Академический Документы
Профессиональный Документы
Культура Документы
May 1985
Amended and Reprinted
November 1996
Accidental damage
robustness
& stability
Prepared by
J. Morton BSe PhD CEng MICE MlnstM
BRICK
DEVELOPMENT
ASSOCIATION
as 5628: The Structural U se of Ma sonry : Part 1: Unreinforced Masonry
Accidental damage
robustness & stabiIity
Prepa red by
J. Morton BSe PhD CEng MICE MlnstM
Based on independent presentations given at BDA seminars by
J.OA Korff SSe CEng FIStructE MICE
R.J.M. Sutherland SA FICE FIStructE FIHE MConsE
J. Morton SSe PhD CEng MICE MlnstM
FOREWORD
'" This
~
~
document supersedes all previous BDA publications on
the subject of Accidental Damage and the 5th Amendment, in
studied in isolation; robustness and stability also need to be
considered. It is, therefore, a blend of masonry design
~ particular Technical Note No 1, Vol 3, July 1971 and Its philosophy combined with the detailed provisions to meet
!" forerunners.
This new publication results from three independent
Parliament's requirements.
Being based on three different presentations by three
~ presentations which were originally given during a series of authors, it is inevitable that within the document certain of the
I
" seminars on BS 5628: Structural use of masonry: Part 1 in late
~
1978 and subsequently.
The aim is both to cover the thinking behind accidental
views expressed represent the opinion of a particular author
rather than of all three. In this way a blend of views are
recorded wh ich represent an up to the minute approach to
~ damage analysis and to explain the basis used in the Code to accidental damage, robustness and stability which, not being
~ fulfil the requirements of the Building Regulations. Because of an exact science. is based on reasonable assumptions
!I the nature of the subject, accidental damage cannot be combined with engineering judgement.
CONTENTS
1 INTRODUCTION
Scope
This publication is concerned WIth the subject of robuslness
and the avoidance of excessive accidental damage in retat.oo
to the sl ructure of masonry buildinqs, It deals Wllh the
provisions contained in Part 1 of BS 5628:The Structural Use
of Masonry: and m particular w ith Section 5 of the Code which
gives detailed recommendations for controlling and limiting
2
accidental damage. The subject is dealt with in its widest The Building' Regulations
sense to give the reader an understanding of what the Code Section D of the Building Regulations, which deals with the
recommends and, more importantly, why the Code structural aspects of buildings, contains the following
recommends it. requirement: 'The structure of a building above the
foundations shall safely sustain and transmit to the
Background foundations the cornbined dead load, irnposed load and wind
The accidental damage provisions in BS 5628 stem from the load without such deflection or deforrnalion as Will impair the
partial collapse of a block of flats in North London, Ronan stability, or cause damage to, the whole or any part of the
Point. in 1968" ', As can be seen in Figure 1, the amount of building. This provision. clause 08, is a legal requirement for
I
CODE PREAMBLE 2
Structural stability & form drafting the Code felt that the designer should be reminded of
In the Code, the main section on accidental damage is the way in which forces can best be carried in rnasonry
Section 5. But there is an earlier section in the Code on structures. Applied loads are best resisted by walls lying
stability (clause 20) where several important points are made parallel to the direction of the applied force. Wind force A can
which are relevant to accidental damage and stability. successfully be carried by the cross walls lying parallel to the
applied force. These are the walls which point into the wind.
These are: There are no spine walls along the centre of the building
1, Robustness and containment of damage; aligned parallel to force B. The structure could therefore
2. Resistance to a prescnbed horizontal force; 'sway' in this direction - It would be 'floppy' in direction B,
3. Prevention of vehicular impact:
4, Special hazards related to service use.
The members of the Technical Comrnittee responsible for
So, the plan form at the top is not at all stable in the
longitudinal direction, Whereas the bottom two plan forms,
with walls in both directions are stable in direction A as well
as in direction B. 3
This, of course, leads to a cellular type of bUilding for between masonry walls and other parts of the structu re,
which masonry offers an excellent structural solution. These points will be considered in greater depth later.
