Академический Документы
Профессиональный Документы
Культура Документы
MODEL YK (STYLE F)
R-134a (COOLING ONLY)
00611VIP
LD05842
FORM 160.73-N1 (904)
ALLOWABLE COMPRESSOR/
EVAPORATOR/CONDENSER/MOTOR COMBINATIONS
NOMENCLATURE
YK CB CB G4 CM F S
Special Modifications
2 YORK INTERNATIONAL
FORM 160.73-N1 (904)
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. During installation, operation maintenance or service,
individuals may be exposed to certain components or conditions including, but not limited to: refrigerants,
oils, materials under pressure, rotating components, and both high and low voltage. Each of these items
has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and
responsibility of operating/service personnel to identify and recognize these inherent hazards, protect
themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements
could result in serious damage to the equipment and the property in which it is situated, as well as severe
personal injury or death to themselves and people at the site.
This document is intended for use by owner-authorized operating/service personnel. It is expected that this
individual posseses independent training that will enable them to perform their assigned tasks properly and
safely. It is essential that, prior to performing any task on this equipment, this individual shall have read
and understood this document and any referenced materials. This individual shall also be familiar with and
comply with all applicable governmental standards and regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbol is used in this document to alert the reader to areas of potential hazard:
CAUTION identifies a hazard which could lead to damage to the machine, damage to other
equipment and/or environmental pollution. Usually an instruction will be given, together with
a brief explanation.
YORK INTERNATIONAL 3
FORM 160.73-N1 (904)
TABLE OF CONTENTS
DIMENSIONS................................................................................................. 6
CHILLER WEIGHTS....................................................................................... 14
MOTOR WEIGHTS ........................................................................................ 15
INTRODUCTION ............................................................................................ 16
General .................................................................................................. 16
Field Assembed Units Only.................................................................... 16
Shipment................................................................................................ 16
Inspection Damage Shortage ....................................................... 17
Chiller Data Plate................................................................................... 17
Rigging................................................................................................... 17
Location ................................................................................................. 18
Motors .................................................................................................... 18
Foundation............................................................................................. 18
Clearance .............................................................................................. 18
Isolators ................................................................................................. 19
INSTALLATION .............................................................................................. 23
Rigging Unit to Final Location................................................................ 23
Locating and Installing Isolator Pads ..................................................... 23
Checking the Isolation Pad Deflection ................................................... 23
Leveling the Unit .................................................................................... 23
Installing Optional Spring Isolators ........................................................ 23
Piping Connections................................................................................ 23
Evaporator and Condenser Water Piping .............................................. 24
Refrigerant Relief Piping........................................................................ 25
Unit Piping ............................................................................................. 25
Control Panel Positioning ...................................................................... 26
Control Wiring ........................................................................................ 26
Power Wiring ......................................................................................... 26
Insulation ............................................................................................... 27
Installation Check Request for Start-up Service ............................... 27
LIST OF FIGURES
Fig. 1 Model YK MaxE Chiller................................................................ 5
Fig. 2 Dimensions (P Compressors Ft.-In.) ............................................ 6
Fig. 3 Dimensions (P Compressors Metric)............................................ 7
Fig. 4 Dimensions (H Compressors Ft.-In.)............................................ 8
Fig. 5 Dimensions (H Compressors Metric) ........................................... 9
Fig. 6 Dimensions (J Compressors Ft.-In.)............................................. 10
Fig. 7 Dimensions (J Compressors Metric) ............................................ 12
Fig. 8 Rigging ............................................................................................ 18
Fig. 9 Neoprene Isolators (Ft.-In.) ............................................................. 19
Fig. 10 Neoprene Isolators (Metric)............................................................. 20
Fig. 11 Spring Isolators (Ft.-In.)................................................................... 21
Fig. 12 Spring Isolators (Metric) .................................................................. 22
Fig. 13 Schematic for a Typical Piping Arrangement................................... 24
Fig. 14 Typical Refrigerant Vent Piping ....................................................... 25
Fig. 15 Control Panel Positioning ................................................................ 26
Fig. 16 Motor Connections (E.M. Starter).................................................... 27
4 YORK INTERNATIONAL
FORM 160.73-N1 (904)
COMPRESSOR
OPTIVIEW MOTOR
CONTROL
CENTER
CONDENSER
EVAPORATOR
00611VIP
YORK INTERNATIONAL 5
FORM 160.73-N1 (904)
P COMPRESSOR UNITS
OPTIVIEW
CONTROL
CENTER
EVAPORATOR
F
LD03885
* Operating Location
of Control Center on
Evaporator Codes G
thru W.
