Академический Документы
Профессиональный Документы
Культура Документы
PART A
The Ton of Refrigeration is the commonly used unit for refrigeration. It is defined as the quantity of heat
required to extract the heat from 1000 kg of water at 0o C into 1000 kg of ice at
0o C within 24 hours.
In summer air conditioning the air gains both sensible and latent heat. Hence the conditioning of air is
done by both cooling and dehumidification. In winter air conditioning, heating and humidification is done
to the air.
It is Room Sensible Heat Factor (RSHF) line. This line is drawn parallel to the base line in the
psychrometric chart.
The ratio of the difference between the mean surface temperature of the coil and leaving air temperature to
the difference between the mean temperature and the entering air temperature
BPF = td 3 - td 2
td3 - td1
5. What is the effect of sub cooling a refrigerant in a vapour compression cycle? `(Apr 2011)
6. What is dew point temperature? (Nov 2010) It is the temperature of air when the water vapour
present, begins to condense. It is measured by thermometer.
7. Define the COP of refrigeration. (Nov 2010) The coefficient of performance is the ratio of heat
extracted in the refrigerator to the work done on the refrigerant.
8. What is the basic difference between vapour compression and vapour absorption refrigeration
system? (Apr 2008) In vapour compression system a compressor is used, hence it is noisy. In vapour
absorption system compressor is not used, hence it is noiseless.
Vapour absorption differs from vapour compression system with a principle that, it uses heat energy
instead of mechanical energy.
Relative humidity is the ratio of mass of water vapour in the air in a given volume at a given
temperature to the mass of water vapour contained in the same volume at same temperature when the air is
saturated.
Heat pump takes the atmospheric air and supplies the heat to the air and the heat is rejected to the space to
be warmed.
Refrigerator extracts the heat from the space to be cooled and heat is given out to the atmosphere.
PART B
Vapour compression refrigeration system uses a liquefiable vapour as the refrigerant.In this system, the
main parts are Compressor, Condenser, Receiver, Throttle valve or Expansion valve, Evaporator
The Compressor in the system increases the temperature and pressure and changes the phase of
the working fluid which is the input power to the system. The working fluid is then passes through
the condenser which transfers the fluid heat to the surrounding keeping pressure constant. The high
pressure fluid is collected in the receiver The fluid is expanded using throttle valve which reduces
the pressure of the fluid, immediately the fluid passes through evaporator The evaporator is part
which absorbs the heat from the surrounding to make the fluid boil which phase changes back the
fluid to initial condition.
2. Explain the working principle of vapour absorption refrigeration cycle with
neat sketch.
Lithium Bromide water based vapour absorption system
Evaporator:Water as a
Refrigerant enters the evaporator at very low pressure and temperature. Since very low pressure is
maintained inside the evaporator the water exists in the partial liquid state and partial vapor state. This
water refrigerant absorbs the heat from the substance to be chilled and gets fully evaporated. It then
enters the absorber.
Absorber: In the absorber concentrated solution of lithium bromide is already available. Since water
is highly soluble in lithium bromide, solution of water-lithium bromide is formed. This solution is
pumped by the pump to the generator.
Generator: The heat is supplied to the refrigerant water and absorbent lithium bromide solution in the
generator from the steam or hot water. Due to heating water gets vaporized and it moves to the
condenser, where it gets cooled. As water refrigerant moves further in the refrigeration piping and
though nozzles, it pressure reduces and so also the temperature. This water refrigerant then enters the
evaporator where it produces the cooling effect. This cycle is repeated continuously. Lithium bromide
on the other hand, leaves the generator and reenters the absorber for absorbing water refrigerant.
The condenser water is used to cool the water refrigerant in the condenser and the water-Li Br
solution in the absorber. Steam is used for heating water-Li Br solution in the generator. To change the
capacity of this water-Li Br absorption refrigeration system the concentration of Li Br can be
changed.
Hot-Wet Weather:
When the air is hot and dry, humidification process has to be carried out
Sketch:
Mixing of streams is very frequently used in air conditioning, with addition or rejection of either
heat or moisture
Sensible heating:
When the air is passed over a surface with the temperature greater than air dry bulb
temperature, it undergoes sensible heating. It is achieved by passing the air over heater coils or
resistance coils.
Sensible cooling:
When the air is passed over a surface with the temperature less than air dry bulb
temperature, it undergoes sensible cooling. It is achieved by passing the air over evaporator coils.
10. A small-size cooling tower is designed to cool 5.5 litres of water per second,
the inlet temperature of which is 44C. The motor-driven fan induces 9 m3/s of
air through the tower and the power absorbed is 4.75 kW. The air entering the
tower is at 18C, and has a relative humidity of 60%. The air leaving the tower
can be assumed to be saturated and its temperature is 26C. Calculate, (i) The
amount of cooling water (make-up) required per second. (ii) The final
temperature of the water. Assume that the pressure remains constant
throughout the tower at 1.013 bar.
