EVCS Compact 5 & Compact 9

Data Sheet

The Emergency Voice Communications System (EVCS) is for Compact 9 System


use as a Fire Telephone system, Disabled Refuge Call system
or as a combined system when both Fire Telephones and The EVCS Compact 9 system comprises of the 9 Line Master
Disabled Refuge Points are required. Exchange Unit and up to 9 Outstations (Type A, Type B, or
Emergency Assist Alarms). Using the 10 line Slave Exchange
Compact 5 System Unit this system can be easily expanded to 19 lines.

The EVCS Compact 5 and Compact 9 systems provide fixed,


The Compact 9 Emergency Voice Communication System
secure, bi-directional, full-duplex voice communication system, to
(EVCS) is designed to fully comply with BS 58399 -2011 for
assist fire fighters within high rise buildings or large sites where
use as a Fire Telephone System, Disabled Refuge Call System
radio communication may not be possible. Where both a fire
or as a combined system when both Fire Telephones and
telephone and disabled refuge system are fitted to a building BS
Disabled Refuge points are required.
5839 Part 9 specifies these should form a single system.

The Compact 9 is modular in design and the controller


The EVCS Compact 5 is designed to comply with BS5839 Part
manages all functions for the first 9 zones. There is no need for
9 2003. The system comprises of a master EVCS Compact
additional equipment such as power supplies.
handset, and up to five outstations (Type A, Type B, or
Emergency Assist Alarms) and is ideal for small buildings that
are required to install an Emergency Voice Communication
Features
System but only need two or three outstations, leaving room for Analogue addressable communications
expansion.
Full duplex communications
Features Simple menu programming
Analogue addressable communications Contact outputs to interface with Fire Detection or Voice
Monitored handset Alarm Systems.

Fully monitored supply and charger Up to 19 Outstations - using 10 Line Slave Exchange unit
and the 9 Line Master Exchange
Up to five outstations per system
In addition to Type A and Type B Outstation can also monitor
Duplex two way communication
Emergency Assist Alarms (using a 2 core radial)
No programming required
BS5839 part 9 2003 compliant
This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability ISO9001
can be accepted for the use of the information therein. Design features may be changed or amended without prior notice. Design, Manufacture and
Supply to Quality Manage-
For more information, contact: ment Systems Certified to
NOTIFIER. Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United Kingdom ISO9001:1994
Phone: +44 (0) 1444 230 300 Fax: +44 (0) 1444 230 888

Page 1 of 10 - 990-142_0213 www.notifierfiresystems.co.uk


EVCS Compact 5 - EVCS-CMPT
The Emergency Voice Communications System (EVCS) is for use as a Fire Telephone system, Disabled Refuge
Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

The EVCS Compact 5 is a self contained enclosure housing a master handset, five line exchange, power supply,
battery charger and can be surface or semi-flush mounted as standard. The enclosure is made from powder
coated Zintec and is fitted with 20mm cable knockouts for all cables needed. It also provides space for the
system backup 12V SLA battery.

The unit is processor controlled, but requires no programming on site, the panel is fitted with end of lines which
are replaced with field wiring when an outstation is connected.

Specifications
EVCS Compact 5
Mechanical Specification Electrical Specification
Dimensions: AC Input 230V AC +/- 10% 50/60Hz
Height: 330 mm
Width: 350 mm Internal Power Supply 14V DC
Depth: 103 mm Supply & Battery Monitored, Open, Short, Fuses
Weight: 6.5Kg Protection Deep discharge, Short, Thermal
Inputs Temperature Compensation Yes
Number of Lines 5 Battery Size and Type 1 x 12V 4.2AHr
Remote Enable Short to Use
Mains Fuse 240V 2A HRC
End of Line 10K
Battery Fuse 1A PTC
Outputs Max Charge Current 250mA
Number 2, Fault & In Use Outstation Cables
Type Volt Free Relay Type Enhanced
Contact 30V DC 1A Cores 2 Core 1mm or 1.5mm
Distance 500m
Controls
Buttons 6, 5 Lines, Standards
1 Fault acknowledgement EMC EN 55103-1 & EN 55103-2
Zone LEDs 5 Status, 5 Fault Status Product Family BS 5839-9 & BS 9999
Fault LEDs 3, AC, DC, General

Page 2 of 10 - 990-142_0213 www.notifierfiresystems.co.uk


EVCS Compact 9 - EVCS-CMPT9
The EVCS Compact 9 is a combined Line Exchange Unit and Master Handset which connects to up to 9
Disabled Refuge or Fire Emergency Telephones. Capable of being extended to 19 outstations it is the ideal
solution for EVCS in small and medium buildings.

