Академический Документы
Профессиональный Документы
Культура Документы
Product Description
The A-ISOMETER model IRDH265 monitors the insulation
resistance level of ungrounded single and three-phase AC, DC
and AC/DC systems. The AC systems may include extensive DC
supplied loads (e.g. rectifiers, thyristor controlled DC drives) The
A1(+) A2(-) L1 (L/+) L2 (L/-) L3 AK device automatically matches to the system leakage capacitance.
A-ISOMETER TEST
k
Serie 260
1 ALARM 2
RESET
MONITOR
Coupling devices are available to extend the voltage range up to
6000V AC/DC.
The IRDH265 is fitted into a standard ABS plastic casing and is
suitable for quick assembly on support rail according to DIN EN 50
KE M+ M <LT> <PT> B A 11 12 14 21 22 24 022 and for screw mounting.
Operational Information
The A-ISOMETER IRDH265 is connected between the
ungrounded system and the equipment grounding conductor.
Via the buttons on the faceplate of the unit, setting of the set-point
values and other parameters can be carried out. The parameters
Dimension Diagram (mm)
are displayed on the LCD-display and are stored in a non-volatile
memory (EEPROM) after setting.
A pulsating AC measuring voltage is superimposed on the system.
The measuring pulse consists of positive and negative pulses of
74
Bender Inc. - 700 Fox Chase - Coatesville, PA 19320 - Toll-free: (800) 356-4266 - Fax: (610) 383-7100
Technical Data, IRDH265-... Please Note:
Insulation
Please check for correct supply voltage.
Rated insulation voltage AC 630 V
Rated impulse voltage / disturbance grade 6 kV / 3
Only one insulation monitoring device may be used in each
Operating mode continuous
interconnected (galvanically isolated) system.
Monitored System
System nominal voltage UN(AC) 3AC 0...690 V The terminals E and KE have to be connected separately to the
Operating range 0...1.15 UN equipment grounding conductor (GND) with one lead each. If
Frequency (for f<50Hz see manual) 50...400 Hz the device is connected with terminals L1, L2, L3, L/+ or L/- or an
System nominal voltage UN(DC) DC 0...500 V external coupling device to the system under operation, the
Operating range 0...1.3 UN connection between the terminals E and KE and the equipment
Supply Voltage grounding conductor (GND) may not be removed or open.
Supply voltage US See Ordering Guide for complete list
120V AC, 50..60Hz (standard) In order to check the proper connection of the device, it is
Operating range 0.8...1.15 US recommeded to carry out a funcational test using a genuine
Maximum self-consumption 5.8 VA ground fault, e.g. via a suitable resistance before starting
operation.
Alarm Response Values
Response value ALARM1 10 ... 990 k When insulation and voltage tests are to be carried out, the
Response value ALARM2 10 ... 990 k device must be isolated from the system for the test period.
Hysteresis approx. 25%
Measuring time (CE=1F / Mode=AMP) approx. 5 sec. The IRDH265-4... are delivered with the following basic settings:
Time delay (DC and UG/AMP mode only) 1 ... 10s
Response value, UG/AMP mode 0.1 ... 5mA Alarm 1 / Alarm 2 = 180k / 40k
Measuring time (CE=1F / Mode=UG/AMP) < 1sec.
Operating mode = Normally De-energized
System leakage capacitance max. 500F
(MENU: 11-12 14 / 21-22 24)
Measuring Circuit
Time delay = OFF (not necessary in AMP mode)
Measuring voltage UM (PEAK VALUE) 27 V
Measuring current IM max. 225 A Measuring mode = AMP
Internal DC resistance 120k
Impedance (60Hz) > 250 k Insulation faults in DC-circuits which are directly connected to
Outputs the AC system are only monitored correctly when the rectifiers
Measuring instrument SKMP 120 k carry a load current > 5...10mA.
Current output (max. load) 400 A (12.5 k)
Ordering Guide
Terminal [AK] for high-voltage coupling device Yes
Serial Communication Interface EIA RS485 Model Supply Voltage US Ordering #
Contact Configuration IRDH265-4 AC 230 V 91068001
Type 2 voltage-free SPDT contacts
Rated contact voltage AC 250 V / DC 300 V IRDH265-413 AC 90 ... 132 V 91068004
Rated current UC 5 A IRDH265-421 DC 10.5...80 V 91068002
Break capacity AC 230 V, p.f. = 0.4 AC 2 A
DC 220 V, L/R = 0.04s DC 0.2 A IRDH265-431 AC/DC 93...132 V 91068003
Operating mode Normally Energized / De-energized IRDH265-432 AC/DC 187..264 V 91068005
Testing
Dielectric test: Test voltage 3 kV
Accessories
Impulse voltage test acc. to IEC255-5 class III
Elec. disturbance test acc. to IEC255-5 class III High-voltage Coupling Devices
Elec. fast transient burst acc. to IEC801-4 severity degree 2
Shock resistance acc. to IEC68-2-27 15g / 11sec Model System voltage Ordering #
Vibration strength acc. to IEC68-2-6 10...15kHz / 0.15mm - 2g AGH204S AC 0...1500V 914013
Bumping acc. to IEC 68-2-29 40g / 11msec
AGH520S AC 0...6000V 913033
Environmental conditions
Operating temperature -10C ... +55C AGH150W DC 0 ... 1000V 915576
Storage temperature -40C ... +70C
Climatic class acc. to DIN 40040 F
External Panel-mount Meters
General Data
Type of connection screw terminals Model Dimensions Ordering #
Wire size, solid 14 AWG
7204S-1421 72x72mm 986804
Wire size, stranded with end sleeve 16 AWG
Mounting DIN rail or screw (#990 056) 9604S-1421 96x96mm 986774
Weight 2 lbs
Page 2 of 4
1.5 - 10.2A / Jan 1997
Bender Inc. - 700 Fox Chase - Coatesville, PA 19320 - Toll Free: (800) 356-4266 - Fax: (610)383-7100
IRDH265-4..