P8 COMPRESSOR P9 COMPRESSOR
EVAPORATOR CONDENSER SHELL CODES EVAPORATORCONDENSER SHELL CODES
EE FF GG HH FF GG HH
A 6'11" 6'11" 7'6-1/2" 7'6-1/2" A 6'11" 7'6-1/2" 7'6-1/2"
B 10'3-1/2" 10'3-1/2" 10'9-1/2" 10'9-1/2" B 9'11-7/8" 10'6" 10'6"
C 2'0" 2'0" 2'1-1/4" 2'1-1/4" C 2'0" 2'1-1/4" 2'1-1/4"
D 1'5-1/2" 1'5-1/2" 1'8" 1'8" D 1'5-1/2" 1'8" 1'8"
E 1'2-7/8" 1'2-7/8" 1'3-5/8" 1'3-5/8" E 1'2-7/8" 1'3-5/8" 1'3-5/8"
F 12'0" 16'0" 12'0" 16'0" F 16'0" 12'0"
NOTES:
1. All dimensions are approximate. Certified dimensions are available on request.
2. For compact water boxes (shown above), determine overall unit length by adding water box depth to tube sheet length.
3. Water nozzles can be located on either end of unit. Add 1/2" (13 mm) to nozzle length for flanges connections.
4. To determine overall height, add 7/8" (22 mm) for isolators.
5. Use of motors with motor hoods may increase overall unit dimensions.
6 YORK INTERNATIONAL
FORM 160.73-N1 (904)
P COMPRESSOR UNITS
OPTIVIEW
CONTROL
CENTER
EVAPORATOR
F
LD03885
* Operating Location
of Control Center on
Evaporator Codes G thru
W.
P8 COMPRESSOR P9 COMPRESSOR
EVAPORATORCONDENSER SHELL CODES EVAPORATORCONDENSER SHELL CODES
EE FF GG HH FF GG HH
A 2,108 2,108 2,299 2,299 A 2,108 2,299 2,299
B 3,137 3,137 3,289 3,289 B 3,045 3,200 3,200
C 610 610 641 641 C 610 641 641
D 445 445 508 508 D 445 508 508
E 378 378 397 397 E 378 379 397
F 3,658 4,877 3,658 4,877 F 4,877 3,658 4,877
NOTES:
1. All dimensions are approximate. Certified dimensions are available on request.
2. For compact water boxes (shown above), determine overall unit length by adding water box depth to tube sheet length.
3. Water nozzles can be located on either end of unit. Add 13 mm (1/2 inch) to nozzle length for flanges connections.
4. To determine overall height, add 22 mm (7/8 inch) for isolators.
5. Use of motors with motor hoods may increase overall unit dimensions.
YORK INTERNATIONAL 7
FORM 160.73-N1 (904)
H COMPRESSOR UNITS
OPTIVIEW
CONTROL
CENTER
EVAPORATOR
LD03885
* Operating Location
of Control Center on
Evaporator Codes G thru
W.
H5 COMPRESSORS
EVAPORATORCONDENSER SHELL CODES
EE EF FE FF FG GF GG
A 6'6" 6'9" 6'11" 7'2" 7'6" 7'4-1/2" 7'8-1/2"
B 8'0-1/4" 8'2-3/4" 8'0-1/4" 8'2-3/4" 8'6-3/4" 8'2-3/4" 8'6-3/4"
C 1'9-1/2" 1'9-1/2" 2'0" 2'0" 2'0" 2'1-1/4" 2'1-1/4"
D 1'5-1/2" 1'7" 1'5-1/2" 1'7" 1'9" 1'7" 1'9"
E 0'5-7/8" 0'5-7/8" 0'5-7/8" 0'5-7/8" 0'5-7/8" 0'6-1/4" 0'6-1/4"
F 14'0" 14'0" 14'0" 14'0" 14'0" 14'0" 14'0"
8 YORK INTERNATIONAL
FORM 160.73-N1 (904)
H COMPRESSOR UNITS
OPTIVIEW
CONTROL
CENTER
EVAPORATOR
LD03886
* Operating Location
of Control Center on
Evaporator Codes G
thru W.