Fully compliant with BS5839 part 9 (2011) each Compact 9 unit is supplied complete with power supply
requiring no further equipment and minimum commissioning effort.

Specifications
EVCS Compact 9
Mechanical Specification Electrical Specification
Dimensions: AC Input 230V AC +/- 10% 50/60Hz
Height 330 mm Internal Power Supply 14V DC
Width 350mm
Supply And Battery Monitored, Open, Short, Fuses
Depth 103mm
Protection Deep Discharge,
Weight 6.5kg
Short Thermal,
Inputs Impedence
Number of Lines 9 or 19 Battery Type 1 x 12V VRSLA (5AH Required)
Remote Enabler Short To Use Mains Fuse 240V 1A HRC
Outputs Battery Fuse 250MA PTC
Number 2 (fault & in-use) Charge Current 250MA
Type Volt Free Relay Outstation Cables
Contact 30V dc 1A Cores 2 core (1mm or 1.5mm)
Controls Distance 500m
Buttons 4 navigation keys Standards
Zone LEDs 3 (in-use, healthy, energised) EMC EN 55103-1 & EN 55103-2
Fault LEDs 3 (Line, PSU And General) Product Family BS 5839-9 & BS 9999

CFVCCS10
VoCALL
EVCS
Compact

General

Supply

VCC S10 Slave Complies to BS5839 Part 9 :2011


EN54-4:A2 :2006

330mm

4 core fire rated enhanced cable

VoCALL
EVCS
Compact
Healthy Line

VoCALL Compact VCCM9


Call PSU
System Healthy
20|01|11 10:20:01
General

  *

350mm 103 mm
 Supply

Making a Call:

Press * for the directory and use the ST


navigation to select the extension name to call
press  to call.

Receiving a Call:

Use the ST navigation keys to select the


caller, press  to connect, press  again to place
on HOLD

CFVCCM9

Page 3 of 10 - 990-142_0213 www.notifierfiresystems.co.uk


Type A Outstation - EVCS-HSP & EVCS-HFP
The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone
system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge
Points are required.

The Type A outstation is a monitored phone handset providing full duplex speech capability. The unit is available
as a surface mounting or flush mounting unit cased in a metal wall mounting enclosure.

The EVCS type A Outstation is a slick compact unit which offers easy access via a magnetic push catch door
and a unique front levelling system allowing the back box to be mounted at a slight angle whilst still retaining a
true front face and door.

Compatible with all EVC systems for use as a standard Fire Telephone or Disabled Refuge call point.

Specifications
EVCS Type A Outstation
Mechanical Specification - EVCS-HSP (Surface Mounting) Electrical Specification
Dimensions: Fully monitored connections. DC open, DC Short and
Height: 320 mm Earth Fault
Width: 152 mm
Depth: 85 mm Status LED
Weight: 1.4 Kg (no batteries) Flashing when ringing
Dimly lit to indicate surveillance
Mechanical Specification - EVCS-HFP (Flush Mounting) Standards
Dimensions (with bezel): EMC: EN 55103-1 & EN 55103-2
Height: 334 mm
Width: 191 mm LVD: EN 60950
Depth: 85 mm Product Family: BS 58399 & BS 9999 &
Dimensions (backbox hole): EN 60118-4
Height: 320 mm
Width: 152 mm Surface mounting enclosure
Depth: 85 mm
Weight: 1.4 Kg (no batteries)

Features
Telephone type handset
Automatic dialling to Compact Handset when off hook
Telecoil for hearing impaired users
Magnetic push catch door

EVCS-HFPSS EVCS-HSPSS
Flush Mount Surface Mount Flush mounting enclosure

334mm 320mm

191mm 85mm 152mm 85mm

Page 4 of 10 - 990-142_0213 www.notifierfiresystems.co.uk


Type A Outstation Stainless Steel - EVCS-HFPSS & EVCS-HSPSS
The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone
system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge
Points are required.

The Type A outstation is a monitored phone handset providing full duplex speech capability. The unit is available
as a surface mounting or flush mounting unit cased in a metal wall mounting enclosure.

The EVCS type A Outstation is a slick compact unit which offers easy access via a magnetic push catch door
and a unique front levelling system allowing the back box to be mounted at a slight angle whilst still retaining a
true front face and door.

Compatible with all EVC systems for use as a standard Fire Telephone or Disabled Refuge call point.

