LANGONE & ASSOCIATES


87 EMERALD COURT
PROPOSED TEWKSBURY, MASSACHUSETTS 01876
OSWEGO (978) 851-0198
50KW
PROPOSED DIESEL DRAWN BY: SEAN M. SPARKS
OSWEGO COUNTY GENERATOR
SHELTER CUSTOMER:
11.5' X 20'
OSWEGO COUNTY
DEPARTMENT OF EMERGENCY
COMMUNICATIONS

INTEROPERABLE COMMUNICATIONS
PROJECT
APPENDIX 1
350' SELF SUPPORT
COMMUNICATIONS TOWER GENERIC SITE PLAN WITH
60 NAME
CO-LOCATE
FENCED COMPOUND SIZE
60' X 80' DATE: APRIL 12, 2010

SITE DATA: GENERIC W/ CO-LOCATE

SCALE: 1/8" = 1'

PAGE SIZE: 11" X 17"


PROPOSED
SHEET: 1 OF 8
CO-LOCATE SHELTER
8'3" X 12'6" SHEET DATA GENERAL DETAIL

DRAWING #: 2010-0002

REVISION HISTORY:

APRIL 16, 2010 LAYOUT CHANGE

APRIL 19, 2010 ADD SHEETS 2-6


PROPOSED CO-LOCATE
20KW GENERATOR APRIL 22, 2010 ADD SHEETS 7-8
UTILITY DEMARCATION
ELECTRIC/TELCO
CO-LOCATE 500 GAL PROPANE TANK
12'-0"

POWER COMPANY TRANSFORMER

PROPOSED BOLLARDS
LANGONE & ASSOCIATES
87 EMERALD COURT
TEWKSBURY, MASSACHUSETTS 01876
(978) 851-0198

DRAWN BY: SEAN M. SPARKS


CUSTOMER:

OSWEGO COUNTY
DEPARTMENT OF EMERGENCY
COMMUNICATIONS

INTEROPERABLE COMMUNICATIONS
PROJECT
APPENDIX 1

GENERIC SITE PLAN WITH


NAME
CO-LOCATE

DATE: APRIL 12, 2010

SITE DATA: GENERIC W/ CO-LOCATE

SCALE: 1/8" = 1'

PAGE SIZE: 11" X 17"

SHEET: 2 OF 8

SHEET DATA UTILITY DETAIL

DRAWING #: 2010-0002

REVISION HISTORY:

APRIL 16, 2010 LAYOUT CHANGE

APRIL 19, 2010 ADD UTILITY DETAIL

12'-0"
OSWEGO COUNTY
THE VENDOR WILL PROVIDE FOR THE TRENCHING AND PLACEMENT OF THREE, (1) INCH AND TWO, THREE (3) INCH SCH-40 PVC
1 CONDUITS FROM THE SHELTER UTILITY DEMARCATION POINT TO THE FOLLOWING. A SINGLE (3) INCH CONDUIT WILL TERMINATE LANGONE & ASSOCIATES
PURCHASE POWER 200 AMPS - 2" SCHEDULE 40 PVC AT THE VENDOR PROVIDED ELECTRICAL METER HUB RISER. THE REMAINING CONDUITS WILL TERMINATE BETWEEN THE SHELTER 87 EMERALD COURT
A1
UTILITY DEMARCATION POINT AND THE GENERATOR FOUNDATION STUB-UP POINT. ALL PVC CONDUITS WILL CONFORM TO NEC TEWKSBURY, MASSACHUSETTS 01876
(978) 851-0198
2 AND APPLICABLE CODES; CONDUIT ABOVE 24 DEPTH GRADE SHALL BE SCHEDULE 80.
GENERATOR POWER - 2" SCHEDULE 40 PVC
A1
DRAWN BY: SEAN M. SPARKS
ONLY SWEEPS WILL BE USED WHEN/WHERE NINETY (90) DEGREE ANGLES MUST BE MADE. EACH CONDUIT WILL BE PROVISIONED
3 WITH TWO PULL LINES CAPABLE OF PULLING ELECTRICAL AND OR COMMUNICATIONS WIRE BETWEEN THE END POINTS. REFERENCE CUSTOMER:
GENERATOR SIGNALING - 1" SCHEDULE 40 PVC
A1 MAY BE MADE TO THE ATTACHED TYPICAL SITE PLAN. AT THE GENERATOR PAD, STUB-UPS WILL BE TEN (10) INCHES ABOVE TOP
OSWEGO COUNTY
OF PAD SURFACE.
4 DEPARTMENT OF EMERGENCY
GENERATOR SIGNALING - 1" SCHEDULE 40 PVC COMMUNICATIONS
A1
VENDOR SHALL HAVE INSTALLED BY A QUALIFIED ELECTRICIAN FOLLOWING; ALL PER NEC, UL, AND LOCAL CODES: A 120/240,
5 200 AMP SERVICE BETWEEN THE ELECTRICAL UTILITY DEMARCATION POINT/METER HUB AND THE 200 AMP TRANSTECTOR
INTEROPERABLE COMMUNICATIONS
GENERATOR SIGNALING - 1" SCHEDULE 40 PVC TRANSFER PANEL LOCATED INSIDE THE COUNTY PROVIDED COMMUNICATIONS SHELTER.
A1 PROJECT
APPENDIX 1
11 AT A POINT OF ~3-FT INSIDE THE COMPOUND FENCE THE VENDOR WILL INSTALL A FOUR (4) METER HUB CABINET USING TWO EA.
TELCO - 1" SCHEDULE 40 PVC 3-IN SCH-40 GALVANIZED PIPE RISERS, THESE RISERS WILL BE SET IN MINIMUM 2500-PSI CONCRETE TO A DEPTH OF THREE (3)
A1 NAME
GENERIC SITE PLAN WITH
FEET, AND MINIMUM 12-IN DIA. FOUNDATIONS. THE METER(S) SHALL BE VISUAL FROM OUTSIDE THE FENCE. THREE OF THE METER CO-LOCATE