H5 COMPRESSORS
EVAPORATOR CONDENSER SHELL CODES
EE EF FE FF FG GF GG
A 1,981 2,057 2,108 2,184 2,286 2,248 2,350
B 2,445 2,508 2,443 2,508 2,305 2,508 2,305
C 546 546 610 610 610 641 641
D 445 483 445 483 533 483 533
E 149 149 149 149 149 159 159
F 4,268 4,268 4,268 4,268 4,268 4,268 4,268
NOTES:
1. All dimensions are approximate. Certified dimensions are available on request.
2. For compact water boxes (shown above), determine overall unit length by adding water box depth to tube sheet length.
3. Water nozzles can be located on either end of unit. Add 13 mm (1/2 inch) to nozzle length for flanges connections.
4. To determine overall height, add 22 mm (7/8 inch) for isolators.
5. Use of motors with motor hoods may increase overall unit dimensions.
YORK INTERNATIONAL 9
FORM 160.73-N1 (904)
J COMPRESSOR UNITS
OPTIVIEW
CONTROL
CENTER
EVAPORATOR
LD03887
* Operating
Location of
Control Center
on Evaporator
J1/J2 COMPRESSORS Codes G thru
EVAPORATOR CONDENSER SHELL CODES W.
10 YORK INTERNATIONAL
FORM 160.73-N1 (904)
F F
1 PASS CONDENSERS
DIM. G H J T V X
F 1'2" 1'9" 1'9-3/4" 1'9-3/4" 1'11-1/8" 1'7-5/8"
H K
J
2 PASS CONDENSERS
DIM. G H J T V X
H 6" 11-1/2" 1'0-1/4" 1'0-1/4" 1'1-7/8" 0'11-3/4"
J 1'2" 1'6-1/4" 1'7-5/8" 1'7-5/8" 1'10-1/8" 1'7-5/8"
K 1'2" 2'0-1/4" 1'7-5/8" 1'7-5/8" 1'10-1/8" 1'7-5/8"
G F
LD10115
3 PASS CONDENSERS
DIM. G H J T V X
G 1'2" 1'4-7/8" 1'7" 1'7" 1'7-3/4" 1'7-5/8"
F 1'2" 1'8-1/8" 1'10-1/8" 1'10-1/8" 1'11-3/8" 1'7-5/8"
YORK INTERNATIONAL 11
FORM 160.73-N1 (904)
J COMPRESSOR UNITS
OPTIVIEW
CONTROL
CENTER
EVAPORATOR
LD03888
* Operating
J1/J2 COMPRESSORS Location
EVAPORATOR CONDENSER SHELL CODES of Control
G-G G-H H-G H-H H-J J-H J-J T-T Center on
Evaporator
A 2286 2388 2400 2502 2604 2718 2769 2769 Codes G
B 2838 2991 2838 2991 2991 2991 2991 2985 thru W.
C 610 610 667 667 667 749 749 749
D 533 584 533 584 635 584 635 635
E 4267 4267 4267 4267 4267 4267 4267 4877
F 603 603 603 603 603 603 603 603
G 375 375 375 375 375 375 375 375
J3 COMPRESSORS J5 COMPRESSORS
EVAPORATOR CONDENSER SHELL CODES EVAPORATOR CONDENSER SHELL CODES
H-H H-J J-H X-X
A 2502 2604 2667 A 10'3"
B 2965 3067 2965 B 11'5"
C 667 667 749 C 2'8"
D 584 635 584 D 2'5-1/2"
E 4267 4267 4267 E 18'-0"
F 603 603 603 F 2'0-3/4"
G 375 375 375 G 1'4-3/4"
J3/J4 COMPRESSORS
EVAPORATOR CONDENSER SHELL CODES
J-J T-T T-V V-T V-V W-V
A 2769 2769 2896 2769 2896 3023
B 3067 3067 3194 3067 3194 3194
C 749 749 749 749 749 813
D 635 635 699 635 699 699
E 4267 4877 4877 4877 4877 4877
F 603 603 603 603 603 629
G 375 375 375 375 375 419
12 YORK INTERNATIONAL
FORM 160.73-N1 (904)
Dimensions (mm)
F F
1 PASS CONDENSERS
DIM. G H J T V X
F 356 533 552 552 587 499
H K
J
2 PASS CONDENSERS
DIM. G H J T V X
H 152 292 311 311 352 299
J 356 464 498 498 562 499
K 356 464 198 498 562 499
G F
LD10115
3 PASS CONDENSERS
DIM. G H J T V X
G 356 429 311 498 562 499
F 356 511 562 562 594 499
YORK INTERNATIONAL 13
FORM 160.73-N1 (904)
14 YORK INTERNATIONAL
FORM 160.73-N1 (904)
YORK INTERNATIONAL 15
FORM 160.73-N1 (904)
INTRODUCTION
GENERAL 6. Do not charge the unit with refrigerant.
