General SSS7740
Specications PRM Advanced Diagnosis
Server
GS 33Y05Q21-31E

GENERAL
The PRM advanced diagnostic function is an optional feature of the Plant Resource Management (PRM) package.
This function acquires parameter information from devices connected to a eldbus to provide a diagnosis execution
environment. By executing diagnosis applications for eld devices, you can carry out proactive, predictive and pre-
ventive maintenance for those devices. Moreover, loop, unit and process diagnoses due to simplied multiple pieces
of information data can also be attained using device parameter and process data.
Diagnostic applications can be easily created by using the PRM Advanced Diagnostic Application Software Develop-
ment Kit (PAA development kit NTPS220-S1, an optional package).

CONFIGURATION FOR PRM ADVANCED DIAGNOSIS


The PRM advanced diagnostic function comprises data acquisition services, the eDIAG DB diagnostic database, and
a diagnostic server (diagnostic algorithm execution environment), as well as an acquisition navigator, a diagnostic
navigator and a diagnostic tool, which are advanced diagnosis clients.

Advanced Diagnostic Function


The use of a vender- or third-party-supplied PRM advanced application that is registered in the PRM advanced diag-
nostic server allows devices, process interfaces, etc. to be diagnosed. In addition, the PAA development kit allows us-
ers to develop their own diagnosis algorithm (PRM Advanced Diagnostic Application: PAA). A created PRM Advanced
Diagnostic Application can be executed by registering it in a PRM Advanced Diagnostic Server as for a supplied PAA.
The PAA development kit includes multiple samples that allow users to easily create application software, such as:
Sample diagnosis 1 (upper and lower limit check)
Sample diagnosis 2 (area monitoring)
Sample diagnosis 3 (monitoring differences between multiple devices)
Sample diagnosis 4 (monitoring failures of reciprocating compressor)

PRM advanced diagnosis client functions are incorporated in a PRM client function. The PRM Client allows the moni-
toring of the PAA start, stop and execution statuses.

Data Acquisition Function (acquisition service)


Data acquisition services are provided to acquire dened and registered data-acquisition parameters from devices and
then store them in the diagnostic database, eDIAG DB. When PAA is started, parameters for the corresponding PAA
are automatically acquired. In addition, if arbitrary parameters need to be monitored as a step prior to the installation
of an advanced diagnostic application, a data acquisition table in the PRM acquisition navigator allows you to register
manually. It is possible to select a data acquisition period that is on a minute, hourly, or daily basis.

Yokogawa Electric Corporation GS 33Y05Q21-31E


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Copyright May 1, 2005
Tel.: 81-422-52-5634 Fax.: 81-422-52-9802 1st Edition May 1, 2005
<<Contents>> <<Index>> 2
PRM Client PAA-SDK

Client for PAA


Other development
function
of PRM
PRM Advanced
Diagnostic
PRM Advanced
Application (PAA)
PRM Advanced Diagnosis Client Diagnostic
PRM Advanced
Application (PAA)
Diagnostic Development
Application (PAA) of PAA
Acquisition Diagnostic Diagnostic
Navigator Navigator Tool

PRM Server

Diagnosis Support Diagnostic Server


Service
Diagnostic Application

PAA Software
Supplied by
third-party vendor

Database

Database for PRM Advanced


Diagnosis (eDIAG DB)

PRM Database (PRM DB)

Acquisition Service

Field Communication Server OPC Server (Exaopc etc.)

F01E.ai

Figure: PRM Advanced Diagnosis Conguration

All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation GS 33Y05Q21-31E May 1, 2005-00
<<Contents>> <<Index>> 3
PRM Advanced Diagnosis Server Specications
The PRM Advanced Diagnosis Server provides diagnostic functions to execute diagnoses and data acquisition func-
tions to collect diagnostic data, as listed in the table below.

Maximum
Function Item Description
Specication
Maximum simultaneously executable number is
Diagnostic applications that can be executed
10 (*1) restricted by optional package specications.
simultaneously
Can be simultaneously executed on up to 5 PCs.
Maximum number of diagnostic modules that can
Diagnostic be executed simultaneously for each diagnostic
function Total diagnostic functions that can be executed function is 1000.
10000 (*1,*2)
simultaneously So, total diagnosis numbers that can be executed
simultaneously on one PC is 10000 (1000 x 10). If
more than 10000 is required, use multiple PC.
Memory capacity for each diagnostic function 120 MB
Data acquisition period (minimum) 5 sec
Total number of data items dened as diagnos-
Data 10000 items Total data items acquired for device diagnosis
tic data
acquisition
function Total data items acquired for other than device
Used-dened total data items 1000 items diagnosis
Data acquired are user-denable.