Vehicular impact
Where vehicular impact may prove a problem, the Code
suggests that attempts should be made to isolate the
structure from the vehicles. This could be achieved using
earth banks, boltarcs. etc, .
In Figure 8, the columns just visible on the right are being
protected from a run-away vehicle. This technrque can equally
well be used to safeguard masonry bUildings.
The high nse blocks of flats In Figure 9 were desiqned for
accioental damage and are structurally safe. Subsequent to
their completion. however, bonards and a crash barrier were
Installed to protect them from run -away vehicles on the steep
road behind them.
,.
~
;;:
Option 1
VERTICAL & HORIZONTAL ELEMENTS. UNLESS
PROTECTED. PROVED REMOVABL E. ONE AT A TIME.
WITHOUT CAUSING COLLAPSE
This clearly indicates that all st ructural members. un less
designed to be protected members. are at risk and mu st be
assu med to be lost following an accidental event.
Notional removal of members
Prot ect ed Mem ber s The Code on ly requires one member at a time to be lost or
If a structural' elemen t is designed to ca rry. wi thout failure. 'notionally removed', Following the notional removal of a
both: member. the structu re mu st be anafysed to pred ict the extent
(a) the reduced design load - de rived f rom the reduced V,'s of collapse. If volume is lost and if it exceeds that perm itted by
and Ym's for accidental damage analysis; the Bu ild ing Regulaltons. the member in question must be
and st rengthened to become a protected member. or the structu re
(b) 34 kNlm' . applied uniforml y to Itself and othe r elements of the building improved to eliminate or reduce the extent of
attached to it, it is designated a protected member. predicted collapse. When this has been done . the member is
In other words. protected members remain intact after an notionally replaced and the next m em ber is notiona lly removed
accidenta l event. They are regarded as being st ructu rally and the structure re -enalysed. This process continues until all
unaffected by It. This is clearly im portant wh en suc h members the non- protected horizontal and vertica l members have been
are indispensable to the stability of the structure. removed one at a time and the consequences assessed.
When adjusting VI values for acc idental damage. VI for O, Theoretically . this is a very good and basically sound
become s 105 whe re the imposed load is of a permanent approach. It does. howe ver. require som e farruliarity With the
nature, such as storage areas, computer room s, etc. technique. Once experience has been gained, dangerous
situations can read ily be spotted. On the other hand. it may
not commend itself to those unfamiliar with the process.
Definition of members
Irrespective of the degree of familiarity, what constitutes a
member for this type of analysis? Table 11 ot the Code
provides the necessary guidance and is reproduced below
Type of Extent
load bearing
element
Beam Clear span betvveen supportsor between a
support and the extremity of a member
Column Clear height between horizontal lateral supports
Slab or other Clear span between supports and/or temporary
floor and roof supportsor betweena suppo rt and the extremity
construction ot a member
The calculation for a protected m ason ry m ember IS based Wall inco rporat- l ength between lateral supportsor length
on a three pinned arch model. From tests. this has been 109 one or more between a lateral support and the end of the wall
fou nd to correlate well with what actually happens when a lateral supports
w all is laterally loaded. The formu la giving the lateral fai lu re (note 2)
load, Qlal' is: Wall without l ength not exceeding 2'25 h anywhere along the
~ lateral supports wall (for internal walls)
Qlat = - where ha * and t are the height and thickness 0 f
h; Full lengt h (for external walls)
(h is the clear height of a wall or column
the wall respeclt vely. and n is the precompression on the wa ll between lateral supports)
per unit length. It must be remembered that for arching action
NOTE t, TemfXJrary supports to slabs can be provided by substantIal or
to be effective. adequate abutments in the form of concrete otheradequate partitions capable of carrying the required load.
surfaces or other construction capable of providing sufficient NOTE 2. Lateral supports to walls can be provided by mtersecting or
resistance against rotation. lateral and axial movements are return walls. piers. stJIfened sectJCN1S of wall, substantial non-
necessary. In this Situation Ym becomes 105, which Ioadbeaflng partdions in accordance with (a). (b) and (c) of clause 37-5.
represents the overall factor of safety. Normally. of cou rse. or purpose-designed structural elements.
