Академический Документы
Профессиональный Документы
Культура Документы
LEVEL 1
27-MAY 2003
3. Corrosion
A. Introduction
B. Types of Corrosion
C. Factors Affecting Corrosion
D. Methods of Corrosion Control
E. Corrosion Inhibitors
4. Deposition
A. Introduction
B. Types of Deposits
C. Factors Affecting Scaling
7. Glossary of Terms
8. Self-Review Guide
GPS//2003
B. Cooling Towers
i) Types of Towers
ii) Definitions
iii) Cooling Process
C. Heat Exchangers
Industrial cooling water systems have one function to remove unwanted heat, regardless of
whether the heat is generated in a process or in an office building. The objective is to design
a suitable cooling system that will be capable of absorbing unwanted heat and transporting it
to where it can be rejected.
Cooling water systems vary considerably in design, function and operation; those of interest
to us are systems that employ water as the cooling media. The purpose of this section will be
to discuss the design and operation characteristics of cooling water systems, including heat
exchangers.
ONCE THROUGH
CLOSED (CHILLED)
OPEN RECIRCULATING
HEAT ABSORPTION
e.g. HEAT EXCHANGER, etc.
WARM WATER
TO SEWER
Figure 1.1 illustrates a once through cooling water system. As can be seen, the cooling media
(water) is pumped from its source through a point of heat exchange where it absorbs the heat
and transports the heat to a point of discharge. In this system, we have heat absorption and
rejection with the water only being used once prior to discharge.
2
GPS//2003
EXPANSION
VALVE
The system illustrated in Figure 1.2 is that of a closed recirculating cooling water system. In
this case, water is continually recirculated through the system, picking up heat at the point of
heat transfer and rejecting the heat at a second point of heat exchange. A common example
would be an automobile engine cooling system. Closed chilled water systems for air
conditioning systems would be typical of this type of cooling system design.
Evaporation
(heat rejection)
Heat Load
Cooling Tower from Process
Make Up Bleed-Off
Figure 1.3 illustrates an open recirculating cooling water system. In this design, cooling
water is pumped through a point of heat exchange or heat transfer, absorbing heat in the
process, and transporting this heat to a cooling tower. At the cooling tower the heat is
Some open recirculating system do not use a cooling tower for heat rejection to the
atmosphere, instead a spray pond is employed.
Like the other cooling systems, water is pumped through a point of heat exchange picking up
Water in
heat and transporting it back to the spray pond. The return water is then sprayed through
nozzles in the distribution piping as shown. This water rejects heat by evaporation and
convection and falls back into the collection basin ready for re-use.
Although spray ponds are used for the same purpose as cooling towers (heat rejection to the
atmosphere) they are inherently less efficient. The amount of space required for a spray pond
is considerably more than that required for a cooling tower. The water losses from a spray
pond in the form of spray and mist are also greater and can pose a problem of unwanted fall
out on parked cars and buildings. For these and other reasons, spray ponds have been
replaced by cooling towers.
It is not uncommon for cooling water designs to incorporate two or more different types of
PUMP
SHELL
& TUBE
HEAT
SOURCE
WATER SUPPLY
FROM WELL
RIVER OR POND
PUMP
SURGE DISCHARGE
TANK TO SEWER
4
GPS//2003
For instance, a once through cooling system (Fig. 1.5) can be tied into a closed cooling
system via a shell and tube heat exchanger. In this example, water is continually pumped
through the closed cooling loop in order to provide cooling to the heat source. The heat
absorbed is carried to the shell and tube heat exchanger where it is picked up by a once
through cooling water and is finally rejected with the discharge.
Figure 1.6 is another example of the use of two different types of cooling systems used in
A cooling tower can also be used in direct combination with a closed cooling system. In this
case, the shell and tube heat exchanger can be eliminated with the heat transfer between the
two systems occurring inside the cooling tower.
In summary, cooling system designs can be placed into one of three different categories. The
above examles do not represent all of the possible varieties of cooling systems designs that
can be encountered. However, all cooling systems can be broken down to their basic
components for ease of understanding.
i) TOWER TYPES
A major component of open recirculating cooling systems is the cooling tower. A cooling
tower, in essence, is a heat rejection device used to lower the temperature of the return
cooling water by evaporation of a small percentage of the water passing over it.
Air
Outlet
Cooling towers can be categorized as either natural draft or mechanical draft. The natural
draft
tower is exemplified by the hyperbolic tower. Air flow through the natural draft tower is by
reliance on the density differential between the warmer air inside the tower and the cooler
outside air. This is the same principle used in the design of a smoke stack on a boiler or
furnace.
The mechanical draft towers illustrated in Figure 1.7 & 1.8 can be further subdivided into
induced draft and forced draft draft design. In the case of forced draft, air is pushed through
the tower whereas induced draft air is pulled through the tower. In both cases, the goal is to
provide sufficient air flow through the tower to cool the return water.
6
GPS//2003
Warm
air out
Air blower
In addition to the way air is drawn through the tower, reference is made to cross-flow and
counter-flow designs. As the names denote, in counter-flow refers towers, the air flow is
opposite to water flow (Fig. 1.9). Cross-flow refers to air flow which is perpendicular to
water flow (Fig. 1.10).
APPROACH The difference between the temperature of the cold water leaving the tower
and the wet-bulb temperature of the air is known as the approach; the approach determines
the operating temperature of the tower and is the simple most important parameter in
determining both tower size and cost.
DRIFT Water entrained in the air flow and lost to the atmosphere. Drift loss does not
include water lost by evaporation; proper tower design will minimize drift loss.
HEAT LOAD The amount of heat to be dissipated by the tower, usually expressed in
BTU/hr (or J/hr); heat load is equal to water circulation rate times the cooling range. Heat
load is also an important factor in determining tower size and cost.
MAKEUP The amount of water required to replace normal losses caused by blowdown,
drift, evaporation, and leaks.
BLEED-OFF Bleed-off is the circulating water in the tower which is discharged to waste;
due to evaporation, the concentration of dissolved solids in the circulating water continually
increases; bleed-off helps keep the dissolved solids concentration of the circulating water
below a maximum limit.
1) evaporative cooling
2) convective cooling
The return cooling water (containing heat absorded at the point of heat exchange) is returned
to the tower and distributed over the tower packing or fill. The tower fill breaks the water
into small droplets which cascade through the tower chamber. At the same time, air passes
through the tower and mixes with the falling water. As the air and water contact each other,
evaporation takes place.
During the evaporation process, heat is removed from the cooling tower water equivalent to
the latent heat of vaporization. This latent heat of vaporization is equivalent to 1,000 BTU
per pound of water evaporated. In general terms, this is equivalent to a 1oF drop in cooling
water temperature for each 0.1% of water evaporated.
For example, 1,000,000 lbs of water flows over a cooling tower and in the process, 0.5% of
the total water flow is lost due to evaporation. The heat removed due to this evaporation is
equivalent to:
8
GPS//2003
Since 1 BTU lost per pound of water is equal to a 1oF temperature drop, the 5,000,000 BTU
lost from 1,000,000 lbs of water would be equivalent to a 5oF drop in temperature.
Cooling towers cool water by evaporation of a given percentage of total recirculating water
flow, rejecting heat to the atmosphere, equivalent to the latent heat of vaporization. There is
a limit to the efficiency of heat rejection obtainable with a cooling tower.
Cooling towers are designed to expose a maximum amount of water droplet surfaces to the
flowing stream of air. Towers are designed to achieve the maximum amount of water
evaporation or heat rejection with a minimum amount of water flow.
The limits of cooling tower efficiency are related to the dry bulb and wet bulb temperature of
the outside air. The temperature of air on an ordinary thermometer is the dry bulb
temperature. The wet bulb temperature is the reading of a thermometer when the bulb is
covered with a wet cloth and the thermometer is whirled around in a sling (sling
The relative humidity of the air is the ratio of the quantity of water vapor actually present in a
given volume of air to the greatest amount of vapor which that air could hold at a given
temperature.
psychrometer).
When the relative humidity is 100%, water will not evaporate, thus:
When the relative humidity is less than 100%, however, water will evaporate and:
This sets the limit for the ability of a cooling tower to cool water. A cooling tower cannot
cool water below the wet bulb temperature of the outside air. The difference between the
cooling tower water effluent temperature and the wet bulb temperature is referred to as the
approach temperature.
It is important to note that not all of the cooling taking place in a cooling tower is due to
evaporative cooling. A second cooling process also takes place, which is referred to
convective cooling. Convective cooling takes place, when colder outside air flows through
the cooling tower, picking up heat from the water. Thus, when the outside humidity is 100%
@ 50oF, and the tower return water is 80oF, the cooling tower can still accomplish some
cooling of the water due to convection cooling.
In addition to evaporative water losses, water can also be lost from an open system as small
droplets entrained in the airflow exiting the tower. These water droplets, typically referred to
as windage or drift losses, are identical in composition to the recirculating water, i.e., these
droplets contain the same dissolved minerals, suspended particles and water treatment
chemicals found in the recirculating cooling water.
Table 1.1
The extent of windage or drift loss, depends on the type of heat rejecting system employed
and on the local operating / weather conditions. Table 1.1 lists typical figures for this water
loss as a percentage of the recirculating rate for a given type of heat rejecting system.
Through improved design and construction of mechanical draft towers, the windage losses in
these systems can be as low as 0.01 percent.
C. Heat Exchangers
A fundamental law of thermodynamics states that heat is transferred from a warmer body to a
cooler body. This is the basic principal upon which heat exchangers function. Two fluids or
gases pass through a heat exchanger with the warmer fluid or gas transferring heat to the
cooler fluid or gas. Our interest is with cooling systems that rely upon water as the cooling
medium. At the heat exchanger, heat is transferred by two primary mechanisms:
1) conduction
2) convection
Conduction relies upon contact of two fluids of different temperature separated by a metal
wall, transferring heat from the warmer fluid to the cooler fluid. Convection cooling plays a
role in distributing heat throughout the coolant by means of coolant flow and turbulence.
Conduction cooling plays the biggest role in overall heat transfer.
Heat transfer in a heat exchanger can be quantified, using the standard equation for heat
exchange:
Q = U x A x T
Where:
Q = total heat flow, BTU/hr
U = heat-transfer coefficient, BTU/hr/ft2/oF
A = area of the heat transfer surface, ft2
T = temperature difference between two surfaces
10
GPS//2003
The use and application for heat exchangers are incredibly numerous; in general heat
exchangers can be broken down into three classes:
1) coolers (non-condensing)
2) condensers (condensing)
3) heaters
depending upon process side activity. Regardless of design or application, the principles of
heat transfer and heat transfer efficiency are identical.
The basic principle is that the water and the fluid (gas) to be cooled is seperated by the metal
barrier. In the case where the water is on the inside of the tube, the type is referred to, as
tubeside exchanger. Figure 1.11 is an example of a shell tube exchanger.
This same style of exchanger can also be used where the water is on the exterior of the tubes
and the process stream is on the inside. This type is referred to, as shellside exchanger and is
normally used where the process stream is under high pressure (for instances, gases). In this
case, the flow would be as shown in Figure 1.12.
