New_project
Full
Page 2/54
Content
1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4
3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14
1 Project description
1.1 Project general settings
Installation standard IEC60364
- P25M
QA 42 1 Multi 9 P25M 18 3P3d M
- P25M
QA 43 1 Acti9 iC60 - 32 3P3d D
iC60H
QA 46 1 Multi 9 P25M 10 3P3d M
- P25M
QA 48 1 Multi 9 P25M 10 3P3d M
- P25M
QA 49 1 Multi 9 P25M 10 3P3d M
- P25M
QA 50 1 Multi 9 P25M 10 3P3d M
- P25M
QA 52 1 Multi 9 C120 80 3P3d D
- C120H
2.1.4 Switch
Name Nbr Range Rating (A) Poles RCD RCD class
QB 21 1 Acti 9 100 3P
iSW
QB 43 1 Multi 9 I 100 3P
QB 52 1 Acti 9 100 3P
iSW
2.1.6 MV Cable
Name Nbr Designation CSA (mm) Icc (A) In (A) Un (kV)
MVWD 1 NA 1 x 240 Al 21.3 418 24
0
3 Calculation notes
MV/LV transformer TA 0
Range Trihal
Technology Dry-type
Rated power 500 kVA
ukrT 6%
Type of losses Normal
PkrT 5.7 kW
System earthing arrangement TN-S
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Cable WD 0
Parameters
Length 13 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 722 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Project: New_project 25/05/2017
Page 8/54
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 0.88
Standard table reference A-52-20
User correction factor 1
Overall factor 0.88
Selected phase
Cross section area 2x185 mm
Core Copper
Iz under real conditions 803 A
Selected neutral
Cross section area 2x185 mm
Core Copper
Iz under real conditions 803 A
Selected PE
Cross section area 1x185 mm
Core Copper
Ii current 9600 A
Cable WD 21
Parameters
Length 7m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 72 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Project: New_project 25/05/2017
Page 10/54
Selected phase
Cross section area 1x16 mm
Core Copper
Iz under real conditions 100 A
Selected PE
Cross section area 1x16 mm
Core Copper
Design current
IL1 IL2 IL3 IN
Cable WD 43
Parameters
Length 7m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Project: New_project 25/05/2017
Page 12/54
Selected phase
Cross section area 1x2.5 mm
Core Copper
Iz under real conditions 32 A
Selected PE
Cross section area 1x4 mm
Core Copper
Design current
IL1 IL2 IL3 IN
Cable WD 52
Parameters
Project: New_project 25/05/2017
Page 14/54
Length 5m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 72 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x16 mm
Core Copper
Iz under real conditions 100 A
Selected PE
Cross section area 1x16 mm
Core Copper
withstand
Pole 3
LV/LV transformer TA 52
Type Transformer
Polarity 3Ph
Technology Dry-type
Rated power 50 kVA
ukrT 4.6 %
Type of losses Normal
PkrT 1800 W
Secondary system earthing TN-S
arrangement
Primary connection D
Secondary connection yn
No load secondary voltage Ur0 420V
Secondary voltage Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Design current
IL1 IL2 IL3 IN
Cable WD 13
Parameters
Length 1m
Max length 50.1 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 624 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 0.88
Standard table reference A-52-20
User correction factor 1
Overall factor 0.88
Selected phase
Cross section area 2x150 mm
Core Copper
Iz under real conditions 702 A
Selected neutral
Cross section area 2x150 mm
Core Copper
Iz under real conditions 702 A
Selected PE
Cross section area 1x150 mm
Core Copper
Contactor LC1K12
Designation LC1K12
Type of coordination T1
Cable WD 12
Parameters
Length 5m
Max length 42.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
Contactor LC1K12
Designation LC1K12
Type of coordination T1
Cable WD 16
Parameters
Length 5m
Max length 42.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
Contactor LC1K12
Designation LC1K12
Type of coordination T1
Cable WD 17
Parameters
Length 5m
Max length 42.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 12 A
Sizing constraint Iz
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
Voltage drop
Cumulated from upstream Circuit
Contactor LC1K12
Designation LC1K12
Type of coordination T1
Cable WD 18
Parameters
Length 5m
Max length 42.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Project: New_project 25/05/2017
Page 26/54
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
Contactor LC1K16
Designation LC1K16
Type of coordination T1
Cable WD 19
Parameters
Length 5m
Max length 30.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Project: New_project 25/05/2017
Page 28/54
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 16 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