*1: Up to 10 diagnostic applications can be simultaneously executed on one PC.


Therefore, when you specify /N5000 as the option code of PRM Advanced Diagnostic Server, it is necessary to prepare
other PCs to install the diagnostic server according to the number of diagnostic applications.
The database for diagnosis is required for one PC only, so you do not have to install Oracle newly.
*2: This specication is applied to R2.06 or later. For the revisions before R2.06, the maximum specication is 1000
(10 diagnostic functions X 100 diagnostic applications).

Notication of Detected Errors to Users


Notication of detected errors to users varies depending on the individual diagnosis PAA (algorithm). The following are
provided as notication methods:
HIS Operation Guide Messages
Notication by E-mail
PRM Client Historical Messages
PRM Client Status Display

OPERATING ENVIRONMENT
Refer to the separate GS 33Y05Q10-31E SSS7700, SSS7710, and SSS7720 Plant Resource Manager (PRM) for the
operating requirement of the PRM server, PRM client, and eld communication server as components of the PRM.

Hardware Requirements for Advanced Diagnostic Function


Below is a description on the difference of the operating requirement of the PRM server when the Advanced Diagnos-
tic function is used and when the standard PRM function is used.
PC (IBM PC/AT-compatible): Pentium IV 2.8 GHz or higher, Xeon Dual 2.8 GHz or higher recommended.
Main memory
The main memory capacity needed for a PRM server when an advanced diagnostic function is used depends on the
number of diagnostic applications. Refer to the table below for the memory capacity when using the advanced diag-
nostic function. This memory capacity is added to the environment where the PRM standard package is operated.

Number of diagnostic applications Main memory capacity


1 A minimum of 256 MB
Up to 5 A minimum of 512 MB
Up to 10 A minimum of 1 GB

All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation GS 33Y05Q21-31E May 1, 2005-00
<<Contents>> <<Index>> 4
MODELS AND SUFFIX CODES
PRM Advanced Diagnostic Server
Description
Model SSS7740 PRM Advanced Diagnostic Server [Media model: SSSSM02-C11]
-S Basic software license
-C Multiple software licenses (for 2 or more)
Sufx Codes
1 Always 1
1 English version
/N0100 Maximum number of applications 1
/N0200 Maximum number of applications 2
Option Codes /N0500 Maximum number of applications 5
/N1000 Maximum number of applications 10
/N5000 Maximum number of applications 50

Note: Plant Resource Manager version R2.05 or later supports this software.
PRM Advanced Diagnostic Server (for addition)
Description
Model SSS7740 PRM Advanced Diagnostic Server [Media model: SSSSM02-C11]
-A Software license for the number of Diagnostic Applications
Sufx Codes 1 Always 1
1 English version
/N0102 Change in maximum number of applications 1 to 2
/N0105 Change in maximum number of applications 1 to 5
/N0110 Change in maximum number of applications 1 to 10
Option Codes /N0205 Change in maximum number of applications 2 to 5
/N0210 Change in maximum number of applications 2 to 10
/N0510 Change in maximum number of applications 5 to 10
/N1050 Change in maximum number of applications 10 to 50

Note: Plant Resource Manager version R2.05 or later supports this software.
PRM Advanced Diagnostic Application Software Development Kit
Please order NTPS220-S11.
R2.05 or later version of Plant Resource Manager supports this software.
Software license and Instruction Manual are issued by ordering this model.Software media is not issued, because
Program of this software itself is included in media:SSSSM02-C11.

ORDERING INFORMATION
Specify model and sufx codes.

TRADEMARKS
PRM is a registered trademark of Yokogawa Electric Corporation in the United States and Japan.
CENTUM is a registered trademark of Yokogawa Electric Corporation.
Pentium is a registered trademark of Intel Corporation.
Ethernet is a registered trademark of XEROX Corporation.
Windows is a registered trademark of Microsoft Corporation in the United States and/or other countries.
FOUNDATION eldbus is a registered trademark of Fieldbus Foundation.
Adobe and Acrobat are registered trademarks of Adobe Systems Incorporated.
Oracle is a registered trademark of Oracle Corporation.
Other product and company names appearing in this document are trademarks or registered trademarks of their
respective holders.

All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation GS 33Y05Q21-31E May 1, 2005-00
Subject to change without notice.

Вам также может понравиться