Installation calculation report

New_project
Full
Page 2/54

Content

1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4

1.2 Settings for wiring device calculation............................................................................................ 4

1.3 List of loads...................................................................................................................................... 4

2 Installation general design.....................................................................................................6


2.1 List of devices.................................................................................................................................. 6

3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14

3.2 Generator circuits.......................................................................................................................... 23

3.3 LV Source circuits.......................................................................................................................... 23

3.4 UPS circuits.................................................................................................................................... 24

3.5 Capacitor bank circuits.................................................................................................................. 24

3.6 Feeder circuits................................................................................................................................ 24

3.7 LV Transformer circuits................................................................................................................. 25

3.8 Couplers circuits............................................................................................................................ 26

3.9 Generic load circuits...................................................................................................................... 27

3.10 Lighting load circuits................................................................................................................ 27

3.11 Power socket load circuits....................................................................................................... 28

3.12 Motor starter combination........................................................................................................ 28

3.13 Busbar circuits.......................................................................................................................... 29

3.14 Busbar trunking system circuits............................................................................................. 29

3.15 Busbar trunking system circuits............................................................................................. 29

3.16 Lighting Busbar trunking system circuits..............................................................................29

Project: New_project 25/05/2017


Page 3/54

1 Project description
1.1 Project general settings
Installation standard IEC60364

Calculation standard TR50480


Circuit breaker standard IEC 60947-2
Frequency 50 Hz

1.2 Settings for wiring device calculation


Maximal CSA 300 mm

1.3 List of loads

1.3.1 Lighting distribution


Name Type of lamp P Lamp (W) P ballast (W) Nb of lamp/light Nb of light
EA 13 Fluorescent 18 4.5 131 131
with
ferromagnetic
ballast
1.3.2 Motor loads
Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)
MA 12 7.97 6.61 11.5 0.83 1 3Ph No 0
MA 16 7.97 6.61 11.5 0.83 1 3Ph No 0
MA 17 7.97 6.61 11.5 0.83 1 3Ph No 0
MA 18 7.97 6.61 11.5 0.83 1 3Ph No 0
MA 19 10.7 8.91 15.5 0.83 1 3Ph No 0
MA 20 24.2 20.9 35 0.86 1 3Ph No 0
MA 24 27.7 23.8 40 0.86 1 3Ph No 0
MA 26 7.97 6.61 11.5 0.83 1 3Ph No 0
MA 27 20.1 17.3 29 0.86 1 3Ph No 0
MA 28 3.39 2.72 4.9 0.8 1 3Ph No 0
MA 29 3.39 2.72 4.9 0.8 1 3Ph No 0
MA 42 10.7 8.91 15.5 0.83 1 3Ph No 0
MA 46 5.89 4.71 8.5 0.8 1 3Ph No 0
MA 48 5.89 4.71 8.5 0.8 1 3Ph No 0
MA 49 5.89 4.71 8.5 0.8 1 3Ph No 0
MA 50 5.89 4.71 8.5 0.8 1 3Ph No 0

Project: New_project 25/05/2017


Page 4/54

2 Installation general design


2.1 List of devices

2.1.1 MV/LV transformer


Nbr Range Insulation Sr (kVA) ukrT (%) Connection U2 (V) SEA Rb
Name
(m)
TA 0 1 Trihal Dry-type 500 6 D 420 TN-S 10000

2.1.2 LV switchboards and busbar


Switchboard name Range Rating (A) IP
UC 8 No preference 0.00 Undefined
UC 15 No preference 0.00 Undefined
UC 23 No preference 0.00 Undefined
UC 45 No preference 0.00 Undefined

Busbar name Switchboard Ks Polarity SEA Equipotential bounding


name
WC 7 UC 8 1 3Ph+N TN-S With
WC 14 UC 15 1 3Ph TN-S With
WC 22 UC 23 1 3Ph TN-S With
WC 44 UC 45 1 3Ph TN-S With

2.1.3 Circuit breaker


Name Nbr Range - Rating (A) Poles Trip unit/Curve RCD RCD class
Designation
QA 0 1 Masterpact 800 4P4d Micrologic 5.0 E
NT - NT08H1
QA 12 1 Multi 9 P25M 14 3P3d M
- P25M
QA 13 1 Compact 630 4P4d Micrologic 2.3
NSX -
NSX630F
QA 16 1 Multi 9 P25M 14 3P3d M
- P25M
QA 17 1 Multi 9 P25M 14 3P3d M
- P25M
QA 18 1 Multi 9 P25M 14 3P3d M
- P25M
QA 19 1 Multi 9 P25M 18 3P3d M
- P25M
QA 20 1 Compact 100 3P3d Micrologic 2.2 M
NSX -
NSX100F
QA 21 1 Multi 9 C120 80 3P3d D
- C120H
QA 24 1 Compact 100 3P3d Micrologic 2.2 M
NSX -
NSX100F
QA 26 1 Multi 9 P25M 14 3P3d M
- P25M
QA 27 1 GV - GV2ME 32 3P3d ME32
QA 28 1 Multi 9 P25M 6.3 3P3d M
- P25M
QA 29 1 Multi 9 P25M 6.3 3P3d M