, ,
11. An ammonia refrigerator produces 30 tons of ice at 0 oC in a day of 24 hours.
The temperature range in the compressor is from 25 o C to -15oC. The vapour is
dry saturated at the end of compression. Assume a COP of 60 % of theoretical
value. Find power required to drive compressor. Assume latent heat of ice is
335 kJ/kg. For properties of ammonia refer table below: (AU May 2013)
Temperature Sg (kJ/kgK)
hf (kJ/kg) hg (kJ/kg) Sf (kJ/kgK)
(oC)
25 298.9 1465.8 1.124 5.039
-15 112.3 1426.5 1.4572 5.549
h3 = hg @ 25 oC = 1465.8 kJ/kg
Refrigeration effect = C.O.P actual x work done = 2.84 x (h3-h2) = 578.13 kJ/kg
Refrigeration capacity = 30 x 1000 x 335 kJ/per day = 10050000 / (24 x 60 x 60) kJ/s =
116.32 kJ/s
Mass flow rate of refrigerant = Refrigeration capacity / Refrigeration effect = 0.2 kg/s
Power required to drive the compressor = Mass flow rate of refrigerant x work done =
40 kW
12. (a) An office is to be air- conditioned for 50 staff when the outdoor conditions
are 30o C DBT and 75% RH if the quantity of air supplied is 0.4 m 3/ min /
person, find the following: (i) Capacity of the cooling coil in tones of
refrigeration, (ii) Capacity of the heating coil in kW, (iii) Amount of water
vapour removed per hour. Assume that required inlet conditions are 20 0 C DBT
and 60% RH. Air is first conditioned by cooling and dehumidifying and then by
heating. (12)
(b) Describe the factors that affect human comfort. (4) (AU May
2013)
@ 30o C DBT and 75% RH h1 = 82.5 kJ/kg of dry air vs1 = 0.89
3
m /kg of dry air
(i) capacity of cooling coil = ma (h1 h2) = 1089.8 kJ/min = 5.19 tons of
refrigeration
(ii) capacity of heating coil = ma (h3 h2) = 3.37 kW
(iii) amount of water vapour removed = ma(w1-w2) x 60 = 16.18 kg/hr
(b) The comfort of the human body depends primarily on three factors: the(dry-bulb)
temperature, relative humidity, and air motion .The temperature of the environment is the
single most important index of comfort.
Most people feel comfortable when the environment temperature is between 22 and 27C
(72 and 80F). The relative humidity also has a considerable effect on comfort since it
affects the amount of heat a body can dissipate through evaporation. Relative humidity is a
measure of airs ability to absorb more moisture. High relative humidity slows down heat
rejection by evaporation, and low relative humidity speeds it up. Most people prefer a
relative humidity of 40 to 60 %. Air motion also plays an important role in human comfort. It
removes the
warm, moist air that builds up around the body and replaces it with fresh air. Therefore, air
motion improves heat rejection by both convection and evaporation. Air motion should be
strong enough to remove heat and moisture
from the vicinity of the body, but gentle enough to be unnoticed. Most people feel
comfortable at an airspeed of about 15 m/min. Very-high-speed air motion causes
discomfort instead of comfort.
Some liquids like water have great affinity for absorbing large quantities of certain
vapors (NH3) and reduce the total volume greatly. The absorption refrigeration
system differs fundamentally from vapor compression system only in the method of
compressing the refrigerant. An absorber, generator and pump in the absorption
refrigerating system replace the compressor of a vapor compression system. Figure
shows the schematic diagram of a vapor absorption system. Ammonia vapor is
produced in the generator at high pressure from the strong solution of NH3 by an
external heating source. The water vapor carried with ammonia is removed in the
rectifier and only the dehydrated ammonia gas enters into the condenser. High
pressure NH3 vapor is condensed in the condenser. The cooled NH3 solution is passed
through a throttle valve and the pressure and temperature of the refrigerant are
reduced below the temperature to be maintained in the evaporator. The low
temperature refrigerant enters the evaporator and absorbs the required heat from the
evaporator and leaves the evaporator as saturated vapor. Slightly superheated, low
pressure NH3 vapor is absorbed by the weak solution of NH3 which is sprayed in the
absorber. Weak NH3 solution (aquaammonia) entering the absorber becomes strong
solution after absorbing NH3 vapor and then it is pumped to the generator through
the heat exchanger. The pump increases the pressure of the strong solution to
generator pressure. The strong NH3 solution coming from the absorber absorbs heat
form high temperature weak NH3 solution in the heat exchanger. The solution in the
generator becomes weak as NH3 vapor comes out of it. The weak high temperature
ammonia solution from the generator is passed to the heat exchanger through the
throttle valve. The pressure of the liquid is reduced to the absorber pressure by the
throttle valve.