Factor I Diseo
DV Alimentador Punto M.D. I Nominal I Diseo Long. Seccion FCT DV Max. DV Sec. DV Acumulado
Corr. corregido
0.5 SAB TG 19.00 31.16 38.95 0.90 34.63 15 35 0.001037 1.10 0.48
0.5 TG TFC 15.50 25.45 31.81 0.90 28.28 15 16 0.002120 1.10 0.81
1.5 TG2 STG2-02 22.01 72.20 90.24 0.90 80.22 155 50 0.000798 3.30 NO
1.5 TG2 STG2-03 13.75 45.11 56.39 0.90 50.12 120 35 0.001037 3.30 NO
1.5 TG2 STG2-04 13.65 44.77 55.96 0.90 49.75 190 35 0.001037 3.30 NO
1.5 TG2 STG2-05 180.30 591.47 739.34 0.90 657.19 130 3(3-1x150) 0.000113 3.30 NO
1.5 TG2 STG2-06 180.30 591.47 739.34 0.90 657.19 130 3(3-1x150) 0.000113 3.30 NO
1.0 STG2-01 TD1-01 14.13 46.35 57.93 0.90 51.49 15 10 0.003294 2.20 NO
1.0 STG2-01 TD1-02 14.13 46.35 57.93 0.90 51.49 25 10 0.003294 2.20 NO
1.0 STG2-01 TD1-03 14.13 46.35 57.93 0.90 51.49 75 25 0.001391 2.20 NO
1.0 STG2-02 TD2-01 2.73 8.97 11.21 0.90 9.97 25 10 0.003294 2.20 0.74
1.0 STG2-02 TD2-02 2.73 8.97 11.21 0.90 9.97 40 10 0.003294 2.20 1.18
1.0 STG2-02 TD2-03 2.73 8.97 11.21 0.90 9.97 65 10 0.003294 2.20 1.92
1.0 STG2-02 TD2-04 2.84 9.31 11.64 0.90 10.34 90 10 0.003294 2.20 NO
1.0 STG2-02 TD2-05 2.73 8.97 11.21 0.90 9.97 115 10 0.003294 2.20 NO
1.0 STG2-02 TD2-06 2.73 8.97 11.21 0.90 9.97 140 10 0.003294 2.20 NO
1.0 STG2-03 TD3-01 1.58 5.20 6.50 0.90 5.77 25 6 0.005446 2.20 0.71
1.0 STG2-03 TD3-02 1.15 3.78 4.72 0.90 4.20 35 6 0.005446 2.20 0.72
1.0 STG2-03 TD3-03 1.15 3.78 4.72 0.90 4.20 50 6 0.005446 2.20 1.03
1.0 STG2-03 TD3-04 1.15 3.78 4.72 0.90 4.20 65 6 0.005446 2.20 1.34
1.0 STG2-03 TD3-05 4.71 15.46 19.32 0.90 17.17 70 6 0.005446 2.20 NO
2 746 1.49 1.00 1.49 REG 300 300
1.0 STG2-04 TD4-01 1.58 5.20 6.50 0.90 5.77 25 6 0.005446 2.20 0.71
1.0 STG2-04 TD4-02 1.15 3.78 4.72 0.90 4.20 35 6 0.005446 2.20 0.72
1.0 STG2-04 TD4-03 1.15 3.78 4.72 0.90 4.20 50 6 0.005446 2.20 1.03
1.0 STG2-04 TD4-04 1.15 3.78 4.72 0.90 4.20 65 6 0.005446 2.20 1.34
1.0 STG2-04 TD4-05 4.61 15.12 18.90 0.90 16.80 70 6 0.005446 2.20 NO
200
250 REG
400
REG
630 REG
ORS NORMAL NYY
POR CAIDA DE TENSION PROTECCION
I Max.
I Max. Proteccion Modo
Formacion Conductor Tuberia
conductor ITM Instalacion
corregido
400
REG
630 REG
3 - 1 x 6 mm NYY+1x6 mm TW(T) 58 52.20 3x 20 Ducto 25
3 - 1 x 6 mm NYY+1x6 mm TW(T) 58 52.20 3x 20 Ducto 25
3 - 1 x 6 mm NYY+1x6 mm TW(T) 58 52.20 3x 20 Ducto 25
3 - 1 x 6 mm NYY+1x6 mm TW(T) 58 52.20 3x 20 Ducto 25
3 - 1 x 6 mm NYY+1x6 mm TW(T) 58 52.20 3x 20 Ducto 25
C. Dilatacin: 0.00393 1/C
T1: 20 C
T2: 35 C
T3: 80 C
Cos 0.8 Sen 0.6
Cos 0.9 Sen 0.436
Cos 1.0 Sen 0 1 2 3 4
3(3-1x185)
3(3-1x240)
3(3-1x300)
3(3-1x400)
3(3-1x500)
4(3-1x95)
4(3-1x120)
4(3-1x150)
4(3-1x185)
4(3-1x240)
4(3-1x300)
4(3-1x400)
4(3-1x500)
Ducto mm 5(3-1x300)
Canaleta 75x300
75x500 CALIBRE
2" 40 50 50
0.120065 0.000228 0.000206 0.000104 636 3 - 1 x 300 mm NYY+1x 95mm TW (T) 100
0.117392 0.000202 0.000179 0.000081 730 3 - 1 x 400 mm NYY+1x 95mm TW (T) 100
Temperatura en el conductor : 80 C
12 13
RO DE FACTORES DE CAIDA DE TENSION
FORMACION FORMACION
3 - 1 x 120 mm NYY+1 x 120 mm NYY(N)+1x50mm TW (T) 3 - 1 x 120 mm NYY+1 x 240 mm NYY(N)+1x50mm TW (T)
3 - 1 x 150 mm NYY+1 x 150 mm NYY(N)+1x50mm TW (T) 3 - 1 x 150 mm NYY+2 x 150 mm NYY(N)+1x50mm TW (T)
3 - 1 x 185 mm NYY+1 x 185 mm NYY(N)+1x50mm TW (T) 3 - 1 x 185 mm NYY+2 x 185 mm NYY(N)+1x50mm TW (T)
3 - 1 x 240 mm NYY+1 x 240 mm NYY(N)+1x70mm TW (T) 3 - 1 x 240 mm NYY+2 x 240 mm NYY(N)+1x70mm TW (T)
3 - 1 x 300 mm NYY+1 x 300 mm NYY(N)+1x 70mm TW (T) 3 - 1 x 300 mm NYY+2 x 300 mm NYY(N)+1x 70mm TW (T)
3 - 1 x 400 mm NYY+1 x 400 mm NYY(N)+1x 70mm TW (T) 3 - 1 x 400 mm NYY+2 x 400 mm NYY(N)+1x 70mm TW (T)
3 - 1 x 500 mm NYY+1 x 500 mm NYY(N)+1x 70mm TW (T) 3 - 1 x 500 mm NYY+2 x 500 mm NYY(N)+1x 70mm TW (T)
Fac.