Cooling Water
Baffles
A. Introduction
B. Cooling Water
i) Corrosion
ii) Scaling
iii) Suspended Solids
iv) Biological
C. Chilled Water
D. Free Cooling
12
GPS//2003
2. Types of Cooling Systems
A. Introduction
All cooling water programs address four issues; the importance of each will vary depending
on the plant. The four, potential water related concerns for cooling water systems are shown
below, along with the major factors that influence them:
i) CORROSION
Makeup Water
Airborne Solids
Corrosion Products
Hardness Precipitates
iv) BIOLOGICAL
i) CORROSION
The corrosion potential of a cooling water system is influenced by several operating
conditions:
pH
calcium level
total alkalinity (M alk.)
total dissolved solids
temperature
As the Langelier Index of a specific cooling water rises above 0, the greater is the tendency
for CaCO3 scaling to occur, while the probability of corrosion decreases accordingly.
However, as the stability index of cooling water falls below 0, the potential for corrosion
increases and the probability of scaling diminishes.
By maintaining cooling water on the slightly alkaline side (pH of 8.2 to 8.6), its corrosivity is
substantially reduced while the scaling tendency is increased. Typically, a water with a pH in
the range of 8.2 to 8.8 would have a LSI above 2.0 and commonly around 2.5.
If the pH value falls below 4.5, then free mineral acidity (FMA) is present and corrosion will
occur regardless of the corrosion inhibitor being used or its concentration. This condition
occurs when the acid (usually sulphuric acid) being applied to the condenser system, for
alkalinity and pH control, is overfed.
14
GPS//2003
Oxygen
Passing cooling water over a cooling tower saturates it with oxygen. Oxygen is an integral
part of the corrosion process, hence a corrosion inhibitor is required to protect both the
O
X c 10
Y c
G
E 8
P
N E
R 6
C
O L
N I 4
T T
E E
N R 2
T
0
o
30 50 70 90 110 130 150 170 190 210 F
Chlorides/Sulphates
Concentrating the makeup water in the cooling water increases the total dissolved solids
(conductivity). In particular, as the chloride and sulphate ions present in the raw water are
concentrated, this results in an increase in the corrosivity of the cooling water. Of the two
anions, chloride has the greatest impact on mild steel corrosion rates.
Suspended solids
The deposition of suspended solids on a metal surface can result in under deposit type
corrosion. This type of corrosion will occur, regardless of the corrosion inhibitor being used
or its concentration, since the treatment is unable to penetrate the deposit in order to provide a
protective film on the metal surface.
Microbiological Activity
The primary corrosion causing organisms are anaerobic bacteria. They grow beneath
deposits and are protected from oxygen present in the cooling water. Sulphate-reducing
bacteria (SRBs) are very corrosive to metals. Since the corrosion inhibitor cannot penetrate
through the deposit to protect the metal surface, it will not provide protection against this type
of organism.
Alkaline pH values
As the pH increases above 7 and particularly in the 8 to 9 range, bicarbonate (HCO3) is
converted to carbonate (CO3), which in turn permits to the formation of insoluble calcium
carbonate and/or calcium and magnesium silicate.
Similarly, calcium phosphate scales can form. Its solubility is controlled by temperature, pH,
calcium level and the ortho-phosphate concentration. If cycles of concentration are allowed
to exceed the calcium phosphate solubility limit, deposits will form.
Makeup Water
Corrosion products; the insoluble reaction products of corrosion such as iron and
copper oxide.
Precipitated hardness; calcium carbonate or calcium phosphate found in the
suspended solids. Also treatment components, such as phosphonates or
polyphosphates can degrade to give phosphate, which can then in turn react with
calcium.
Sand, silt, etc. (usually silica and aluminium silicate)
Organic matter (leaves, weed, etc.)
Biomass; both living and dead.
Airborne Solids
Dust
Inorganic and insoluble organic matter
16
GPS//2003
iv) BIOLOGICAL
Biological growth is detrimental to a cooling water program for several reasons.
C. Chilled Water
Chilled water contains all the impurities of condenser cooling water, however, they are all
present at a much lower concentration (Table 2.1).
The rather frequent no-flow operating conditions in chilled water distribution systems,
requires a different treatment approach, one that can provide low corrosion rates under these
conditions.
Comparison of Condenser Cooling Water to Chilled Water
Constituent Condenser Cooling Water Chilled Water
Total Dissolved Solids (T.D.S.) T.D.S. in makeup water Same as makeup water
X cycles of concentration
Table 2.1
In addition, the chilled water systems are generally more complex as they are typically an
integral part of a system. Therefore, there are usually no convenient points in the system, to
easily flush or drain any objectionable accumulated sludge deposits from the heat exchangers
or piping.
The effective prevention and removal of particulate matter from a chilled water system is one
of the basic keys to both cooling operation and treatment.
In-line filters are required to remove objectionable particulate matter from a chilled water
system and should be an integral part of any closed loop system.
In-line cartridge type filters that will remove suspended solids down to 10 micron size should
be installed in the system. If a system is dirty, then a 50 micron size cartridge filter would be
more suitable initially. The number of cartridge filters required, their filtering capacity and
where they should be located, depend upon the particular system.
Biological problems in chilled water are far more serious and more difficult to control than in
open recirculating cooling water systems. This is because chilled water is normally shock
treated with biocide for biological problems. However, when the biocide is applied, certain
sections of the chilled water distribution lines may be out of service. The chilled water in
these stagnant lines then re-infects the chilled water, when they are put back into service.
One option to consider for systems with chronic micro problems is to use by-pass filters with
a pore size of 1 micron. These very low pore size filters will remove bacteria from the water.
The use of a biocide to reduce the microbiological population and strip biofilms from
surfaces, coupled to a small pore size filter is an effective way to remove the conditions that
encourage biological activity.
Continually monitoring the microbiological activity in a closed system and in particular the
chilled water system is essential for a trouble free operation. The use of dipslides to evaluate
bacteria levels should be used at least once per quarter. These biological tests should be
backed up with an ATP analyses when possible, to ensure that all forms of microbes are
under control.
18
GPS//2003
D. Free Cooling
Free cooling was introduced as a unique energy savings development for comfort cooling, air
conditioning systems. The energy savings features of free cooling are:
COOLING
TOWER
CONDENSER
STRAINER
CHILLER
COOLING LOAD
Normally, whenever the outside air temperature is 60oF (15oC) or below, then the free
cooling cycle can be economically justified.
Before the condenser cooling water enters the chilled water system, it first passes through a
multi tube filter. This removes any suspended solids down to approximately 100 microns in
size. The filter is automatically backwashed upon a preset pressure differential.
Operating on the free cooling cycle allows condenser water to enter the chilled water system
and this presents new water treatment problems. Therefore, very specific water conditioning
technology is required, to provide the desired results for both systems.
The intermittent static operating conditions in chilled water system, requires a much higher
level of corrosion inhibitor than for condenser cooling water, to protect the system from
corrosion. Static conditions result in the protective corrosion inhibitor film on the metal
surface being used up over a period of time. Unless there is sufficient treatment available to
continually maintain this protective film, corrosion will occur. High concentrations of
treatment are required to continuously provide a supply of corrosion inhibitor. This reserve is
essential to maintain the protective film on the metal surface, during no-flow conditions.
Condenser cooling water however, is always being recirculated (unless the system is out of
service). Therefore, a lower level of treatment will still provide a high degree of corrosion
protection for the system.
In view of the condenser cooling water also becoming the chilled water, it is essential that a
water treatment program be designed, that is both cost effective and efficient. Open system
cooling water inhibitors will not provide protection of ferrous and non-ferrous metals, under
the static operating conditions, which can be the case for extended periods of time.
It is important to appreciate the potential operating problems that may develop in allowing
condenser cooling water to enter a chilled water system, and ensure that the appropriate steps
are taken to protect the closed loop segment.
This type of system is only infrequently seen now, due to the limitation noted above.
However it is not uncommon to see free cooling systems where a heat exchanger isolates
the chilled system from the open recirculating loop. In this case, the advantages of free
cooling are realized, without the significant liabilities.
20
GPS//2003
3. CORROSION
A. Introduction
B. Types of Corrosion
i) General Corrosion
ii) Galvanic Corrosion
iii) Pitting Corrosion
iv) Concentration Cell Corrosion
v) Dealloying
vi) Intergranular
vii) Transgranular
viii) Stress-Corrosion Cracking
ix) Other Forms of Corrosion
E. Corrosion Inhibitors
What is it?
Corrosion is the electrochemical reaction (destruction) of a metal due to a reaction with its
environment. It is the reversion of the refined metal to its natural state, which is commonly
an oxide. Examples are :
Fe Fe2O3
Fe(OH)3
Fe3O4
Al Al2O3
Zn ZnO
Zn(OH)2
The word corrosion comes from the Latin corrodere to gnaw away. Of the many types
of metallic corrosion, six corrosion mechanisms typical of cooling water systems, will be
discussed.
Why is it a concern?
The primary reason for concern is economic - it is estimated that :
>100 million tons of steel are required yearly to replace corroded steel.
Cost to industry in N.A. is estimated to be $10 to $15 billion annually.
Due to its use and tendency to corrode, steel is the primary metal of concern. Of lesser
concern are copper, copper alloys and aluminum.
The above four components make up a corrosion cell and are the basis for the various
chemical treatment programs that are meant to minimize corrosion.
22
GPS//2003
Corrosion cell
The electrochemical reaction that takes place is the oxidation of iron and the use of the
electrons that are generated to reduce oxygen in the cooling water.
This reaction occurs in cooling systems, at neutral to alkaline pH range and is illustrated in
Fig. 3.1
Figure 3.1
O2 Tubercule
Fe +2 OH - OH -
e-
Anode Cathode
In single metal corrosion, cathodic and anodic sites develop on the surface and this is due to
the following factors :
Strained metal
Localized areas of oxygen depletion
Imperfect surface oxide film
Impurities in the metal
Impurities on the metal
Localized temperature differences
Imperfect grain boundaries
Poor water treatment / pH
Unstrained metal
Localized areas of high oxygen content
Good surface oxide film
Localized low temperatures
Grain characteristics
Corrosion can be the result of chemical or mechanical effects and it is critical to be able to
identify the cause/type of corrosion in order to be able to effectively correct it.
i) GENERAL CORROSION
Any fresh metal surface exposed to an aqueous environment containing dissolved oxygen and
salts will experience corrosion. A multitude of both anodes and cathodes exist on the same
O2 Tubercule
Fe +2 OH - OH -
e-
Anode Cathode
metal surface, in close proximity.
Figure 3.2
Anodes are defined as those locations where metal oxidation (corrosion) occurs (see Fig. 3.2).
Mo Mn+ + ne-,
While at the cathodes, reduction of oxygen occurs,
The cathodic reaction predominates at pHs above 5. The metal ion produced at the anode is
further oxidized by dissolved oxygen to form an insoluble metal oxide. Local anodes and
24
GPS//2003
cathodes continuously shift position, resulting in a general penetration of the metal surface
exposed to the corrosive environment.
