Вы находитесь на странице: 1из 7

661

PERFORMANCE OF AVERAGE CURRENT MODE CONTROLLED PWM UPS INVERTER


WITH HIGH CREST FACTOR LOAD

M.E. Fraser and C.D. Manning

Loughborough University of Technology, England

ABSTRACT which includes a neutral connection. Ths allows for


unbalanced loading. Three-phase, four-wire inverter
topologies are discussed in Divan (3). One of the most
This paper highlights h e problems encountered when common methods is the use of a centre-tapped dc supply. If
attempting to supply a high crest factor load ffom a ups the dc supply is derived limn a rectifier then a centre-tapped
inverter. Inverter voltage control using an inner loop capacitor provides the neutral connection as in Figure 1.
consisting of an average current mode controller and an The inverter consists of six switches and six diodes allowing
outer loop is investigated. The choice of parameters, filter for bi-duectional power flow. An L-C filter is used in each
components and compensators, will be discussed. phase to reduce the high hquency switching components of
Simulation results will show the steady state and dynamic current and voltage. The neutral connection decouples the
performance of the inverter. The addition of load current three phases allowing easier analysis of the circuit. To this
feedfonvard can cause the system to become unstable and effect only one phase need be considered.
dbe explained with the aid of simplified control models.
The inverter under consideration is rated at 3OKVA with a
pwm switching frequency of 1SKHz

INTRODUCTION

Unintenuptablepower supplies (ups) are frequently used to


supply computers. Typically, a computer will use a standard
bndge rectifier with a large filter capacitor to provide the dc
voltage requirements. Thus,the ups inverter will 'see'a hgh
crest factor load. If the response of the inverter to the hgh
crest factor load is poor then the inverter output voltage will Figure I : Three Phase Inverter with Neutral Connection
be distorted.

There are many methods of inverter control. Only current Inverter Control
mode control schemes will be considered here. These
include hysteresis controllers, peak current mode controllers
and average current mode controllers. An average current The switches in one leg (one phase) of the inverter are
mode controller is used here in a buck derived (step-down) switched altematively, with the proviso that a deadband is
converter arrangement. Among the advantages of average introduced when considering real switches to allow for the
current mode control over the hysteresis and peak current tum-off tune of a switch. A sinusoidal voltage can be
mode controllers are constant switchmg frequency, achieved at the centre point of the leg with respect to
improved noise immunity and true average current mode neutral with the use of a pulse width modulated (PWM)
control afforded by sensing and controlling the average control scheme
inductor current, Dixon (I), Tang, Lee and Ridley (2).
The average current mode control system is shown in Figure
2. In this scheme the current in the filter inductor (ILf)is
THREE PHASE INVERTER measured and compared to a reference winch f o m the
current error. The error is passed through a Proportional
and Integral (PI) compensator to form the modulating signal.
Inverter Topology The PI compensator provides high gain at low frequencies,
but has a filtering effect on the switchmg component of the
measured current. The modulating signal is compared to a
Commonly, a three phase ups requires a four-wire output triangular carrier signal to generate the required pwm signal

'Power Electronics and Variable-SpeedDrives: 26 - 28 October 1994, Conference PublicatfonNo 399, 0IEE, 1994
662

to control the switches

The average current mode control forms the inner current


loop. As it is the output voltage which requires regulation,
an outer voltage loop is used. The output voltage is
compared to a reference and the voltage error signal is
passed through another PI compensator. The signal then
forms the current reference for the inner current loop. The Figure3: Filter Inductor Ripple Current
proportional and integral constants in the PI compensators
are chosen to produce a stable systeim with good transient
response. variations in the input voltage. If the maximum inductor
ripple current is limited to 20% of the maximum peak-peak
output current (20% of 120 amps) and the switching
frequency is 15KHz then the filter inductance per phase (LJ
= 560pH.

The output filter capacitor size is determined by the


allowable output voltage ripple AV, and can be calculated
from (4)

Figure 2: Closed Loop Control of Inverter Output Voltage


in One Phase

Ifthe maximtun ripple voltage is limited to 2% of the peak-


COMPONENT SELECTION peak output voltage (2% of 680 volts) then the required
filter capacitor (C,) 20uF.
'-

