Notes:
7000 7000
0.8 1. Short-time-delay element is optional.
6000 6000
Long-Time The instantaneous element may be omitted.
5000 5000
0.9
Pickup 0.8C to 1.1C 2. For 50 Hertz operation of the following breakers
4000 equipped with Ground Trip element, the Short-Time 4000

pickup settings should not exceed the following max-


3000 3000
1.0 imums to avoid ground error signals possible due to
sensor saturation.
2000 Sensor Tap Max. Pickup 2000
1.1 Breaker Setting Setting
Type (Amperes) (Amperes)
AK, AKR-50 1200 14,000
1600 18,000
1000
AKT, AKRT-50 1600 16,000 1000
900 2000 20,000 900
800 800
700 700
600 600
500 500

400 Hi-Range Instantaneous H Suffix 400

300 300

200 200
40

Long-Time 60
Delay Bands
100 80 100
90 4 90
80 80
Maximum Total 100
70 70
60 Clearing Time 60
TIME IN SECONDS

TIME IN SECONDS
50 50

40 40
Minimum 3

30 Total 30
Clearing
Time 2
20 20

1.5

1
10 2.0 10
9 40 60 80 100 200 9
8 8
7
2.5 PERCENT OF SHORT-TIME RATING 7
6 6
5 3.0 5

4 4

3 4.0 3

2 2
5.0

1 7.0
Short-time MULTIPLES OF CURRENT SENSOR 1
.9 Pickup Points .9
.8 TAP SETTING, X .8
.7 .7
9.0
GES-6193

GES-6193
.6 .6
4000 Amp Sensor

Fixed Instantaneous
.5 Override D Option .5
2500 and 3000

Short-Time
Amp Sensors

Amp Sensors
200 To 2000

.4 Maximum .4
Delay Bands
.3 .3

Intermediate Application
.2 Determines Low Voltage Power
.2
End of Curve Circuit Breaker
Total Clearing Time
Minimum 9.0 15.0

.1 13.0 .1
.09 Molded Case and .09
.08 Insulated Case .08
TIME IN SECONDS

.07 Circuit Breaker


.07
Total Clearing Time
.06 .06
.05 .05

.04 .04

.03 .03

.02 .02

.01 .01
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
100

200

300

400

500
600

8
9
10

20

30

40

50
60
70
80
90
100

MULTIPLES OF CURRENT SETTING, C

GE Consumer & Industrial -


Electrical Distribution
Low-Voltage Power Circuit Breakers
POWER BREAK and Molded Case GES-6193
Programmer Set Points:
X = Current Sensor Taps (Amperes) Circuit Breakers with MicroVersaTrip Long Time Current Setting:
AKR-30 100, 150, 225, 300 or 300, 400, 600, 800 Solid-State Overcurrent Trip Device 50, 60, 70, 80, 85, 90, 95 and 100%
AKR-50 300, 400, 600, 800 or 600, 800, 1200, 1600 multiples of sensor current tap setting or rating (X).
Type AKR Pickup: 0.8, 0.9, 1.0, 1.1 multiples of the current setting (C).
AKRT-50 800, 1200, 1600, 2000
AKR-75 1200, 1600, 2000, 3200 Long-time-delay, Short-time delay Delay Bands: 1, 2, 3 and 4.
AKR-100 1600, 2000, 3000, 4000 and Special Instantaneous Units Short Time Pickup: 1.5, 2.0, 2.5, 3.0, 4.0, 5.0, 7.0 and 9.0
multiples of current setting (C). For 50 Hz operation,
Power Break and Molded Case Circuit Breakers Time-Current Curves see Note 2.
150, 200, 300, 400, 500, 600, 800, 1000, 1200, Curves apply at 50/60 Hertz Time Delay Bands: MIN, INT, MAX.
1600, 2000, 2500, 3000 and 4000 Amperes and from -20C to 70C Programmer Ambient. Instantaneous Adjustments: FIXED INSTANTANEOUS
Voltage Ratings: 600 Vac For 50 Hz operation see note above. OVERRIDE D Option. Pickup set at 15X for 200A through
2000A ratings, 13X for 2500A and 3000A Ratings.