Securing your power supply

Change-over and transfer switches


for Critical Power applications
Index

Constant commitment
ABBs solutions and products to ensure continuity
of operation......................................................................... 4

Never ending reliability


Generator-set application..................................................... 6

Maximizing availability of Data centers


while providing efficiency and reliability............................ 8

Critical in every condition


Manual, motorized, automatic: the features of ABBs
change-over switches........................................................ 12

Features of ABBs automatic transfer switches................... 14

A tailor-made choice
Selection examples............................................................ 17

Safety over all


The warranty to choose products complying
with all regulations............................................................. 18

Customer case
OTM switch disconnectors support Pramac generators
the world over................................................................... 20

Securing your power supply | 3


Constant commitment
ABBs solutions and products to ensure
continuity of operation

Critical applications require a constant and reliable power


supply to keep fundamental services running and prevent
serious consequences due to interruption or absence of the
electrical grid. This need is even stronger nowadays because
of the increasing significance of key role, capacity and features
of these systems. In order to ensure the high level of reliability
requested, the system must include generators and UPS
equipment which ensure the right power supply to the critical
loads in case of grid failure.

4 | Securing your power supply


In todays world, electrical power plays a key role in almost These products range from low voltage generators for
every activity of our life. For some equipment a reliable, generator sets (Gen-set) to iPDU (intelligent Power Distribution
uninterruptible and free of disturbance power supply is an Units) switchboards, and include all types of equipment
absolute need. specifically required to provide safety and reliability: air,
From this point of view, a fault in the power supply of moulded-case and miniature circuit breakers, protections
communications systems, hospital apparatus, security against overvoltages, isolators and switch-disconnectors,
systems, water and gas distribution devices, banking contactors, manual and motorized change-over switches,
computers and many other crucial appliance may bring about automatic transfer switches and automatic control units,
serious problems, with consequences that can easily be current sensors and many other devices.
imagined. ABB products comply with the most important international
All these applications can be identified as Critical Power standards - either European or North American - and with the
applications: they are specifically designed to leverage a requirements of the Navy Registry; they are also designed
constant and secure power supply, for example using UPS and built on the basis of the most modern and advanced
equipment or power generators. environmental standards.
In the area of Critical Power ABB can offer a wide range of ABB products are backed by a consolidated experience in
products, including both components for on board installation power and automation technologies. They are supported
and complete power distribution systems. through a global assistance and service network which covers
more than 100 countries all over the world.

Securing your power supply | 5


Never ending reliability
Generator-set application

Generator-set building generators for all power generation applications.


A generator set (Gen-set) is fundamental in many Critical ABB has modern products, experience and resources needed
Power applications where a constant and reliable source of to support plant builders and operators from the initial project
electrical energy is required. concept through design, installation and management.
Such a power source may be placed at various levels in a Today, ABB is the market leader in generators powered by
distribution network, wherever there are critical power nodes gas and steam turbines, gas and diesel engines and wind
- industrial or service facilities, data processing centers, small turbines. It has extensive applications experience coming
structures, and even individual items of machinery or devices from thousands of installations around the world. ABB also
that are of paramount importance for the plant to which they supplies generators for concentrated solar and geothermal
belong - or when environmental conditions dont allow a installations, other renewable energy applications and energy
reliable connection with the electrical grid. recovery expanders.
A Gen-set provides continuous, standby or emergency ABB generators achieve the highest standards of efficiency
power when the primary source fails or theres no chance to and reliability. They are available over a wide range of
connect the main grid. The most common applications of a operating parameters and enclosures, complying with all
Gen-set are related to key areas where is essential protect internationally accepted standards.
the security and the safety of people, services and assets, ABB also offers complete sets of generator control equipment
such as residential buildings, commercial premises, hospitals, as well as upgrades for existing equipment.
schools, telecommunication facilities, industrial sites, mines, A Gen-set solution is a combination of an electric generator
off-shore platforms, marine installations, airports, military (alternator), a combustion engine and an auxiliary and control
installations, car parks, galleries, sport installations, auxiliary logic. The function of this system is to provide electricity
power stations and many other critical environments. to a load which cannot be powered from the main grid at
ABB has a long and successful history of designing and that time due to an equipment failure, connection absence,