This instruction describes the installation of a MODEL 7. Do not attempt to start the system.
YK MaxE Liquid Chilling Unit. This unit is shipped 8. Do not run hot water (110F / 43C max) or steam
as a single factory assembled, piped, wired package, through the evaporator or condenser at any time.
requiring a minimum of field labor to make chilled water
connections, condenser water connections, refrigerant SHIPMENT
atmospheric relief connections, and electrical power
The chiller may be ordered and shipped in any of the
con nec tions. (Refrigerant and oil charges shipped
following forms:
separately unless optional condensor isolation valves
are ordered.) Form 1 Factory Assembled Unit, complete with
motor, refrigerant and oil charges.
Chillers can also be shipped dismantled when required by
rigging conditions, but generally it is more economical 1. The motor/compressor assembly mounted,
to enlarge access openings to accommodate the factory with all necessary interconnecting piping
assembled unit. Chillers shipped dismantled MUST assembled. OptiView Control Center is
be field assembled under the supervision of a YORK mounted on the unit. Complete unit factory
representative, but otherwise installation will be as leak tested, evacuated and charged with R-
described in this instruction. 134A.
FIELD ASSEMBLED UNITS ONLY An optional Solid State Starter or Variable
Speed Drive can be factory mounted and
Use Form 160.73-N3 in conjunction with this installation wired.
instruction. This instruction will be furnished with all
units that are to be field assembled. Extra copies may 2. Miscellaneous material Four (4)
be ordered from the York Publication Distribution vi bra tion isolation pads (or optional
Center. spring isolators and brackets).
The services of a YORK representative will be furnished Form 2 Factory Assembled Unit, complete with
to check the installation, supervise the initial start-up motor (refrigerant and oil charges shipped
and operation of all chillers installed within Continental separately).
United States.
1. The motor/compressor assembly mounted,
The YORK Warranty may be voided with all necessary interconnecting piping
if the following restrictions are not assembled. OptiView Control Center is
adhered to: mounted on the unit. Complete unit factory
leak tested, evacuated and charged with
holding charge of nitrogen.
1. No valves or connections should be opened under An optional Solid State Starter or Variable
any circumstances because such action will result Speed Drive can be factory mounted and
in loss of the factory nitrogen charge. wired.
2. Do not dismantle or open the chiller for any 2. Miscellaneous material Four (4)
reason except under the supervision of a YORK vibration isolation pads (or optional spring
representative. isolators and brackets).
3. When units are shipped dismantled, notify the Form 3 Driveline Separate From Shells Shipped
nearest YORK office in ample time for a YORK as two major assemblies. Unit first factory
rep re sen ta tive to supervise rigging the unit as sem bled, refrigerant piped, wired and
to its op er at ing position and the as sem bly of leak tested; then dismantled for shipment.
components. Compressor/motor assembly removed from
4. Do not make final power supply connections to the shells and skidded. Evaporator/condenser is
compressor motor or control center. not skidded.
All wiring integral with compressor is left on damage. Any damage or signs of possible damage must
it, and all conduit is left on shell. All openings be reported to the transportation company immediately
on compressor, oil separator, and shell are for their inspection.
closed and charged with dry nitrogen (2 to 3
PSIG) (115/122 kPa). YORK WILL NOT BE RESPONSIBLE FOR ANY
DAM AGE IN SHIPMENT OR AT JOB SITE OR
Miscellaneous packaging of control center,
LOSS OF PARTS. (Refer to Shipping Damage Claims,
tubing, water temperature controls, wiring,
Form 50.15-NM)
oil, isolators, solid state starter (option), etc.;
refrigerant charge shipped separately.