SOCKETS WILL BE COVERED FOR FUTURE USE. DATE: APRIL 12, 2010
PROPOSED CO-LOCATE
SITE DATA: GENERIC W/ CO-LOCATE
THE VENDORS ELECTRICIAN WILL BE RESPONSIBLE FOR THE COMPLETE INSTALLATION INCLUDING TRENCHING OF BURIED SERVICE
PER THE ELECTRICAL UTILITY COMPANY SERVING THE SITE LOCATION. SCALE: 1/8" = 1'
6 PAGE SIZE: 11" X 17"
PURCHASE POWER 200 AMPS - 2" SCHEDULE 40 PVC
A1 ALL CONDUIT WILL TERMINATE IN A PRE-INSTALLED PULL BOX MOUNTED ON THE SHELTER. A 200 AMP DISCONNECT WILL BE SHEET: 3 OF 8
PROVIDED AND INSTALLED AT THE ELECTRICAL UTILITY DEMARCATION/METER LOCATION. THE VENDOR WILL ALSO HAVE
7 SHEET DATA UTILITY NOTES
GENERATOR POWER - 2" SCHEDULE 40 PVC INSTALLED BETWEEN THE 50KW GENERATOR AND THE SHELTER A 200 AMP SERVICE TERMINATED TO THE TRANSTECTOR
A1 DRAWING #: 2010-0002
TRANSFER PANEL (ATS) EMERGENCY POWER BUSS. VENDOR SHALL INSTALL A 120 VAC, 20 AMP SERVICE BETWEEN THE