6 | Securing your power supply


maintenance or environmental troubles. This solution also fulfills the requirement for making and
The electrical power is generated by the combustion engine withstanding short-circuit currents (Class PC equipment).
usually diesel, gas or hybrid fuelled. The crankshaft of the Usually, the switch has three positions:
combustion motor is connected to the rotor of the generator, - Position I: load connected to the line
exploiting the laws of electromagnetism to convert kinetic - Position II: load connected to the Gen-set
energy into electrical energy. -P osition 0: intermediate position which ensures that the load
In addition, the Gen-set is usually equipped with a speed is never connected to both power sources; can eventually
regulator (to maintain the frequency of the voltage within be used to isolate the load from both sources
limits), a voltage regulator and possibly a programmable When the load is properly powered by the main source, the
control unit which regulates the switching from the network to switch remains in I position.
the group and vice versa. A control unit processes the signals coming from the voltage
The Gen- Set is connected to the load through manual, sensors.
motorized or automatic transfer switches (ATS) which change Sensors normally monitor if voltage amplitude, frequency and
the source of power - primary or Gen-set - as needed. other parameters on the load fall within predefined limits.
When the control unit detects a fail condition, it sends a
The role of the change-over switch command and speed stability after a start-up period.
One of the key functions related to a Gen-set is the change- Switching usually does not happen immediately after the
over switching when the main power source fails. failure of the main power: this prevents to power the load with
This function is maintained with a change-over switching voltage levels and frequencies different from nominal values.
device according to IEC 60947-6-1 norm. The change-over As long as this voltage is not within the thresholds and is not
switch is typically a dedicated switching device, consisting stabilized, the switch remains stationary in position 0 or I.
of two mechanically interlocked switch-disconnectors and a After the stabilization the switch can change to position II.
motor operator for electrical operation. The switching device The load is powered by the generator until the line returns
might also have an integrated automatic control unit, enabling within limits. At this point, the control unit sends a command
a full automatic operation of the switching device. Therefore to move the switch to position I and, after a transitional period
the change-over switches can be operated manually or needed to ensure a slow cooling, the engine is turned off.
electrically by using an electric motor.

load

Manual, automatic, motorized: the change-over


switch holds a key function in every Gen-set
application.

Securing your power supply | 7


Maximizing availability of Data centers
while providing efficiency and reliability

A growing number of private and public businesses have


their crucial point in the Data center. Collecting, storing
and managing data requires maximum operating reliability
to prevent data losses that may have serious consequences.

Data centers with rows of servers storing trillions of How does a datacenter work
megabytes of information operate around the clock to enable A Data center is a facility used to host not only computers,
organizations to run applications, process information and telecommunication systems, IT equipment or storage
automate their operations. resources but also a wide spectrum of components related to
In a Data center the energy absorbed by power supply and energy management and environmental control.
environmental control is on average 15 to 20 times as much A Data center must keep high standards for assuring the
the energy as a normal office of comparable size. All this availability and functionality of core computing, in order to
energy affects plant costs: when you plan an office building, minimize any chance of disruption and data security violation.
the electrical and mechanical portions usually equal to 15 This is accomplished through an accurate and integrated
percent of the investment, but in the case of a Data center design approach which involves facility (building localization
this value increases to 70 percent. The ever-increasing and layout), engineering infrastructure (i.e. power and cooling)
demand for computing power also has an impact: with the and technology infrastructure (servers, cabling and so on).
new technologies between 20-22 kW of power is required for
each single rack, compared to 4-5 kW normally needed in the Not only servers
past. In total that represents millions of megawatt hours of Data centers are some of the most complex structures on
electricity a year and going forward, these environments will earth, full of intricate and interrelated equipment and systems:
become one of the main consumers of power in the world. beyond servers, consolle and computers a Data center
With the addition of more than 5.75 million new servers requires fans, pumps, chillers, valves, switchgear, control
every year and reported outages costing $1 million or more systems, transformers, PDUs, RPPs, UPSs and many other
per hour, the priorities of this rapidly changing market components which often represent the most of the investment
can therefore be summarized as follows: security, service and operating costs.In this scenario, the redundancy of
continuity, economic and environmental sustainability. backup power supplies and communications, an accurate
environmental control and a tight security policy are the key
for maximize the availability of a so crucial resouce.
And, like all mission-critical installations, also a Data center
needs regular monitoring and maintenance to ensure extreme
reliability.
Significant amounts of energy can be saved through
improvements to Data center equipment, facility design
and management, and ABB provides a wealth of expertise,
engineering, products and support, to not only help todays
Data centers operate more efficiently, but also to operate
safely and more reliably.