Contactor LC1D40A
Designation LC1D40A
Type of coordination T1
Cable WD 20
Parameters
Length 5m
Max length 58.7 m
Installation method 31
E
Multi-core cables on horizontal
Project: New_project 25/05/2017
Page 30/54
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 35 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x4 mm
Core Copper
Iz under real conditions 42 A
Selected PE
Cross section area 1x4 mm
Core Copper
Design current
IL1 IL2 IL3 IN
Contactor LC1D50A
Designation LC1D50A
Type of coordination T1
Cable WD 24
Parameters
Length 5m
Max length 51.2 m
Installation method 31
Project: New_project 25/05/2017
Page 32/54
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 40 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x4 mm
Core Copper
Iz under real conditions 42 A
Selected PE
Cross section area 1x4 mm
Core Copper
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN
Contactor LC1K12
Designation LC1K12
Type of coordination T1
Cable WD 26
Parameters
Project: New_project 25/05/2017
Page 34/54
Length 5m
Max length 42.7 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
cos 0.83
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN
Contactor LC1D32
Designation LC1D32
Type of coordination T1
Cable WD 27
Parameters
Length 5m
Max length 17.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 29 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x2.5 mm
Core Copper
Iz under real conditions 32 A
Selected PE
Cross section area 1x4 mm
Core Copper
Ir for sizing 29 A
Sr for sizing 20.1 kVA
Pr for sizing 17.3 kW
cos 0.86
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN
Contactor LC1K06
Designation LC1K06
Type of coordination T1
Cable WD 28
Parameters
Length 5m
Max length 101 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 5A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
U 400 V
Mechanical power 2.2 kW
Startup current Id/Ir 6
Transient current Id/Ir <=19
Ir for sizing 4.9 A
Sr for sizing 3.39 kVA
Pr for sizing 2.72 kW
cos 0.8
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN
Ii current NA
Contactor LC1K06
Designation LC1K06
Type of coordination T1
Cable WD 29
Parameters
Length 5m
Max length 101 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 5A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
Contactor LC1K16
Designation LC1K16
Type of coordination T1
Cable WD 42
Parameters
Length 5m
Max length 30.7 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 16 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
Contactor LC1K09
Designation LC1K09
Type of coordination T1
Cable WD 46
Parameters
Length 5m
Max length 37.8 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 9A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
Contactor LC1K09
Designation LC1K09
Type of coordination T1
Cable WD 48
Parameters
Length 5m
Max length 37.8 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 9A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
Designation P25M
Circuit breaker rating 10 A
Breaking capacity 150 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 10 A
Long delay settings
Ir 9A
Tr NA
Short delay settings
Isd current 138 A
Tsd NA
Instantaneous tripping
Ii current NA
Contactor LC1K09
Designation LC1K09
Type of coordination T1
Cable WD 49
Parameters
Length 5m
Max length 37.8 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 9A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm
Core Copper
Project: New_project 25/05/2017
Page 49/54
Contactor LC1K09
Designation LC1K09
Type of coordination T1
Cable WD 50
Parameters
Length 5m
Max length 37.8 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 C
Level of third harmonic THDI 0%
Ib 9A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm
Core Copper
Load 13 QA 13 NSX630F
LV transformer 21 QA 21 C120H
LV transformer 43 QA 43 iC60H
LV transformer 52 QA 52 C120H
3.5.2 Circuit WC 14
Busbar WC 14
Parameters
Switchboard Name UC 15
Switchboard Range No preference
Rating (A) 0
IP Undefined
Feeder
Circuit name Protection name Protection type
3.5.3 Circuit WC 22
Busbar WC 22
Parameters
Switchboard Name UC 23
Switchboard Range No preference
Rating (A) 0
IP Undefined
Feeder
Circuit name Protection name Protection type
3.5.4 Circuit WC 44
Busbar WC 44
Parameters
Switchboard Name UC 45
Switchboard Range No preference
Rating (A) 0
IP Undefined
Project: New_project 25/05/2017
Page 54/54
Feeder
Circuit name Protection name Protection type