Project: New_project 25/05/2017


Page 5/54

- P25M
QA 42 1 Multi 9 P25M 18 3P3d M
- P25M
QA 43 1 Acti9 iC60 - 32 3P3d D
iC60H
QA 46 1 Multi 9 P25M 10 3P3d M
- P25M
QA 48 1 Multi 9 P25M 10 3P3d M
- P25M
QA 49 1 Multi 9 P25M 10 3P3d M
- P25M
QA 50 1 Multi 9 P25M 10 3P3d M
- P25M
QA 52 1 Multi 9 C120 80 3P3d D
- C120H

2.1.4 Switch
Name Nbr Range Rating (A) Poles RCD RCD class
QB 21 1 Acti 9 100 3P
iSW
QB 43 1 Multi 9 I 100 3P
QB 52 1 Acti 9 100 3P
iSW

2.1.5 Cable schedule

Name Nbr Incomer Feeder Type Insulation L (m) L1/L2/L3 N PE/PEN


WD 0 1 TA 0 QA 0 Multi-core XLPE 13 2x185 2x185 1x185
Copper Copper Copper
WD 43 1 QA 43 TA 43 Multi-core XLPE 7 1x2.5 1x4 Copper
Copper
WD 21 1 QA 21 TA 21 Multi-core XLPE 7 1x16 1x16
Copper Copper
WD 52 1 QA 52 QB 52 Multi-core XLPE 5 1x16 1x16
Copper Copper
WD 50 1 QA 50 MA 50 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
WD 49 1 QA 49 MA 49 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
WD 48 1 QA 48 MA 48 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
WD 46 1 QA 46 MA 46 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
WD 42 1 QA 42 MA 42 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
WD 29 1 QA 29 MA 29 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
WD 28 1 QA 28 MA 28 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
WD 27 1 QA 27 MA 27 Multi-core XLPE 5 1x2.5 1x4 Copper
Copper
WD 26 1 QA 26 MA 26 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
WD 24 1 QA 24 MA 24 Multi-core XLPE 5 1x4 Copper 1x4 Copper
WD 20 1 QA 20 MA 20 Multi-core XLPE 5 1x4 Copper 1x4 Copper
WD 19 1 QA 19 MA 19 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
WD 18 1 QA 18 MA 18 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
Project: New_project 25/05/2017
Page 6/54

WD 17 1 QA 17 MA 17 Multi-core XLPE 5 1x1.5 1x4 Copper


Copper
WD 16 1 QA 16 MA 16 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
WD 12 1 QA 12 MA 12 Multi-core XLPE 5 1x1.5 1x4 Copper
Copper
WD 13 1 QA 13 EA 13 Multi-core XLPE 1 2x150 2x150 1x150
Copper Copper Copper

2.1.6 MV Cable
Name Nbr Designation CSA (mm) Icc (A) In (A) Un (kV)
MVWD 1 NA 1 x 240 Al 21.3 418 24
0

Project: New_project 25/05/2017


Page 7/54

3 Calculation notes

3.1 Source circuits


3.1.1 Circuit Source 0
MV power supply W0
Max. upstream short circuit power 500 MVA
Min. upstream short circuit power 250 MVA
MV Cable MVWD 0
Parameters
Length 10 m
Type of cable Single core
Ib 14 A
Nb of conductor per phase 1
Cross section area 1 x 240 Al mm
Core Aluminium
Short circuit withstand 21.3 kA
Assigned voltage 20 kV
Insulation voltage 24 kV

MV/LV transformer TA 0
Range Trihal
Technology Dry-type
Rated power 500 kVA
ukrT 6%
Type of losses Normal
PkrT 5.7 kW
System earthing arrangement TN-S
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Cable WD 0
Parameters
Length 13 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 722 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Project: New_project 25/05/2017
Page 8/54

Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 0.88
Standard table reference A-52-20
User correction factor 1
Overall factor 0.88

Selected phase
Cross section area 2x185 mm
Core Copper
Iz under real conditions 803 A
Selected neutral
Cross section area 2x185 mm
Core Copper
Iz under real conditions 803 A
Selected PE
Cross section area 1x185 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 11.80 10.22 11.80 8.41 9.39 0.00 0.00

Synthesis for all operating mode


(kA) 11.80 10.22 11.80 8.41 9.39 0.00 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Circuit breaker QA 0
Ib 722 A
Distance from origin NA

Sizing Information Sized by system


Range Masterpact NT
Designation NT08H1
Circuit breaker rating 800 A
Breaking capacity 42 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.0 E
Trip unit rating 800 A
Long delay settings
Ir 736 A
Tr 24 s
Short delay settings
Isd current 5888 A
Tsd 0.08 s
Instantaneous tripping
Project: New_project 25/05/2017
Page 9/54

Ii current 9600 A

3.2 LV Transformer circuits


3.2.1 Circuit LV transformer 21
Circuit breaker QA 21
Ib 72.2 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 C120
Designation C120H
Circuit breaker rating 80 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation D
Trip unit rating 80 A
Long delay settings
Ir 80 A
Tr NA
Short delay settings
Isd current 960 A
Tsd NA
Instantaneous tripping
Ii current NA