8 | Securing your power supply


Data centers need a constant and reliable power supply and an
accurate control of environmental conditions to keep services
running and prevent any consequences due to interruption or
absence of energy.

The role of the change-over switch Fully automatic operation ensures that loads are transferred
The automatic transfer switch shall be managing different automatically to the secondary source in case of mains failure.
power supplies to one or more load circuits and guarantees Both local operation with the control unit and full automatic
the continuity of performance. The automatic transfer switch operation enables a short switch-off time between the normal
ensures the switching and isolation between the primary and the alternative supply.
power supply and the alternate power supply or standby
generator. The type of operation shall be open transition, i.e. In Data centers automatic transfer switches are predominantly
break-before-make. used to backup cooling facilities (air-handling units and
chillers) on UPS (Uninterruptible Power Supply) that ensures
short time power supply in case of emergency.

Securing your power supply | 9


Maximizing availability of Data centers
while providing efficiency and reliability

1
3

6
2

5
7

1. - Microgrid connectivity 3. - I ntelligent power distribution 5. - EFF1 high-efficiency motors 7. - i-bus EIB/KNX
- S trategic partner to leading units - Inverter - Network Communication
wind and solar OEMs - Remote power panels - Network Communication - Active filter
- Branch circuit monitoring - Power factor correction
2. - Substations - S trategic partner to leading 6. - HVAC solutions - Rectifier
- Transformers OEMs - High-efficiency motor - Uninterruptible Power Supplies
- M edium-voltage switchboards - AC or DC battery chargers - L ow-harmonic variable
/ switchgear frequency drives / inverters 8. - D
 ata center automation and
- Dry-type transformers 4. - L
 ow-voltage switchboards / - Circuit breakers power optimization
- Network Communication switchgear - Cooling -R  emote monitoring and
- Generators - Circuit breakers - Automation and control diagnostics
- Power quality assessments - iPDUs (Power Distribution - Energy efficiency audit - Automation switchboards
- HV UPS Units) - iPDUs (Power Distribution - Inverter
- Active filter Units) - PLC
- Power factor correction - Remote Power Panel - Control Gear
- Network Communication - Power Measurement - Network Communication
- Network Communication
- ATS

10 | Securing your power supply


Typical generator 2250kW / 11kV / 3P Transformer
12 / 16 MVA - 34,5 / 11 kV

G G G G G

MV-SG 11kV / 2000A

MV-SG 11kV / 2000A MV-SG 11kV / 2000A

LV-SG 6000A / 400V LV-SG 6000A / 400V

LV-SG I 2500A / 400V LV-SG II 2500A / 400V

Air handling unit (AHU) - Chiller - UPS - Secondary chiller water pump (SCHWP)

In Data centers automatic transfer switches are predominantly used to backup cooling facilities (air-handling units and chillers) on UPS (Uninterruptible
Power Supply) that ensures short time power supply in case of emergency.