Intentional galvanic couples are compensated for by substantially increasing the thickness of
the anodic (less noble) metal. Prediction of galvanic relationships can be made from the data
in Table 3.1 Examples of galvanic couples would be :
26
GPS//2003
No Corrosion Pitting
Under deposit corrosion
Poor inhibitor film formation
High chloride concentrations
Suspended solids build up on piping
Low levels of anodic inhibitors
Overfeed of chlorine
Another cause is exposure to varying aeration because of turbulence, agitation, etc., where
specific areas are shielded from the general environment. This type of corrosion is promoted
by:
Anion concentration
Oxygen concentration
Deposits
Poorly sealed joints
Temperature differences
Flanged fittings
Couplings
Fasteners
Gaskets
Tube sheets at tube protrusions
v) DEALLOYING
A common problem in certain brasses is selective leaching. This type of corrosion removes
one element from a solid alloy. In the case of brass, the more active zinc is preferentially
corroded, leaving behind a copper matrix of little or no structural strength. The usual
situation is to use an appropriate alloy. For example, Admiralty brass containing 1 percent
tin and 0.015 percent arsenic is more immune to dezincification than 70:30 brass.
Graphic corrosion is unique to cast iron and is a condition where iron is preferentially lost.
This leaves behind a weak, porous matrix of graphite. Typical causes are :
Warm temperature
Sulfates
Anaerobic bacteria
H2S
Deposits
28
GPS//2003
vi) INTERGRANULAR
Intergranular is a localized attack along the grain boundaries of a metal or alloy. The
distinguishing characteristics is :
Causes include:
This type of corrosion occurs primarily in austenitic stainless steels and certain aluminum
alloys.
Microbiological corrosion
This form of corrosion is caused by the products of the life cycle of various forms of
organisms. There are two general types of corrosion caused by micro-organisms :
Acid attack, due to the formation of acid as part of their metabolic processes. For
instance SRBs generate H2S and nitrifying bacteria can convert ammonia into
nitric acid. In addition, various organic acid can also be formed.
Erosion corrosion
Turbulent water flow results in significant components of force acting at right angles to the
direction of flow and thus acting directly on the metal surface. The abrasive action of the
water physically removes metal from the surface. This abrasive action is accentuated by
entrained air and suspended solids. Factors that contribute to this include :
Names given to this type of damage vary according to the cause and location :
Erosion
Cavitation
Cavitation is caused by the formation of bubbles or vapor filled cavities in low pressure
regions of the flowing fluid. The bubble later collapses, causing a breakdown of the
protective layer, on the metal surface.
Fretting
Fretting occurs at the interface between contacting metal surfaces subject to slight motion
resulting in a rubbing action. Although most commonly seen on titanium alloys, it can also
occur on stainless steel.
30
GPS//2003
The rate of corrosion is dependent on the ability of the corrosion reactions to occur. Those
reactions are dependent upon many variables such as :
pH
Conductivity (measure of waters ability to carry current)
Water Velocity
Temperature
Dissolved oxygen concentration
Of the various factors, the water pH and temperature are usually the two most significant
factors. Although the specific pH will vary with the type of program being used, in general
alkaline (>8.3) condition are preferred.
C
O
R
RR
OA
S T
I E
O
N
TEMPERATURE
pH pH
The effect of temperature is not as clear since increasing temperature raise corrosion rates,
yet at the same time, higher temperatures also increase the speed with which protective films
can form. In general though, the higher the temperature, the greater the corrosion rate.
Just as the causes of corrosion are various, so too are the option to control or minimize
corrosion. Examples of steps that can be taken are :
Metallurgy
Use a better grade of stainless resistant to chloride induced cracking
Change brass valves to mild steel
Change mild steel components to brass or stainless
Environmental
Change flow rates
Deaeration
pH adjustments
Side stream filtration
Improve water quality
Protective coatings
Electrochemical
Sacrificial anodes
Dielectric couplers (isolate galvanic couples)
Cathodic protection
32
GPS//2003
Design
Lower velocity by using larger piping
Change flow to tube side
Change impeller size to prevent cavitation
Increase head pressure to impeller inlet (to minimize cavitation)
Welds instead of rivets or bolts
Large anode to cathode ratio
Water treatment
Although the specific program will be unique to each plant, the goals for corrosion inhibitors
are to use those that :
E. Corrosion Inhibitors
Although these will be discussed more fully in a later section, the main characteristics of
various corrosion are as follows :
Chromates
Anodic oxidizing inhibitor
Broad usage (hard or soft water)
Works rapidly
Environmental restrictions
Can be consumed by reducers such as oils, H2S, etc.
Polyphosphates
Generally cathodic
pH, temperature sensitive
Can function as scale inhibitor
Transports iron (potable)
Can be used in soft waters
Works best with ortho phosphate
Ortho phosphate
Primarily an anodic inhibitor forming calcium, iron phosphates
pH and temperature sensitive
Works in moderate to hard water
Nitrite
Anodic oxidizing inhibitor
Oxygen not required
Needs fairly high level without O2
Can be a nutrient for microbes
Can be used in open systems
Phosphonates
Generally cathodic inhibitors
Requires Ca+2, Zn+2 or Fe+3
Needs alkaline pHs (> 8.3)
Azoles
Chemisorbed films (direct bonding to the Cu)
Copper/copper alloy inhibitor
Molybdate
Excellent pit inhibition properties
Broad pH range
Works best in closed systems
Can be a problem in hard water
Environmentally acceptable
Used with other inhibitors
Calcium Carbonate
Cathodic inhibitor
Scale potential
pH and temperature dependent
Environmentally acceptable
34
GPS//2003
4. DEPOSITION
A. Introduction
B. Types of Deposits
i) Scales
ii) Suspended Solids
iii) Corrosion Products
iv) Organics
A. Introduction
What is it?
Deposits are the accumulation of foreign matter on heat transfer surfaces or in cooling system
components, such as tower fill, etc.
Why is it a concern?
Deposits can impair the operation of a cooling system since they can :
B. Types of Deposits
While the deposits seen in cooling systems are quite variable, they can however, be
simplified into four general groups :
i) SCALES
Caused by the precipitation of salts when their solubilities are exceeded. Scales are
crystalline in nature and include examples such as :
CaCO3
Mg SiO4
CaSO4
Ca SiO4
36
GPS//2003
These differ from deposits in that they form and grow specifically on heat transfer surfaces.
These sources are self-explanatory however, the last category does merit more explanation.
Like scales, these are dependent on temperature, pH and concentration. They are often
caused by the treatment program itself, due to :
A variety of factors will influence the scaling potential of a cooling water system. In general
these can be grouped into three categories :
Water chemistry is normally the defining parameter and others are simply related to it,
although they can have a significant impact.
i) WATER CHEMISTRY
Temperature
Inverse solubility with temperature of several scale types, the most important
being calcium carbonate. The higher the temperature, the lower the solubility.
pH
Most scales form readily in alkaline environment
Severity increases with increasing pH
Concentration
The higher the concentration of calcium greater the potential
Mineral scales
Scales can be prevented by operating at subsaturated conditions, this can be done by :
Acid adjustment of pH
Operation at lower cycles of concentration
Partial softening
38
GPS//2003
pH adjustment is achieved by dosing acid to destroy a portion of the alkalinity. The amount
needed to change the alkalinity depends on the type of chemical used.
Operation at lower cycles
This is an option but can be expensive in terms of both chemical and water costs, for
instance :
Lowering the cycles from 3 to 2 resulted in a dramatic increase in water consumption due
solely to the change in bleed-off rates.
Mechanical
Partial Softening
RO
Cold lime softening takes a considerable capital investment in equipment but can be viable if
equipment on hand is under-used. It offers an excellent approach to improve water quality
since it removes both hardness and suspended solids. RO water added to a cooling system
can dramatically lower the hardness levels, although the cost of the water is relatively high.
Sidestream filters
Clarification
Low cycles
Proper tower location
Periodic cleaning
Exchanger design
Exchanger backwash
Unlike inorganic foulants/scales, organic contaminants pose a different set of concerns but
they too can be controlled by several methods. Organics could be anything, ranging from oil
to glycol, to methanol, however the approach is the same :
D. Calculations
i) Introduction
ii) Open Recirculating
iii) Closed Loop Systems
iv) Once-Through Systems
40
GPS//2003
A. Objectives
The objective for treating cooling water is to maintain optimum heat transfer by reducing
corrosion, scaling and fouling. In order to achieve this, the first step is to understand what
can contribute to reduction in cooling efficiency.
Scale
Causes
CaCO3, CaSO4, calcium phosphate, magnesium silicate, silica, MnO2
Treatment
Bleed-off
Pretreatment
Phosphonates, polymers, polyphosphates.
Alkalinity control H2SO4, NaOH, Na2CO3.
Deposition
Causes
Oil; silt; clay; muds; microbiological growths
Degraded treatments (calcium phosphate, Zn++); incompatible treatments
Process contaminants; hydrocarbons
Iron oxides, other corrosion products
Treatment
Chemical pretreatment
Filtration
Bleed-off
Side stream filtration
Polymers
Surfactants, penetrants
Microbicides
Corrosion
Causes
O2, CO2, H2S, acids, anaerobic bacteria (SRBs), corrosive anions (chlorides).
Treatment
Mechanical/chemical pretreatment
Inorganic inhibitors
Zinc; polyphosphates
Organic inhibitors
pH control agents (buffers)
Causes
Algae, bacteria, fungi, protozoa.
Treatment
Filtration
Oxidizing biocides
Non-oxidizing biocides
Organic penetrants
Wood deterioration
Causes
Cellulolytic fungi and bacteria
chlorine
carbonate (CO3) alkalinities
high temperature
high TDS
Treatment
Microbicides
Alkaline/acid pH control
Pressure treatment of tower wood.
42
GPS//2003
B. Treatment of Open Recirculating Cooling Water Systems
i) INTRODUCTION
Corrosion, scale and microbiological fouling, can all impede the efficient and economical
operation of open recirculating cooling water systems. Cooling water quality, availability
and disposal limitations further impact the selection of an effective water management
program. An open recirculating cooling water system consists of a combination of the
following pieces of equipment:
Cooling water is pumped from the cooling tower basin or cold well, through the
vessel, which requires cooling.
This water absorbs heat by conduction from the unit being cooled and circulates
back into the cooling tower.
The absorbed heat is then released in the tower primarily through the evaporation
of a small amount of the recirculating cooling water.
evaporation
Because water evaporates from a cooling water system, it must be continuously replaced by
makeup water, which is usually untreated incoming plant water that contains dissolved
minerals, gases, suspended solids and other impurities. Therefore, due to the evaporation
process, suspended or dissolved impurities in the recirculating cooling water will constantly
increase in concentration. Eventually the most insoluble minerals approach their saturation
limits and precipitate as scale in the system.
Suspended solids also contribute to the formation of deposits. In addition to forming hard
scale on heat transfer surfaces, high concentrations of mineral salts and suspended solids in
the water also generally accelerate the corrosion and fouling of system components.
To minimize the risk of corrosion, deposit formation and fouling of a system, a portion of the
concentrated recirculating water is continuously removed from the system through a process
referred to as bleed-off. This water and all other system water losses are constantly replaced
with fresh makeup water. The net effect is the maintenance of a consistent recirculating
water quality at a specified level of dissolved solids. Maintaining this level avoids cooling
The extent to which an open system needs to be bled-off depends upon six primary factors:
To provide efficient process cooling with the least amount of water consumption, the cooling
water should be concentrated to a maximum safe operation level consistent with minimizing
bleed-off.
44
GPS//2003
ii) HISTORICAL
Naturally occurring waters are impure and contain both dissolved and suspended minerals.
The types and quantities of these contaminants in raw water depend on the water source.
Varying amounts of:
Calcium
Magnesium
Sodium
Bicarbonate
Silica
Chloride
Sulfate
Iron
are found in the water. Phosphate, nitrate, fluoride and other dissolved species may be found
in smaller but sometimes significant concentrations, although less frequently.