Cable WD 21
Parameters
Length 7m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 72 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Project: New_project 25/05/2017
Page 10/54

Loaded neutral factor 1


Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x16 mm
Core Copper
Iz under real conditions 100 A
Selected PE
Cross section area 1x16 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 11.46 9.93 0.00 6.97 0.00 6.35 0.00

Synthesis for all operating mode


(kA) 11.46 9.93 0.00 6.97 0.00 6.35 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
LV/LV transformer TA 21
Type Transformer
Polarity 3Ph
Technology Dry-type
Rated power 50 kVA
ukrT 4.6 %
Type of losses Normal
PkrT 1800 W
Secondary system earthing TN-S
arrangement
Primary connection D
Secondary connection yn
No load secondary voltage Ur0 420V
Secondary voltage Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Switch QB 21
Range Acti 9 iSW
Designation iSW
Rating 100 A
Icm (making capacity) 75 kA
Icw 2.5 kA - 1 s.
Cascading with upstream circuit No
breaker
Reinforced short circuit NA
withstand
Pole 3

Design current
IL1 IL2 IL3 IN

Project: New_project 25/05/2017


Page 11/54

Operating mode Normal


(A) 72.169 72.169 72.169 0

Synthesis for all operating mode


(A) 72.169 72.169 72.169 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.589 0.284
UL1L2 (%) 0.681 0.328
UL2L3 (%) 0.681 0.328
UL3L1 (%) 0.681 0.328
UL1N (%) 0.306 0.000
UL2N (%) 0.306 0.000
UL3N (%) 0.306 0.000

3.2.2 Circuit LV transformer 43


Circuit breaker QA 43
Ib 28.9 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60H
Circuit breaker rating 32 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation D
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 384 A
Tsd NA
Instantaneous tripping
Ii current NA

Cable WD 43
Parameters
Length 7m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Project: New_project 25/05/2017
Page 12/54

Level of third harmonic THDI 0%


Ib 29 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x2.5 mm
Core Copper
Iz under real conditions 32 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 12.17 10.54 0.00 2.54 0.00 1.91 0.00

Synthesis for all operating mode


(kA) 12.17 10.54 0.00 2.54 0.00 1.91 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
LV/LV transformer TA 43
Type Transformer
Polarity 3Ph
Technology Dry-type
Rated power 20 kVA
ukrT 5.4 %
Type of losses Normal
PkrT 900 W
Secondary system earthing TN-S
arrangement
Primary connection D
Secondary connection yn
No load secondary voltage Ur0 420V
Secondary voltage Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Switch QB 43
Range Multi 9 I
Designation I
Rating 100 A
Project: New_project 25/05/2017
Page 13/54

Icm (making capacity) 1 kA


Icw 2 kA - 1 s.
Cascading with upstream circuit No
breaker
Reinforced short circuit NA
withstand
Pole 3

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 28.868 28.868 28.868 0

Synthesis for all operating mode


(A) 28.868 28.868 28.868 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.973 0.668
UL1L2 (%) 1.124 0.771
UL2L3 (%) 1.124 0.771
UL3L1 (%) 1.124 0.771
UL1N (%) 0.306 0.000
UL2N (%) 0.306 0.000
UL3N (%) 0.306 0.000

3.2.3 Circuit LV transformer 52


Circuit breaker QA 52
Ib 72.2 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 C120
Designation C120H
Circuit breaker rating 80 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation D
Trip unit rating 80 A
Long delay settings
Ir 80 A
Tr NA
Short delay settings
Isd current 960 A
Tsd NA
Instantaneous tripping
Ii current NA

Cable WD 52
Parameters
Project: New_project 25/05/2017
Page 14/54

Length 5m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 72 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x16 mm
Core Copper
Iz under real conditions 100 A
Selected PE
Cross section area 1x16 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 11.46 9.93 0.00 7.43 0.00 7.28 0.00

Synthesis for all operating mode


(kA) 11.46 9.93 0.00 7.43 0.00 7.28 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Switch QB 52
Range Acti 9 iSW
Designation iSW
Rating 100 A
Icm (making capacity) 75 kA
Icw 2.5 kA - 1 s.
Cascading with upstream circuit No
breaker
Reinforced short circuit NA
Project: New_project 25/05/2017
Page 15/54

withstand
Pole 3

LV/LV transformer TA 52
Type Transformer
Polarity 3Ph
Technology Dry-type
Rated power 50 kVA
ukrT 4.6 %
Type of losses Normal
PkrT 1800 W
Secondary system earthing TN-S
arrangement
Primary connection D
Secondary connection yn
No load secondary voltage Ur0 420V
Secondary voltage Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 72.169 72.169 72.169 0

Synthesis for all operating mode


(A) 72.169 72.169 72.169 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.507 0.201
UL1L2 (%) 0.586 0.233
UL2L3 (%) 0.586 0.233
UL3L1 (%) 0.586 0.233
UL1N (%) 0.306 0.000
UL2N (%) 0.306 0.000
UL3N (%) 0.306 0.000