Securing your power supply | 11


Critical in every condition
Manual, motorized, automatic: the
features of ABBs change-over switches

Every backup generator needs a reliable change-over switch These products feature many integrated safety features and
to transfer loads from the primary source to the emergency or are particularly suitable for critical power applications, since
standby power system. they guarantee an effective and rapid switchover from main
ABB provides a complete portfolio of change-over and supply to Gen-set during voltage failure.
transfer switches for Gen-set and Data center applications. The three positions that characterize the mechanism of the
The range comprises of manual (OTC), motorized (OTM_C) change-over switches ensure that the two different power
and automatic transfer switches (OTM_C_D). supplies always remain isolated; additionally, in the motorized
ABBs range is tested according to IEC 60947-3 and version, the electric control circuit offers further safety:
IEC 60947-6-1, assuring correct operation both in normal and if the motor receives two commands simultaneously, the OFF
emergency conditions. command always takes priority.

12 | Securing your power supply


Manual change-over switches Motorized change-over switches
Manual change-over switches are suitable for Gen-set Motorized change-over switches are required in applications
applications where the transfer doesnt need to be done where the transfer must be done quickly after source failure.
particularly fast. Manual change-over switches can be Thanks to the possibility to command the motor remotely with
operated only locally by manual operation so there is a need a PLC or PC-based controller, there is no need for manpower
for manpower to make the transfer. In some cases it can take in making the transfer. This means that the equipment can be
up to one hour to get a skilled person to operate the switch. located in isolated areas or places.
The OTC switches for manual change over are available Motorized change-over switches consist of a change-over
in OTC16...2500_C version and provide open transition switch (type OTC) and a motor operator. The ABBs OTM
switching (I-O-II) and a range of nominal current from 16 A up family range from 40 to 2500 A. Switches can be operated
to 2500 A. either electrically by using the motor operator or manually by
The products are tested for a high number of operations, using the local handle.
with safe and separate opening of contacts in all possible The remote control can easily be prevented by a selector
positions. switch Motor/Manual on the motor operator. This ensures
that maintenance work can be executed safely. Remote
control is also prevented whenever the manual handle or a
padlock has been inserted.
Products are tested in compliance with the IEC 60947-6-1
standard utilization categories AC-31B and AC-33B.

Securing your power supply | 13


Critical in every condition
Features of ABBs automatic transfer
switches

Thanks to its automatic control unit, which monitors the voltage


parameters on the primary supply, the automatic transfer
switch is able to start the backup generator and quickly and
safely transfer the load to the temporary power. ABBs range of
solutions perfectly matches every application need according to
international standards

14 | Securing your power supply


Automatic transfer switches ABBs range of ATS products offers nominal currents
Automatic transfer switches transfer the load automatically, between 160 A and 1600 A and includes sophisticated
from one supply to another. features in an extremely compact footprint. Specific features
Automatic transfer switches (ATS) are suitable for applications make assembly easy and guarantee safe operations.
where the transfer must be done quickly after source failure. The change-over mechanism, for example, offers three stable
In this case the motorized change-over switch is operated by positions which ensure isolation of the two asynchronous
an ATS control unit provided by the generator manufacturer power supplies. This eliminates any risk of short-circuit
or a local panel builder. The generator manufacturer or panel between them, even in the presence of transient voltages.
builder does the necessary work to connect the motorized The automatic transfer switch is equipped with handle for
change-over switch to the ATS control unit. They are also manual operation in case of emergency
responsible for the reliable operation of the equipment. The design of ABB automatic transfer switch is advanced
For customers who dont want to design the equipment by and compact, allowing installation in confined spaces at
themselves an automatic transfer switch provides a considerable savings. The automatic control unit OMD can be
ready-made solution. adjusted according to the mounting depth of the panel.
ABB OTM_C_D series of automatic transfer switches from Voltage sensing kit is preinstalled at the factory thus reducing
160A to 1600A provides an intelligent and fully automatic the expensive and time-consuming installation work.
solution for Gen-set and Datacenter applications. The motor operator of the ATS is protected by a fuse. If the
An automatic switching device can be managed and operation frequency is exceeded, the fuse protects the motor,
controlled by PLC or by special electronic devices. ABB can thus saving it from expensive repair work.
supply the necessary PLC devices (available in the AC500 Furthermore, the ODPSE230C Dual Power Source energizes
series). the motor operator using two lines: the motor operator is
An ABB ATS solution comprises of a change-over switch, automatically energized with the correct voltage whenever
a motor operator and an automatic control unit (OMD). power is available in one of the lines. The ODPSE230C is
Motorized change-over switches and OMD control units can available as an accessory.
be used to build different ATS combinations.
The automatic control units (OMD200, OMD300, OMD800)
have two sensors to check the supply characteristics of the
main and secondary line (voltage, frequency and the phase
balance) and send start/stop commands to the generator.
The automatic control units are able to work with single
or three-phase lines. The OMD800 version has two-way
communication enabling the ATS control unit to be monitored
and controlled through the Modbus RTU connection.
The OMD800 has also a graphic display offering user-friendly
interface.

