CONDICIONES DE OPERACION 4
FACTORES DE CORRECCION
FACTORES DE CORRECCION FACTOR
ALTITUD
ZONA Segn C.N.E. Tomo IV-Norma IEC 137 DE CORRECCION
m.s.n.m. ALTITUD TEMPERATURA RESULTANTE
1000 I 0000 - 1000 1.0000 1.00 1.00
2000 II 1000 - 2000 1.1250 1.00 1.13
3000 III 2000 - 3000 1.2500 1.00 1.25
3100 IV 3000 - 3100 1.2625 1.00 1.26
3200 IV 3100 - 3200 1.2750 1.00 1.28
3300 IV 3200 - 3300 1.2875 1.00 1.29
3400 IV 3300 - 3400 1.3000 1.00 1.30
3500 IV 3400 - 3500 1.3125 1.00 1.31
3600 V 3500 - 3600 1.3250 1.00 1.33
3700 V 3600 - 3700 1.3375 1.00 1.34
3800 V 3700 - 3800 1.3500 1.00 1.35
3900 V 3800 - 3900 1.3625 1.00 1.36
4000 V 3900 - 4000 1.3750 1.00 1.38
4100 VI 4000 - 4100 1.3875 1.00 1.39
4200 VI 4100 - 4200 1.4000 1.00 1.40
4300 VI 4200 - 4300 1.4125 1.00 1.41
4400 VI 4300 - 4400 1.4250 1.00 1.43
4500 VI 4400 - 4500 1.4375 1.00 1.44
4600 VII 4500 - 4600 1.4500 1.00 1.45
4700 VII 4600 - 4700 1.4625 1.00 1.46
4800 VII 4700 - 4800 1.4750 1.00 1.48
4900 VII 4800- 4900 1.4875 1.00 1.49
5000 VII 4900 - 5000 1.5000 1.00 1.50
ANEXO N 2.1. SELECCION DEL NIVEL DE AISLAMIENTO DE REDES PRIMARIAS
NOTA: En la zona de proyecto, se tiene un nivel bajo (ligero) de contaminacin y Segn la Tabla II, de la Norma IEC-815
corresponde una mnima distancia de fuga especfica nominal de: 16 [mm/kV]
ANEXO N2.2. NIVELES DE CONTAMINACION AMBIENTAL Y DISTANCIAS DE FUGA
NORMA IEC 815:
GUIDE FOR THE SELECTION OF INSULATORS IN RESPECT OF POLLUTED CONDITIONS
TABLE I
1)
Use of fertilzens by spraying, or the buraing of crop residues, can lead to a higher pollution level due to
2) dispersal by
Distances wind.
from sea coast depend on the topography of the coastal area and on the extreme wind conditions.
TABLE II
2)
Ratio leakage distance measured between phase and earth over the r.m.s. phase value of the highest voltge
for the equipment ( see IEC publication 71-1)
Notes
1. In very lightly polluted areas, specific nominal creepage distances lower than 16 mm/kV can be used
depending on service experience 12 mm/kV seems to be a lower limit.
2. In the case of exceptional pollution severity, a especific nominal creepage distance of 31 mm/kV may not
be adequate. Depending on service experience and/or on laboratory test results, a higher value of specific
creepage distance can be used, but in some instances tha practicability of washing or greasing (see
Appendix B) may have to be considered.
TABLE III
1)
S.D.D. Salt Deposit Density.