The primary make-up water quality parameters, which determine either the corrosive or
scaling tendencies of water, include:
Corrosion process involves reactions that take place at either the cathode or the anode (site of
metal loss). Inhibitors tend to interact at one location or the other; those that inhibit the
corrosion process at the cathode are called cathodic inhibitors, while those that interact at the
anode are called anodic inhibitors.
ortho-phosphate poly-phosphate
nitrite most phosphonates
molybdate azoles
chromate zinc
Typical programs use combinations of these actives to minimize corrosion rates. Examples
of different programs are listed on the following pages.
The degree of corrosion protection for iron and steel is reasonable uniform over the pH range
of 5 to 8 but with increasing alkalinity, bulk precipitation Zn (OH)2 becomes a problem.
Copper and its alloys also show a marked decrease in penetration rate with a chromate-zinc
inhibitor. The rate of penetration is reasonably constant in the pH range 5.5 through 8.
Although extremely effective, chromate based programs are rarely found, due to
environmental concerns over chromate.
Zinc-Phosphate
The harmful effects of chromate on the environment have prompted interest in corrosion
inhibitors free of chromium.
Alkalinity control, preferably in the pH range of 6.5 - 7.0 was essential to provide maximum
corrosion protection and to avoid the problems of phosphate sludging and Zn(OH)2
deposition at higher pH. Azole was included in the treatment to reduce the amount of Cu2+
available to plate on steel and to minimize the subsequent galvanic corrosion.
Combinations of zinc and HEDPA (or PBTC) offer steel corrosion protection, which is
enhanced by the addition of tolyltriazole (TT). Not only is the corrosion protection of copper
improved by the addition of azole but also the inhibition of mild steel. As mentioned
previously, HEDPA have an advantage over aminophosphonates with regard to chemical
stability, which is an important consideration when oxidizing microbicides are used.
Zinc-based corrosion inhibitors are generally very effective cooling water treatments.
However, zinc concentrations as low as 5 ppm are known to be toxic to some forms of
aquatic life. Therefore, zinc levels, in effluent discharged to ponds, streams and other public
waters, must be maintained well below this concentration and are widely restricted.
Phosphate Programs
The next evolution was the combination of ortho and polyphosphate under neutral pH
conditions. With the advent of polymers that could inhibit calcium phosphate, it became
feasible to use higher levels of ortho phosphate. These programs became the standard against
which other programs were compared to in refineries, or other high stress conditions.
A variation on this theme are low phosphate programs that operate under alkaline conditions,
where they are just below the calcium phosphate saturation index. These low phosphate
programs provide good corrosion protection with a lower risk of calcium phosphate
deposition.
46
GPS//2003
Triazole-Phosphonate blends
During the past two decades a great amount of research has been conducted on the
development of effective, non-metal cooling water treatments. Initially, low-polluting
products of this description included multi-functional treatments containing phosphonate(s)
and a non-ferrous metal inhibitor, such as BT or tolytriazole (TT), along with a conventional
natural organicpolymeric dispersants.
By using effective calcium phosphate precipitation inhibitors, ortho phosphate levels as high
as 15 to 20 ppm can be carried. In addition to functioning as a cathodic inhibitor, this high
level of phosphate promotes passification at anodic corrosion sites in neutral water through
the formation of a passive iron oxide film and by directly reacting with the iron ions
generated by the corrosion process.
Molybdate formulations
There has been a considerable amount of interest in the use of molybdate as a cooling water
corrosion inhibitor. The primary advantages offered by a molybdate-based cooling water
treatment are that molybdate is non toxic.
iii) SCALING
Although the importance of good corrosion control in industrial cooling water systems cannot
be over-emphasized, preventing deposits from adhering to heat exchange surfaces is the most
important objective of virtually all cooling water treatment program. Clean, scale-free
cooling systems:
CH 3
N
N
H
Tolyltriazole (TT)
Scaling can be defined as the deposition of slightly soluble inorganic minerals on the metal
surfaces of a cooling water system. The deposits that form are usually the least soluble
substances present in the recirculating water. These deposits, or scales, are typically dense,
non-conducting hard, tightly bound particles, that adhere to metallic surfaces. Calcium
carbonate (CaCO3) is the most frequently encountered scale because of its very limited water
solubility and the high concentration of calcium and alkalinity normally found in cooling
Fe(OH)3 (amorphous) 38
Fe3(PO4)2 33
Ca3(PO4)2 26
Fe(OH)2 14.5
Mg(OH)2 10.7
CaCO3(calcite) 8.34
MgCO3 5.0
CaSO4 4.59
SiO2(amorphous) 2.7
More soluble
Scales, such as calcium carbonate and calcium sulfate, form on cooling water heat transfer
surfaces because these substances have an inverse solubility; that is, these substances are
more soluble in cold water than in hot. The solubility of calcium carbonate is also affected
by:
M-alkalinity
calcium hardness
pH
total dissolved solids
Table 5.1
Langelier studied the role of these factors in the precipitation of calcium carbonate and
developed a calcium carbonate saturation index (LSI). Also referred to as the Langelier
Index, this index is useful in predicting the corrosive or scaling tendencies of a water.
LSI = pH - pHs
where pH is the measured pH of the water in question. A negative index indicates non-
scaling, usually corrosive water, while a positive index predicts scaling tendencies. For
example, to find the LSI of a water at 120oF (49oC) which has the following characteristics:
48
GPS//2003
It follows that:
pHs = (9.3 + A + B) (C + D)
= (9.3 + 0.2 + 1.6) (1.6 + 2.2)
= (11.1) (3.8)
= 7.3
And:
LSI = pH - pHs
= 7.8 7.3
= 0.5
Thus this water is slightly scaling and likely corrosive. The Ryznar Index is another similar
method for determining the scaling tendencies of water.
0.65
Where :
PO4 as ppm PO4 CaH as ppm CaCO3 T = oC
The insulating properties of water-formed scales is well documented. In more practical
terms, a calcium phosphate (Ca3(PO4)2) scale as thin as 0.04 inches will reduce heat transfer
approximately 8 percent.
A uniform scale of 0.04 inches in a 1.0 inch I.D. heat exchanger tube also results in an 8
percent loss of tubing capacity. Energy losses attributed to reduced heat transfer capabalities
and increased pumping costs, associated with added frictional resistance to water flow, easily
justify the time and expense of implementing a good chemical water management program.
Increasing the bleed-off of a cooling tower is a very effective method of preventing all types
of scale. However, to minimize chemical treatment and water consumption, an evaporative
cooling system should operate at a maximum possible number of concentration cycles,
particularly in the water-short areas.
Softening by ion exchange methods offers a potentially serious disadvantage because the
softener effluent contains a higher concentration of sodium salts which in turn increases the
corrosiveness of the cooling water. Furthermore, non-zinc corrosion inhibitor programs are
typically enhanced by the presence of at least approximately 50 ppm of calcium hardness in
the recirculating cooling water.
Sulfuric (H2SO4) acid is most often used to prevent calcium carbonate scale formation. The
acid functions by converting recirculating water alkalinity to carbonic acid. Carbonic acid
(H2CO3) dissociates into carbon dioxide (CO2) and water. Gaseous CO2 is driven from the
system as the warm cooling water cascades down over the tower fill.
50
GPS//2003
The use of acids as scale control agents has limitations, including handling, storage and
disposal problems. Acid use also adds additional chemical and feed equipment costs to the
treatment program. There is always the potential for over-dosing the acid, which can cause
severe corrosion of the system metals. Finally, high concentrations of sulfate salts in the
cooling water can potentially result in the formation of calcium sulfate scale.
Several additional chemical treatment methods can be used to control the formation of scales
and deposits in cooling water systems. These methods typically rely on the use of a chemical
scale inhibitor in the recirculating water. These inhibitors are effective at holding large
quantities of scaling minerals in solution at the threshold of precipitation; hence these
inhibitors are referred to as threshold treatments. These inhibitors retard/prevent
precipitation of scale in super-saturated solutions, by interfering with crystal growth. These
inhibitors also disperse particles of scale, thus preventing the adhesion of scale to heat
transfer surfaces.
The general classifications of threshold treatments that have been used in cooling water
systems, include:
1) phosphonates
2) synthetic organic polymers
3) polyphosphates
4) natural organic polymers
The concentration at which each individual material is used in a treated water, depends upon
the severity of the scaling problem. Synthetic organic polymers and phosphonates are the
most effective treatments available. These inhibitors are typically employed at 1 to 5 ppm as
active material.
Lignosulfonates (natural polymers) at unusually high concentration (15-20 ppm) are needed
to inhibit the precipitation of the same amount of calcium phosphate as 1 to 2 ppm of
synthetic organic polymers.
The most widely used materials for threshold scale control are the phosphonates. These
materials, are characterized by a direct carbon to phosphorus bond, which confers excellent
hydrolytic stability. Various members of this class of scale inhibitors are also used as boiler
water scale control agents.
These are some drawbacks to using phosphonates as scale and corrosion inhibitors.
Nitrogen-based phosphonates react with chlorine and bromine oxidizing agents used as
biocides, rendering these substances ineffective as scale retardants. Phosphonate also
contribute to the total phosphorus levels of cooling tower discharges. Additionally, the
presence of some heavy metals interfere with antiscalant activity.
iv) CORROSION
From an electrochemical viewpoint there are two distinct methods of providing corrosion
protection to a metal substrate :
Water-borne inhibitors which retard the anodic reaction are termed anodic inhibitors or
passivators. Chemicals serving this function include high dosages of oxidizing agents such as
the chromate (CrO4-2), and nitrite (NO-2), phosphates (o-PO4-3) and molybdate (MoO4-2). A
passivator alone is an uneconomical means of controlling corrosion in open recirculating
cooling water systems.
v) FOULANTS
The deposition of insoluble matter other than mineral scales is defined as fouling. In addition
to producing the same undesirable effects as scales, fouling materials also combine with
precipitated minerals to produce more voluminous and tenacious deposits. Foulants also
contribute to under-deposit corrosion.
1) inorganic
2) organic
3) microbiological
52
GPS//2003
Some examples of inorganic foulants include: sand; silt; clarifier carryover; corrosion
products; phosphate and alum sludges. Organic foulants include: lubricants; fats; greases;
plant extracts; petroleum products. Fouling occurs predominantly in high temperature, low
flow (less than approximately 1 ft/sec) areas and is more influenced by system design and
operation than by water chemistry.
Physical methods for preventing fouling include side-stream filtration and other particulate
removal techniques.
Chemical methods for controlling inorganic and organic foulants include the application of
anionic, (infrequently cationic and non-ionic polymers also), to suspend and disperse
troublesome particulates. Foulants thus treated are readily removed in the tower bleed-off.
Various surfactants are also used to penetrate and emulsify organic foulants. Anionic
dispersants are the most widely used approach and these can include both homo and co-
polymers.
vi) MICROBIOLOGICAL
Open recirculating cooling water systems are continuously exposed to microorganisms. If
unchecked, microbes rapidly multiply in the warm cooling water, and can lead to:
Identify the types and level of microorganisms present in the cooling water
Determine which specific types of microbicides are appropriate
Establish an effective microbicide treatment program
Microbicides fall into two major classes: oxidizing and non-oxidizing types.
