of f1 Execution sequence: As input prior to protection, points:
THD: 1. f1 > 0.4pu: (0.25% + 0.035% / control, and FlexLogic. No. of remote 16
harmonic) of reading or 0.20% of SELECTOR SWITCH devices:
100%, whichever is greater Number of elements: 2 Default states on On, Off, Latest/Off, Latest/On
2. f1 < 0.4pu: as above plus %error Upper position limit: 1 to 7 in steps of 1 loss of comms.:
of f1 Selecting mode: Time-out or Acknowledge Ring configuration: Yes, No
DEMAND Time-out timer: 3.0 to 60.0 s in steps of 0.1 Data rate: 64 or 128 kbps
Measurements: Phases A, B, and C present and Control inputs: step-up and 3-bit CRC: 32-bit
maximum measured currents Power-up mode: restore from non-volatile CRC alarm:
3-Phase Power (P, Q, and S) present memory or synchronize to a Responding to: Rate of messages failing the CRC
and maximum measured currents 3-bit control input Monitoring message 10 to 10000 in steps of 1
Accuracy: 2.0% USER-DEFINABLE DISPLAYS count:
FREQUENCY Number of displays: 16 Alarm threshold: 1 to 1000 in steps of 1
Accuracy at 0.01 Hz (when voltage signal is used Lines of display: 2 20 alphanumeric characters Unreturned message alarm:
V = 0.8 to 1.2 pu: for frequency measurement) Parameters: up to 5, any Modbus register Responding to: Rate of unreturned messages in the
I = 0.1 to 0.25 pu: 0.05 Hz addresses ring configuration
I > 0.25 pu: 0.02 Hz (when current signal is used Invoking and scrolling: keypad, or any user- Monitoring message 10 to 10000 in steps of 1
for frequency measurement) programmable condition, count:
VOLTAGE HARMONICS including pushbuttons Alarm threshold: 1 to 1000 in steps of 1
Harmonics: 2nd to 25th harmonic: per phase, USER-PROGRAMMABLE LEDS IRIG-B INPUT
displayed as a % of f1 (fundamental Number: 48 plus Trip and Alarm Amplitude 1 to 10 V pk-pk
frequency phasor) THD: per phase, Programmability: from any logical variable, modulation:
displayed as a % of f1 contact, or virtual input DC shift: TTL
Accuracy: Reset mode: Self-reset or Latched Input impedance: 22 kW
Harmonics: 1. f1 > 0.4pu: (0.20% + 0.035% / USER-PROGRAMMABLE PUSHBUTTONS (OPTIONAL) Isolation: 2 kV
harmonic) of reading or 0.15% of Number of pushbuttons: 12 REMOTE INPUTS (IEC 61850 GSSE)
100%, whichever is greater Mode: Self-Reset, Latched Number of input 32, configured from 64 incoming bit
2. f1 < 0.4pu: as above plus %error Display message: 2 lines of 20 characters each points: pairs
of f1 8-BIT SWITCH Number of remote 16
THD: 1. f1 > 0.4pu: (0.25% + 0.035% / Number of elements: 6 devices:
harmonic) of reading or 0.20% of Input signals: two 8-bit integers via FlexLogic Default states on On, Off, Latest/Off, Latest/On
100%, whichever is greater operands loss of comms.:
2. f1 < 0.4pu: as above plus %error Control: any FlexLogic operand RTD INPUTS
of f1 Response time: < 8 ms at 60 Hz, < 10 ms at 50 Hz Types (3-wire): 100 W Platinum, 100 W &
120 W Nickel, 10 W Copper
Sensing current: 5 mA
Range: -50 to +250C
Accuracy: 2C
Isolation: 36 V pk-pk

GEDigitalEnergy.com 17
UR Technical Specifications
OUTPUTS COMMUNICATIONS INTER-RELAY COMMUNICATIONS
CONTROL POWER EXTERNAL OUTPUT RS232 * Note: Typical distances listed are based on the following
(FOR DRY CONTACT INPUT) Front port: 19.2 kbps, Modbus RTU, DNP 3.0 assumptions for system loss. Actual losses will vary from one
Capacity: 100 mA DC at 48 V DC RS485 installation to another, the distance covered by your system
Isolation: 300 Vpk 1 or 2 rear ports: Up to 115 kbps, Modbus RTU, DNP may vary.
