Вы находитесь на странице: 1из 1

GENERAL STRUCTURAL NOTE & TABLES

CONT. TOP BARS


CONT. TOP BARS ADD'L. TOP BARS
ADD'L. TOP BARS
1.0 GENERAL
1.01 DRAWINGS SHALL NOT BE SCALED, UNLESS DIRECTED BY THE ENGINEER.
1.02 SUBMIT SHOP DRAWINGS FOR ALL STRUCTURAL STEEL AND REINFORCING STEEL
FOR APPROVAL BEFORE FABRICATION.
1.03 FOR STRUCTURAL ELEMENTS, STRUCTURAL DIMENSIONS PREVAIL OVER
ARCHITECTURAL DRAWINGS.
NOTE 3.7 ANCHORED
NOTE 3.7 ANCHORED BOTTOM BARS
BOTTOM BARS ANCHORED
2.0 DESIGN LOADS BOTTOM BARS
ADD'L. BOTTOM BARS NOTE 6.1
2.01 BASIC DESIGN LOADS ARE AS INDICATED ON TABLE 1. LIVE LOADS SHALL NOT BE
EXCEEDED AT ANY TIME. NOTE 6.1
2.02 PARTITIONS: REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LAYOUT. DO NOT
ALTER PARTITION TYPES IF IT RESULTS
IN INCREASED WEIGHT. PROVIDE ALL NEEDED DOWELS AND ANCHORS BEFORE
POURING CONCRETE.
2.03 EQUIPMENT LOADS
COLUMN BEAM CONNECTION TRANSITION OF DIFF. BEAM TYP. DETAIL
- RECHECK EQUIPMENT LOADS SO THAT SLAB LOADS DO NOT EXCEED 1.9KPA,
INCLUDING MOUNTING PADS.
- IF LOAD EXCEEDS 1.9KPA, PROVIDE STEEL SPREADER BEAMS TO TRANSFER
LOADS TO BEAMS AND COLUMNS.
- SUBMIT CALCULATIONS AND SHOP DRAWINGS FOR SPREADER BEAMS.
- INSTALL HEAVY EQUIPMENT USING CRANES DIRECTLY TO FINAL POSITION
THRU WALL OPENINGS
- DO NOT BRING IN HEAVY EQUIPMENT THRU CORRIDORS, STAIRS OR ELEVATORS
UNLESS WITH PRIOR APPROVAL.
- LOCATIONS THAT CAN BE OVERLOADED BY PASSAGE OF HEAVY EQUIPMENT CONT. TOP BARS
BEAM CONT. TOP BARS
SHALL BE TEMPORARILY PROPPED DURING PASSAGE. ADD'L. TOP BARS
ADD'L. TOP BARS

3.0 STRUCTURAL DESIGN CRITERIA


3.01 APPLICABLE CODES: WORK SHALL BE GOVERNED BY ANY OR ALL OF THE FOLLOWING : NOTE 6.1
1. NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP), 2001 EDITION BY ASEP
GIRDER
2. UNIFORM BUILDING CODE, 1997 EDITION, VOLUME 1-3, BY ICBO
3. ACI BUILDING CODE 318-05 ANCHORED
4. AISC 1997 EDITION CONT.BOTTOM BARS BOTTOM BARS
5. ACI-315, MANUAL OF STANDARD PRACTICE FOR DETAILING CONCRETE
3.02 SOIL BEARING CAPACITY ADD'L. BOTTOM BARS
ADD'L. BOTTOM BARS
SOIL BEARING CAPACITY USED FOR DESIGN ARE AS FOLLOWS:
FOOTINGS RESTING ON SOIL 3500 PSF (167.58 KPA)
NOTE 6.1

4.0 EARTHWORK CANTILEVER BEAM TYP. DETAIL BEAM TO GIRDER DETAIL


4.01 EXCAVATE FOOTINGS AS SHOWN. FOOTINGS SHALL REST DIRECTLY ON
UNDISTURBED "ADOBE." IF LOOSE, SOFT OR POOR SUBGRADE IS FOUND, NOTIFY
THE DESIGN ENGINEER FOR RE-EVALUATION OF SOIL BEARING.
4.02 COMPACT ALL BACKFILL IN LAYERS NOT MORE THAN 150MM TO 90% DENSITY.
4.03 BELOW SLAB ON GRADE PROVIDE 50MM GRANULAR BASE COMPACTED TO 90% DENSITY.