Hypochlorous acid is the most widely used oxidizing microbicide, and is formed by feeding
either chlorine gas or one of several other compounds including sodium or calcium
hypochlorite. Organic chlorine donors such as the chlorinated cyanurates can also be used.
Bromine salts such as sodium bromide and BCDMH offer the advantages of chlorine but
perform better at high pHs, or in environments where amines (such as ammonia) are present.
A second class of biocides are those that function not on the basis of their oxidizing ability
but by interfering with metabolic processes non-oxidizing biocides. There are two general
types of non-oxidizing microbicides:
surface active
metabolic poisons
Metabolic poisons are biocides that interfere or arrest metabolic processes by directly
affecting cellular activities. Examples of these chemicals include:
Dibromonitrilopropionamide (DBNPA)
Bromonitropropanediol (BNPD)
Bis (trichloromethyl) sulfone
Thiones
Thiocarbamates
Methylene bis thiocyanate (MBT/MBTC)
Isothiazolone (MCI)
Bromohydroxyacetophenone (BHAP)
Thiocyanomethylene benzothiazole (TCMTB)
Tetrakishydroxymethyl phosphonium sulphate (THPS)
These types of biocides must be absorbed into the cell before they can have an effect on them
and this generally makes them slower acting than either oxidizers or surface active biocides.
Surface active compounds used as microbicides include quaternary ammonium salts, amines
and polyquats. These materials are generally cationic and it is this property is what makes
them effective. However, as for most things there are exceptions (amines and
glutaraldehyde). Examples of this class of biocide include:
Since non-oxidizing biocides act on metabolic process, organisms can develop a tolerance to
them, much in the same way that bacteria can become immune to antibiotics. Hence,
alternating chemically different types of microbicides provides better control.
In many instances, the maximum utility of a microbicide is not achieved. Better control of
microbiological growths can be obtained by following a few simple guidelines during
microbicide application.
Most non-oxidizing biocides are fed on a slug basis. Slug feeding has proven to be an
effective, rapid method of reducing microbiological populations. The rate of application of a
54
GPS//2003
microbicide depends on the severity of the microbiological problem, retention time of the
microbicide, etc.
There are three primary classes of corrosion inhibitors used in these applications:
Reducing agents
Oxidizing agents
Film formers
In conjunction with the above agents, secondary corrosion inhibitors supplement the protection
by:
Buffering/controlling pH
Minimizing yellow metal corrosion
Reducing Agents
Although rarely seen now, tannin type materials were used to both remove oxygen and form
an iron-tannin film on steel surfaces. While tannins have a number of advantages, they can
form organic deposits and are not always effective corrosion inhibitors.
A more common oxygen scavenger is sulphite. Unless there is sufficient sulphite present at all
times, free oxygen will exist and this can initiate corrosion of the boiler metal. A major
drawback is that as sulphite continues to be fed, to counteract the ongoing ingress of oxygen, the
concentration of sulphate builds and this increases the conductivity of the water. In turn, this
makes the water more corrosive, increasing the potential for SRB (sulphate reducing bacteria)
growth along with the attendant corrosion risks.
Organic reducers such as hydrazine (N2H4) and DEHA (diethylhydroxylamine) have been used
but, decomposition (catalysed by copper) and health concerns (hydrazine) have largely
eliminated their use.
Oxidizing Agents
In contrast to the preceeding type of chemicals, oxidizers either directly oxidize metal
surfaces (chromate and nitrite) or work in conjunction with oxygen (molybdate) to form a
passive film on the metal.
The standard inhibitor in this category, nitrite, has been used to inhibit mild steel corrosion for
many years in neutral or alkaline aqueous solutions. Nitrite is the only remaining anodic,
oxidizing inhibitor that can still be used. Unlike molybdate, another anodic inhibitor, nitrite can
function without the need for oxygen and for this reason is very effective in closed systems.
When nitrite is used alone, or in conjunction with pH buffering agents, relatively high
concentrations (700 - 1200 mg/L as NaNO2) are needed to completely inhibit pitting corrosion.
It is generally recognized that the nitrite will be influenced by the amount of chloride and
sulphate present in the water since they can affect the stability of the magnetite layer.
Characteristic of anodic inhibitors, if the concentration is allowed to fall below approximately
500 mg/L (of sodium nitrite), severe pitting attack can occur.
Loss of nitrite can occur via electrochemical and biological processes. In the former case, if
corrosion continues, nitrite can be electrochemically reduced at the cathode to form ammonia
according to the equation:
In chilled water loops (or hot water systems, that are not in operation) exposure to bacterial
contamination has the potential to convert nitrite to nitrate, ammonia or nitrogen gas. The
ability to control biological activity is difficult since oxidizing biocides will oxidize the nitrite
to nitrate and the efficacy of non-oxidizing biocides tends to be less certain.
The use of molybdate for corrosion protection in cooling water, either open recirculating or
closed loop systems, is extremely common. While molybdate is not as strong an oxidizing
agent as chromate, it can function in this role in the presence of oxygen and its ability to
inhibit pitting attack has been well documented, especially at low concentrations in cooling
water applications.
It has been reported in literature that molybdate is too weak an oxidizing agent to convert ferrous
ions to the ferric state. In the presence of oxygen, molybdate will convert hematite to magnetite.
This process is quite visible as boilers (either hot water or steam) change from a reddish colour
to black when treated with molybdate. This mechanism predominates at higher concentrations
(>50 mg/L as Mo), since in previously reported work, at low levels (5 mg/L as Mo), it is found
to accumulate almost exclusively within pits.
The only concern regarding molybdate use is related to its accumulation in sludge from waste
treatment plants, when the sludge is spread on agricultural land. In rare cases, molybdate may
accumulate, to the point where there may be a sufficient concentration present, to interfere with
copper uptake by ruminants. Overall, based on its low human and aquatic toxicity, molybdate is
not restricted in most areas of North America.
The last oxidizer is hexavalent chromium, or chromate, which while a very effective
corrosion inhibitor, is seldom used due to concerns of health/environmental effects.
56
GPS//2003
Film Formers
Among primary corrosion inhibitors, four filmers are employed; the two most common being
ortho-phosphate and neutralized dibasic acids.
Ortho-phosphate is the most widely used inhibitor for glycols, acting both as corrosion inhibitor
and buffering agent. At the relatively high concentrations that phosphate is used at (1000 5000
mg/L as PO4), it provides positive protection against corrosion on mild steel and yellow metals.
The primary mode of action is via precipitation at the anode to form insoluble metal phosphates.
The ability of phosphate to form a protective film via a direct precipitation mechanism is both its
strength and weakness. While it will go onto the metal surfaces, it will just as readily precipitate
with metal ions or hardness salts in the bulk water. Since ortho-phosphate is an anodic inhibitor,
if the concentration falls below the critical level, rapid corrosion attack will happen.
Various dibasic acids can be used for both pH buffering and corrosion inhibition, much in the
same way as phosphate. Their limited solubility with transition metals and alkaline earth cations
make them effective corrosion inhibitors. The neutralized dibasic acid can react with the
ferrous/ferric ions (from the corrosion site) and precipitate, either directly or as related reaction
products. As this process continues, the anode becomes progressively more restricted until it is
no longer able to function as a corrosion site.
A difficulty with dibasic acids is that they display varying degrees of biodegradability and in
chilled water loops this can pose a serious limitation. This can be especially troublesome in
loops where there are other nutrients (e.g. nitrite) or a high bacterial population. In nitrite treated
chilled water systems, rapid biological growth can quickly consume the dibasic acids.
A final type of film former are some substituted triazines, that selectively react with iron to form
an inhibitory film on the metal. Although they are widely used in oil-field applications, they
have not seen extensive use in closed loops.
Buffers/pH Control
The function of corrosion inhibitors and buffering/pH control agents are intertwined. Inhibitors
generally function only across certain pHs, for instance nitrite is typically used under alkaline
conditions. Others, such as some of the dibasic acid mixtures, show best performance at neutral
pHs.
Given that most hot and chilled systems are composed of a variety of metals and elastomers, the
pH range chosen must, by definition, be a compromise. The primary metallurgies seen in North
America are mild steel and copper alloys. As a compromise between steel and copper, the fluid
pH is typically controlled in the range from 8.5 10.5
inorganic phosphate
organic amines
Ortho phosphate, typically dipotassium phosphate, can be used to control the pH between 8.5
10.5. At these high levels, typically used, ortho phosphate provides excellent buffering capacity.
In glycol containing loops, they are able to neutralize glycol breakdown products for extended
periods of time.
Another inorganic buffering system is borate. Borates allow a slightly higher pH and buffering
capacity but at a lower concentration than is needed for phosphates. Organic amines can also be
used to tailor the pH range, depending on the circumstances. A benefit of organic amines is that
the amount needed in the fluid is low (200 300 mg/L) and their contribution to conductivity is
less than for other buffering systems.
In order to prevent both the initial corrosion of copper alloys, as well as to inhibit copper
deposits on mild steel surfaces, azoles are used. TT (tolyltriazole) has become the inhibitor
of choice since it provides improved formulating ease and superior resistance to the corrosive
effect of chloride ions. In contrast to precipitating agents, azoles bond onto the metal surface
via co-ordination between the nitrogen atoms and copper oxide molecules on the surface.
D. CALCULATIONS
i) INTRODUCTION
As previously mentioned, there are three basic types of cooling water systems that may exist
alone or in combinations:
1) once-through
2) closed recirculating
3) open recirculating
As always, there are exceptions, for instance it is not uncommon to find a once-through
cooling water partially or wholly used as makeup to an open recirculating system. A closed
system that is open to the atmosphere such as a central sump, in this case the sump serves
only as a collecting point for the cooling waters; evaporative cooling does not take place.
Although one may encounter cooling systems that do not seem to fit the simple categories,
the approach to treating these systems will usually be based on the considerations of whether
the systems are once-through, closed or open recirculating.
1) non-evaporative
58
GPS//2003
2) evaporative
Evaporative cooling system, which utilizes the latent heat of vaporization plus convection
cooling, cause substantial changes to the water used. Concentration of mineral impurities due
to evaporation must be considered when calculating treatment requirements.
In this design, cooling water is pumped through a point of heat exchange or heat transfer,
increasing the temperature of the cooling water to T2. The cooling water flows through the
recirculating lines to the cooling tower deck from which the water falls by gravity through the
tower packing (or fill) to the tower basin. Heat is rejected to the atmosphere by means of
evaporation (E) as cooling water droplets are broken up in the packing and air passes upward
by means of mechanical or natural draft. The rejection of heat in the recirculating water (R)
by evaporation (E) restores the cooling water to temperature T1, at which point the cooling
cycle begins again. The cooling tower serves two purposes:
heat rejection
water conservation
In the operation of the cooling tower, water is continuously evaporated and must be replaced
Evaporation
(heat rejection)
Heat Load
Cooling Tower from Process
Make Up Bleed-Off
with fresh makeup water. This results in an increase in the concentration of dissolved solids
in the recirculating water. The ratio of the total dissolved solids in the recirculating water to
the total dissolved solids in the makeup water (TDSR/TDSM) is called C (cycles of
concentration).
As cycles of concentration (C) increase, some of the dissolved solids in the recirculating
water approach the limit of their solubility in water. This is especially significant for
dissolved minerals, which form scales, as they become less soluble as the temperature of the
recirculating water increases. Therefore, they tend to deposit in areas of elevated temperature
and lower water velocity such as in heat exchange equipment.