EF FP Cab.
1.25
HP FT KW CANT TOTAL KW
1.00 3.73
5 746 3.73
1.00 0.00
1.00 0.00
TD 2.00%
carga 1.50%
I Max.
I Max. Proteccion Modo I
DV Max. DV Sec. Formacion Conductor Tuberia
conductor ITM Instalacion Interruptor
corregido
Fac. Fac.
DVAlimentador Punto M.D. I Nominal I Diseo
Cab. Int.
0.8 0.9 1.25 1.25 4.0 PMI TRAFO N01 2.00 4.01 5.01
ITM Icc
kA
3
6
10
15
25
35
50
70
150
I Diseo
Factor
corregid Long. Seccion FCT DV Max. DV Sec. Formacion
Corr.
o
I Max. I
I Max. conductor Conductor Proteccion ITM Tuberia Interrupt
corregido or
En aire,bandeja o ducto:
Aislamiento Temperatura ambiente ( a) (C)
10 15 20 25 30 35 40 45
Tipo PVC (termoplstico) 1,40 1,34 1,29 1,22 1,15 1,08 1,00 0,91
Tipo XLPE o EPR (termoestable) 1,26 1,23 1,19 1,14 1,10 1,05 1,00 0,96
En conducto subterraneo:
Aislamiento Temperatura del terreno (a) (C)
10 15 20 25 30 35 40 45
Tipo PVC (termoplstico) 1,16 1,11 1,06 1,00 0,94 0,88 0,81 0,75
Tipo XLPE o EPR (termoestable) 1,11 1,08 1,05 1,00 0,97 0,93 0,86 0,83
Factores de correccion de la intensidad admisible para cables (en conductos enterrados) en terrenos de resistividad d
Resistividad trmica K.m / W 1 1,5 2 2,5 3
Factor de correccin 1,18 1,1 1,05 1 0,96
3 Capa nica en el techo 0,95 0,80 0,70 0,70 0,65 0,60 0,60 0,60
5 Capa nica sobre escaleras de cables, abrazaderas, etc. 1,0 0,85 0,80 0,80 0,80 0,80 0,80 0,80
Factores de correccin por agrupamiento de varios circuitos, cables directamente enterrados (unipolares o multipolares)
Distancia entre cables (a)
Nmeros de circuitos
Nmeros de circuitos Nula (cables Un dimetro de
0,125 m0,25 m 0,5 m
en contacto) cable
2 0,75 0,80 0,85 0,90 0,90
3 0,65 0,70 0,75 0,80 0,85
4 0,60 0,60 0,70 0,75 0,80
5 0,55 0,55 0,65 0,70 0,80
6 0,50 0,55 0,60 0,70 0,80
Factores de reduccin por agrupamiento para varios cables multiconductores a aplicar a los valores para cables multicondu
Nmer
o de Nmero de cables
Mtodo de instalacin de la tabla
bandej 1 2 3 4 6
as
1 1.00 0,88 0,82 0,79 0,76
Cables en
2 1.00 0,87 0,80 0,77 0,73
contacto
3 1.00 0,86 0,79 0,76 0,71
Bandejas perforadas
1 1.00 1,00 0,98 0,95 0,91
Cables
2 1.00 0,99 0,96 0,92 0,87
separados
3 1.00 0,98 0,95 0,91 0,85
Cables
2 1.00 0,99 0,98 0,97 0,96
separados
3 1.00 0,98 0,97 0,96 0,93
( a) (C)
50 55 60
0,82 0,70 0,57
0,90 0,83 0,78
nductores
20
0,40
0,70
0,60
0,70
0,80
unipolares o multipolares)
lores para cables multiconductores instalados al aire
cables
9
0,73
0,68
0,66
-
-
-
0,72
0,70
-
-
0,78
0,73
0,70
-
-
-
FACTOR DE FACTOR DE
CORRECCIN REDUCCION FACTOR DE
POR POR MAS DE UN CORRECCIN
AGRUPAMIENTO CIRCUITO FINAL
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00