3.3 Lighting load circuits

3.3.1 Circuit Load 13


Circuit breaker QA 13
Ib 624 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Project: New_project 25/05/2017
Page 16/54

Trip unit designation Micrologic 2.3


Trip unit rating 630 A
Long delay settings
Ir 630 A
Tr 16 s
Short delay settings
Isd current 6300 A
Tsd 0.02 s
Instantaneous tripping
Ii current 6900 A

Cable WD 13
Parameters
Length 1m
Max length 50.1 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 624 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 0.88
Standard table reference A-52-20
User correction factor 1
Overall factor 0.88

Selected phase
Cross section area 2x150 mm
Core Copper
Iz under real conditions 702 A
Selected neutral
Cross section area 2x150 mm
Core Copper
Iz under real conditions 702 A
Selected PE
Cross section area 1x150 mm
Core Copper

Project: New_project 25/05/2017


Page 17/54

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 12.29 10.64 11.94 8.41 9.39 9.66 0.00

Synthesis for all operating mode


(kA) 12.29 10.64 11.94 8.41 9.39 9.66 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge EA 13
U 400 V
S 432 kVA
P 386 kW
I 624 A
cos 0.9
Ku (Normal) 1
Number of circuit 1
Polarity 3Ph+N
Phase connection
Type of luminaries Fluorescent with ferromagnetic ballast
Nb of luminaries 131
Nb of lights/luminaries 131
Lights power 18 W
Ballast power 4.5 W
Ia 624 A
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 623.971 623.971 609.790 14.2

Synthesis for all operating mode


(A) 623.971 623.971 609.790 14.2
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.330 0.024
UL1L2 (%) 0.381 0.028
UL2L3 (%) 0.380 0.027
UL3L1 (%) 0.380 0.027
UL1N (%) 0.330 0.024
UL2N (%) 0.330 0.024
UL3N (%) 0.330 0.024

Synthesis for all operating mode


U3L (%) 0.330
UL1L2 (%) 0.381
UL2L3 (%) 0.380
UL3L1 (%) 0.380
UL1N (%) 0.330
UL2N (%) 0.330

Project: New_project 25/05/2017


Page 18/54

UL3N (%) 0.330

Project: New_project 25/05/2017


Page 19/54

3.4 Motor starter combination


3.4.1 Circuit Motor Load 12
Circuit breaker QA 12
Ib 11.5 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 14 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 14 A
Long delay settings
Ir 12 A
Tr NA
Short delay settings
Isd current 170 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K12
Designation LC1K12
Type of coordination T1

Cable WD 12
Parameters
Length 5m
Max length 42.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16

Project: New_project 25/05/2017


Page 20/54

Loaded neutral factor 1


Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.37 1.19 0.00 0.75 0.00 0.79 0.00

Synthesis for all operating mode


(kA) 1.37 1.19 0.00 0.75 0.00 0.79 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 12
Startup type Direct
U 400 V
Mechanical power 5.5 kW
Startup current Id/Ir 7.2
Transient current Id/Ir <=19
Ir for sizing 11.5 A
Sr for sizing 7.97 kVA
Pr for sizing 6.61 kW
cos 0.83
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 11.500 11.500 11.500 0

Synthesis for all operating mode


(A) 11.500 11.500 11.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.328 0.328
UL1L2 (%) 0.378 0.378
UL2L3 (%) 0.378 0.378
Project: New_project 25/05/2017
Page 21/54

UL3L1 (%) 0.378 0.378


UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.484
3.4.2 Circuit Motor Load 16
Circuit breaker QA 16
Ib 11.5 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 14 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 14 A
Long delay settings
Ir 12 A
Tr NA
Short delay settings
Isd current 170 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K12
Designation LC1K12
Type of coordination T1

Cable WD 16
Parameters
Length 5m
Max length 42.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1

Project: New_project 25/05/2017


Page 22/54

Standard table reference A-52-14


Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.37 1.19 0.00 0.75 0.00 0.79 0.00

Synthesis for all operating mode


(kA) 1.37 1.19 0.00 0.75 0.00 0.79 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 16
Startup type Direct
U 400 V
Mechanical power 5.5 kW
Startup current Id/Ir 7.2
Transient current Id/Ir <=19
Ir for sizing 11.5 A
Sr for sizing 7.97 kVA
Pr for sizing 6.61 kW
cos 0.83
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 11.500 11.500 11.500 0

Synthesis for all operating mode


(A) 11.500 11.500 11.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


Project: New_project 25/05/2017
Page 23/54

U3L (%) 0.328 0.328


UL1L2 (%) 0.378 0.378
UL2L3 (%) 0.378 0.378
UL3L1 (%) 0.378 0.378
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.484
3.4.3 Circuit Motor Load 17
Circuit breaker QA 17
Ib 11.5 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 14 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 14 A
Long delay settings
Ir 12 A
Tr NA
Short delay settings
Isd current 170 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K12
Designation LC1K12
Type of coordination T1