DCMA OUTPUTS 3.0 isolated together at 36 Vpk CONNECTOR LOSSES (TOTAL OF BOTH ENDS)
Range: -1 to 1 mA, 0 to 1 mA, 4 to 20 mA Typical distance: 1200 m ST connector 2dB
Max. load resistance: 12 k for -1 to 1 mA range Isolation: 2 kV FIBER LOSSES
12 k for 0 to 1 mA range ETHERNET PORT 820 nm multimode 3 dB/km
600 for 4 to 20 mA range 10Base-F: 820 nm, multi-mode, supports 1300 nm mulimode 1 dB/km
Accuracy: half-duplex/full-duplex fiber optic 1300 nm singlemode 0.35 dB/km
0.75% of full-scale for 0 to 1 mA with ST connector 1550 nm singlemode 0.25 dB/km
range Redundant 10Base-F: 820 nm, multi-mode, half-duplex/ Splice losses: One splice every 2 km, at 0.05 dB
0.5% of full-scale for -1 to 1 mA full-duplex fiber optic with ST loss per splice
range connector SYSTEM MARGIN
0.75% of full-scale for 0 to 20 mA 10Base-T: RJ45 connector 3 dB additional loss added to calculations to compensate for
range Power budget: 10 dB all other losses.
99% Settling time to a 100 ms Max optical input power: -7.6 dBm Compensate difference in transmitting and receiving (channel
step change: Max optical output asymmetry) channel delays using GPS satellite clock: 10 ms
Isolation: 1.5 kV power: -20 dBm
Driving signal: any FlexAnalog quantity Receiver sensitivity: -30 dBm POWER SUPPLY
Upper & lower limit for -90 to 90 pu in steps of 0.001 Typical distance: 1.65 km LOW RANGE
the driving signal: SNTP clock Nominal DC voltage: 24 to 48 V at 3 A
DIRECT OUTPUTS synchronization error: <10 ms (typical) Min/max DC voltage: 20 / 60 V
Output points: 32 PROTOCOLS * NOTE: Low range is DC only.
FORM-A CURRENT MONITOR HIGH RANGE
Threshold current: approx. 80 to 100 mA RS232 RS485 10BaseF 10BaseT 100BaseT
Nominal DC voltage: 125 to 250 V at 0.7 A
FORM-A RELAY IEC 61850 Min/max DC voltage: 88 / 300 V
Make & carry for 0.2s: 30 A as per ANSI C37.90 DNP 3.0 Nominal AC voltage: 100 to 240 V at 50/60 Hz, 0.7 A
Carry continuous: 6A Modbus Min/max AC voltage: 88 / 265 V at 25 to 100 Hz
Break at L/R of 40 ms: 1 A DC max. at 24 V IEC104 ALL RANGES
0.5 A DC max. at 48 V Volt withstand: 2 Highest Nominal Voltage for 10 ms
0.3 A DC max. at 125 V EGD Voltage loss hold-up: 50 ms duration at nominal
0.2 A DC max. at 250 V Power consumption: Typical = 15 VA; Max. = 30 VA
Operate time: < 4 ms INTER-RELAY COMMUNICATIONS INTERNAL FUSE
Contact material: Silver alloy SHIELDED TWISTED-PAIR INTERFACE OPTIONS RATINGS
FORM-A VOLTAGE MONITOR INTERFACE TYPE TYPICAL DISTANCE Low range power 8 A / 250 V
Applicable voltage: approx. 15 to 250 V DC RS422 1200m supply:
Trickle current: approx. 1 to 2.5 mA High range power 4 A / 250 V
G.703 100m
supply:
INPUT VOLTAGE IMPEDANCE INTERRUPTING CAPACITY
2W RESISTOR 1W RESISTOR * NOTE: RS422 distance is based on transmitter power and AC: 100 000 A RMS symmetrical
250 V DC 20 K 50K does not take into consideration the clock source provided DC: 10 000 A
by the user. Hold up time: 200 ms
120 V DC 5K 2K
48 V DC 2K 2K LINK POWER BUDGET TYPE TESTS
24 V DC 2K 2K EMITTER, TRANSMIT RECEIVED Electrical fast transient:ANSI/IEEE C37.90.1
POWER BUDGET
FIBER TYPE POWER SENSITIVITY IEC 61000-4-4
FORM-C AND CRITICAL FAILURE RELAY 820nm LED IEC 60255-22-4
Make & carry for 0.2 s: 30 A Multimode -20dBm -30dBm 10dB Oscillatory transient: ANSI/IEEE C37.90.1
Carry continuous: 8A 1300 nm LED IEC 61000-4-12
Break at L/R of 40 ms: 0.25 A DC max. at 48 V -21dBm -30dBm 9dB
Multimode Insulation resistance: IEC 60255-5