Securing your power supply | 15


Critical in every condition
Features of ABBs automatic transfer
switches
A wide portfolio of accessories for every application Effective installation
ABBs change-over products benefit from a wide range of All products are designed to offer an easy, cost-effective
accessories to extend the features and increase safety and layout of the installation.
security, such as auxiliary contacts, bridging bars, attachment Mounting of the units is allowed in any direction, offering
for interlocking, terminal shrouds for finger-safe assembly and more flexibility to plan the layout of installation. The length
many others. of the shaft is adjustable in manual change-over switches,
meaning that there is no need to cut the shaft to the precise
length. Mounting depth of the automatic control unit can be
adjusted by sliding the controller towards the door. Terminal
clamps are available for Al and Cu cables while bridging
bars allows quick and flexible cabling. Wires are evenly
tightened with closing compression contacts. On motorized
and automatic versions, clearly market terminals prevent false
connections.

Voltage sensing wires

Change-over switch

Place for auxiliary contact blocks

Automatic control unit


(Three types: OMD200,
OMD300, OMD800)

Switch panel,
the operating mechanism

Motor/Manual selection

Fuse (F1) of motor operator Locking clip for locking


manual operation
Terminals for motor operator voltage supply

Handle for manual operation


Terminals (X2) for locking state
information, optional

Locking latch for releasing


the handle and locking
Motor operator (type OME_) electrical control

16 | Securing your power supply


A tailor-made choice
Selection examples

First of all the required operation method needs to be


determined. If the transfer time is not very critical and there
is manpower available to make the transfer when needed a
manual change-over switch is suitable.
If there is no manpower available to make the transfer or the
Gen-set manufacturer wants to use their own ATS control unit
solution, motorized change-over switches are a suitable choice.
An automatic transfer switch is most suitable when a
ready-made solution is wanted.

Example 1 Example 2
Secondly, the correct size of the change-over device needs If the size of the load is unknown but the size of the generator
to be determined. The size of the switch is determined by is known, for example 400 Volt generator with maximum
the load in Amperes or the size of the generator itself in kVA. output of 500 kVA which makes approximately 720 Amperes
If the size of the load is already known, for example 370
Amperes selection is easy to make. In this case the suitable 500 kVA / 0,4 kVA / 3 = 720 Amperes
size would be 400 Amperes device.
In this case the suitable size of the change-over switch would
be 800 Amperes.

Suitable selections: Suitable selections:


- Manual: OT400E03CP (3-poles) OT400E04CP (4-poles) - Manual: OT800E03CP (3-poles) OT800E04CP (4-poles)
- Motorized: OTM400E3CM230C (3-poles) -M otorized: OTM800E3CM230C (3-poles)
OTM400E4CM230C (4-poles) OTM800E4CM230C (4-poles)
- Automatic: OTM400E3C8D230C (3-poles) -A utomatic: OTM800E3C8D230C (3-poles)
OTM400E4C8D230C (4-poles) OTM800E4C8D230C (4-poles)

In these examples other control voltage options than 230VAC


for motorized change-over switches were not taken into
consideration. Also only one type of automatic transfer switch
was taken into consideration.

