General Models SSS5700, SSS6700


Specications Fieldbus Communication
Functions (R4)
GS 33Y05P10-32E

GENERAL PC
With the Fieldbus Communication Function, a eld Engineering Tool
control station (FCS) can be connected via the ACF11 Device Management Tool
or ALF111 Fieldbus Communication Module installed
Ethernet
in an I/O module nest to eldbus-ready sensors and
valves. The GS covers the following communication HIS
functions: HIS
for builder
Fieldbus Feature
Fieldbus Communication Specications Overview
SSS5700 Engineering Tool for Fieldbus V(VL)net
SSS6700 Device Management Tool for Fieldbus
FCS FCS

FUNCTION SPECIFICATIONS ESB bus


ACF11
Fieldbus Feature FCS
A eldbus is a digital, bidirectional and multi-drop con- H1 Fieldbus
nection communication bus that connects eld devices SB401
ALF11 H1 Fieldbus
to control systems, and which replaces conventional
4-20 mA communication. Its specications have been
standardized by the Fieldbus Foundation. With the
multi-sensing function, various data as well as eld F01E.ai
devices PVs and MVs are transferrable. A eldbus
ensures interoperability between diverse vendors Figure Fieldbus Conguration of
products. CENTUM CS 1000/CS 3000
The Engineering Tool and the Device Management Tool
of Field Communication Function (R4) can be installed
in common HIS or HIS for builder of CENTUM CS
1000/CENTUM CS 3000 R3.01 or later versions.
PC
Engineering Tool/
Device Management Tool
E net/Ethernet
ICS
EWS
ACG

V net

FCU

RIO Bus

Node Interface Unit

ACF11 Card

Fieldbus

F08E.ai

Figure Fieldbus Connection Conguration of


CENTUM CS

Yokogawa Electric Corporation GS 33Y05P10-32E


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Copyright Sep. 25, 2001
Tel.: 81-422-52-5634 Fax.: 81-422-52-9802 4th Edition Dec. 1, 2004
<<Contents>> <<Index>> 2
Fieldbus Communication Specications FCS
Overview Sequence
Regulatory Control Block Control Block
Communications with function blocks
The eldbus-ready eld devices are connected through
the ACF11 (ALF111) installed in the FCS I/O module
nest. Field devices data is stored in the PI/O image
area in the ACF11 (ALF111) and sent to the PI/O image
Data Setting /
area in the FCS. The data is then sent to the I/O termi-
Reference
nals of function blocks like analog/digital I/O signals.
PI/O image

See the GS Foundation Fieldbus Communication Pack-


age for ACF11 or Foundation Fieldbus Communication ACF11 (ALF111)
Package for ALF111 about Fieldbus communication
specications.
PI/O image
Other eldbus specications are the same as those of
FOUNDATION Fieldbus.
Fieldbus Communication Function

F02E.ai

Figure Process Data Flow of Fieldbus


Communication

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation GS 33Y05P10-32E Nov. 1, 2001-00
<<Contents>> <<Index>> 3
Model SSS5700 Engineering Tool for PC
Fieldbus Engineering Tool
Specications
The Engineering Tool is used for eldbus engineer-
ing, such as dening a part of ACF11 function and Upload parameters View setting
eldbus compliant eld devices. It runs on a per-
sonal computer connected to a control bus or HIS for Ethernet
builder in the CENTUM CS 1000/CS 3000 systems;
it runs on a personal computer connected to the E
net/Ethernet of the CENTUM CS systems. With HIS HIS for
the tool, the users can graphically dene a devices Builder
parameters, inter-instrument data connections, the Control Bus
sequence and period of data connections.
The tool also has the function to send the settings to
the CENTUM CSs builder and read the les auto- FCU
matically on the builder.
Features
The Engineering Tool for Fieldbus consists of the fol-
lowing features: Download setting

Engineering Tool
ACF11 Download setting
Project Manager

Builder

Network Startup Function F04E.ai

Maintenance Function Figure Data Flow in Engineering Tool of


CENTUM CS 1000/CS 3000
Utility
PC
F03E.ai
Engineering Tool
Figure Engineering Tool for Fieldbus

Project Manager Upload Parameter


Manages all elements and functions of Engineering
Tool. Send
E net/Ethernet Settings
Builder
Creates the setting data of eld devices function
block application function and ACF11s communica-
ICS ACG EWS
tion function. It is used to:
Register eldbus devices;
Dene network conguration; V net
Create function blocks of eldbus devices;
Set parameters of function blocks of eldbus devices
and communication scheduling. FCU
Network Startup Function RIO Bus
Downloads the builder-dened data to eld devices
and ACF11. NIU
Executes Tag Assignment and Address Assignment. Download Settings
(supported by R3.10 or later versions of Fieldbus
Communication Function (Engineering Tool)) ACF11 Download
Maintenance Function Settings
Uploads parameters such as eldbus function blocks
from eldbus devices.
Utility
F09E.ai
Provides print and security functions.
Figure Data Flow in Engineering Tool of CENTUM CS

