Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated
Total coil load ........................................................ 238.6 kW Load occurs at .................................................... Jun 1100
Sensible coil load ................................................. 172.1 kW OA DB / WB ...................................................... 44.2 / 29.3 C
Coil L/s at Jun 1100 ............................................... 8108 L/s Entering DB / WB ............................................. 30.1 / 20.4 C
Max block L/s ........................................................ 8108 L/s Leaving DB / WB .............................................. 12.5 / 11.7 C
Sum of peak zone L/s ........................................... 8108 L/s Coil ADP ..................................................................... 10.5 C
Sensible heat ratio ............................................... 0.721 Bypass Factor .......................................................... 0.100
m/kW ....................................................................... 2.1 Resulting RH ................................................................. 43 %
W/m ..................................................................... 471.5 Design supply temp. ................................................... 12.0 C
Water flow @ 5.6 K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 K
Max coil load .......................................................... 45.0 kW Load occurs at ................................................... Dec 0500
Coil L/s at Dec 0500 .............................................. 8108 L/s W/m ......................................................................... 175.0
Max coil L/s ........................................................... 8108 L/s Ent. DB / Lvg DB .............................................. 14.4 / 23.4 C
Water flow @ 11.1 K drop ...................................... N/A
Actual max L/s ....................................................... 8108 L/s Fan motor BHP ........................................................... 6.04 BHP
Standard L/s .......................................................... 8093 L/s Fan motor kW ............................................................. 4.50 kW
Actual max L/(s-m) .............................................. 16.02 L/(s-m) Fan static ..................................................................... 300 Pa