Securing your power supply | 17


Safety over all
The warranty to choose products
complying with all regulations
IEC 60947-6-1 IEC 60947-6-1 covers all change-over device solutions: switch-disconnectors, contactors and
Low-voltage switchgear circuit breakers.
and controlgear Part 6: Transfer switching equipment is classified according to:
Multiple function a) T heir short-circuit capability
equipment Section 1: - Class PC: capable of making and withstanding short-circuit currents
Automatic transfer b) The method of controlling the transfer
switching equipment. - Manually operated switching equipment (MTSE)
- Remotely operated transfer switching equipment (RTSE)
- Automatic transfer switching equipment (ATSE)

IEC 60947-3 IEC 60947-3:2008 applies to switches, disconnectors, switch-disconnectors and fuse-
Low-voltage switchgear combination units to be used in distribution circuits and motor circuits of which the rated
and controlgear - Part 3: voltage does not exceed 1 000 V a.c. or 1 500 V d.c.
Switches, disconnectors,
switch-disconnectors and
fuse-combination units

IEC 60947-3 vs. 60947-6-1 Motorized change-over switches


- IEC 60947-3, for switches, disconnectors, switch-disconnector and fuse-combination units
- IEC 60947-6-1, for transfer switching equipment, the right change-over switch standard

18 | Securing your power supply


Securing your power supply | 19
Customer case
OTM switch disconnectors support
Pramac generators the world over
The delicate process of transferring loads from the distribution
network to the backup generators in emergency situations
requires components of first-rate technology and reliability.
This is why Pramac chose ABB as a technological partner. ABB
is able to supply quality and total assistance in all areas of the
world.

Pramac supplied 44 electricity generators for the lighting system of the Abu Dhabi Formula 1 Grand Prix track. Each one has electrical power from 250
kW to 370 kW and is able to supply enough power to light more than 4,000 flats.
Pramac generators are equipped with special anti-sand filters able to prevent any potential blackouts caused by desert sand storms.

20 | Securing your power supply


The PRAMAC Group of Siena develops, manufactures and risks for equipment and personnel.
sells a wide range of generators (1 kW to 3 MW) all over Another important advantage lies in the presence of an
the world. ABB OTM motorized change-over switches intermediate stable 0 position. This technical feature makes
disconnectors are used in the Load Transfer Solution (LTS) it possible to disconnect from the network when necessary
network switchboards, which are supplied separately with because it is unreliable in that moment even during the
external logic. The complete system, consisting of a control starting phase preceding generator connection. Other factors,
panel and an LTS network switchboard, supervises the none the less important, were the completeness of the
distribution network and automatically starts the motor when OTM range, specifically designed for use with generators,
a problem occurs, so that within a few seconds the load is in addition to its reliability and intrinsic quality. Worthy of
powered by the generator. note is the fact that the OTMs are produced in such a way
The choice to use the ABB OTM products was made for a as to minimize the micro-recoils of the contacts during the
number of reasons. In looking for a technological partner, operation phases. This contributes to significantly improving
international leaders such as ABB were favored. That is to their reliability and preventing the chance that they create
say, companies able to provide pre- and aftersale support in electric arcs so that potential problems for people and
all contexts where PRAMAC generators are used. equipment are avoided.
It was then basically the presence of the double sectioning Last but not least, their compactness is a key factor, which
solution in the ABB offer that decided the choice, since it has allowed panel sizes to be reduced.
guarantees higher levels of protection against the risk of
electric arcs that are disconnected in two points instead of
one. This prevents the contacts from sticking and the relevant

Securing your power supply | 21


22 | Securing your power supply
Securing your power supply | 23
Contact us

ABB Oy The data and illustrations are not binding. We reserve

OTC26GB 12-06 1SCC303043D0201


the right to modify the contents of this document on
Breakers and Switches the basis of technical development of the products,
P.O. Box 622 without prior notice.
FI-65101 Vaasa, Finland Copyright 2012 ABB. All rights reserved.
Phone: +358 10 22 11
Fax: +358 10 22 45708
E-Mail: firstname.surname@fi.abb.com

www.abb.com
www.abb.com/lowvoltage
www.abb.com/motors&generators