Contain ing the damage
Thus. a member is defined as a beam, a column, a slab or a
wall. Beams. columns and slabs are fairty straightforward, but ~
walls are not. If a wall is not a protected member, what
am ount of the wall shou ld be deemed to be removed follow ing
i
;::
an Incident? The Code gives guidance on thi s by suggesting Ii}
three specific cases where the spread of damage is limited by j
the provision of vertical bracing in the form of intersecting or !b
return walls, substantial partitions or piers. ~
Case 1: Intersecting &: return walls ~
The first instance is where there is an intersecti ng or return :.
~
I"
~
~
~ Both the wall (fig 22) and Its short return (fig 23) will
disappear following an internal explosion, The Code
"~ Where intemal walls do not have any stiffening effect from
, return walls or intersecting walls, one should assume that a
height. If it is longer than this. It is deemed to remain even if
the main wall is demolished.
Considering both situations, each floor must be capable of 7
shown In Figure 26 can be thought of as a floor encastre along
all ItS Internal ecges - as shown in Figure 27.
Option 2
The second option may be summarised as follows:
-- .."'-
Ib
- -
..
- formula shown in Figure 32. Normally. in domestic
construction. La is 5 m or less and Gk+ Ok is of the order of 75
- .........
p-
-c.=:,
~
kN/m' . Therefore. F, usually suffices. Beyond the domestic
scale, for example in a warehouse type of building with 10 m
spans. the force required may well be 4F, or more. The
magnitude of the force for which internal transverse ties are to
be designed is F, in all cases.
The internal ties in Figure 32 are evenly spread. Of course,
the peripheral steel is also required.
walls into the structure. The force which the horizontal wall or
column bes should be designed to carry is the lesser of 2F, or
~" For domestic constructon, h is normally approximately
25
25 m, and the tie force usually approximates to F,.
This type of wall connection can be justified by either shear
or friction (the factors of 2 are for double shear or fricbon)'"), In
the case of shear. F, per m run must be less than 035 (the
minimum value for shear) dwided by Y~ . multiplied by the
area of 1m run of wall multipl ied by 2 for double shear. Note
that Y~ becomes 125 for accidental damage analysis.
Option 3
Option 3 is the fully tied solution. and involves the full
horizontal tying, just descnbec, plus vertical ties. The object is ,.
to ensure that the vertical members remain after an accident. ~
In other words. with the level of vertical tying prescribed. the >:
vertical members are deemed to behave as protected "-
members. j
~
The pressure of 34 kNlm' acting on the wall Will produce a PROVIDE FULL HORIZONTAL & VERTICAL TIES NO
REMOVAL CHECKS REOUIRED
~=
force shown as F,'m , equal to 34x
2
425 kNim width,
Vertical ties ~
::
assuming a normal storey height. (Remember that the Vertical ties are either vertical wall ties. Vw, or vertical column :
accidental pressure can only occur in the upper or in the lower ties. Vc. These are contained Within the walls or columns of ~
10 compartment at any one bme.) Although the force is the building, '<
.......
--"'"
......__vc
whi ch offers a more practical approach . When vertica l ties are
concentrated in poc kets at 5 m centres, the use of horizontal
wall ties sim ilarly concentrated become s clearer. As With the
.............
Ir--
horizonta l case. vertica l wall ties, etc, should not be posit ioned
further than 25 m from a free or unrestra ined edge.
- ...--
--w.-
c.=-
p-
BACKGROUND PRINCIPLES
4
~ To better app reciate some of the princi ples embodied in the
~ Code, it is useful to consider a few examples of damaged
"ffi buildinqs,
"0
!
