Вы находитесь на странице: 1из 5

Article 430 Motors Motor Circuits and Controllers Page 1 of 5

Article 430: Motors, Motor Circuits, and Controllers

Charting a course through the largest chapter of the NEC

Mike Holt for EC&M Magazine

Article 430, with its tough subject and thirteen parts, presents a challenge. At first
glance, correctly applying Article 430 may seem impossible. But, a closer look
shows reveals usability features-such as its tables-that make Article 430 more
user-friendly than many people realize. One especially notable feature is Figure
430.1, which provides a graphical representation of how to apply Article 430.
Figure 430.1 allows you to proceed through Article 430 methodically and not miss
a key requirement. Let's see what some of those requirements are.

Part I. General Requirements

 Full load currents. Use the motor full load current rating (see Tables 430.147,
430.148, or 430.150) when determining conductor ampacity [430.22], the
branch-circuit short-circuit and ground-fault protection device [430.52 and 62],
and the ampere rating of switches [430.110]. Do not use the current rating on
the motor nameplate for this purpose (Figure 430-2).

Note: Graphics not part of this newsletter, they are contained in the textbook,
Understanding the National Electrical Code.

 Motor nameplate current rating. Use the motor nameplate current rating when
selecting devices intended to protect motors, motor control apparatus, and
motor branch-circuit conductors against excessive heating due to motor
overloads and failure to start [430.31].
 Motor controller terminals. Connect motor controllers and terminals of control
circuit devices with copper conductors, unless identified otherwise. Torque
motor control conductors 14 AWG and smaller at a minimum of 7 lb-in. for
screw-type pressure terminals, unless identified otherwise. See [430.9],
[110.3(B)], and [110.14 FPN].
 Motor locations. Locate motors to facilitate maintenance and provide
adequate ventilation [430.14].

Part II. Conductor Size

Some people misapply Chapter 3 ampacity tables when sizing motor conductors,
and therefore undersize the motor conductors. Motors have inrush current, which
conductor sizing must allow for.

 Single motors. Per [430.22], size motor branch-circuit conductors no smaller


than 125 percent of the motor FLC rating listed in Table 430.147 or 430.148

http://www.mikeholt.com/mojonewsarchive/NEC-HTML/HTML... 7/31/2010
Article 430 Motors Motor Circuits and Controllers Page 2 of 5

(Figure 430-4). Size the branch-circuit short-circuit and ground-fault


protection device per 240.6(A) and 430.52(C)(1) Ex. 1.
 Multiple motors. Per [430.24], size multiple motor conductors as follows. First,
multiply the full-load current rating of the highest-load motor by 1.25. Then,
add up the full-load current ratings of all the other motors in the group. Add
these two numbers. That's your motor load for calculating ampacity. Add any
other loads on that conductor, to calculate total conductor ampacity.

Test your knowledge, with the following question. What size branch-circuit
conductor does a 71/2-hp, 230V, 3Ø motor need if the conductor terminals are
rated 60°C (Figure 430-5)?

(a) 14 AWG
(b) 12 AWG
(c) 10 AWG
(d) none of these

Answer: (c) 10 AWG


22A x 1.25 = 27.5A, 10 AWG, rated 30A at 60°C.

Size the branch-circuit short-circuit and ground-fault protection device per 240.6(A)
and 430.52(C)(1) Ex. 1. For an inverse-time breaker: 22A x 2.5 = 55A, next size up
= 60A.
Let's try sizing a motor feeder conductor. Here's your question. What size 75°C
feeder conductor is required for two 71/2-hp, 230V, 3Ø motors (Figure 430-7)?

(a) 14 AWG
(b) 12 AWG
(c) 10 AWG
(d) 8 AWG

Answer: (d) 8 AWG


(22A x 1.25) + 22A = 49.5A, 8 AWG rated 50A at 75°C

Size the feeder protection device [430.62] as follows:

Step 1. Determine the branch-circuit protection rating. Inverse-Time Breaker: 22A


x 2.5 = 55A, next size up 60A.
Step 2. Size the feeder protection device. Inverse-Time Breaker: 60A + 22A =
82A, next size down, 80A.

Part III. Overload Protection

An overload is not a short-circuit or ground fault. It's an operating current that is


just too high. Overload protection devices will interrupt a current that is too high,

http://www.mikeholt.com/mojonewsarchive/NEC-HTML/HTML... 7/31/2010
Article 430 Motors Motor Circuits and Controllers Page 3 of 5

when it persists for too long (typically on the order of seconds). The time factor
allows for the starting current of the motor, which is higher than the operating
current but only momentary. A branch-circuit short-circuit and ground-fault
protection device protects the motor, the motor control apparatus, and the
conductors against short circuits or ground faults, but not against overload (Figure
430-11).

You must protect each motor branch circuit against short circuit and ground fault
by a protection device sized no greater than the percentages listed in Table
430.52. Motor branch-circuit conductors are protected against overcurrent by
overloads sized at 115 to 125 percent of motor nameplate current rating [430.32].