8 TRANSTECTOR SERVICE PANEL AND THE GENERATOR TO SERVICE THE JACKET WATER HEATER AND BATTERY CHARGING UNIT. REVISION HISTORY:
GENERATOR SIGNALING - 1" SCHEDULE 40 PVC
A1 APRIL 16, 2010 LAYOUT CHANGE
THE THREE (3) INCH CONDUIT INSTALLED BETWEEN THE GENERATOR AND THE SHELTER SHALL BE USED TO PROVISION THE
APRIL 19, 2010 ADD UTILITY NOTES
9 GENERATOR BACKUP ELECTRICAL SERVICE TO THE SHELTER ATS. THE FIRST 1-INCH CONDUIT SHALL BE USED TO PROVISION THE
GENERATOR SIGNALING - 1" SCHEDULE 40 PVC 20-AMP 120VAC CIRCUIT FOR THE GENERATORS CHARGER/HEATER, THE SECOND 1-INCH CONDUIT SHALL BE USED TO PROVISION
A1
THE GENERATORS CONTROL WIRING, THE THIRD 1-INCH CONDUIT SHALL BE USED TO PROVISION THE GENERATOR ALARM WIRING,
10 AND SHALL BE INSTALLED BETWEEN THE GENERATOR LOCAL CONTROL PANEL, TO THE ALARM ANNUNCIATION PANEL INSIDE THE
GENERATOR SIGNALING - 1" SCHEDULE 40 PVC
A1 SHELTER. THE VENDOR WILL PROVIDE THE ALARM CABLING; RAYCHEM WIRE & CABLE, CHEMINAX REMOTE ANNUNCIATOR
CABLE PT. NO. 2019D0309-0 (OR APPROVED EQUAL).
12
TELCO - 1" SCHEDULE 40 PVC
A1 THE VENDOR WILL PROVIDE ALL END TO END CONNECTIVITY BETWEEN THE SHELTER AND THE PROVIDED UTILITY ELECTRICAL
DEMARK, AND ALL CONNECTIVITY BETWEEN THE SHELTER AND THE 50-KW GENERATOR. THE GENERATOR WILL BE PROVIDED
13 AND SET BY OTHERS. ONCE THE GENERATOR IS IN PLACE THE VENDOR SHALL (USING , PT. NO. LAGSHIELD750LONG; USS
PROPANE FUEL LINE
A1 FLAT WASHER, GR 2, HDG WUSSGR2012-000HDG; AND HEX LAG SCREW, GR 2, ZINC X 3, PT NO.
HLAGGR2012C056ZN) SECURE THE GENERATOR TO THE CONCRETE PAD USING THREE LAG SCREWS END MIDDLE END ALONG
EACH SIDE OF THE GENERATOR FUEL TANK RAIL.
LANGONE & ASSOCIATES
87 EMERALD COURT
TEWKSBURY, MASSACHUSETTS 01876
(978) 851-0198

DRAWN BY: SEAN M. SPARKS


CUSTOMER:

OSWEGO COUNTY
DEPARTMENT OF EMERGENCY
COMMUNICATIONS

INTEROPERABLE COMMUNICATIONS
PROJECT
APPENDIX 1

GENERIC SITE PLAN WITH


NAME
CO-LOCATE

DATE: APRIL 12, 2010

SITE DATA: GENERIC W/ CO-LOCATE

SCALE: 1/8" = 1'

PAGE SIZE: 11" X 17"

SHEET: 4 OF 8

SHEET DATA GROUNDING DETAIL

DRAWING #: 2010-0002

REVISION HISTORY:

APRIL 16, 2010 LAYOUT CHANGE

APRIL 19, 2010 ADD GROUNDING PAGE

12'-0"

ALL GROUNDING, MATERIAL, CONNECTIONS AND PLACEMENT SHALL BE PER


MOTOROLA R-56 STANDARD 2005, INCLUDING REVISIONS, IF ANY.
ALL GROUNDING SHALL MEET CURRENT MOTOROLA R-56 STANDARDS (REV. 9/05). LANGONE & ASSOCIATES
87 EMERALD COURT
TEWKSBURY, MASSACHUSETTS 01876
THE TOWER ONCE INSTALLED, SHALL BE GROUNDED FROM EACH OF THE TOWERS THREE LEGS TO A HALO GROUND RING. GROUND
(978) 851-0198
WIRE ATTACHMENT WILL BE VIA A STEEL TAB WELDED AND MADE A PART OF THE BASE FLANGE OF EACH TOWER LEG. ALL BONDING TO
THE TOWER TAB AND GROUND RODS AND ANY INTEGRATED SPLICES WILL BE BY EXOTHERMIC BONDING ONLY. NO BONDING DIRECTLY DRAWN BY: SEAN M. SPARKS
TO THE TOWER LEG IS PERMITTED.
CUSTOMER:
A HALO GROUND WILL ALSO BE INSTALLED AROUND THE COMMUNICATIONS SHELTER FOUNDATION AND GENERATOR FOUNDATION AND OSWEGO COUNTY
BONDED TO THE TOWER HALO. ONLY TINNED COPPER GROUND WIRES PER MOTOROLA R-56 STANDARD WILL BE PROVIDED FOR
DEPARTMENT OF EMERGENCY
FINAL CONNECTION TO THE SHELTER BUSS BAR AND GENERATOR GROUNDING POINT AS DIRECTED BY THE NETWORK COMMUNICATIONS
COMMUNICATIONS
INFRASTRUCTURE ADMINISTRATOR FOR FINAL ATTACHMENT BY THE VENDOR AT THE INSTALLATION OF BOTH THE SHELTER AND
GENERATOR. ALL FOUR CHAIN LINK FENCE CORNER POSTS AND GATE POSTS SHALL BE BONDED TO THE HALO GROUND.
INTEROPERABLE COMMUNICATIONS
PROJECT
GROUNDING SYSTEM IS TO ADHERE TO MOTOROLA R-56 STANDARDS FOR FIXED NETWORK EQUIPMENT - TOWER SITES OR EQUAL. APPENDIX 1
THE GROUND SYSTEM SHALL CONNECT TO THE EQUIPMENT SHELTERS SINGLE POINT GROUND SYSTEM ACCORDING TO THE MOST
RECENT R-56 STANDARDS. AFTER THE GROUNDING SYSTEM IS INSTALLED, THE VENDOR SHALL PERFORM AND RECORD GROUND GENERIC SITE PLAN WITH
NAME
SYSTEM TESTING USING ONE OF THREE METHODS: THREE-POINT/FALL-OF-POTENTIAL TESTING, CLAMP-ON OHMMETER, COMBINED SOIL CO-LOCATE