The magnitude of the ripple current and ripple voltage in


the output of the inverter are d e t e d e d by the size of the L- PI Compensator Constants Selection
C filters. Once the filter size has been chosen the PI
compensator constants are chosen. For this design example
a 30KW inverter is used (IOKW per phase) with an output The choice of parameters for the proportional and integral
voltage of 240V,, 50Hi. The switching frequency is controllers in the cw-rent and voltage loop not only depend
1 SKHZ. upon the Nyquist criieria, but also on the fact that the slope
of the measured current should be limited to no more than
that of the hiangular wave which form the inputs to the pwm
G C Filter Size comparator, as described in Dixon (5) for a dc-dc buck
converter. Th~s prevenb subharmonic oscillations occurring
and also prevents multiple switching (converter switching
The inductor ripple current is dependant on the size of the faster than specified by the frequency of the triangular
inductor and the switching frequency Figure 3 shows the carrier wave).
ripple waveform. It can be shown, Chryssis (4). that the
value of the inductance of the output lilter inductor is given Based upon the analysis of control loop design given in (5)
an approximate linearized control model of the inverter is
shown in Figure 3(a). The feedback signals of the inductor
Vdc current and output voltages obviously have to be scaled
Lr= - down to low voltage control signals. For this example the
4fA i feedback signals are converted into per unit (pu) values of
full-load: I p.u. voltage feedback represents 340 volts
where V, is the dc bus voltage ;and f is the inverter (d2*240 volts) and 1 p.u. current feedback represents 60
switching frequency. amps. The triangular waveform also has an amplitude of 1
p.u. and by approxunating the pulse width modulator to a
The dc bus voltage must be at least twice the peak output linear function this can be neglected from the model in
voltage, and V, is thus chosen as 800 volts allowing for Figure 3(a).
663

Current Loop PI Constants. The proportional constant K&,= 0,/2, p i n g &=23,810 rads-'.
(KJ in the current loop PI controller is set to make sure the
slope of the measured current is less than the slope of the
triangular wave. The worst slope of the inductor current is Voltage Loop PI Constants. Figure 5 shows the
generalized straight line approximation of the voltage loop
gains, ignoring for the moment the effects of feedfonvard.
di. f-

Gain d 0
I 1 ..T7r I I I I
when the maximum potential dlference is across the
inductor. With e being the inverter output voltage, the
m a x i " potential dlference is given by

f L = VdCl2+e (4)

For th~sdesign example the worse slope is :-


(400+340)/560.106 = 11321 Alms
In terms of per unit slope this is 1321/60 = 22 ms-'
The slope of the per unit triangular waveform is :-
4f = 4* 15.IO' = 60 ms-'

Setting $= 2 w ill guarantee the inductor current slope does


not exceed the triangular wave slope and leave extra margin
for the additional slope from the output voltage ripple. Figure 5: Straight Line Approximation of Voltage Loop

Figure 4 shows a generalized straight line approximation of


the gaidfrequency responses in the current loop (ignoring The overall gain of the voltage loop should cross the 0 dB
the feedfonuard) of the pudpower circuit and compensator (U,,)somewhere between 5 and 10 times lower than 0,.
circuit. These were produced with the aid of the software Th~swdl make selectionof the voltage loop PI compensator
packages Matlab with Simulmk. The overall gain should easier as the closed current loop will have a flat gain up to
cross O B (at oc) with ample phase margin. U,, and prevents the current loop 'chasing' the voltage loop.
If U,, is chosen to be 2400 rads-' then, in h s case, the
400 compensator will have to cross over the power gain below
0 =-*K (5) I/RC, (on the flat part of the gain).
60L *
To make 0,,=2400 rads-' the open-loop gain of the voltage
loop is set to 1. for full-load (R=5.76Q) &is chosen as 0.5
and& is 2033 rads? whch gives ample phase margin. As
ovis less than I R C , it should be noted that U,,will vary
with load. The amount of voltage ripple fed back to the
current loop is negligible and so will not cause any
problems.

SIMULATION RESULTS.

A time domain simulation of the performance of one phase


of the inverter was run using the SABER simulation
software. Figure 6 shows a step load change (1 00% - 10%
full-load) on the inverter at 2 5 m , giving per unit values of
the voltage refermce and output voltage. It can be seen that
Figure 4: Straight Line Approximation of Current Loop
the steady state (SO&) gain at 100% full-load (first 2Sms)
is not high enough and the output voltage does not track the
reference well. At 10% full-load (after 25ms) the steady
In th~sexample placing the pi compensator zero at w,/2 =
state gain is higher and the output voltage tracks the
1 1,905 rads-' will give a phase margin of =63" (5).
664

reference better. The output voltage rings at the load change Accessing the effects of load current feedforward on the
where the stability of the system is worsened due to the stability of the system is not directly possible, but re-
reduced load. arranging the system from two feedback signals and one
load current f d o r w a r d signal (ignoring the filter capacitor
current feedforward) to just two fL=dback signals allows
conventional feedback analysis to be performed on the
'I..
system. This is done by addmg the feedback signal I, to the
feedforward signal I,, which actually is the equivalent of
f&g back the filter capacitor current I,. This gives a new
inner current loop.