When received at the job site all containers should be
Units shipped dismantled MUST be re- opened and contents checked against the packing list.
assembled by, or under the supervision Any material shortage should be reported to YORK
of, a YORK representative. (See Form immediately. (Refer to Shipping Damage Claims, Form
50.15-NM)
160.73-N3)
CHILLER DATA PLATE
Form 7 Split Shells Shipped as three major
assemblies. Unit first factory assembled, A unit data plate is mounted on the control center
refrigerant piped, wired and leak tested; then assembly of each unit, giving unit model number; design
dismantled for shipment. Compressor/motor working pressure; water passes; refrigerant charge;
assembly removed from shells and skidded. serial numbers; and motor power characteristics and
connection diagrams.
Evaporator and condenser shells are separated
at tube sheets and are not skidded. Refrigerant
Additional information may be found on the motor
lines between shells are flanged and capped,
data plate. This information should be included when
requiring no welding.
contacting the factory on any problem relating to the
All wiring integral with compressor is left on motor.
it. All wiring harnesses on shells are removed.
All openings on compressor and shells are RIGGING (See Fig. 8)
closed and charged with dry nitrogen (2 to 3
PSIG) (115/122 kPa). The complete standard chiller is shipped without skids.
(When optional skids are used it may be necessary to
Miscellaneous packaging of control center,
remove the skids so riggers skates can be used under the
tubing, water temperature controls, wiring,
unit end sheets to reduce overall height.)
oil isolators, solid state starter (option), etc.;
refrigerant charge shipped separately.
Each unit has four (4) lifting holes (two in each end) in
Units shipped dismantled MUST be re- the end sheets which should be used to lift the unit.
assembled by, or under the supervision
of, a YORK representative. (See Form Care should be taken at all times during rigging and
160.73-N3) handling of the chiller to avoid damage to the unit and
its external connections. Lift only using holes shown
in Fig. 8.
When more than one chiller is involved, the major
parts of each unit will be marked to prevent mixing of Do not lift the unit with slings around
assemblies. (Piping and Wiring Drawings to be furnished motor/com pres sor assembly or by
by YORK.) means of eyebolts in the tapped holes
of the compressor motor assembly. Do
INSPECTION DAMAGE SHORTAGE
not turn a unit on its side for rigging.
The unit shipment should be checked on arrival to see Do not rig vertically.
that all major pieces, boxes and crates are received. Each
unit should be checked on the trailer or rail car when
received, before unloading, for any visible signs of
YORK INTERNATIONAL 17
FORM 160.73-N1 (904)
LD00700(R)
FIG. 8 RIGGING
The rigging and operating weights and overall or other sufficiently large opening
dimensions are given on pages 6 thru 13 as a guide in properly located may be used. The
determining the clearances required for rigging. Add 6" chiller should be located in an indoor
(15 cm) to overall height for optional skidded unit. location where temperatures range
from 40F to 110F (4.4C to 43.3C).
LOCATION
MOTORS
YORK MaxE Chillers are furnished with vibration
The YK open motor is air cooled. Check state, local and
isolator mounts for basement or ground level installations.
other codes for ventilation requirements.
Units may be located on upper floor levels providing the
floor is capable of supporting the total unit operating
weight and optional spring isolators are used. FOUNDATION
A level floor, mounting pad or foundation must be
Sufficient clearance to facilitate provided by others, capable of supporting the operating
normal service and maintenance weight of the unit.
work must be provided all around
and above the unit and particularly CLEARANCE
space provided at either end to Clearances should be adhered to as follows:
permit cleaning or replacement of Rear and above unit 2 ft (61 cm).
evaporator and condenser tubes Front of unit 3 ft (91 cm).
see CLEARANCE. A doorway Tube Removal 14 ft.* (4.3 m) (either end)
* 16 ft. (4.9 meters) on shell codes T-T, T-V, V-T, V-V & W-V.
** 18 ft. (5.5 meters) on shell code X-X.
18 YORK INTERNATIONAL
FORM 160.73-N1 (904)
LD08521 LD08522
LD08523
9 LD10113
UNIT WEIGHT 28,836 TO 53,530 LBS. UNIT WEIGHT 100,465 TO 130,000 LBS.
8 8
3 3
FLOOR LAYOUT
10 10
2 2
CONDENSOR
CENTERLINE
A*
SHELLS CENTERLINE
END
SHEET
END SHEET
COOLER
CENTERLINE
* See Fig. 2, 4, or 6
3 See Fig. 2, 4, or 6 3
YORK INTERNATIONAL 19
FORM 160.73-N1 (904)
LD08525 LD08526
254
LD08527 LD10116
UNIT WEIGHT 13,081 TO 24,281 Kgs. UNIT WEIGHT 45,570 TO 58,968 Kgs.
