Вы находитесь на странице: 1из 16

Substation Automation and PCM 600

Protection Training Application Configuration


CAP 531
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


1

Application Configuration CAP 531

CAP 531 IS THE MASTER TOOL!

You MUST start the engineering from CAP 531.


After COMPILING the graphic configuration, CAP 531 passes
IMPORTANT INFORMATION to other subtools:

PCM 600 receives the list of used functions


SMT receives the list of hardware cards and used virtual I/O
GDE receives the used control and measurement blocks
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


3
Application Configuration CAP 531

In CAP 531 the application configuration is drawn without


considering the hardware set-up of the IED.

The association VIRTUAL I/O PHISICAL I/O is done in SIGNAL


ABB Power Technologies AB, 2007

MATRIX

2007-09-07 Substation Automation and Protection Training


4

Application Configuration CAP 531


ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


5
CAP 531 On Line Software Library Synchronization
ONLINE / UPLOAD OPTIONS

IF YOU HAVE THE IED connected to the PC, the fastest way to get the PC
function library synchronized with the IED library is to run Upload Options:

BEFORE UPLOAD OPTIONS:


PC contains more functions than IED
ABB Power Technologies AB, 2007

AFTER UPLOAD OPTIONS:


PC contains the same functions than IED

2007-09-07 Substation Automation and Protection Training


6

CAP 531 On Line Software Library Synchronization


EDIT / FUNCTION SELECTOR
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


7
ABB Power Technologies AB, 2007
CAP 531 Draw the Configuration

2007-09-07 Substation Automation and Protection Training


8

CAP 531 Insert a Work Sheet


Select the terminal and choose the menu Edit / Insert:

Enter the name of the work sheet


ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


9
CAP 531 Insert Function Blocks
Choose the menu Object / Function Block:
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


10

CAP 531 Insert Function blocks


In the window choose the correct function block and click on Ok.
ABB Power Technologies AB, 2007

The function block will appear on your work sheet.

2007-09-07 Substation Automation and Protection Training


11
CAP 531 Connect Function Blocks
Click on the button and start connecting the signals
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


12

CAP 531 Variables


This configuration:
Is equivalent to this one:
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


13
CAP 531 Cross Referenced vs Not Cross Referenced
CROSS REFERENCES

If you want a variable to be


cross-referenced in
CAP print-out, just drag
the variable to cross
the red dashed line
shown by CAP 531
when you choose the
menu Layout / Page
Borders.
ABB Power Technologies AB, 2007

Cross Referenced Variables


NOT Cross Referenced Variables

2007-09-07 Substation Automation and Protection Training


14

CAP 531 Graphic Buttons

Zoom Out

Zoom In

Select Zoom Area Create Variable

Select Mark Mode Insert Function Block

Select Drawing Mode Free Text


ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


15
ABB Power Technologies AB, 2007
CAP 531 CAD Features

2007-09-07 Substation Automation and Protection Training


16

CAP 531 Insert a Template


ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


17
CAP 531 Page Layout

With CAP 531 you have the possibility to associate a page layout
to your drawing with all the important data:

- customer name
- issue date
- drawing number
- etc.

It is also possible to customize the page layout according to your


customer needs.
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


18

CAP 531 Page Layout


From Page Preview you can see how the drawing will be printed out:
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


19
CAP 531 Compiling the Configuration
When the Application Configuration is
ready you have to compile it

Note: The Graphic Application


Configuration does not contain any
Input/Output information. It only
contains VIRTUAL I/O information!
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


20

CAP 531 Downloading the Configuration

The successfully compiled


configuration can be downloaded
into the IED:
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


21
CAP 531 Downloading Phase
1) Secret Upload Options (reading)

2) Download of operative configuration (writing)


ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


22

CAP 531 Downloading Phase


3) Uploading of configuration (reading)

4) Comparing PC configuration against uploaded one


ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


23
CAP 531 Downloading Phase
5) If Compare is not Ok you are requested to download again

6) If Compare is Ok :
Download of graphic information of configuration
(the so called zip file) (writing)
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


24

CAP 531 Exit CAP531 and go back to PCM 600


When you exit CAP 531 containing a successfully compiled
configuration, the list of used functions is associated to your
IED in PCM 600 structure.
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


25
CAP 531 Uploading application configuration from IED

UPLOAD THE CONFIGURATION


ABB Power Technologies AB, 2007

You can upload the graphic configuration from the terminal into the PC.

2007-09-07 Substation Automation and Protection Training


26

CAP 531 Uploading application configuration from IED


ABB Power Technologies AB, 2007

COMPILE and EXIT CAP531!

2007-09-07 Substation Automation and Protection Training


27
CAP 531 Uploading application configuration from IED
This happens while you exit CAP531:
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


28

CAP 531 Compare Configurations

CAP 531 has the possibility to compare the configuration located


into the PC with the configuration stored into the terminal.

This process is very useful to check if the configuration stored in


the terminal is the same configuration which was downloaded
during the commissioning or during the last download.
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


29
CAP 531 Compare Configurations

If these two different configurations will be compared, a window


with the list of differences will be produced:
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


30

CAP531 On-line/Debug
ABB Power Technologies AB, 2007

2007-09-07 Substation Automation and Protection Training


31