In order to prevent the formation of scales, a portion of the concentrated recirculating water is
bled (bleed-off) from the system and replaced by less concentrated makeup water. Bleed-off
(B) maintains the recirculating water at the desired level of cycles of concentration.
In addition to bleed-off, some water droplets containing concentrated dissolved solids are lost
through the evaporation equipment in the cooling tower. This windage (W) loss may vary
from one cooling tower to another between 0.05% and 0.1% of the recirculating rate (R). For
most cooling tower calculations, windage (W) is included in the tower bleed-off (B).
Make-up is the sum of all water losses:
M=E+B+W or M = E + B* (2)
Evaporation can be estimated for the system using the following expression:
E = .001 x R x T x f (3)
This expression indicates that the evaporation rate (E) is approximately equal to 0.1% of the
water circulated (R) over the tower for each 1oF of temperature drop times a factor (f).
The factor (f) represents the percent of cooling that is contributed by evaporation only. The
total cooling effect when warm water is in contact with cooler air is not due to evaporation
alone. Sensible heat transfer from the warm return water to the cooler air will accomplish a
certain percentage of the cooling depending on the temperature of the ambient air. The
convective cooling effect may range from 40% in winter to 10% in summer or conversely f
will vary between .6 and .9 depending upon time of year. A typical number is 0.8 for a
yearly average.
To calculate the amount of bleed-off water (B) required to maintain a given level of cycles of
concentration (C), use the equation:
B=E
C-1 (4)
60
GPS//2003
Makeup (M)
1000
Blowdown (M-E)
Evaporation (E)
In practice, the quantity of makeup water required for the operation of a given cooling tower
may be estimated with a fair degree of accuracy, using the previous equations.
50
40
Bleed-off (GPM)
Savings
30 3 Cycle s
4 Cycle s
5 Cycle s
20 6 Cycle s
10
0
0 20 40 60 80 100 120
Evaporation (GPM)
Cycles of concentration, (C), are frequently determined, not by total dissolved solids
measurement, but by specific conductance or by any non-reactive chemical constituent which
can be accurately tested in both the makeup and the recirculating water. Care should be taken
that the measured constituent is not one, which is added with the treatment chemicals.
Chloride ion is often used but is not well suited for this purpose when chlorination is
practiced or other treatment products containing appreciable chloride are added to the system.
In most open recirculating cooling water systems, the concentration of treatment in the
cooling water required to inhibit scale and corrosion is relatively constant. Therefore, as
cycles of concentration are increased to a maximum, the amount of treatment required to
maintain a given concentration in the recirculating water is diminished proportionately. In
order to determine the quantity of treatment needed to maintain a given concentration in the
recirculating water, use:
As cycles of concentration increase, the potential for corrosion, scale or fouling generally
increases. There is a practical limit beyond which cycles of concentration cannot be
increased for most cooling systems. Potential problems and their control are discussed in a
later section.
The quantity of treatment required to slug dose a cooling system of V (Gal) is:
It is frequently useful to determine the time elapsed to deplete the cooling system of a given
species of treatment or of a contaminant. The half-life (t1/2) of a given species within a
cooling system is a special case of equation (6):
This is the amount of the time required to reduce the concentration of treatment (or
contaminant) by 50%.
62
GPS//2003
EXAMPLE
An open recirculating cooling water system has a design recirculating rate of 12,000 USgpm
and operates consistently 24 hours per day, year round.
The cooling range measured across the cooling tower is 18oF (108oF at the top of the tower
and 90oF in the tower sump). The heat load on the system is constant. There are no water
meters on the tower makeup line, but the blowdown line has been monitored and flow
measured at 60 USgpm. The design specifications for the tower indicate windage losses at
0.05% of the recirculating rate.
E = .001 x R x T x f
E = .001 x 12,000 USgpm x 18oF x 0.8 = 172.8 USgpm
The specific conductance of the recirculating water measure four times that of the makeup
water indicating that the system is operating at four cycles of concentration. This was
confirmed by the silica concentrations as well:
B = E/(C-1)
B = 172.8 gpm/(4-1)
B = 57.6 gpm
Using the design specification for windage, 0.05 of the recirculating rate, or 6 USgpm, the
calculated blowdown rate compares reasonably well with the measured rate of 60 USgpm.
Equation (1) is used to determine makeup requirements for the system and may be compared
with other plant water consumption data (when available) for accuracy.
M=E+B
M = 172.8 + 57.6
M = 230.4 USgpm
Biocides, are frequently slug fed to a cooling water system, at a recommended dosage (65
ppm, for example). The total system volume has been determined to be 75,000 gallons. The
quantity of biocide required to slug dose the system can be determined from equation (5).
Occasionally, the cooling water system becomes fouled with oil contamination. To
determine how long it will take to blowdown 50% of a 300 ppm oil contamination at a
maximum bleed rate of 100 gallons/minute, use equation (7):
= 525 minutes
= 8.75 hrs
Each of the above factors must be taken into consideration prior to selection of a treatment
program.
Calcium carbonate
Cycles of concentration in many systems are limited by calcium carbonate solubility. The
common measure of calcium carbonate solubility for cooling water systems is the Langelier
Saturation Index (LSI). For maximizing cycles of concentration when applying moderate
duty products, limit the LSI to +2.0. For heavy duty products limit the LSI to +2.5 to +2.75.
Calcium phosphate
In the makeup water for the cooling water system which contain phosphate (ortho or poly),
the cycles of concentration will usually be limited by calcium phosphate solubility. Using the
calcium hardness, ortho phosphate, pH and maximum heat exchanger exit temperature of the
recirculating water, determine the maximum cycles of concentration based upon calcium
phosphate solubility.
64
GPS//2003
Silica
Some cooling water systems are limited in cycles of concentration by silica (SiO2). Silica
solubility is a complex function of several variables including silica concentration, pH,
temperature, magnesium and calcium concentrations. In general, bulk silica deposition
occurs in the colder areas of the system and is relatively independent of pH. The solubility of
magnesium and calcium silicate salts is very pH dependent. They tend to deposit on hot
surfaces at elevated pH like other salts with inverse temperature solubility curves. As a
general rule, keep silica concentrations below 170 ppm (SiO2) to limit cycles of concentration
and to prevent silica-based deposits.
Calcium sulfate
In sulfuric acid-modified cooling systems, calcium sulfate may become the limiting factor for
maximizing cycles of concentration. Where sulfuric acid is fed, add the sulfate in the
makeup water to the M alkalinity removed from the makeup water before multiplying by
the anticipated cycles. Using the calcium hardness and the sulfate concentration, one can
determine if precipitation is expected (or not) under various conditions. Calcium sulfate
precipitation is independent of pH.
Suspended solids
To prevent fouling of critical heat exchange equipment by dirt, airborne debris, or other
various sources of suspended solids, limit cycles of concentration to around 7. If a system
has side-stream filtration, it is possible to operate at much higher cycles of concentration.
Leaks or overflow
Some cooling systems are limited in cycles of concentration by windage, leaks,
uncontrollable system losses, or uncontrollable sources of makeup (in-flow). In these
circumstances, these other parameters will be the controlling factor.
Alkalinity/pH Control
Although the trend in cooling water treatment appears to de-emphasize control of cooling
water alkalinity or pH due to the disadvantages and dangers of feeding acid, the concept is
widely used and should be considered where difficult water supplies exist or if water
availability is limited.
Sulfuric acid (66O Baume, 93% H2SO4 density 1.8) is is the most commonly used. The
reaction with bicarbonate alkalinity:
Since the equivalent weights of CaCO3 and H2SO4 are approximately the same, approximately
1 ppm of acid is necessary to react with 1 ppm M alkalinity. For all practical purposes and
for speed of calculation H2SO4 reacts with M alkalinity on a 1:1 basis.
In water chemistry, total alkalinity is expressed as calcium carbonate. Therefore, ions such as
HCO3 and CO3, which are responsible for the bulk of alkalinity in water supplies, are also
expressed as CaCO3.
The original concept of feeding acid was predicated on maintaining the solubility of the
calcium compound, calcium carbonate. Assuming that carbonate ion will only exist in a
cooling water at above pH 8.3, enough acid is fed to depress pH of the cooling water below
Acid was fed to cooling waters, then to maintain a pH range below the P alkalinity end
point (pH 8.3). This precluded the presence of CO3 ion, which would unite with Ca+2 to form
CaCO3 scale.
Originally, when acid feed was adopted, the control range was expressed as ppm M
alkalinity in the recirculating water. P alkalinity was always zero. Sufficient acid was
applied to maintain a safe M alkalinity range whereby non-scaling conditions would exist
and to provide a margin of safety in the event of a temporary acid feed insufficiency.
This method of control is still reliable and is utilized for treatment programs such as zinc-
phosphate, zinc-polyphosphate, zinc-phosphonate and high phosphate. The trend today is for
alkaline treatment programs in which acid is used to maintain pH (and M alkalinity) in the
alkaline range, generally above 8.3 where corrosion is minimized and scale is inhibited has
resulted in a different control strategy.
Acid requirements based on M alkalinity are much easier to calculate. The M alkalinity
desired in pH-controlled cooling water can vary from approximately 20 to as high as 500
ppm depending upon the treatment program. Buffering, common ion effect, varying
temperature, errors in pH measurement, etc, tend to influence pH readings which, in turn,
make pH control less dependable than alkalinity measurements.
The pH control agent (acid) dosage will be determined by the amount of M alkalinity
desired as well as its activity. H2SO4 requirements may readily be calculated after the
desired pH range of M alkalinity range is determined.
66
GPS//2003
Example:
An open recirculating system is to be treated with acid to prevent scale and an inhibitor for
corrosion control. It is estimated that the desired M alkalinity should be in the control
range of 20-40 ppm in the recirculating water. In most instances this will produce an average
cooling water pH 7.0 7.5.
The makeup water contains 270 ppm M and the system operates at 3 cycles. What quantity
of H2SO4 must be fed to the makeup to produce an average of 30 ppm M in the
recirculation cooling water?
If 30 ppm M is desired in the cooling water, then the alkalinity of the makeup water must
be reduced to 10 ppm M. The 10 ppm M x 3 cycles will concentrate to 30 ppm M in
the cooling water.
M in makeup M desired in makeup = ppm
M to be neutralized = ppm H2SO4
or:
270 ppm M 10 ppm M = 260 ppm M or 260 ppm H2SO4
then:
Makeup USgpd X 260 ppm = lbs H2SO4 required per day
120,000
Example:
106
Example:
Once-though water used to cool air compressors flows at 300 gal/min before discharge to the
river. How many lbs/day of a polyphosphate product is required if the recommended dosage
is 3 ppm?
120,000
68
GPS//2003
B. Types of Micro-organisms
i) Bacteria
ii) Fungi
iii) Algae
C. Microbiological Control
i) Oxidizing Biocides
ii) Non-oxidizing Biocides
iii) Selection Criteria
iv) Monitoring
Microorganisms foul and corrode cooling systems. For these reasons (and others), it is
important to maintain control of microbiological activity.
Cooling towers are designed and operated to dissipate waste heat from industrial
manufacturing processes and air conditioning systems. In typical refrigerant condensers
(chillers), water enters at 80-90oF and leaves 90-100oF. Similar heat loads are seen in many
industrial processes. This waste heat is then removed from the water across the cooling
tower.