203 203
76 76
FLOOR LAYOUT
254 254
51 51
CONDENSOR
CENTERLINE
A*
SHELLS CENTERLINE
END
SHEET
END SHEET
COOLER
CENTERLINE
* See Fig. 3, 5, or 7
76 See Fig. 3, 5, or 7 76
LD10117
FIG. 10 NEOPRENE ISOLATORS (METRIC DIMENSIONS)
20 YORK INTERNATIONAL
FORM 160.73-N1 (904)
EVAPORATOR
*See Fig. 2, 4, or 6
See Fig. 2, 4, or 6
LD03830
EVAPORATOR
*See Fig. 2, 4, or 6
See Fig. 2, 4, or 6
LD03831
8"
SHELL
CONDENSER "
CENTERLINE
13 "
SHELLS
CENTERLINE
EVAPORATOR A*
CENTERLINE
CAP
SCREW
ADJUSTING
BOLT 13 "
"
ACOUSTICAL 8" *See Fig. 2, 4, or 6
NONSKID See Fig. 2, 4, or 6
A*
NEOPRENE PAD
LD10119
14"
11"
UNIT WEIGHT 89,341 LBS. UP TO 115,000 LBS.
EVAPORATOR
*See Fig. 3, 5, or 7
See Fig. 3, 5, or 7
LD03834
EVAPORATOR
*See Fig. 3, 5, or 7
See Fig. 3, 5, or 7
LD03835
343 mm
SHELLS
CENTERLINE
EVAPORATOR A*
CENTERLINE
CAP
SCREW
ADJUSTING
BOLT 343 mm
*See Fig. 3, 5, or 7
13 mm
ACOUSTICAL See Fig. 3, 5, or 7 203 mm
NONSKID
A*
NEOPRENE PAD
LD10118
356 mm
280 mm
UNIT WEIGHT 40,252 Kgs. UP TO 52,164 Kgs.
INSTALLATION
RIGGING UNIT TO FINAL LOCATION
INSTALLING OPTIONAL SPRING ISOLATORS
Rig the unit to its final location on the floor or mounting (REFER TO FIG. 11 OR 12)
pad, lift the unit (or shell assembly) by means of an
overhead lift and lower the unit to its mounting position. When ordered, spring type isolator assemblies will be
(If optional shipping skids are used, remove them before furnished with the unit. The 4 assemblies are identical
lowering the chiller to its mounting position.) and can be placed at any of the 4 corners of the unit.
YORK INTERNATIONAL 23
FORM 160.73-N1 (904)
springs are out of alignment, the misalignment must Permanent strainers (supplied by others) are required
be corrected by properly supporting the piping or by in both the evaporator and condenser water circuits to
applying heat to anneal the pipe. protect the chiller as well as the pumps, tower spray
nozzles, chilled water coils and controls, etc. The
If the piping is annealed to relieve strainer must be installed in the entering chilled water
stress, the inside of the pipe must be line, directly upstream of the chiller.
cleaned of scale before it is finally Water piping circuits should be arranged so that the
bolted in place. pumps discharge through the chiller, and should be
controlled as necessary to maintain essentially constant
EVAPORATOR AND CONDENSER WATER PIPING chilled and condenser water flows through the unit at
all load conditions.
The evaporator and condenser liquid heads of chiller
have nozzles which are grooved, suitable for welding If pumps discharge through the chiller, the strainer may
150 PSIG DWP flanges or the use of Victaulic couplings. be located upstream from pumps to protect both pump
Factory mounted flanges are optional. and chiller. (Piping between strainer, pump and chiller
must be very carefully cleaned before start-up.) If pumps
The nozzles and water pass arrangements are furnished are remotely installed from chiller, strainers should be
in accordance with the job requirements (see Product located directly upstream of the chiller.
Drawings) furnished with the job. Standard units are
designed for 150 PSIG DWP on the water side. If job Condenser Water Circuit
requirements are for greater than 150 PSIG DWP, check
the unit data plate before applying pressure to evaporator For proper operation of the unit, condenser refrigerant
or condenser to determine if the chiller has provisions pressure must be maintained above evaporator pressure.
for the required DWP. If operating conditions will fulfill this requirement, no
attempt should be made to control condenser water
Inlet and outlet connections are identified by labels temperature by means of automatic valves, cycling of
placed adjacent to each nozzle. the cooling tower fan or other means, since chillers are
designed to function satisfactorily and efficiently when
Chilled Water condenser water is allowed to seek its own temperature
level at reduced loads and off-peak seasons of the year.