~ cent re, and began to knock down all the partition walls. After
many of the supporting walls had been demol ished. the beam
, suddenly lu rched into the deflected shape shown. 11
The fact that the beam did not collapse has more to do with The concept of lateral supports limiting the spread of damage
catenary action than with the flexural strength of the beam. is illustrated in Figure 46. The end wall has been blown out -
The concept of horizontal ties is similar to this. Even when but only up to the stlHened section provided by the chimney
floor slabs are taken beyond their safe strength limit. It ISlikely breast.
that the floors will span any external gaps in a catenary mode. The stiffened section restricted the damage to the outer wall
The floors may deflect excessively. but should not collapse. in a similar manner to the pier discussed earlier. It
demonstrates the way in which piers. substantial crosswalls
Transverse & longitudinal ties and partitions can limit the spread of damage.
The same house again is seen in Figure 47, in more detail.
Notice the damaged partition. At the instant of the explosion.
It had equal pressure on both sides due to the door being left
open. So. although cracked. the partition remained in position
relatively undamaged.
This was not true of the external wall which completely
disappeared up to the chimney breast - as shown in the
previous illustration. Thus, external walls are vulnerable
because the pressure cannot be equalised on both sides. It is
this reasoning which precludes unbraced external walls from
having a limit on the length of wall to be removed. The
building also provides an example of the alternative path
approach - but the Code does not recommend reliance on
wardrobes to prop up roofsl
5 ROBUSTNESS
12
- - - - - - -- - - -- - - - - - - -- - - - - - - -- -
I
capable of suppo rting the tops of the wall s, If this is done, the
force from wall C whi ch is transferred into the roof w ill then be
transmitted into the end gab le wa lls - walls A and B, Since
these end gable walls are the stiff shear wal ls, when the wi nd
is blow ing as shown, they w ill resist the applied wind load, In
order to achieve th is effect, the roof may need to be stiffened,
It also require s care in the way that the roof is connected to
the walls ,
Connectorslstrapslties
--- ==-
Lateral movement
54 -
-
I*:i<F4l
-- j,--- -- --
=ii, .~.
_I,' ,'
8lrIp
-- --
_ :, .:!'
- bIocIUng. 8lrIp
...A _ _ 8"
Deta ils of some of these connectio ns are provided in Append ix
C of the Code, Figure 54 illustrates the principles required in
any detail whose purpose is to hold a gable wall into a timber
Structural synthesis floor,
Straps, bent Into the shape of an L, are fixed to the floor
Precast floors
Save or sacrifice?
The same paper by Sutherland' ) also drscusses the concept
of dividing the structure into component blocks, each stable
on its own but with definitive breaks to limit the spread of
Pursuing this argumen t to its logical conclusion, stability
could be achieved by using buttressed and independent
blocks to get the best of both worlds. Where there is a
buttressed block at one end only, the other blocks would need
to be tied back to it - thus becoming tied blocks.
Verlicalties
Discrete blocks -
--
A suggestion, which has much to comme nd it, is to
stagger the vertical ties' ) or anchor them independently in the
top and bottom of the floor slab" O). The building would still be
fully tied vertically, but the ties wo uld be discontinuous.
Explosions: pipedgas 33
cylinder gas 3
other 4
total 40
Vehicle impacts 27
overall total 67
CONCLUSIONS 7
That properly designed buildings can withstand gas The effect of venting, mentioned earlier, can clearly be seen
explosions was demonstrated in a seriesof tests(13) carried out in the illustration. When the air/gas mixture is ignited,
in the aftermath of Ronan Point. The tests were conducted in pressure builds up very rapidly indeed. At a pressure of about
a building designed to simulate the top 31'1 storeys of a 7 to 14 kNlm2 (12 psi) the windows blow out. allowing much
modern masonry structure. of the unignited mixture to be expelled. This can be seen
'exploding' harmlessly outside the building.
Whilst the walls were damaged in this series of tests, no
. wall was blown out by the explosion and no partial collapse
occurred. When this evidence is viewed in the context of
current legislation, the guidance available within the Code of
Practice, and the basic principles involved, the engineer
should have every confidence in the inherent ability of well
designed masonrystructures to withstand unforeseen events.
