Вы находитесь на странице: 1из 24

NFN

VESDA-HLI-GW
Programming and Operation Manual

Document: LS10023-000NF-E
6/26/12 Rev: A2
P/N: LS10023-000NF-E: Rev. A2 ECN: 12-0294
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm systemtypically made up of smoke detec- bedrooms), smoking in bed, and violent explosions (caused by escap-
tors, heat detectors, manual pull stations, audible warning devices, ing gas, improper storage of flammable materials, etc.).
and a fire alarm control panel with remote notification capabilitycan Heat detectors do not sense particles of combustion and alarm only
provide early warning of a developing fire. Such a system, however, when heat on their sensors increases at a predetermined rate or
does not assure protection against property damage or loss of life reaches a predetermined level. Rate-of-rise heat detectors may be
resulting from a fire. subject to reduced sensitivity over time. For this reason, the rate-of-
The Manufacturer recommends that smoke and/or heat detectors be rise feature of each detector should be tested at least once per year
located throughout a protected premise following the recommenda- by a qualified fire protection specialist. Heat detectors are designed to
tions of the current edition of the National Fire Protection Association protect property, not life.
Standard 72 (NFPA 72), manufacturer's recommendations, State and IMPORTANT! Smoke detectors must be installed in the same room
local codes, and the recommendations contained in the Guide for as the control panel and in rooms used by the system for the connec-
Proper Use of System Smoke Detectors, which is made available at tion of alarm transmission wiring, communications, signaling, and/or
no charge to all installing dealers. These documents can be found at power. If detectors are not so located, a developing fire may damage
http://www.systemsensor.com/html/applicat.html. the alarm system, crippling its ability to report a fire.
A study by the Federal Emergency Management Agency (an agency Audible warning devices such as bells may not alert people if these
of the United States government) indicated that smoke detectors may devices are located on the other side of closed or partly open doors or
not go off in as many as 35% of all fires. While fire alarm systems are are located on another floor of a building. Any warning device may fail
designed to provide early warning against fire, they do not guarantee to alert people with a disability or those who have recently consumed
warning or protection against fire. A fire alarm system may not provide drugs, alcohol or medication. Please note that:
timely or adequate warning, or simply may not function, for a variety
of reasons: Strobes can, under certain circumstances, cause seizures in people
with conditions such as epilepsy.
Smoke detectors may not sense fire where smoke cannot reach the
Studies have shown that certain people, even when they hear a fire
detectors such as in chimneys, in or behind walls, on roofs, or on the
alarm signal, do not respond or comprehend the meaning of the signal.
other side of closed doors. Smoke detectors also may not sense a fire
It is the property owner's responsibility to conduct fire drills and other
on another level or floor of a building. A second-floor detector, for training exercise to make people aware of fire alarm signals and
example, may not sense a first-floor or basement fire. instruct them on the proper reaction to alarm signals.
Particles of combustion or smoke from a developing fire may not In rare instances, the sounding of a warning device can cause tempo-
reach the sensing chambers of smoke detectors because: rary or permanent hearing loss.
Barriers such as closed or partially closed doors, walls, or chimneys A fire alarm system will not operate without any electrical power. If
may inhibit particle or smoke flow. AC power fails, the system will operate from standby batteries only for
Smoke particles may become cold, stratify, and not reach the ceiling a specified time and only if the batteries have been properly main-
or upper walls where detectors are located. tained and replaced regularly.
Smoke particles may be blown away from detectors by air outlets. Equipment used in the system may not be technically compatible
Smoke particles may be drawn into air returns before reaching the with the control panel. It is essential to use only equipment listed for
detector. service with your control panel.
The amount of smoke present may be insufficient to alarm smoke Telephone lines needed to transmit alarm signals from a premise to a
detectors. Smoke detectors are designed to alarm at various levels of central monitoring station may be out of service or temporarily dis-
smoke density. If such density levels are not created by a developing abled. For added protection against telephone line failure, backup
fire at the location of detectors, the detectors will not go into alarm. radio transmission systems are recommended.
Smoke detectors, even when working properly, have sensing limita- The most common cause of fire alarm malfunction is inadequate
tions. Detectors that have photo-electronic sensing chambers tend to maintenance. To keep the entire fire alarm system in excellent work-
detect smoldering fires better than flaming fires, which have little visi- ing order, ongoing maintenance is required per the manufacturer's
ble smoke. Detectors that have ionizing-type sensing chambers tend recommendations, and UL and NFPA standards. At a minimum, the
to detect fast-flaming fires better than smoldering fires. Because fires requirements of NFPA 72 shall be followed. Environments with large
develop in different ways and are often unpredictable in their growth, amounts of dust, dirt or high air velocity require more frequent mainte-
neither type of detector is necessarily best and a given type of detec- nance. A maintenance agreement should be arranged through the
tor may not provide adequate warning of a fire. local manufacturer's representative. Maintenance should be sched-
uled monthly or as required by National and/or local fire codes and
Smoke detectors cannot be expected to provide adequate warning of should be performed by authorized professional fire alarm installers
fires caused by arson, children playing with matches (especially in only. Adequate written records of all inspections should be kept.