Wiring Diagram
11 UN
alarm LED yellow, illuminates 3 AC - System L1
Supply Voltage Alarmrelay
when the insulation level falls L2
RALARM1
US below the preset response value
12 14
L3
(see on
(depends nameplate)
unit ordered) RALARM1
L1 L2 L3
+/~ / ~ Alarm LED yellow, illuminates
when the insulation level falls 21
3N AC - System L1
below the preset response value L2
Alarmrelay L3
Fuse 6 A RALARM2
RALARM2 N
22 24
L1 L2 L3
Combined TEST/RESET-button AC - System L1
A1(+) A2(-) L1 (L/+) L2 (L/-) L3 AK
short-time pressing (<1s) = Reset
long-time pressing (>2s) = Test
A-ISOMETER TEST L2
Serie 260 k
RESET
1 ALARM 2 MONITOR
KE M+ M <LT> <PT> B A 11 12 14 21 22 24 L-
Insula
tion
(L/+) (L/-)
KE M+ M- <LT> <PT> B A
RS485
k Fuse 6 A
external test button,
if required 3 AC >690 V / 2
Achtung Hochspannung
Danger High Voltage
DC >500 V with
external k-measuring external reset button (N/C contact or wire bridge), 5 4
Ankopplungsgert
Typ AGH520S
3
coupling device
instrument (analog) when the terminals are open the fault alarm
will not be stored
PE
L1 (L/+) L2 (L/-) L3 AK
10 9 Serial Interface
Monitor Transmission protocol 9600 Baud - 1 Start bit - 1 Stop bit - 8 Data bits
8
AL1=250k R=193k
7 After each measurement update the following data block will be sent.
The data transmission is carried out continuously and cannot be
KE M+ M- <LT> <PT> B A 1 12 14 21 22 24
1 interrupted or influenced in some other way by any other bus member.
1 2 3 4 5 6
Start US= Unit seperator US US
02H 0H 30H 30H 30H 31H 32H 38H 0FH 30H 30H 30H 30H 30H 36H 30H 0FH
1 AL1 = Alarm 1, AL2 = Alarm 2
Mewert Ansprechwert
2 set response value (k) measuring value response value
Alarm 1 z.B. 60k
z.B. 128k
3 fault location
"+" = insulation fault at L+
"-" = insulation fault at L- US US US US End
"s" = new measuring value is being calculated
30H 30H 30H 31H 32H 30H 0FH 30H 0FH 30H 0FH 30H 0FH 03H
4 measuring value
5 unit measuring value (k = k) Ansprechwert
response value
30H = Kein/no
No AlarmAlarm
31H = Alarm 1
Alarm 2 z.B. 120k
32H = Alarm 2
6, 7, 8 operator buttons 33H = Alarm 1/2
30H = K1 off, K2 off 30H = AC Fault
Fehler/fault
9 TEST/RESET-button 31H = K1 on, K2 off 31H = DC- Fault
Fehler/fault
32H = K1 off, K2 on 32H = DC+
DC+ Fault
Fehler/fault
10 alarm LEDs Alarm1/Alarm 2 33H = K1 on, K2 on
Page 3 of 4
1.5 - 10.3A / Jan 1997
Bender Inc. - 700 Fox Chase - Coatesville, PA 19320 - Toll-free: (800) 356-4266 - Fax: (610) 383-7100
Response Time Setup 1
SETUP1
t (s)
35
PASSWORD: X X
30
RF = 1M
25
ALARM1=990k
ALARM1=10k
20
RF = 100k
15
ALARM2=10k ALARM2=990k
10
5 RF = 0...10k
K1: 12 - 11 14
K1: 12 11 - 14
2 3 4 5 6 7 8 9 10
K2: 12 11 - 14 K2: 12 - 11 14
CE (F)
t (s)
SETUP2[Y/N] N SETUP2[Y/N] Y
540
480
RF = 1M AL1=180k R= 150k
420 SETUP2
360
300
RF = 100k
240
180
Setup 2
120
RF = 0...10k
60 SETUP 2
ALARM2: AC OR DC
ALARM2: ONLY AC *)
U (V)
COUPLING TEST : OFF
10000 COUPLING TEST : ON
IRDH265+AGH520
FLASH: OFF FLASH: K1
IRDH265+AGH204S
1000 FLASH: K2
IRDH265
FLASH: K1/K2
100
RELAYTEST: ON RELAYTEST: OFF
TIME DELAY: ON
10 TIME DELAY: OFF
TIME: t = 1s TIME: t = 10s
0,2 50
0,1 1 10 100 f (Hz) CE MAX: 150F CE MAX: 500F
PASSWORD: ON
PASSWORD: OFF
RESET [Y/N] Y
RESET [Y/N] N
AL1=180k R= 150k AL2=040k R= 150k
SOFTWARE V XXXX
SETUP3[Y/N] Y
SETUP3[Y/N] N
SETUP1[Y/N] N SETUP1[Y/N] Y
AL1=180k R= 150k
SETUP3
SETUP1
Page 4 of 4
1.5 - 10.4A / Jan 1997
Bender Inc. - 700 Fox Chase - Coatesville, PA 19320 - Toll-free: (800) 356-4266 - Fax: (610) 383-7100