B-1 CT secondary core detail - PS class Primary Current - Amp(Ipr) Secondary Current - Amp(Isr)
B-2 600 1
B-3 300 1
E-2 Internal Fault, Vk REQUIRED= 0.4x(Iint max X 1000 / Primary Current ) X ( Rct + Rb + 2 Rl' )
Rb+2Rl'= 5.6454
0.4x(If X 1000 / Primary Current )= 16.6666666667
selected knee point voltage= 20 (RCT + 10) volt
E-3 Internal Fault, Vk REQUIRED=1.6x(Iext max X 1000 / Primary Current ) X ( Rct + Rb + 2 Rl' )
Rb+2Rl'= 5.6454
1.6xIextmax / Primary Current )= 8.7476666667
selected knee point voltage= 10 (RCT + 10) volt
B-1 CT secondary core detail - Primary Current - Amp Secondary Current - Amp CLASS VA
B-2 METERING 600 1 0.2s 20
B-3 PROTECTION 600 1 5P20 20
E - CT ADEQUACY CALCULATION - VA REQUIRED = Meter Burden + Lead Burden = Meter Burden + (2 * Rl') Available Required
E-1 = Rm + ( 2 X Rl') VA VA
20 5.6454
E - CT ADEQUACY CALCULATION - VA REQUIRED = RELAY Burden + Lead Burden = RELAY Burden + (2 * Rl') Available Required
E-1 = Rr + ( 2 X Rl') VA VA
20 5.6454
REMARKS:The required burden is within 25% to 100% of available burden hence CT is suitable