Cable WD 17
Parameters
Length 5m
Max length 42.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 12 A
Sizing constraint Iz

Project: New_project 25/05/2017


Page 24/54

Sizing Information Sized with Ir


Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.37 1.19 0.00 0.75 0.00 0.79 0.00

Synthesis for all operating mode


(kA) 1.37 1.19 0.00 0.75 0.00 0.79 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 17
Startup type Direct
U 400 V
Mechanical power 5.5 kW
Startup current Id/Ir 7.2
Transient current Id/Ir <=19
Ir for sizing 11.5 A
Sr for sizing 7.97 kVA
Pr for sizing 6.61 kW
cos 0.83
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 11.500 11.500 11.500 0

Synthesis for all operating mode


(A) 11.500 11.500 11.500 0

Project: New_project 25/05/2017


Page 25/54

Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.328 0.328
UL1L2 (%) 0.378 0.378
UL2L3 (%) 0.378 0.378
UL3L1 (%) 0.378 0.378
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.484
3.4.4 Circuit Motor Load 18
Circuit breaker QA 18
Ib 11.5 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 14 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 14 A
Long delay settings
Ir 12 A
Tr NA
Short delay settings
Isd current 170 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K12
Designation LC1K12
Type of coordination T1

Cable WD 18
Parameters
Length 5m
Max length 42.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Project: New_project 25/05/2017
Page 26/54

Level of third harmonic THDI 0%


Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.37 1.19 0.00 0.75 0.00 0.79 0.00

Synthesis for all operating mode


(kA) 1.37 1.19 0.00 0.75 0.00 0.79 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 18
Startup type Direct
U 400 V
Mechanical power 5.5 kW
Startup current Id/Ir 7.2
Transient current Id/Ir <=19
Ir for sizing 11.5 A
Sr for sizing 7.97 kVA
Pr for sizing 6.61 kW
cos 0.83
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 11.500 11.500 11.500 0

Project: New_project 25/05/2017


Page 27/54

Synthesis for all operating mode


(A) 11.500 11.500 11.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.328 0.328
UL1L2 (%) 0.378 0.378
UL2L3 (%) 0.378 0.378
UL3L1 (%) 0.378 0.378
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.484
3.4.5 Circuit Motor Load 19
Circuit breaker QA 19
Ib 15.5 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 18 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 18 A
Long delay settings
Ir 16 A
Tr NA
Short delay settings
Isd current 223 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K16
Designation LC1K16
Type of coordination T1

Cable WD 19
Parameters
Length 5m
Max length 30.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Project: New_project 25/05/2017
Page 28/54

Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 16 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.37 1.19 0.00 0.75 0.00 0.79 0.00

Synthesis for all operating mode


(kA) 1.37 1.19 0.00 0.75 0.00 0.79 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 19
Startup type Direct
U 400 V
Mechanical power 7.5 kW
Startup current Id/Ir 7.2
Transient current Id/Ir <=19
Ir for sizing 15.5 A
Sr for sizing 10.7 kVA
Pr for sizing 8.91 kW
cos 0.83
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Project: New_project 25/05/2017


Page 29/54

Operating mode Normal


(A) 15.500 15.500 15.500 0

Synthesis for all operating mode


(A) 15.500 15.500 15.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.441 0.441
UL1L2 (%) 0.510 0.510
UL2L3 (%) 0.510 0.510
UL3L1 (%) 0.510 0.510
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.660
3.4.6 Circuit Motor Load 20
Circuit breaker QA 20
Ib 35 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.2 M
Trip unit rating 50 A
Long delay settings
Ir 36 A
Tr 5s
Short delay settings
Isd current 468 A
Tsd 0.03 s
Instantaneous tripping
Ii current 750 A

Contactor LC1D40A
Designation LC1D40A
Type of coordination T1

Cable WD 20
Parameters
Length 5m
Max length 58.7 m
Installation method 31
E
Multi-core cables on horizontal
Project: New_project 25/05/2017
Page 30/54

perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 35 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x4 mm
Core Copper
Iz under real conditions 42 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.37 1.18 0.00 0.90 0.00 0.93 0.00

Synthesis for all operating mode


(kA) 1.37 1.18 0.00 0.90 0.00 0.93 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 20
Startup type Direct
U 400 V
Mechanical power 18.5 kW
Startup current Id/Ir 7.2
Transient current Id/Ir <=19
Ir for sizing 35 A
Sr for sizing 24.2 kVA
Pr for sizing 20.9 kW
cos 0.86
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Project: New_project 25/05/2017
Page 31/54

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 35.000 35.000 35.000 0

Synthesis for all operating mode


(A) 35.000 35.000 35.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.389 0.389
UL1L2 (%) 0.449 0.449
UL2L3 (%) 0.449 0.449
UL3L1 (%) 0.449 0.449
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.636
3.4.7 Circuit Motor Load 24
Circuit breaker QA 24
Ib 40 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.2 M
Trip unit rating 50 A
Long delay settings
Ir 40 A
Tr 5s
Short delay settings
Isd current 520 A
Tsd 0.03 s
Instantaneous tripping
Ii current 750 A

