Zone Design Load Summary for GF-AHU-01 w heat/humidifier

Project Name: DG Affairs- Office rev. 1 08/27/2011


Prepared by: abc 07:22AM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 0600 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.9 C / 28.2 C HEATING OA DB / WB 12.0 C / 10.0 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m 4587 - 44 m - -
Wall Transmission 170 m 2956 - 170 m 914 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 44 m 3035 - 44 m 1331 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 3 m 88 - 3 m 39 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 174 m 3840 - 174 m 0 -
Ceiling 29 m 911 - 29 m 0 -
Overhead Lighting 10325 W 9916 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 12400 W 12181 - 0 0 -
People 236 16108 14179 0 0 0
Infiltration - 2615 2411 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 8436 2488 0% 0 0
>> Total Zone Loads - 64673 19078 - 2284 0

Hourly Analysis Program v.4.3 Page 1 of 1