0.10 A DC max. at 125 V 1300 nm ELED Dielectric strength: IEC 60255-6
Operate time: < 8 ms -21dBm -30dBm 9dB
Multimode ANSI/IEEE C37.90
Contact material: Silver alloy 1300 nm Laser Electrostatic discharge: EN 61000-4-2
-1dBm -30dBm 29dB
FAST FORM-C RELAY Singlemode Surge immunity: EN 61000-4-5
Make & carry: 0.1 A max. (resistive load) 1550 nm Laser RFI susceptibility: ANSI/IEEE C37.90.2
+5dBm -30dBm 35dB
Minimum load impedance: Singlemode IEC 61000-4-3
Operate time: < 0.6 ms IEC 60255-22-3
Internal Limiting 100, 2 * NOTE: These power budgets are calculated from the Ontario Hydro C-5047-77
Resistor: manufacturers worst-case transmitter power and worst-case Conducted RFI: IEC 61000-4-6
IRIG-B OUTPUT receiver sensitivity. Voltage dips/interruptions/variations:
Amplitude: 10 V peak-peak RS485 level IEC 61000-4-11
Maximum load: 100 ohms MAXIMUM OPTICAL INPUT POWER
IEC 60255-11
Time delay: 1 ms for AM input EMITTED, FIBER TYPE MAX. OPTICAL INPUT POWER Power frequency magnetic field immunity:
40 s for DC-shift input IEC 61000-4-8
Isolation: 2 kV 820 nm LED, Multimode -7.6 dBm Vibration test IEC 60255-21-1
LATCHING RELAY 1300 nm LED, Multimode -11 dBm (sinusoidal):
Make & carry for 0.2 s: 30 A as per ANSI C37.90 1300 nm ELED, Singlemode -14 dBm Shock and bump: IEC 60255-21-2
Carry continuous: 6A 1300 nm Laser, Singlemode -14 dBm * NOTE: Type test report available upon
Break at L/R of 40 ms: 0.25 A DC max. 1500 nm Laser, Singlemode -14 dBm request.
Operate time: < 4 ms
Contact material: Silver alloy TYPICAL LINK DISTANCE PRODUCTION TESTS
Control: separate operate and reset inputs THERMAL
Control mode: operate-dominant or reset- CONNECTOR
EMITTED TYPE FIBER TYPE TYPICAL DISTANCE Products go through an environmental test based upon an
dominant TYPE
accepted quality level (AQL) sampling process
REMOTE OUTPUTS (IEC 61850 GSSE) 820 nm LED Multimode -7.6 dBm 1.65 km ENVIRONMENTAL
Standard output points: 32 1300 nm LED Multimode -11 dBm 3.8 km OPERATING TEMPERATURES
User output points: 32 Cold: IEC 60028-2-1, 16 h at -40C
SOLID-STATE OUTPUT RELAY 1300 nm ELED Singlemode -14 dBm 11.4 km Dry Heat: IEC 60028-2-2, 16 h at +85C
Operate & release time: <100 s 1300 nm Laser Singlemode -14 dBm 64 km OTHER
Maximum voltage: 265 V DC 1500 nm Laser Singlemode -14 dBm 105 km Humidity(noncondensing):
Maximum continuous 5 A at 45C; 4 A at 65C IEC 60068-2-30, 95%, Variant
current: 1,6days.
Make & carry for 0.2 s: as per ANSI C37.90 Altitude: Up to 2000 m
For 0.3s: 300 A Installation Category: II
Breaking capacity: APPROVALS
UTILITY UL Listed for the USA and Canada
IEC 647-5/UL508 APPLICATION INDUSTRIAL Manufactured under an ISO9000 registered system.
(AUTORECLOSE APPLICATION
SCHEME) LVD 73/23/EEC: IEC 1010-1
5000 ops 5 ops/
1 s-On, 9 s-Off .2 s-On, 10000 ops/
EMC 81/336/EEC: EN 50081-2, EN 50082-2
Operations/ 0.2 s-Off
interval 0.2 s-On,
1000 ops within 1 30 s-Off
0.5 s-On, 0.5 s-Of minute
3.2 A
Break L/R = 10 ms
capability 1.6 A 10 A 10 A IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
(0 to 250 VDC) L/R = 20 ms L/R = 40 ms L/R = 40 ms trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
0.8 A Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
L/R = 40 ms
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General Electric
Company.

GE reserves the right to make changes to specifications of products described at any time without notice
and without obligation to notify any person of such changes.
GEA-12657E(E)