Contactor LC1D50A
Designation LC1D50A
Type of coordination T1

Cable WD 24
Parameters
Length 5m
Max length 51.2 m
Installation method 31
Project: New_project 25/05/2017
Page 32/54

E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 40 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x4 mm
Core Copper
Iz under real conditions 42 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.35 1.17 0.00 0.89 0.00 0.92 0.00

Synthesis for all operating mode


(kA) 1.35 1.17 0.00 0.89 0.00 0.92 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 24
Startup type Direct
U 400 V
Mechanical power 22 kW
Startup current Id/Ir 7.2
Transient current Id/Ir <=19
Ir for sizing 40 A
Sr for sizing 27.7 kVA
Pr for sizing 23.8 kW
cos 0.86
Polarity 3Ph
Number of circuit 1
Project: New_project 25/05/2017
Page 33/54

Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 40.000 40.000 40.000 0

Synthesis for all operating mode


(A) 40.000 40.000 40.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.445 0.445
UL1L2 (%) 0.513 0.513
UL2L3 (%) 0.513 0.513
UL3L1 (%) 0.513 0.513
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.754
3.4.8 Circuit Motor Load 26
Circuit breaker QA 26
Ib 11.5 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 14 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 14 A
Long delay settings
Ir 12 A
Tr NA
Short delay settings
Isd current 170 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K12
Designation LC1K12
Type of coordination T1

Cable WD 26
Parameters
Project: New_project 25/05/2017
Page 34/54

Length 5m
Max length 42.7 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.35 1.17 0.00 0.74 0.00 0.78 0.00

Synthesis for all operating mode


(kA) 1.35 1.17 0.00 0.74 0.00 0.78 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 26
Startup type Direct
U 400 V
Mechanical power 5.5 kW
Startup current Id/Ir 7.2
Transient current Id/Ir <=19
Ir for sizing 11.5 A
Sr for sizing 7.97 kVA
Pr for sizing 6.61 kW
Project: New_project 25/05/2017
Page 35/54

cos 0.83
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 11.500 11.500 11.500 0

Synthesis for all operating mode


(A) 11.500 11.500 11.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.328 0.328
UL1L2 (%) 0.378 0.378
UL2L3 (%) 0.378 0.378
UL3L1 (%) 0.378 0.378
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.484
3.4.9 Circuit Motor Load 27
Circuit breaker QA 27
Ib 29 A
Distance from origin NA

Sizing Information Sized by system


Range GV
Designation GV2ME
Circuit breaker rating 32 A
Breaking capacity 10 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation ME32
Trip unit rating 32 A
Long delay settings
Ir 30 A
Tr NA
Short delay settings
Isd current 416 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1D32
Designation LC1D32
Type of coordination T1

Project: New_project 25/05/2017


Page 36/54

Cable WD 27
Parameters
Length 5m
Max length 17.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 29 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x2.5 mm
Core Copper
Iz under real conditions 32 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.35 1.17 0.00 0.83 0.00 0.86 0.00

Synthesis for all operating mode


(kA) 1.35 1.17 0.00 0.83 0.00 0.86 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 27
Startup type Direct
U 400 V
Mechanical power 15 kW
Startup current Id/Ir 7.2
Transient current Id/Ir <=19
Project: New_project 25/05/2017
Page 37/54

Ir for sizing 29 A
Sr for sizing 20.1 kVA
Pr for sizing 17.3 kW
cos 0.86
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 29.000 29.000 29.000 0

Synthesis for all operating mode


(A) 29.000 29.000 29.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.514 0.514
UL1L2 (%) 0.594 0.594
UL2L3 (%) 0.594 0.594
UL3L1 (%) 0.594 0.594
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.805
3.4.10 Circuit Motor Load 28
Circuit breaker QA 28
Ib 4.9 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 6.3 A
Breaking capacity 150 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 6.3 A
Long delay settings
Ir 5A
Tr NA
Short delay settings
Isd current 78 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K06

Project: New_project 25/05/2017


Page 38/54

Designation LC1K06
Type of coordination T1

Cable WD 28
Parameters
Length 5m
Max length 101 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 5A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.35 1.17 0.00 0.74 0.00 0.78 0.00

Synthesis for all operating mode


(kA) 1.35 1.17 0.00 0.74 0.00 0.78 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 28
Startup type Direct

Project: New_project 25/05/2017


Page 39/54

U 400 V
Mechanical power 2.2 kW
Startup current Id/Ir 6
Transient current Id/Ir <=19
Ir for sizing 4.9 A
Sr for sizing 3.39 kVA
Pr for sizing 2.72 kW
cos 0.8
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 4.900 4.900 4.900 0

Synthesis for all operating mode


(A) 4.900 4.900 4.900 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.135 0.135
UL1L2 (%) 0.155 0.155
UL2L3 (%) 0.155 0.155
UL3L1 (%) 0.155 0.155
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.193
3.4.11 Circuit Motor Load 29
Circuit breaker QA 29
Ib 4.9 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 6.3 A
Breaking capacity 150 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 6.3 A
Long delay settings
Ir 5A
Tr NA
Short delay settings
Isd current 78 A
Tsd NA
Instantaneous tripping