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation GS33Y05P10-32E Nov. 1, 2001-00
<<Contents>> <<Index>> 4
Model SSS6700 Device Management Tool PC
for Fieldbus Device Management Tool
Specications
The Device Management Tool monitors and manages
the eldbus-connected devices. It runs on a per- Acquire the status of
sonal computer connected to a control bus or HIS for Acquire
devices and parameters messages
builder in the CENTUM CS 1000/CS 3000 systems; Ethernet
it runs on a personal computer connected to the E
net/Ethernet of the CENTUM CS systems. With the HIS
tool, the users can monitor, manage eld devices HIS for (*1)
(sensors, positioners and analyzers) on a eldbus, Builder
display, dene and maintain parameters. The tool Control Bus
also has the function to automatically read messages
from eld devices on a eldbus via HIS (ICS), which
allows total management of eldbus devices. FCU
Features
The Device Management Tool for Fieldbus consists ACF11 Define
of the following features: parameters
Device Management Tool

Field Device Listing


*1: Exaopc OPC Interface (for HIS). F06E.ai

Field Device Status Display Figure Data Flow of Device Management Tool of
CENTUM CS 1000/CS 3000 (For using ACF11)
Message Display
PC
Parameter Display and Setting Device Management Tool
Device Method (*1)

Common Features
Acquire the status of Acquire
*1: Supported by R3.10 or later versions of devices and parameters messages
Ethernet
Fieldbus Communication Function / Device
Management Tool. F05E.ai
HIS
Figure Device Management Tool for Fieldbus HIS for (*1)
Builder
Control Bus
Field Device Listing
Manages eld devices and lists the dened data for
devices. FCU
Field Device Status Display
Displays eld device status, READY/NOT_READY.
ALF111 Define
Message Display parameters
Displays messages from eld devices and ACF11
or ALF111 by acquiring alarms and events of eld
devices from HIS (ICS) historical message les.
Parameter Display and Setting *1: Exaopc OPC Interface (for HIS).
Displays the parameters of function blocks in eld de- F07E.ai

vices and changes them if possible. Tuning param- Figure Data Flow of Device Management Tool of
eters are also displayed and changed. CENTUM CS 1000/CS 3000 (For using ALF111)
Device Method (supported by R3.10 or later ver- Note: Supported by R4.01 or later versions of Fieldbus
sions of Fieldbus Communication Function / Communication Function / Device Management
Device Management Tool) Tool.
Runs control procedures congured by the device
vendors. It describes procedures to run specic fea-
tures for the device such as calibration and reset.
Common Features
Displays the device management history of eld de-
vices, prints reports, and provides security function.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation GS 33Y05P10-32E Nov. 1, 2002-00
<<Contents>> <<Index>> 5
PC OPERATING ENVIRONMENT
Device Management Tool
DDE Server
Hardware Requirements
PC: IBM PC/AT-compatible
Acquire device status Main memory: 128 MB or larger (For PC used without
Acquire HIS functions)
and parameter
E net/Ethernet message Main memory capacity required for HIS
environment specications plus 32 MB
DDE ICS (For PC used with HIS functions)
EWS Remote Hard disk space:
ACG Server
100 MB or bigger for Engineering Tool
V net
and
100 MB or bigger for Device Management
Tool respectively;
120 MB or bigger to use both tools
FCU
CPU: Pentium 300 MHz or faster
RIO Bus Interface card: Ethernet card
Control bus interface card: VF701
NIU CRT resolution: 800 x 600 or more

Software Requirements
ACF11 Windows XP Professional Service Pack 1.2 (*1)
Parameter
Settings
Windows 2000 Professional Service Pack 4 (*2)
Windows 2000 Server Service Pack 4 (*3)
Windows Server 2003 (*3)

F10E.ai When using Fieldbus support tools, Windows 2000


Figure Data Flow of Device Management Tool of Server and Windows Server 2003 cannot be used.
CENTUM CS
*1: Supported by R4.20 or later versions.
*2: Supported by R4.01 or later versions.
*3: Supported by R4.30 or later versions.

Others
To use the Device Management Tool, the following
packages are required:
For CENTUM CS 1000/CS 3000:
LHS2411/PHS2411 Exaopc OPC Interface Package
(for HIS)
For CENTUM CS:
SHW5860, SIH5860 or SIU5860 DDE Communica-
tion Builder
SIH2410 or SIU2410 DDE Remote Server Package
SSS2410 DDE Server Package

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation GS33Y05P10-32E Dec. 1, 2004-00
<<Contents>> <<Index>> 6
MODELS AND SUFFIX CODES TRADEMARKS
CENTUM and Exaopc are registered trademarks of
Description YOKOGAWA Electric Corporation.
Engineering Tool for Fieldbus Pentium is a registered trademark of Intel Corpora-
Model SSS5700
[Media model: SSSSM01-C11] tion.
-S Basic Software License Ethernet is a registered trademark of XEROX Corpo-
Multiple Software License ration.
Sufx -C
(for 2 or more computers) Windows is a registered trademark of Microsoft Cor-
Codes
1 Windows 2000, Windows XP poration in the United States and /or other countries.
1 English version FOUNDATION of FOUNDATION Fieldbus is a registered
trademark of Fieldbus Foundation.
Other product and company names appearing in this
Description document are trademarks or registered trademarks of
Device Management Tool for Fieldbus their respective holders.
Model SSS6700
[Media model: SSSSM01-C11]
-S Basic Software License
Multiple Software License
Sufx -C
(for 2 or more computers)
Codes
1 Windows 2000, Windows XP
1 English version

ORDERING INFORMATION
Specify model and sufx codes.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation GS 33Y05P10-32E Dec .1, 2004-00
Subject to change without notice.