RESISTIVELY TESTING WITH CLAMP-ON OHMMETER TESTING DATE: APRIL 12, 2010

SITE DATA: GENERIC W/ CO-LOCATE


A GROUNDING BUSS BAR SHALL BE PROVIDED AT THE POINT ON THE TOWER WHERE THE COAX TRANSITIONS TO ATTACH TO THE
SCALE: 1/8" = 1'
WAVEGUIDE-BRIDGE. BUSS BAR WILL BE ATTACHED TO THE TOWER GROUNDING RING BY TINNED 2/0 SOLID COPPER.
PAGE SIZE: 11" X 17"

SHEET: 5 OF 8

SHEET DATA GROUNDING NOTES

DRAWING #: 2010-0002

REVISION HISTORY:

APRIL 16, 2010 LAYOUT CHANGE

APRIL 19, 2010 ADD GROUNDING NOTES


2
B1

LANGONE & ASSOCIATES


87 EMERALD COURT
TEWKSBURY, MASSACHUSETTS 01876
(978) 851-0198

DRAWN BY: SEAN M. SPARKS


CUSTOMER:

OSWEGO COUNTY
DEPARTMENT OF EMERGENCY
COMMUNICATIONS

INTEROPERABLE COMMUNICATIONS
1
B1 PROJECT
3 APPENDIX 1
6 B1
B1
GENERIC SITE PLAN WITH
NAME
CO-LOCATE

DATE: APRIL 12, 2010

SITE DATA: GENERIC W/ CO-LOCATE

SCALE: NOT TO SCALE

PAGE SIZE: 11" X 17"

SHEET: 6 OF 8

SHEET DATA FOUNDATIONS

DRAWING #: 2010-0002

REVISION HISTORY:

APRIL 16, 2010 LAYOUT CHANGE

APRIL 19, 2009 ADD FOUNDATIONS

4
B1
7
B1

5
B1

1-B1 CO-LOCATE SHELTER


2-B1 CO-LOCATE SHELTER
3-B1 PROPANE TANK FOUNDATION
4-B1 20KW GENERATOR FOUNDATION
5-B1 20KW GENERATOR FOUNDATION
6-B1 OSW EQUIPMENT SHELTER FOUNDATION
7-B1 OSW GENERATOR FOUNDATION
VENDOR SHALL PROVIDE CONCRETE FOUNDATION FOR COUNTY PREFABRICATED COMMUNICATIONS SHELTER. THE SUCCESSFUL VENDOR WILL ASSURE THAT ONLY CONCRETE
FROM, OR THE AGGREGATE (SAND/STONE) MATERIAL USED WILL BE AS SPECIFIED AS COMING FROM A NYS DOT APPROVED COMPANY FOR USE WITH THESE FOUNDATIONS.
LANGONE & ASSOCIATES
CONCRETE WILL BE A MINIMUM OF 4000-LBS AT 28-DAYS CURE. SLAB ON GRADE FOUNDATIONS ARE THE PREFERRED DESIGN FOR THIS PROJECT, FOR BOTH THE SHELTER AND 87 EMERALD COURT
GENERATOR SET SYSTEMS. THE FOLLOWING TYPICAL SPECIFICATIONS WILL BE USED FOR THEIR CONSTRUCTION: TEWKSBURY, MASSACHUSETTS 01876
(978) 851-0198
1.) SHELTER FOUNDATION: EXCAVATE TO A DEPTH OF TWENTY-FOUR (24) INCHES BELOW GRADE. SLAB ON GRADE AREA SIZE 12-FT X 20-FT.
DRAWN BY: SEAN M. SPARKS
2.) COMPACT TO GRADE, USING 6 LIFTS AT 95% COMPACTION RUN-OF-CRUSH STONE. CUSTOMER:

3.) BOTH FOUNDATIONS: PREPARE FORMS TO ACHIEVE A CONCRETE SLAB EIGHT (8) INCHES FOR SHELTER FOUNDATION AND TEN (10) INCHES THICK FOR GENERATOR OSWEGO COUNTY
FOUNDATION AS DELINEATED IN THE ATTACHED DRAWING(S). NO CONTROL JOINTS ARE CALLED FOR OR WILL BE ACCEPTED. ATTAIN A FINAL SLAB ELEVATION FOUR (4) INCHES DEPARTMENT OF EMERGENCY
ABOVE GRADE. THE FINISHED SIDES OF EACH FOUNDATION MUST BE WITHIN 1/8 DEVIATION (NO BOWING WILL BE PERMITTED) OF SPECIFIED FINISHED LENGTH AND WIDTH OVER COMMUNICATIONS
THE ENTIRE PERIMETER OF THE FOUNDATION SLAB.
INTEROPERABLE COMMUNICATIONS
4.) ATTACHED TO AND MADE A PART OF THE PAD WILL BE A 5 FT X 4.5 FT. STOOP TO BE USED FOR ENTRY TO THE SHELTER. BOTH WILL BE POURED AT THE SAME TIME PROJECT
AND BE CONNECTED AS ONE. UPON COMPLETION OF THE SHELTER DELIVERY, A SINGLE GRIP STRUT (OR EQUAL) STEP OF 12-GA STEEL, 24-IN. WIDE, 2.5-IN DEEP AND FIVE APPENDIX 1
(5) FEET LONG SHALL BE PLACED ON THE STOOP IN FRONT OF THE SHELTER DOOR TO ACT AS A NON-SKID STEP.
GENERIC SITE PLAN WITH
NAME
CO-LOCATE
5.) GENERATOR FOUNDATION TO BE 126-IN L. X 64-IN.W AND 10.0-IN D.
DATE: APRIL 12, 2010

6.) BOTH FOUNDATIONS. USING CHAIRS (HOUSE BRICK ACCEPTABLE) INSTALL WELDED WIRE FABRIC, 4 X 4 - W2.9 X W2.9 WELDED WIRE FABRIC; MAINTAIN THREE (3) SITE DATA: GENERIC W/ CO-LOCATE
INCHES FROM SIDES. SCALE: NOT TO SCALE

PAGE SIZE: 11" X 17"


7.) FOR BOTH FOUNDATIONS - PROVIDE 4000-PSI CONCRETE, USING 1 & 2 STONE, SAND (AS SPECIFIED ABOVE), AIR ENTRAINED AND 1.5-LBS OF FIBERMESH 300 FIBER PER
YARD. SHEET: 7 OF 8

SHEET DATA FOUNDATIONS

8.) FOR BOTH FOUNDATIONS - POUR AND FINISH CONCRETE TO A FLAT AND LEVEL SURFACE WITH NOT MORE THEN 1/8 DEVIATION OVER THE SLABS ENTIRE SURFACE. DRAWING #: 2010-0002

REVISION HISTORY:
9.) CONCRETE SHALL NOT BE POURED DURING RAIN PERIODS. CONCRETE AFTER POURING AND FINISHING, WILL (WHEN OR IF IN DIRECT SUNLIGHT) BE COVERED TO PROTECT
FROM HIGH TEMPERATURES. STRESS CRACKS FOR ANY REASON NOTED PRIOR TO THE SHELTER BEING INSTALLED WILL REQUIRE THE REMOVAL OF THE PAD AND A REPLACEMENT APRIL 22, 2010 ADD FOUNDATION NOTES

PROVISIONED BY THE BIDDER AT THEIR COST.

REFER TO ATTACHED DRAWINGS FOR FURTHER DETAILED INFORMATION ON SHELTER AND GENERATOR FOUNDATIONS.