Project: New_project 25/05/2017


Page 40/54

Ii current NA

Contactor LC1K06
Designation LC1K06
Type of coordination T1

Cable WD 29
Parameters
Length 5m
Max length 101 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 5A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.35 1.17 0.00 0.74 0.00 0.78 0.00

Synthesis for all operating mode


(kA) 1.35 1.17 0.00 0.74 0.00 0.78 0.00

Project: New_project 25/05/2017


Page 41/54

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 29
Startup type Direct
U 400 V
Mechanical power 2.2 kW
Startup current Id/Ir 6
Transient current Id/Ir <=19
Ir for sizing 4.9 A
Sr for sizing 3.39 kVA
Pr for sizing 2.72 kW
cos 0.8
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 4.900 4.900 4.900 0

Synthesis for all operating mode


(A) 4.900 4.900 4.900 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.135 0.135
UL1L2 (%) 0.155 0.155
UL2L3 (%) 0.155 0.155
UL3L1 (%) 0.155 0.155
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.193
3.4.12 Circuit Motor Load 42
Circuit breaker QA 42
Ib 15.5 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 18 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 18 A
Long delay settings
Ir 16 A
Tr NA

Project: New_project 25/05/2017


Page 42/54

Short delay settings


Isd current 223 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K16
Designation LC1K16
Type of coordination T1

Cable WD 42
Parameters
Length 5m
Max length 30.7 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 16 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.35 1.17 0.00 0.74 0.00 0.78 0.00

Project: New_project 25/05/2017


Page 43/54

Synthesis for all operating mode


(kA) 1.35 1.17 0.00 0.74 0.00 0.78 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 42
Startup type Direct
U 400 V
Mechanical power 7.5 kW
Startup current Id/Ir 7.2
Transient current Id/Ir <=19
Ir for sizing 15.5 A
Sr for sizing 10.7 kVA
Pr for sizing 8.91 kW
cos 0.83
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 15.500 15.500 15.500 0

Synthesis for all operating mode


(A) 15.500 15.500 15.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.441 0.441
UL1L2 (%) 0.510 0.510
UL2L3 (%) 0.510 0.510
UL3L1 (%) 0.510 0.510
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.660
3.4.13 Circuit Motor Load 46
Circuit breaker QA 46
Ib 8.5 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 10 A
Breaking capacity 150 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M

Project: New_project 25/05/2017


Page 44/54

Trip unit rating 10 A


Long delay settings
Ir 9A
Tr NA
Short delay settings
Isd current 138 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K09
Designation LC1K09
Type of coordination T1

Cable WD 46
Parameters
Length 5m
Max length 37.8 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 9A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Project: New_project 25/05/2017
Page 45/54

Operating mode Normal


(kA) 0.47 0.41 0.00 0.30 0.00 0.34 0.00

Synthesis for all operating mode


(kA) 0.47 0.41 0.00 0.30 0.00 0.34 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 46
Startup type Direct
U 400 V
Mechanical power 4 kW
Startup current Id/Ir 6
Transient current Id/Ir <=19
Ir for sizing 8.5 A
Sr for sizing 5.89 kVA
Pr for sizing 4.71 kW
cos 0.8
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 8.500 8.500 8.500 0

Synthesis for all operating mode


(A) 8.500 8.500 8.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.233 0.233
UL1L2 (%) 0.270 0.270
UL2L3 (%) 0.270 0.270
UL3L1 (%) 0.270 0.270
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.351
3.4.14 Circuit Motor Load 48
Circuit breaker QA 48
Ib 8.5 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 10 A
Breaking capacity 150 kA
TNS One pole breaking capacity NA

Project: New_project 25/05/2017


Page 46/54

IT One pole breaking capacity NA


Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 10 A
Long delay settings
Ir 9A
Tr NA
Short delay settings
Isd current 138 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K09
Designation LC1K09
Type of coordination T1

Cable WD 48
Parameters
Length 5m
Max length 37.8 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 9A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm

Project: New_project 25/05/2017


Page 47/54

Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 0.47 0.41 0.00 0.30 0.00 0.34 0.00

Synthesis for all operating mode


(kA) 0.47 0.41 0.00 0.30 0.00 0.34 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 48
Startup type Direct
U 400 V
Mechanical power 4 kW
Startup current Id/Ir 6
Transient current Id/Ir <=19
Ir for sizing 8.5 A
Sr for sizing 5.89 kVA
Pr for sizing 4.71 kW
cos 0.8
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 8.500 8.500 8.500 0

Synthesis for all operating mode


(A) 8.500 8.500 8.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.233 0.233
UL1L2 (%) 0.270 0.270
UL2L3 (%) 0.270 0.270
UL3L1 (%) 0.270 0.270
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.351
3.4.15 Circuit Motor Load 49
Circuit breaker QA 49
Ib 8.5 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 P25M
Project: New_project 25/05/2017
Page 48/54

Designation P25M
Circuit breaker rating 10 A
Breaking capacity 150 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 10 A
Long delay settings
Ir 9A
Tr NA
Short delay settings
Isd current 138 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K09
Designation LC1K09
Type of coordination T1