5.0 CONCRETE
5.01 REFER TO TABLE 2 FOR CONCRETE STRENGTH, SLUMP AND AGGREGATE SIZE.
5.02 COMPACT CONCRETE WITH VIBRATORS AND CURE FOR AT LEAST 7 DAYS USING
APPROVED METHODS
5.03 PROVIDE ALL DOWELS, ANCHORS, EMBEDDED CONDUITS, MOULDINGS, GROOVES,
ETC. BEFORE POURING.

6.0 FORMWORK
6.01 REFER TO TABLE 3 FOR FORMWORK STRIPPING DURATIONS.
6.02 PROVIDE CAMBER FOR ALL BEAMS WITH MORE THAN 6.0M SPANS, AT LEAST 2MM PER

0.15
METER SPAN AND/OR AS DIRECTED BY THE ENGINEER.
6.03 CHAMFER OR ROUND ALL EXPOSED EDGES OF COLUMNS AND BEAMS 20MM IF
REQUIRED BY ARCHITECT.

7.0 REINFORCEMENT
7.01 REFER TO TABLE 4 FOR TENSILE STRENGTH OF REINFORCING STEEL. WHERE NOT
SPECIFIED, USE ASTM GRADE 415.
7.02 REFER TO TABLE 5 FOR MINIMUM CONCRETE COVER.
7.03 REFER TO TABLE 6 FOR HOOKS AND BENDS. ALL STIRRUPS AND TIES FOR FRAMES
SHALL BE SEISMIC HOOPS.
7.04 SPLICES-GENERAL:
- SPLICES MAY BE LAPPED BARS, WELDED OR MECHANICAL.
- SPLICES ARE ALLOWED ONLY WHERE INDICATED ON SHOP DRAWINGS
APPROVED BY THE ENGINEER. 1A SPOT DETAIL 'A'
- LAP SPLICES SHALL NOT BE LOCATED WITHIN JOINTS OR 2 TIMES MEMBER SCALE:
-
DEPTH FROM FACE OF JOINTS
- STAGGER SPLICES AT LEAST 600MM
100mm THK D10@250 TOP BARS
7.05 LAP BAR SPLICES: 3-D12 TOP BARS
- USE CLASS B TENSION SPLICES FOR ALL COLUMNS, BEAMS, SUSPENDED LIGHTWEIGHT CHB D10@100 TOP BARS
SLABS, ELEVATOR WALLS
- USE CLASS A SPLICES ONLY WHERE ALLOWED BY THE ENGINEER. LANDING BEAM
- INDIVIDUAL BAR SPLICES WITHIN A BUNDLE SHALL NOT OVERLAP. ENTIRE
BUNDLES SHALL NOT BE LAP SPLICED.

0.15
- PROVIDE HOOP REINFORCEMENT OVER LAP LENGTHS SPACED NOT MORE
THAN D/4 OR 100MM
7.06 WELDED SPLICES: D10 TIES @ 200MM
100mm THK O.C. D10@250 BOT BARS
- CONFORM TO STRUCTURAL WELDING CODE. LOAD BEARING CHBBARS
4-D12 CONT. D10@130 CONT. D10 STIRRUPS @ 200 O.C
- ALL WELDED SPLICES MUST DEVELOP AT LEAST 125% FY.
BOT BARS 3-D12 BOTTOM BARS
- WELDING OF STIRRUPS AND TIES TO MAIN BARS NOT ALLOWED.

8.0 MASONRY
8.01 REFER TO ARCHITECTURAL DRAWINGS FOR EXACT TYPE, LOCATION. IF NOT
SPECIFIED, REFER TO TABLE 9.
1B SPOT DETAIL 'B'
8.02 IF NOT SHOWN ON THE DRAWINGS, PROVIDE 2-12MM REBAR AT ALL CORNERS, - SCALE:
WALL INTERSECTIONS AND PERIMETERS OF ALL OPENINGS.
8.03 GROUT ALL CELLS CONTAINING REBAR.
8.04 SEAL AND GUARANTEE ALL EXTERIOR MASONRY WALL JOINTS WITH COLUMNS
AND BEAMS FROM WATER PENETRATION BY USING GROUTED TUBE WATERSTOP
SYSTEMS.

HEHERSON B. JUAN AS-BUILT (2) TWO-STOREY


RESIDENCE S - 02

Вам также может понравиться