17
8 REFERENCES
1. Repo rt of the Inqui ry Into the co llapse of flats at 8. Design Guide for strapping and tying of loadbearing
Ronan Po int, Cann ing Town, London. Ministry of brickwork in low rise construction. British Ceramic
Housing & Local Government. HMSO 1968. Research Association SP93: 1977.
2. Flats constructed with precast concrete panels: 9. R. J . M. Sutherland. Principles for ensuring stability.
Appra isal and strengtheni ng of ex isting high blocks. Proceedings of symposium on stability of low rise buildings
Design of new blocks. Ministry of Housing & Local of hybrid construction . Institution of Structural Engineers.
Government Circular 62/68. 1978.
3. Notes for gu idance on the Interp retati on of Appendix 10. J . O. A. Korff. The overall appraisal of brickwork
I to Min istry of Hou sing & Local Govern ment Circular buildings. Paper read at the Conference for Engineering
62/68. Institution of Structural En9ineers RP/68102. 1968. Tutors, Maidenhead 1978. Brick Developmen t Association.
Guidance on the design of domestic accommodation in 11. W. G. Curtin, G. Shaw, J . K. Beck & W. A. Bray. Design
loadbearing brickwork and blockwork to avo id collap se of brick diaphragm walls. Brick Development Associatio n.
following an Internal explosion. Institution of Structural Revised 1982 (Reprinted 1990).
Engineers RP/68/03. 1968. 12. W. G. Curtin, G. Shaw, J . K. Beck & W. A. Bray. Design
4. Th e Bu ild ing Regulations 1976 No. 1676. HMSO. of brick fi n walls in tall single-storey buildings. Brick
Reprinted 1978. Development Association . 1980.
5. J . Morton. S. R. Davies & A. W. Hendry. The stability of 13. N. F. Astbury et al. Gas explosions in loadbearing
loadbearing br ickwork structures following accident al brick structures. British Ceramic Research Association
damage to a major bearing wall or pier . Proceedings of SP68: 1970.
2nd International Brick Masonry Conference, edited West &
Speed. 1970.
Additional References (1996)
6. J . O. A. Korff. Accidental loading - Part II, Application.
14. The Building Regulations 1991. Approved Document
Proceedings of symposium on the struclu ral use of
A Structure A3 & A4 (1992 edition). HMSO.
masonry. The Institulion of Structural Engineers . 1974.
15. BS 5628. Use of Masonry: Part I: 1992. Stru ctural
7. J . B. Menzies & G. D. Grainger. Report on th e collapse
use of unre inforce d masonry. SSI Standards.
of the sports hall at Rockferry Comprehens iv e School,
Blrkenhead. Building Research Establishment Current 16. BS 5628. Use of Mas onry: Part 2: 1995. Stru ctural
Paper 69/76. 1976. use of re inforced and prestressed masonry. BSI
Standards.
The Building Regulations have been amended since the issue of the 1976 edition referenced in lhis publicalion, although the
requirements for accidental damage for five or more storey buildings have not altered significantly. The guidance given in BS 5628: Part
1: 1992 has not altered from the provisions in the 1978 version of that Code in respect of design for accidental damage. BS 5628: Part
2 was first published in 1985 and amended in 1995 and includes guidance for the selection of partial safety factors for material strength
for the accidental damage design of reinforced and prestressed masonry structures.
ReadfHS 8re expressly 8dvisfld thst whilst 1116 contents of this publication 8re believed to be BCCUrst9, correct and complete, no relisncfI should be placed upon its contents 8$ being
applicsbltt to any particulafCirCumstances. Any advice, opinionor information contained is publishedonly on the footing that the Brick Development Association. its servants or agents snd
sl1contributors to this pUblicstion shsll be under no liability whstsooll$f in respectof its contents.
Designed and produced to( the Brick Development Association, Woodside House, Winkfield, Windsor, Berkshire Sl 4 2DX. Tel. Winkfield Row (01344 885651)
Printed in England by P.L Blake l td.. Perivale. Middlesex