Cable WD 49
Parameters
Length 5m
Max length 37.8 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 9A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm
Core Copper
Project: New_project 25/05/2017
Page 49/54

Iz under real conditions 23 A


Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 0.47 0.41 0.00 0.30 0.00 0.34 0.00

Synthesis for all operating mode


(kA) 0.47 0.41 0.00 0.30 0.00 0.34 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 49
Startup type Direct
U 400 V
Mechanical power 4 kW
Startup current Id/Ir 6
Transient current Id/Ir <=19
Ir for sizing 8.5 A
Sr for sizing 5.89 kVA
Pr for sizing 4.71 kW
cos 0.8
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 8.500 8.500 8.500 0

Synthesis for all operating mode


(A) 8.500 8.500 8.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.233 0.233
UL1L2 (%) 0.270 0.270
UL2L3 (%) 0.270 0.270
UL3L1 (%) 0.270 0.270
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.351
3.4.16 Circuit Motor Load 50
Circuit breaker QA 50
Ib 8.5 A
Distance from origin NA
Project: New_project 25/05/2017
Page 50/54

Sizing Information Sized by system


Range Multi 9 P25M
Designation P25M
Circuit breaker rating 10 A
Breaking capacity 150 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 10 A
Long delay settings
Ir 9A
Tr NA
Short delay settings
Isd current 138 A
Tsd NA
Instantaneous tripping
Ii current NA

Contactor LC1K09
Designation LC1K09
Type of coordination T1

Cable WD 50
Parameters
Length 5m
Max length 37.8 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 9A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1

Project: New_project 25/05/2017


Page 51/54

Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 0.47 0.41 0.00 0.30 0.00 0.34 0.00

Synthesis for all operating mode


(kA) 0.47 0.41 0.00 0.30 0.00 0.34 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor MA 50
Startup type Direct
U 400 V
Mechanical power 4 kW
Startup current Id/Ir 6
Transient current Id/Ir <=19
Ir for sizing 8.5 A
Sr for sizing 5.89 kVA
Pr for sizing 4.71 kW
cos 0.8
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 8.500 8.500 8.500 0

Synthesis for all operating mode


(A) 8.500 8.500 8.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.233 0.233
UL1L2 (%) 0.270 0.270
UL2L3 (%) 0.270 0.270
UL3L1 (%) 0.270 0.270
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.351

Project: New_project 25/05/2017


Page 52/54

3.5 Busbar circuits


3.5.1 Circuit WC 7
Busbar WC 7
Parameters
Switchboard Name UC 8
Switchboard Range No preference
Rating (A) 0
IP Undefined
Feeder
Circuit name Protection name Protection type

Load 13 QA 13 NSX630F

LV transformer 21 QA 21 C120H

LV transformer 43 QA 43 iC60H

LV transformer 52 QA 52 C120H

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 11.46 9.93 11.14 8.43 9.44 9.73 0.00

Synthesis for all operating mode


(kA) 11.46 9.93 11.14 8.43 9.44 9.73 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.5.2 Circuit WC 14
Busbar WC 14
Parameters
Switchboard Name UC 15
Switchboard Range No preference
Rating (A) 0
IP Undefined
Feeder
Circuit name Protection name Protection type

Motor Load 12 QA 12 P25M

Motor Load 16 QA 16 P25M

Motor Load 17 QA 17 P25M

Motor Load 18 QA 18 P25M

Motor Load 19 QA 19 P25M

Motor Load 20 QA 20 NSX100F

Project: New_project 25/05/2017


Page 53/54

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.36 1.18 0.00 1.01 0.00 1.16 0.00

Synthesis for all operating mode


(kA) 1.36 1.18 0.00 1.01 0.00 1.16 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.5.3 Circuit WC 22
Busbar WC 22
Parameters
Switchboard Name UC 23
Switchboard Range No preference
Rating (A) 0
IP Undefined
Feeder
Circuit name Protection name Protection type

Motor Load 24 QA 24 NSX100F

Motor Load 26 QA 26 P25M

Motor Load 27 QA 27 GV2ME

Motor Load 28 QA 28 P25M

Motor Load 29 QA 29 P25M

Motor Load 42 QA 42 P25M

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 1.35 1.16 0.00 0.99 0.00 1.15 0.00

Synthesis for all operating mode


(kA) 1.35 1.16 0.00 0.99 0.00 1.15 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.5.4 Circuit WC 44
Busbar WC 44
Parameters
Switchboard Name UC 45
Switchboard Range No preference
Rating (A) 0
IP Undefined
Project: New_project 25/05/2017
Page 54/54

Feeder
Circuit name Protection name Protection type

Motor Load 46 QA 46 P25M

Motor Load 48 QA 48 P25M

Motor Load 49 QA 49 P25M

Motor Load 50 QA 50 P25M

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 0.47 0.41 0.00 0.34 0.00 0.39 0.00

Synthesis for all operating mode


(kA) 0.47 0.41 0.00 0.34 0.00 0.39 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Project: New_project 25/05/2017