Part VI. Motor Control Circuits

You must provide motor control circuit conductors with a disconnecting means that
opens all conductors of the motor control circuit [430.74]. The controller disconnect
can serve as the disconnecting means for control circuit conductors, if the control
circuit conductors are tapped from the controller disconnect [430.102(A)]. If the
control circuit conductors are not tapped from the controller disconnect, provide a
separate disconnect for the control circuit conductors and locate it adjacent to the
controller disconnect (Figure 430-17). The control circuit disconnect cannot not be
higher than 6 ft 7 in. above the floor or working platform, unless located adjacent to
the equipment it supplies [404.8(A)].

Part V. Feeder Short-Circuit and Ground-Fault Protection

Per [430.62], protect feeder conductors against short circuits and ground faults by
a protection device sized:

 Not greater than the largest rating of the branch-circuit short-circuit and
ground-fault protective device for any motor
 Plus the sum of the full-load currents of the other motors in the group.

What size feeder protection (inverse-time breakers with 75°C terminals) and
conductor do you need for the following two motors (Figure 430-15)?

Motor 1: 20-hp, 460V, 3Ø = 27A


Motor 2: 10-hp, 460V, 3Ø = 14A

(a) 8 AWG/70A
(b) 8 AWG/80A
(c) 8 AWG/90A
(d) none of these

Answer: (b) 8 AWG/80A

http://www.mikeholt.com/mojonewsarchive/NEC-HTML/HTML... 7/31/2010
Article 430 Motors Motor Circuits and Controllers Page 4 of 5

(27A x 1.25) + 14A = 48A


8 AWG rated 50A at 75°C [110.14(C) and Table 310.16]

Feeder Protection [430.63(A)] not greater than largest branch-circuit protection


device plus other motor FLC.

Step 1. Determine largest branch-circuit protection device [430-52(C)(1)]

20-hp Motor = 27A x 2.5 = 68, next size up = 70A [430.52(C)(1) Ex.]
10-hp Motor = 14A x 2.5 = 35A

Step 2. Size Feeder Protection = 70A + 14A, = 84A, next size down = 80A

Part VII. Motor Controllers

Each motor requires its own controller [430.87]. Select an enclosure suitable for
the environment that controller occupies, per Table 430.91.

Controllers other than circuit breakers and molded case switches must have a
horsepower rating no less than that of the motor. A circuit breaker can serve as a
motor controller [430.111]. A molded case switch, rated in amperes, can serve as
a motor controller.
For stationary motors rated at 2-hp or less and 300V or less, the controller can be
either of the following:

 A general-use switch having an ampere rating not less than twice the full-load
current rating of the motor.
 A general-use snap switch where the motor full-load current rating is not more
than 80 percent of the ampere rating of the switch.

The motor controller is required to open only as many conductors of the circuit as
necessary to start and stop the motor [430.84]. For example, one conductor must
open to control a 2-wire, 1Ø motor; two conductors must open to control a 3-wire,
3Ø motor (see Figure 430-19). The controller starts and stops the motor; it is not a
disconnecting means [430.103].

Part IX. Disconnecting Means

You need a disconnect for each motor controller. You must locate it within sight of
the controller (see Figure 430-20). "Within sight" means visible and not more than
50 ft from each other [Article 100]. Under certain circumstances, [430.102(B)]
allows exceptions to this requirement.

The controller disconnect must open all circuit conductors simultaneously


[430.103] (see Figure 430-21). The controller disconnect can serve as the

http://www.mikeholt.com/mojonewsarchive/NEC-HTML/HTML... 7/31/2010
Article 430 Motors Motor Circuits and Controllers Page 5 of 5

disconnect for motor control circuit conductors [430.74] and the motor [430.102(B)
Ex.].

The disconnecting means for the motor controller and the motor must open all
ungrounded supply conductors simultaneously [430.103] (see Figure 430-24).

The disconnecting means must be legibly marked to identify its intended purpose
[110.22 and 408.4]. When operated vertically, the "up" position corresponds to the
"on" state [240.81 and 404.6(C)]. The controller disconnect or motor disconnect
required by [430.102] must be readily accessible (Figure 430-25).

Additional Tables

Table 430.148 lists the full-load current for single-phase alternating-current motors.
Use these values to determine motor conductor sizing, ampere ratings of
disconnects, controller rating, and branch-circuit and feeder protection-but not
overload protection [430.6(A)(1)].

Table 430.150 lists the full-load current for 3-phase alternating-current motors. Use
these values to determine motor conductor sizing, ampere ratings of disconnects,
controller rating, and branch-circuit and feeder protection-but not overload
protection [430.6(A)(1)].

Table 151(A) contains locked-rotor current for single-phase motors, and Table 151
(B) contains the locked-rotor current for 3-phase motors. Use these values in the
selection of controllers and disconnecting means when the horsepower rating is
not marked on the motor nameplate.

Article 430 is an amazing document, given the complexity of the subject it covers
and the ease with which you can apply it. That ease of application is possible
because of usability features, such as the various tables and Figure 430.1. If you
proceed methodically, you will correct apply Article 430 every time.

http://www.mikeholt.com/mojonewsarchive/NEC-HTML/HTML... 7/31/2010

Вам также может понравиться