Foreign objects which could lodge in, or block flow
However, if entering condenser water temperature can
through, the evaporator and condenser tubes must be
go below the required minimum, (refer to 160.73-O1)
kept out of the water circuit. All water piping must be
condenser water temperature must be maintained equal
cleaned or flushed before being connected to the chiller
to or slightly higher than the required minimum. Refer
pumps, or other equipment.
to Fig. 13 for typical water piping schematic.
EVAPORATOR
LD08529
VENT TO ATMOSPHERE
CONDENSATION
TRAP
CONDENSER
DUAL RELIEF
SEE NOTE
VALVES
EVAPORATOR
COOLER
Stop Valves and carefully check the evaporator and condenser water
heads and piping for leaks. Repair leaks as necessary.
Stop valves may be provided (by others) in the
evaporator and condenser water piping adjacent to the Before initial operation of the unit both water circuits
unit to facilitate maintenance. Thermometer wells and should be thoroughly vented of all air at the high
pressure taps should be provided (by others) in the piping points.
as close to the unit as possible to facilitate operating
check. REFRIGERANT RELIEF PIPING
After the water piping is completed, but before any water Compressor lubricant piping and system external piping
box insulation is applied. Tighten and torque to maintain are factory installed on all units shipped assembled. On
between 30 and 60 ft. lbs. (41 and 81 Nm) the nuts on units shipped dismantled, the following piping should
the liquid head flanges. Gasket shrinkage and handling be completed under the supervision of the YORK
during transit cause nuts to loosen. If water pressure is representative: (1) the lubricant piping to oil sump and
applied before tightening is done, the gaskets may be oil evaporator and system oil return connections using
damaged and have to be replaced. Fill the chilled and material furnished. See Form 160.73-N3.
condenser water circuits, operate the pumps manually
YORK INTERNATIONAL 25
FORM 160.73-N1 (904)
LD03826
26 YORK INTERNATIONAL
FORM 160.73-N1 (904)
having a clearance hole for a 3/8" bolt, motor terminal should be furnished (by others) and applied to the
lugs are not furnished. evaporator shell, end sheets, liquid feed line to flow
chamber, compressor suction connection, and evaporator
Chiller with Solid State Starter or liquid heads and connections. The liquid head flange
Variable Speed Drive insulation must be removable, to allow head removal for
the tube maintenance. Details of areas to be insulated
A chiller equipped with a factory mounted Solid State
are given on the Product Drawing.
Starter or Variable Speed Drive does not require wiring
to the compressor motor. The motor power wiring is Units are furnished factory anti-sweat insulated on order
factory connected to the Solid State Starter or Variable at additional cost. This includes all low temperature
Speed Drive (or an optional factory installed disconnect surfaces except the two (2) cooler liquid heads.
switch). See Field Wiring Diagram. All wiring to the
control panel and the oil pump starter is completed by INSTALLATION CHECK
the factory. A control transformer is furnished with the REQUEST FOR START-UP SERVICE
Solid State Starter or Variable Speed Drive.
The services of a YORK representative will be furnished
INSULATION to check the installation and supervise the initial start-
(SEE PRODUCT DRAWINGS FORM 160.52-PA1) up and operation on all chillers installed within the
Continental United States.
DO NOT field insulate until the unit has
been leak tested under the supervision After the unit is installed, piped and wired as described
of the YORK representative. in this Instruction, but before any attempt is made to start
the unit, the YORK District Office should be advised so
that the start-up service, included in the contract price,
can be scheduled. Notification to the YORK office
should be by means of Installation Check List and
Insulation of the type specified for the job, or minimum Request, Form 160.49-CL1, in triplicate.
thickness to prevent sweating of 30F (-1C) surfaces
3 PHASE NOTES:
MOTOR MOTOR RATED LOAD AMPS
A. Requires passing motor lead thru current transformer (CT) once
VOLTAGE CT RATIO before connecting to power supply.
50 / 60 Hz 200:1 350:1 700:1 1400:1 B. Requires passing motor lead thru CT twice before connecting to
200-600 65-111A 112-224A 225-829A 830-1790A power supply.
11-18C C. Requires passing motor lead thru CT three times before
2300-4160 19-37B 124-264A 265-518A connecting to power supply.
38-123A
LD00710