Specifications
EVCS Type A Outstation Stainless Steel
Mechanical Specification - EVCS-HSPSS (Surface Mounting) Electrical Specification
Dimensions: Fully monitored connections. DC open, DC Short and
Height: 320 mm Earth Fault
Width: 152 mm
Depth: 85 mm Status LED
Weight: 1.4 Kg (no batteries) Flashing when ringing
Dimly lit to indicate surveillance
Mechanical Specification - EVCS-HFPSS (Flush Mounting) Standards
Dimensions (with bezel): EMC: EN 55103-1 & EN 55103-2
Height: 334 mm
Width: 191 mm LVD: EN 60950
Depth: 85 mm Product Family: BS 58399 & BS 9999 &
Dimensions (backbox hole): EN 60118-4
Height: 320 mm
Width: 152 mm
Depth: 85 mm
Weight: 1.4 Kg (no batteries)

Features
Telephone type handset
Automatic dialling to Compact Handset when off hook
Telecoil for hearing impaired users
Magnetic push catch door

EVCS-HFPSS EVCS-HSPSS
Flush Mount Surface Mount

334mm 320mm

191mm 85mm 152mm 85mm

Page 5 of 10 - 990-142_0213 www.notifierfiresystems.co.uk


Type A Outstation IP65 Lockable Surface Mount - EVCS-HFW
The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone
system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge
Points are required.

The Type A outstation is a monitored phone handset providing full duplex speech capability.

The EVCS-HFW is a type A EVCS outstation compatible with the Notifier Compact and Network systems. It is
supplied in an IP65 case fitted with a standard firemans key lock to prevent unauthorised use.

Specifications
Type A Outstation IP65 Lockable Surface Mount
Mechanical Specification - EVCS-HFW Electrical Specification
Dimensions: Fully monitored connections. DC open, DC Short and
Height: 300 mm Earth Fault
Width: 200 mm
Depth: 120 mm Status LED
Weight: 2.5 Kg Flashing when ringing
Material Zintec, Powder coated Dimly lit to indicate surveillance
Colour RAL7035 Grey
Standards
Outstation Cables EMC EN55103-1, EN55103-2
Type Enhanced LVD EN60950
Cores 2 core 1mm or 1.5mm Product Family: BS 58399 & BS 9999 &
EN 60118-4
Distance 500m

Mounting The Unit


Features
The Handset should be mounted at a height of either 1200mm from the
Telephone type handset
fioor, or on a 1400mm centre line to comply with the requirements of
Automatic dialling to Compact Handset when off hook Building Regulations Document M (Access for the Disabled). The back box
Telecoil for hearing impaired users has four indented feet to allow mounting on uneven walls.
Fitted with a standard firemans key lock to prevent unauthorised use If the unit is to be used as a refuge point suitable space must be allowed to
the side of the unit to allow a wheelchair to be parked for using the system.
300mm

200mm 120mm

Page 6 of 10 - 990-142_0213 www.notifierfiresystems.co.uk


Type B Outstation - EVCS-HSBG, EVCS-HSB, EVCS-HSFSS
The EVCS Type B outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone
system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge
Points are required.

The Type B outstation is a fixed, monitored and maintained, bi-directional, full duplex voice communication
system to assist the orderly evacuation of disabled or mobility impaired people and enhance fire fighters
communication during emergencies.

Please note: When choosing the outstation type for use with an EVCS we recommend reading Section 11 of
BS5839-9:2003 which deals with outstation types. Type B outstations can only be used where the background
noise is below 40dBA (therefore there can be no sounder or voice alarm coverage in the area).

Specifications
Type B Outstation
Mechanical Specification Electrical Specification
Dimensions: Fully monitored connections. DC open, DC Short and
Height: 133 mm Earth Fault
Width: 133 mm
Depth: 45 mm Outstation Cables
Weight: 1.1Kg Cores 2 core 1mm or 1.5mm
Construction Zintec powder coated Distance 500m
Colour Green, Red or Stainless Steel
Indications & Controls
Status LEDs 2 off red -flashes location,
lights solid in use
Call Press to call button
Cancel Press to cancel button

Hands Free Communications


Push button dialling to EVCS Master Handset
Echo cancellation
Noise reduction
Induction loop output for hearing impaired users
Push button cancel
Braille Signage
Standards
EMC: EN55103-1 & EN55103-2
LVD: EN60950
Product Family: BS5839 Pt9 & BS9999

Mounting The Unit


All Type B Outstations should be mounted at a height of either 1200mm
from the floor, or on a 1400mm centre line to comply with the requirements
of Building Regulations Document M (access for the disabled).
The back box has 4 indented feet to allow mounting on uneven walls.
Type B Outstations can be flush mounted by cutting a hole 133mm x
133mm and 45mm deep, and using the stainless steel bezel to finish
the surround.

Page 7 of 10 - 990-142_0213 www.notifierfiresystems.co.uk


Roaming Handset and Jack Plate
The Roaming Handset and Jack plate are designed to provide a cost effective solution for Fire Telephones in
high rise buildings. Notifiers range of EVCS systems cover a wide range of building sizes providing high quality
full duplex Emergency Voice Communication.

