Вы находитесь на странице: 1из 2

CMP Cable Glands

E10
> Ex d and Ex e versions
> Versions for
unarmoured
Single Wire Armour (SWA) E10
Steel Tape Armour (STA)
Wire Braid Armour

E10

E10

E10
www.stahl.de

E10
E10

04997E00

E10
The cable glands are suitable for the direct entry of cables into
enclosures of the "flameproof" type of protection and for the indirect
entry of cables into "increased safety" enclosures.
The cable glands are available for both non-armoured and metal- E10
armoured cables and meet all requirements of the European ATEX
Guidelines, the relevant IEC standards and many other national
standards. The relevant approvals can be found in the individual
data sheets. E10
The modular structure of the cable glands enables them to be ad-
apted precisely to the relevant cable design.
In addition to the normal sealing of the cable sheaths, it is especially
important that the armouring is securely clamped since the metal E10
armouring on the cable provides both mechanical protection and
electrical safety. When the armouring is live, it acts as a protective
conductor or earthing conductor and must therefore be integrated
into the protective conductor system via the cable gland according
to regulations. E10
When entering the cables directly into enclosures of the "flame-
proof" type of protection, also make sure that selection and
installation takes place in accordance with the provisions of
IEC/EN 60079-14. E10
ATEX / IECEx
Zone 0 1 2 20 21 22
For use in x x x x E10

WebCode CMPA
E10
2016-02-18EK00IIIen Installation Equipment and Accessories E10/1
CMP Cable Glands

Selection Tables
The most important selection criteria are listed in the following selection tables.
The selection is made according to the current standard based on the IEC/EN 60079-1.
The cable structure is also taken into account in the table ensuring that you can find the right cable gland quickly and easily.

17747E01