NOTE: ONCE FOUNDATIONS ARE COMPLETED AND THE TOWER ERECTED; BOTH THE SHELTER AND GENERATOR SET WILL BE DELIVERED BY OTHERS TO EACH SITE AND OFF
LOADED AND PLACED ON THEIR RESPECTIVE FOUNDATIONS BY THE BIDDER.
THE VENDOR WILL PROVIDE A SECURITY FENCE AROUND THE TOWER COMPOUND AREA WITH 12-FT WIDE DOUBLE SWING GATE. THE TOWER COMPOUND INCLUDING GATE WILL BE ~60-FT X
~80-FT, UNLESS OTHERWISE SPECIFIED. THE TOP RAIL WILL BE NOT LESS THAN 6-FT ABOVE GRADE. BARBED-WIRE WILL BE PLACED 1-FT ABOVE THE TOP ELEVATION. FENCE FABRIC WILL BE
LANGONE & ASSOCIATES
87 EMERALD COURT
FLUSH TO GRADE.
TEWKSBURY, MASSACHUSETTS 01876
(978) 851-0198
NOT ALL SITES WILL REQUIRE A NEW SECURITY FENCE. SOME SITES WILL REQUIRE EXPANSION OF THE EXISTING FENCE. REFER TO APPENDIX #1 FOR DETAILS.
DRAWN BY: SEAN M. SPARKS
ALL MATERIAL AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE ASTM REQUIREMENTS FOR INDUSTRIAL FENCE SYSTEMS, AND INCLUDE BUT NOT BE LIMITED TO: METALLIC COATED
CUSTOMER:
CARBON STEEL BARBED WIRE, GALVANIZED BEFORE WEAVING STEEL FENCE FABRIC, METAL-COATED STEEL WIRE FOR CHAIN-LINK FENCE FABRIC AND TENSION WIRE, READY MIXED CONCRETE
(3K-PSI), INSTALLATION OF CHAIN LINK FENCE, FENCE FITTINGS, INDUSTRIAL SWING GATES, STRENGTH AND PROTECTIVE COATINGS ON METAL INDUSTRIAL CHAIN-LINK FRAMEWORK, PIPE, PIPE OSWEGO COUNTY
CAPS, STEEL AND HOT-DIPPED (2.OZ) GALVANIZED WELD FOR FENCE STRUCTURES. ALL PIPES WILL BE SCH-40. THE 4 CORNER POSTS AND 2 GATE POSTS WILL BE BONDED TO THE HALO DEPARTMENT OF EMERGENCY
GROUND. COMMUNICATIONS

OTHER MINIMUM REQUIREMENTS INCLUDE BUT ARE NOT LIMITED TO: FENCE MESH WIRE NOT LIGHTER THAN 9-GA., MESH SIZE 2-INCHES, TOP RAIL NOT SMALLER THEN 1-5/8-INCHES, LINE INTEROPERABLE COMMUNICATIONS
POST NOT SMALLER THEN 2.5-INCHES AND TERMINAL POST NOT LESS THAN 3-3/4-INCHES. ALL TERMINAL POSTS WILL BE PLACED IN AN EXCAVATED PIER 10-INCH IN DIAMETER AND TO A PROJECT
DEPTH OF NOT LESS THAN 42. LINE POSTS WILL BE PLACED IN AN EXCAVATED PIER 8-INCH IN DIAMETER, AND TO A DEPTH OF NOT LESS THAN 36-INCHES. THERE WILL BE NOT LESS THAN AN APPENDIX 1
ADDITIONAL 6-INCH OF #2 STONE PLACED AT THE BOTTOM OF EACH EXCAVATED PIER.
GENERIC SITE PLAN WITH
NAME
CO-LOCATE
GATE FRAME WORK WILL BE NOT LESS THAN 3-3/4-INCHES O.D. SCH-40 GALVANIZED PIPE TOP, AND THE BOTTOM NOT LESS THAN 2.5-INCHES O.D. SCH-40. HORIZONTAL UP RIGHTS WILL BE
NOT LESS THAN 2.25-INCHES O.D, AND GALVANIZED TUBING DIAGONAL MEMBERS NOT LESS THAN 2-INCHES. GATE FABRIC AND BARBED WIRE WILL BE THE SAME AS THE FENCE. DATE: APRIL 12, 2010

SITE DATA: GENERIC W/ CO-LOCATE

SCALE: NOT TO SCALE

PAGE SIZE: 11" X 17"

SHEET: 8 OF 8

SHEET DATA FOUNDATIONS

DRAWING #: 2010-0002

REVISION HISTORY:

APRIL 22, 2010 ADD MISC NOTES