The effects of load current feedforward on the new inner


current loop and the outer voltage loop can be Seen in the
gaidfrequency plots in Figures 4 and 5 respectively. The
effect of the load current feedforward in the new inner
current loop does not alter where the new overall current
loop gain crosses 0 dF3 as, in this case, o,was set higher
Figure 6 : Step-Load Change on Inverter than the resonant point (I/dL&). For systems designed
such that oL < IRC, without feedforward, the effect of
adding feedforward is to give a new higher O d B cross over
LOAD CURRENT FEEDFORWARD frequency in the voltage loop. Thls is due to the pole at
IRC,ofthe power gain now moving to the origin. The use
of the software &lackages Matlab with Simulink prove
The dynamic and steady state perfbrmance of the inverter invaluablefor m o d e h g the system in the frequency domain
may be improved with the we of filter capacitor current (no- to find out if the system is stable. In thls example there is
load cwent) and load current feedforward signals as shown ample phase margin in the voltage loop. It is worth noticing
in (3) and Venkataramanan, Divan and Jahns (6). This that with load c w e n t feedforward the new voltage and
effectively by-passes the slow voltage loop. An outer loop current loops are independent of the load resistance.
voltage PI compensator is used for trimming purposes and
compensates for any deviation in output voltage accuracy
due, for example, to component viiriations. Figure 7 shows Load Current Feedfonvard Simulation Results
the control of one phase of the iriverter with the current
feedforward signals added. The load current feedforward
signal is measured straight from the load, the capacitor filter Figure 8 shows a time domain simulation of one phase of the
current feedfmard signal canbe derived from the reference inverter with a step load change of 100% - 10% full-load
voltage. with the addition of the current feedforward signals. The
graph shows the per unit values of the voltage reference and
the output voltage. If Figure 8 is compared to Figure 6 it
can be Seen that the feedforward signals have improved the
steady state response of the inverter before and after the step

21 1
' load change and the dynamic response has also improved.

Figure 7: Control of One Phase ofthe Inverter with Filter


Capacitor Current and Load Current Feedforward Signals

Stability with Feedfonvard

Generally, if the system is stable without the feedforward


signals then it should be stable with the feedforward signals. Figure 8: Step-Load Change on Inverter with Feedforward
A new approximate equivalent linearized model of the
system with load current feedforward (ignoring the
negligible effect of the filter capacitor cunent feedforward)
is given in Figure 3(b) of the control system in Figure 7.
665

HIGH CREST FACTOR LOAD reference well. The output voltage is clipped. The crest
factor of the inductor current is also much lower than
expected due to the output voltage being clipped.
A computer will typically load the inverter of a UPS with a
non-linear load consisting of a diode bridge rectifier with
smoothng capacitor. The current drawn from the inverter
will no longer be sinusoidal and will have a high crest
factor. The output voltage ideally should be sinusoidal, but
ifthe dynamics of the inverter are not 'good enough then the
sine wave will be distorted, typically the top of the sine wave
will be 'chopped off.

Effectively, during each1 half of the 5OHz cycle, the


combined R-C rectifier load is being switched on and off the
inverter by the rectifier. In terms of stability, the large
&er smoothmg capacitor needs to be taken into account.
The simplest method is lo create an equivalent circuit by
removing the diode bridge rectifier and moving the large Figure IO: Output of Inverter with Non-Linear Load
snoothmg capacitor and the dc load resistance to the ac side
ofthe load. Care should tie taken in the voltage loop as the
pole in the power gain is dependant on the total capacitance Feedfomard and Non-Linear Loads
of the filter and load in parallel.

The use of filter capacitor current feedforward and load


Simulation Results for High Crest Factor Load current feedforward has already demonstrated the
improvements to steady state and dynamic performance of
the inverter with a linear load, so it would be natural to use
Figure 9 shows one phase of the inverter with a non-linear feedforward with the non-linear load. A time domain
load consisting of a single-phase full-bridge diode rectitier simulation has been performed on such a system and it
with smoothmg capacitor, C. The rectifier, if connected to shows the system to be highly unstable.
atypically stlffsinusoidal voltage source, supplies a dc load
of IOKW at 290 volts dc with 2.5mF smoothing capacitor
giving 100 volts pk-pk lO0Hz ripple and a crest factor of
the input current of just above 3. This non-linear load is
supplied by the inverter. The voltage PI compensator is
adjusted to take into accoiunt the dc smoothing capacitor to
maintain stability and to give adequate phase margin.