During the cooling process, the warm water is pumped to a distribution deck from which it
cascades over the tower fill as droplets or a thin film. Having the water as small droplets
allows for creation of greater surface area, which is exposed to the air flow. This enhances
the cooling effect. The cooled water is pumped back through the heat exchangers (or
condenser system), and the cycle is repeated.
As cooling and evaporation of the water takes place, the dissolved solids in the water
concentrate. As the impurities in the cooling water concentrate up, nutrients also increase,
which enhances the potential for biological activity.
Microbiological activity in cooling water systems reveals itself in various ways. The most
obvious are the visible signs of slime, sludge, and algae deposits on the cooling tower itself.
Less obvious are the problems of reduced cooling efficiency and ineffective corrosion
protection.
Microbiological fouling in cooling water systems results from the growth and multiplication
of bacteria, fungi, and algae through the various parts of a system. A few slime-forming
organisms enter the tower water from the air or make-up water and multiply very rapidly to
form slime masses. Cooling towers and their recirculating water environment are able to
provide the invading organisms with nutrients, temperature, and pH necessary for growth. As
they grow, these bacteria secrete large amounts of a sticky, glue-like slime, also called EPS
extra-cellular polysaccharide, which coats condenser tubes, transmission piping, and cooling
tower surfaces (Figure 6.1).
The sticky nature of EPS allows it to trap other organisms, dirt and silt. These biological
slime growths may show different physical properties depending on the type of organisms
involved : stringy, gelatinous, thick and viscous, or leathery.
The resulting effects of slime formation include plugged recirculation lines and condenser
tubes, reduced filter flow, reduced heat transfer efficiency, formation of hot spots,
establishment of potential corrosion sites, and related problems.
70
GPS//2003
O2
OH- Microbial
colony
M2+
Cathodic area
Anodic area
Loss of heat transfer efficiency is probably the most common cause of excessive operating
costs in water cooled air conditioning systems.
For example, slime deposits as small as 0.012 inch (less than 1/64on a condenser tube will
cause a chiller unit to consume 10-20% more electricity than when the tubes are clean.
Corrosion, which occurs beneath slime deposits, can result in pits completely penetrating
condenser tubes.
Slime formation is only one of several problems that can be related to microbiological
contamination.
Fouling
Loss of heat transfer
Energy losses (pumping problems)
Reduced efficiency
Could cause shutdowns
Health risks (Legionella, etc.)
Corrosion
Equipment replacement
Production losses
Tower components
Deterioration of wood
Plugging
Reduced tower efficiency
Tower replacement
B. Types of Microorganisms
Slime formers forms a protective sheet that entrap solids which can:
- Causes underdeposit corrosion
- Plugs heat exchanger
- Reduces flow through piping
- Interferes with treatments
- Survives best in pH range of 5-9
Iron Bacteria
- Uses ferrous iron in its metabolic process Fe+2 Fe+3
- Deposits red/brown slime mass
- May lead to plugging
- Promote underdeposit corrosion
- Thrive in the pH range of 7.5-9.5
Sulfur Bacteria
- Uses sulfides or sulfur for metabolic process
- Cause depressed pH and severe corrosion
- Thrive in acidic environments
- Can support sulfate reducers
Nitrogen Bacteria
- Can be slime formers
- Usually found in conjunction with nitrite reducers
- Acid producing NH3 NO3- + H+
- Can cause severe copper corrosion to occur
- Thrives in the pH range of 4-8
72
GPS//2003
Algae Chlorella Single Cell 5.5 to 9.5 Require air (aerobes) Green and blue-green slimy
Ulothrix or thread- 60 to 130oF and light for growth growths in lighted areas.
Oscillatoria like
Melosira
Bacteria Flavobacterium Spheres and 5 to 9 Most require air Slime masses due to capsule
Aerobacter rods 60 to 150oF (aerobes) for growth. or waste materials can plug
Pseudomonas occuring However, there are heat exchangers, reduce heat
Bacillus singly or in some that cannot transfer efficiency, accelerate
Achromobacter chains tolerate any air corrosion and cause build-up
(anaerobes). Do not of foulants. Color of slime
require light. mass is usually gray-brown.
Iron Gallionella Single Cell 5.5 to 8.2 Require air (aerobes) Require ferrous iron for
Bacteria Crenothrix or thread- 41 to 77oF and light for growth growth. Deposit insoluble
like ferric hydroxide which results
in a red-brown slime mass.
The slime mass can plug heat
exchangers, piping and can
materially reduce heat
transfer efficiency.
Sulfate Desulfovibrio Single rods 5.5 to 8.5 Generally cannot Black insoluble ferrous
Reducing straight or 77 to 140oF tolerate air. Do not sulfide deposits plus heat
Bacteria curved require light to grow exchangers and accelerate
corrosion. Capable of
generating large quantities of
hydrogen sulfide.
Table 6-1
Facultative
These types of bacterial make up part of most bacterial colonies, since they :
Molds
Filamentous
Cause surface rot of wood
Slime
Nutrients
Yeasts
Slime formers
Very thick rubbery growth
Difficult to kill
Basidiomycetes
Internal wood rot, uses cellulose
Very difficult to kill
All the above form spores which are practically impossible to kill. These organisms thrive in
a very broad pH range anywhere from 2-8.
ii) ALGAE
As can be seen in Table 6.1, algae shares many characteristics in common with bacteria,
except for one they can produce their own food. Algae :
Requires sunlight
Can form thick mats on decks and fill
Can cause rapid deposit formation
Is difficult to control
Can cause severe flow problems
Provides nutrients for bacteria
May cause severe corrosion of galvanized decks
Thrive at a pH range of 5-9
74
GPS//2003
C. Microbiological Control
i) OXIDIZING BIOCIDES
Oxidizing biocides are widely used and offer a variety of advantages however, their
application must be matched to the particular system to see the strengths realized.
Chlorine
The most commonly used biocide is chlorine and it is the standard against which all others
are compared. Chlorine gas is typically fed continuously to maintain a free residual
chlorine level of 0.2 0.5 ppm. The feed rate is usually based on the recirculation rate of
the cooling water.
HOCl H+ + OCl-
Other disadvantages of chlorine are its short persistence, thus requiring frequent feed, its lack
of effectiveness on some species of fungi and algae, and its inability to penetrate slime
masses. High dosages will cause deterioration of tower lumber, and chlorine gas is
dangerous to handle. In addition, chlorine in water discharged is generally not permitted.
The more common practice is to use bleach (sodium hypochlorite) as the chlorine source.
The strength of sodium hypochlorite can vary considerably from <10% to over 12%. Also,
sodium hypochlorite solutions are inherently unstable and will auto-decompose to oxygen gas
and chloride. The rate of breakdown is governed by temperature and the quality of the bleach
solution.
Hypochlorous acid is an effective, low cost microbicide. However, best results are most
frequently achieved when used in conjunction with a non-oxidizing microbicide or a
biodispersant.
Advantages :
Economical
Effective on nearly all microorganisms
Easily applied
Easily controlled
Disadvantages :
Table 6.2
76
GPS//2003
Sodium Hypochlorite
Advantages :
Convenient liquid
Economical
Easy to feed
Easy to test
Disadvantages
Calcium hypochlorite
A common name for this material is HTH and is routinely sold for swimming pool use.
Advantages :
Powder
Disadvantages :
Adds hardness
Adds alkalinity
Chlorine dioxide
Chlorine dioxide has been widely used as a disinfectant for many years. It is effective over a
wide pH range (6-10) and is a stronger oxidizing agent than hypochlorous acid. It does not
react with ammonia or amines, which gives it a distinct advantage over hypochlorous acid in
amine contaminated systems. However, it does react with other contaminants, which can
result in a high chlorine dioxide demand. It is frequently generated on site using chlorine and
sodium chlorite and is considerably more expensive on a weight-to-weight comparison with
chlorine gas.
Advantages :
Very expensive
Requires special generation on site
Cl2 + NaClO2 2 NaCl + 2 ClO2
Advantages :
Easy to handle
No special equipment
Works well at higher pH
Cuts slimes
Little effect on pH
Dissolves slowly
Disadvantages :
Expensive
Can be extremely corrosive
Feeding can be a problem
Ozone
Advantages :
Powerful oxidizer
Works well on all living organisms
No undesirable reaction products
No effect on system water chemistry
Decomposes photochemically
Harmless to aquatic life
Disadvantages :
78
GPS//2003
Bromine
Bromine salts such as sodium bromide and BCDMH offer the advantages of chlorine but
perform better at high pHs. Sodium bromine on its own has no biological activity and must
be activated by an oxidizing agent. The most common one is bleach and the reaction is:
In a water system, a significant portion of the NaOBr is actually present as HOBr, a non-
ionized species.
In contrast to the need to feed two separate liquids (sodium bromide and hypochlorite
solutions) the advantages of bromine chemistry can be achieved using BCDMH. BCDMH is
available in several forms (powder, granules, tablets), although the tablet form is the most
widely used.
Since the halogen is attached to the BCDMH, it acts like a donor and prevents the halogen
from reacting (to some degree) with trash organics in the cooling water.
Advantages :
pH % HOCl % HOBr
6.0 97 100
7.0 76 98
7.5 50 94
8.0 24 83
8.5 9 60
9.0 3 33
Table 6-3
In Table 6-3, one can see that at any given pH there is a significantly higher concentration of
the non-ionized HOBr than there is for HOCl. Since the hypohalous acid can more readily
penetrate the micro organisms cell wall, it is more effective as a biocide. This is the
advantage of using bromine chemistry compared to chlorine its ability to achieve more
rapid kills under alkaline conditions.
Characteristics
80
GPS//2003
Mode of Action :
Advantages :
Broad spectrum
Good for molds
Good dispersant qualities
Excellent algaecide
Disadvantages :
Mode of Action :
Broad spectrum
Broad pH range
Exibits some surfactant/detergent action
Glutaraldehyde
Mode of Action :
Advantages :
Disadvantages :
82
GPS//2003
Metabolic Poisons
MCI (Isothiazolones)
This is perhaps one of the most widely used biocides due to it wide range of application.
Mode of Action :
Metabolic Inhibitor
Advantages :
Broad spectrum
No odor
Wide pH activity
Not affected by foulants
Nonionic
Biodegrades chlorine resistant
Photo-degrades
Very good for nitrite reducers
Disadvantages :
Inactivated by
Amines
Sulfides
Long retention times required (4 6 hours)
Is skin sensitizer and irritant
Weak algicide
Mode of Action :
Enzyme poison
Chelates iron in energy producing step
Advantages :
Non-ionic
Broad spection
Excellent for sulfate reducers
Rapid decomposition
Good fungicide
Thiones
Thione (tetrahydro-3, 5-dimethyl-2H-1, 3, 5 triadiazine-2-thione) is a reducing biocide. It
will react with iron (corrosion products) and forms a dark precipitate. Thione hydrolyzes in
water to form formaldehyde a known carcinogen. It also reduces the efficacy of DBNPA and
oxidizers. It can also produce MITC (methyl iso thiocyanate).
Mode of Action :
Reproductive Inhibitor
It is recommended fro aerobic and filamentous bacteri but, not for fungi, anaerobic bacteria
and SRBs.
Sulfones
Sulfone (bis (trichloromethyl) sulfone) is not commonly used in microbicide formations. The
activity of this compound is pH sensitive being effective in a pH range of 6.5 to 8.5.