The Roaming Handset is used along with the Jack Plate for Emergency Voice Communication System
installations in countries whose fire codes allow for Roaming Handsets*. When used together, the Roaming
Handset and Jack Plate form a Type A Outstation which is compatible with all EVCS systems.

Low noise high quality telephone jack with Telecoil for hearing impaired users.

Stainless steel jack plate can be surface or flush mounted

Specifications
Jack Plate Roaming Handset
Mechanical Specification Mechanical Specification
Dimensions: Dimensions:
Height: 86 mm Height: 210 mm
Width: 86 mm Width: 66 mm
Depth: 25 mm Depth: 45 mm
Weight: 140g Weight: 700g
Construction Brushed stainless steel Construction ABS UL90V1
Connection 1/4 mono neutrik heavy duty jack
Outstation Cables
Cores 2 core 1mm or 1.5mm Standards Compliance
Distance 500m EMC EN55103-1,EN55103-2
End of Line 10K 1/4 W LVD EN60950

Electrical Specification Controls


Fully monitored connections. DC open, DC Short and Call Automatic off hook dialing
Earth Fault

*These units are not suitable for installation in the UK to BS5839 Pt9

Page 8 of 10 - 990-142_0213 www.notifierfiresystems.co.uk


Emergency Assist Alarm Kit - EVCS-TA
The Emergency assist alarm kit has been specifically designed to integrate disabled call functions into the EVCS Network or EVCS
Compact ranges providing the perfect solution for conformity with the Building regulations Document M and Equality Act 2010.

The Emergency Assist Alarm Kit solution is fully monitored and battery backed by the EVCS system, saving local power supplies and
giving confidence in the system integrity.

The Emergency Assist Alarm Kit shows up as a call on the EVCS system, but has no speech path
so a conversation cannot be had with the occupant, use of the Type B Outstations would allow this.

Features Benefits
Monitored to BS 58399 No PSU is required remote powered by
Remote powered from EVCS exchange EVCS system

Dual loop pull cord All calls from disabled toilets and refuge
points monitored from one location
High contrast labels
Tactile braille signage to assist partially
Braille on cancel plate
sighted people
Blue indication

Specifications
Emergency Assist Alarm Kit EVCS-TA
Width: 87 mm
Dimensions: Height: 87 mm
Depth: 31.5 mm
Over door indicator
Electrical Specification: Operating voltage: 12V dc (nominal)

Physical: Construction: PC

Width: 87 mm
Dimensions: Height: 87 mm
Depth: 25 mm
Cancel button
Electrical Specification: Operating voltage: 12V dc (nominal)

Physical: Construction: PC

Width: 87 mm
Dimensions: Height: 87 mm
Depth: 30.5 mm
Pull cord unit
Electrical Specification: Operating voltage: 12V dc (nominal)

Physical: Construction: PC

Wiring Guide Using 2 Core Cable

Power - -
12V + + IN Over Door OUT IN
Supply
- Indicator EVCS Exchange Over Door Indicator
+ OUT
Over Door Indicator Cancel Unit
Pull Cord Unit -
IN Cancel Unit Pull Cord Unit
+ Cancel
- Unit
-
+ OUT
+

Page 9 of 10 - 990-142_0213 www.notifierfiresystems.co.uk


Product Range at a Glance
Part Number

EVCS Compact Master Handset-Wall Mount EVCS-CMPT

Compact 9 line master exchange unit EVCS-CMPT9

10 line slave exchange unit EVCS-XC10

Flush Outstation Push Door. Type A EVCS-HFP

Flush Outstation Type A, Push Door, Stainless Steel EVCS-HFPSS

Surface Outstation. Push Door. Type A EVCS-HSP

Surface Outstation Type A, Push Door, Stainless Steel EVCS-HSPSS

Weatherproof Type A Outstation EVCS-HFW

Surface Outstation, Type B, Green EVCS-HSBG

Surface Outstation, Type B, Red EVCS-HSB

Surface Outstation, Type B Stainless Steel EVCS-HSFSS

Wall Jack Outlet Point EVCS-WJP

Loose Handset with Jack Lead EVCS-HLJ

Emergency Assist Alarm Kit (without PSU) EVCS-TA

EVCS-HSB Stainless Steel flush mounting bezel EVCS-VCFHB

EVCS-MS Rackmount Kit 6U. EVCS-RM

Charles Avenue T: +44 (0) 116 246 2255


Burgess Hill F: +44 (0) 116 246 2210
Page 10 of 10 - 990-142_0213 W. Sussex E: sales@notifierfiresystems.co.uk
RH15 9UF www.notifierfiresystems.co.uk

Вам также может понравиться