Figure 1 1 : Straight Line Approximation of Current Loop


Gains with R-C 1 .oad

Figure 9 One Phase of Inverter with a Diode Bridge


Rectifier Load

Figure I O shows the per unit values of the output voltage


reference of the inverter, the output voltage of the inverter
and the inductor current from a time domain simulation A
number of observations can be made from the simulation. Figure 12: Straight Line Approximation of Voltage Loop
The output voltage from the inverter does not track the Gains with R-C Load
666

It can be seen that the output voltage now tracks the


Approximate Linearized Model To show why the system reference much better, and the crest factor is much larger
becomes unstable an approximate equivalent linearized and is nearer that expected from a stiff voltage source.
model is used. This model lumps the rectifier load Practical problems with this solution include the
resistance and smoothing capacitor together and moves them requirement of a large per phase ac capacitor for the inverter
to the inverter output, thereby enabling the diode bridge to filter and the inverter switches have to he rated higher due
be removed from the model. The model is derived in a to the much larger reactive current flowing in the inverter
similar way to that used to produce Figure 3(b) in that the filter capacitor.
filter capacitor (C,) feedforward current is neglected and the
inductor current feedback and load current feedforward are
summed together resulting in a new feedback signal from CONCLUSIONS
the filter capacitor (C,) current. This gives a new inner loop
as shown in Figure 3(c).
The use of average current mode control to control the
Figures 1 1 and 12 show the generalized straight line output of a three phase W S inverter has been presented in
power/pwm gadtkequency plot:; of the system for the new this paper, backed up with time simulations using the
current loop and voltage loop. The dc smoothing capacitor SABER simulation software. The choice of L-C filter
is considerably larger than the inverter filter capacitor. Load components has been discussed for a resistive load. The PI
current feedforward has the e f i c t of separating the filter compensator parameters are selected for optimum
capacitor (Cf) from the load capacitor (C) in the linearized performance by using an approximate linearized model of
representation of the system model. This difference in size the system, including an equivalent model with load current
can introduce instability as will be explained as follows. It feedforward with a resistive load.
can he seen that the bandwidth of the new current loop is
drastically reduced with the load 'currentfeedforward due to High crest factor loads present a problem to the inverter
the zero of the filter capacitor ((2,)' alone passing through the resulting in clipping of the output voltage waveform. The
origin (Figure 3(c)). The voltage loop bandwidth has use of full load current feedforward in an attempt to improve
increased due to the pole of the filter capacitor (C,) alone the inverter performance can cause the system to become
passing through the origin. The result of this is that there is unstable due to the presence of the large dc smoothing
a reduced phase margin in the boltage loop at 0dB (in this capacitor, as was demonstrated with the aid of an equivalent
case Matlab/Simulmk shows there is a negative phase approximate linearized model. One solution to the problem
margin) due to the closed current loop gain rolling off at a of instability is to use an inverter filter capacitor which is
much lower frequency. comparable in size to the rectifier smoothing capacitor, but
at the expense of increased inverter cost.

Stable Load Current Feedforward. The simplest solution


to stabilize the system with such a non-linear load is to REFERENCES
replace the inverter filter capacitor with one comparable in
size with the dc smoothing capacitor, thus increasing the
current loop bandwidth and reducing the voltage loop l.DixonL., 199l,UnitrodeSEM-800,Cl-l- Cl-14
bandwidth. Such an arrangement has been simulated using
an inverter filter capacitor the same size as thz dc smoothing 2. Tang W., I,ec F.C., Ridley R.I3., 1992, APEC,747 - 755
capacitor. The results of the simulation giving the per unit
output voltage reference, output voltage and output current 3.DivanD.M..1991,APEC,81 - 8 7
from the inverter are shown in Figure 13.
4. Chryssis G., 1984, "High-Frequency Switching Power
Supplies",McGraw-MI Book Company, New York, U.S.A.

5. DixonL., 1991, UnitrodeSEM-800,7-1 - 7-10

6. Venkataranianan G., Divan D.M., Jahns T.M., 1989,


PESC REC., 2, 1013 - 1020

Figure 13: Inverter Output with Non-linear Load, Large


Filter Capacitor and Current Feedforward
667

v o l r n g c pi current p i

R
I+ I )
fsRC

(a): Inverter with Current and Voltage Loops with R Load

1-1

(b): Inverter with Load Current Feedforward with R Load

new inner loop


currenrpi I /ZfS)

fib

r --I

(c) Inverter with Load Current Feedforward and R-C Load

Figure 3: Per-Phase Approximate Lmeanzed Model of Inverter and Controller

Вам также может понравиться