Carbamates
Thiocarbamates are excellent microbicides against slime forming bacteria, cellulolytic fungi
and sulfate reducers. At low dosages these compounds are not effective.
Advantages :
Similar to others
Broad pH range
Not affected by foulants
Good for sulfate reducers
Disadvantages :
Precipitated by metals
Not effective on algae
Slow acting (at least 6 hours contact)
84
GPS//2003
DBNPA
Dibromonitrilopropionamide (DBNPA) is gaining increasing acceptance due to its ability to
hydrolyze to essential harmless degradation products. It is effective at low dosages and has
broad spectrum activity. However, it does decompose rapidly at high pH and is, therefore,
limited to use in systems operating at a pH of 7.5 or less.
Mode of Action :
Advantages :
Broad spectrum
Fast acting (80% kill in 30 minutes)
Effective at low concentrations
Nonfoaming
Non-ionic not affected by foulants
Degrades rapidly
Decomposes to nontoxic products
Disadvantages :
BNPD
Bromonitropropane diol (BNPD) is gaining market share due to its safety profile. It is widely
used as a preservative for cosmetics, shampoos and pharmaceuticals.
Mode of Action :
Advantages :
Broad spectrum
Safe to use / enviromentally acceptable
Nonfoaming
Non-ionic not affected by foulants
Disadvantages :
Mode of Action :
Enzyme inhibitor
Advantages :
Broad pH range
Excellent on mold, fungi and algae
Good as a preservative
Disadvantages :
THPS
THPS (tetrakis hydroxymethyl phosphonium sulphate) is only now beginning to be seen in
cooling water applications, although it is not a new biocide.
Mode of Action :
Advantages :
Broad spectrum
Particularly effective against SRBs
Good environmental profile
Formulated with a low form anionic surfactant to enhance biofilm removal
Disadvantages :
86
GPS//2003
BHAP
BHAP (2-bromo-4-hydroxyacetophenone) is used by Buckman on a limited basis.
Mode of Action :
Advantages :
Broad spectrum
Good under alkaline conditions
Effective on slime and deposits containing filamentous iron bacteria
Disadvantages :
Chosen properly
Applied properly
Alternated using different classes of biocides
Monitored properly
Targeted to control the actual problem
Organics
Reducing agents
Sulfite
Bisulfite
Sulfides
- All reduce the effectiveness of oxidizers
- Sulfides consume MCI and DBNPA
Iron
Anionic organics
Anionic antifoulants
Tannins
Lignins
Humic acid
All the above, anionic organics, reduce the effectiveness of Quats and amine biocides by
precipitation due to charge neutralization.
88
GPS//2003
System pH
Water hardness
Retention time
Environmental restrictions
Practical restrictions
Aside from theoretical/chemical aspects, there are several additional factors that can
influence the biocide selection. These include :
Foam
- Safety hazard
- Can limit equipment efficiency
- Can cause physical damage
- Unsightly
Odor
- Usually only a minor complaint
Water sampling
Deposit samples
Visual inspections
Physical inspections
Other methods
Biocide Enhancement
All biocides are the primary tool to maintain biological control; other steps can be taken to
enhance their performance both physical and chemical.
Physical cleaning
Surfactants/Biopenetrants
90
GPS//2003
The above diagram shows what one would expect given a good control program. Namely
B iological A ctivity
B iocide
F eed
L evel
T im e
that the level of micro activity (regardless of whether ATP or CFUs are used as the
controlling parameter) is kept below a pre-selected value. Once the micro level reaches the
action-point, the biocide is dosed to the system and kills the organisms to a lower value,
where it remains for a period of time before rising back to the action-point.
Some definitions in this glossary are specific to cooling water applications and as such their
usage in other areas may vary.
A
Acid: A compound that dissociates in water to give an increase in hydrogen
ion concentration.
Acid Cleaning: The act of removing adhering deposits by dissolving with an acid
solution in which the deposited material is converted into a soluble
state or where the binding material is made soluble. In the latter
action, the insoluble part is disintegrated or dislodged.
Admiralty Brass: An alloy of 70 percent copper, 29 percent zinc and 1 percent tin.
Arsenic or antimony may be included to minimize dezincification.
Algae: Simple forms of aquatic plant life which use sunlight for
photosynthesis and as part of their life cycle.
92
GPS//2003
B
Bacteria: A lower form of life. These organisms are usually in the form of rods,
or spheres. Bacteria are responsible for slime in cooling water
systems.
Basin: That part of a cooling tower that receives the water that has passed
through the tower. This may sometimes be referred to as the sump or
it may also be used to designate the pond area of a constructed spray
cooling system.
Bicarbonate: A form of alkalinity found in varying amounts in all natural waters and
in cooling water systems. It represents carbonic acid with half of the
acidity neutralized or it can be considered carbonate with half of the
alkalinity neutralized.
Bimetallic Couple: Two metals in electrical contact that have different electromotive
activity in a solution to produce an electrochemical cell with corrosion
occurring on the more soluble or active metal.
Bleed-off Rate: This generally refers to continuous bleed-off where the regulated
amount of water withdrawn.
Calcium Sulfate: In precipitated or insoluble form, it can produce a very inert, adherent
deposit or scale.
Carbon Dioxide: A gas that has an acidic reaction when dissolved in water, it forms
carbonic acid.
Cathodic Inhibitor: A chemical that prevents or reduces chemical reactions at the cathodic
surface of a metal.
94
GPS//2003
Continuous Feed: The act of continuously adding chemicals to a water in appropriate
amounts. Generally requires some means of control or regulation to
proportion chemicals into the water being treated.
Cooling Tower: A structure, generally of wood parts in the larger units, that provides
for cooling of water by its evaporation. Water is dispersed and flows
downward through a flow of air.
Cooling Water: Any water that removes heat from a point or area of higher
temperature and delivers to a point or area of lower
temperature.
Cycles of Concentration:
This is a numerical expression of the degree to which the soluble
mineral salts have been concentrated in a water. It is a direct ratio of
the minerals in a system subjected to evaporation and the minerals in
the make-up water to that system.
D
Delignification: Action on wood resulting from chemical or biological activity that
destroys tannins and lignins from wood leaving the structure in a
fibrous, weakened state.
Deposition: This can indicate the act of depositing. Sometimes used synonymously
with deposits.
E
EDTA: Ethylenediaminetetraacetic acid - a chelating agent widely used as a
reagent in hardness determination.
Eductor: The mechanical arrangement for the removing of a gas or a liquid from
a system by means of a high velocity flow of another gas or water
stream through an orifice, etc.
Electrolyte: A solution of positive and negative ions which will conduct electric
currents.
Extractives: Generally refers to those natural substances in wood that are soluble in
water and therefore can be dissolved out of it over time.
F
Ferric Iron: A form of iron oxidized to its trivalent, most stable state. Ferric salts
are generally insoluble in water.
Flow Rate: The movement of water expressed in volume per unit time, eg. M3/hr
gallons per minute, etc.
Flushing: The act of cleaning out a system, using a flow of water generally at
high rates.
G
Galvanic: An electrochemical action due to a couple made up of dissimilar
metals.
General Corrosion: A form of corrosion that is distributed widely and more or less
uniformly over a metal surface.
96
GPS//2003
Hydrogen Sulfide: A toxic gas which smells like rotten eggs. It forms a weak acid in
water.
Hydroxide: The counter part to hydrogen ions in water solutions. It represents the
degree of basicity of a solution.
I
Inhibitor: Refers to material or materials in water solutions that prevent or
minimize corrosion or scale.
Intermittent Feed: Feed of chemicals at separate, generally set intervals, i.e. not
continuous.
Iron: The major component of steel - widely used in cooling water systems.
Iron Oxides: A reaction product of oxygen with iron. It may refer to ferrous oxide,
ferric oxide, or a combination that produces magnetite.
Iron
Phosphate: A reaction product of iron with ortho phosphate. A frequent foulant in
phosphate-treated systems which have experiences excessive
corrosion.
Iron Rot: Deterioration of wood in contact with iron, a problem associated with
iron fastenings, or other iron-wood assemblies.
L
Langelier Index: An empirical correlation for calcium carbonate solubility that is useful
in predicting scaling behavior in cooling waters.
M
1-CWT Page 97 of 117 0902
Magnesium Hardness:
Water hardness due to soluble magnesium.
Make-Up: Refers to fresh or raw water added to a system to replace that lost by
evaporation, bleed-off, leaks, wind drift, etc.
Methyl Orange: An indicator dye used to determine total alkalinity. Color change at
end point (pH 4.3) from yellow to salmon pink. Also used as part of a
test that is specific for free halogen.
Methyl Purple: An indicator due used to determine total alkalinity. End point color
change is from green to purple (Acid) at pH 4.3 4.5.
Mill Scale: Accumulated oil, grease, and debris which is associated with the
manufacturing process of (and is found adherent to) pipes and
equipment used in water systems.
Minerals: Generally refers to any soluble or insoluble metal salt, eg. CaCO3,
Fe2O3, MgSO4, etc.
N
Nitrites: Common term for sodium nitrite which is used for corrosion inhibition
in water solutions.
Nonferrous: Metals other than iron or steel, or alloys containing as their principle
constituent, metals other than iron or steel.
O
Open Recirculating: Any system in which water is recirculated and cooled primarily by
evaporation.
Oxide film: A thin film formed by the reaction product of oxygen with a metal.
98
GPS//2003
Oxygen: A gaseous material that is very reactive with most common metals
when it is dissolved in water contacting these metals. In cooling
waters, air is the source of the dissolved oxygen.
P
Parts Per Million: A measure of concentration (parts of solution per million parts of
solvent), i.e. ppm. It is also equivalent to mg/L.
pH of Saturation: The pH above which a solution of otherwise soluble ions will begin to
precipitate. Useful in predicting scaling potential of a water.
R
Recirculating Cooling Water:
Any cooling water system where the water is repeatedly used to cool a
system, rather than being used once and then discharged.
Rot: Wood destruction by biological organisms that use the wood for food.
Rust: Common designation for the stable ferric oxide product of corrosion of
iron or steel.
S
Sample: A small portion of a solution taken from a system for purpose of tests
to determine chemical and physical conditions therein.
Scale: Any dense, cohesive, crystalline material that forms a tightly adhering
mass on a surface. In cooling water systems, this may include
precipitated mineral salts, corrosion products, and/or suspended matter.
Scale Control: Any measure that will prevent or minimize scale deposits.
Softening: The act of removing all or part of the hardness constituents from a
water solution.
100
GPS//2003
Sulfur Dioxide: A gaseous oxide of sulfur, which gives rise to sulfurous acid in water.
Sump: A reservoir into which water collects and from which it can be
pumped, used synonymously with cooling tower basin.
Synergistic: A system in which the total effect is greater than the sum of the two
effect taken independently.
T
Tannins: Dark colored extractives present in cell cavities of wood.
Treated Lumber: Wood treated with a chemical preservative prior to its use in
fabrication of a cooling tower. CCA (chromate, copper, arsenic) is the
most commonly used treatment.
Tubercle: Mounds of corrosion products covering the anodic spots where pits are
developing.
W
Wood Deterioration:Degradation of cooling tower wood through chemical or biological
action.
Z
Zinc Ion: Cathodic inhibitor commonly used in conjunction with ortho
phosphate, phosphonates, organics or combinations of these.