2 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12


Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to Like all solid state electronic devices this system may operate errati-
the fire alarm control panel. Disconnect all sources of power before cally or can be damaged when subjected to lightning-induced tran-
servicing. The control unit and associated equipment may be dam- sients. Although no system is completely immune from lightning
aged by removing and/or inserting cards, modules, or interconnecting transients and interferences, proper grounding will reduce susceptibil-
cables while the unit is energized. Do not attempt to install, service, ity. Overhead or outside aerial wiring is not recommended, due to an
or operate this unit until this manual is read and understood. increased susceptibility to nearby lightning strikes. Consult with the
CAUTION - System Reacceptance Test after Software Changes. To Technical Services if any problems are anticipated or encountered.
ensure proper system operation, this product must be tested in accor- Disconnect AC power and batteries prior to removing or inserting cir-
dance with NFPA 72 after any programming operation or change in cuit boards. Failure to do so can damage circuits.
site-specific software. Reacceptance testing is required after any Remove all electronic assemblies prior to any drilling, filing, reaming,
change, addition or deletion of system components, or after any mod- or punching of the enclosure. When possible, make all cable entries
ification, repair or adjustment to system hardware or wiring. from the sides or rear. Before making modifications, verify that they
All components, circuits, system operations, or software functions will not interfere with battery, transformer, and printed circuit board
known to be affected by a change must be 100% tested. In addition, location.
to ensure that other operations are not inadvertently affected, at least Do not tighten screw terminals more than 9 in-lbs. Over-tightening
10% of initiating devices that are not directly affected by the change, may damage threads, resulting in reduced terminal contact pressure
up to a maximum of 50 devices, must also be tested and proper sys- and difficulty with screw terminal removal.
tem operation verified.
Though designed to last many years, system components can fail at
This system meets NFPA requirements for operation at 0C to 49C any time. This system contains static-sensitive components. Always
(32F to 120F) and at a relative humidity 93% 2% RH (non-con- ground yourself with a proper wrist strap before handling any circuits
densing) at 32C 2C (90F 3F). However, the useful life of the so that static charges are removed from the body. Use static-sup-
system's standby batteries and the electronic components may be pressive packaging to protect electronic assemblies removed from
adversely affected by extreme temperature ranges and humidity. the unit.
Therefore, it is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15- Follow the instructions in the installation, operating, and program-
27 C/60-80 F. ming manuals. These instructions must be followed to avoid damage
to the control panel and associated equipment. FACP operation and
Verify that wire sizes are adequate for all initiating and indicating reliability depend upon proper installation by authorized personnel.
device loops. Most devices cannot tolerate more than a 10% I.R.
drop from the specified device voltage.

FCC Warning
WARNING: This equipment generates, uses, and can radi- Canadian Requirements: This digital apparatus does not
ate radio frequency energy and if not installed and used in exceed the Class A limits for radiation noise emissions
accordance with the instruction manual, may cause inter- from digital apparatus set out in the Radio Interference
ference to radio communications. It has been tested and Regulations of the Canadian Department of Communica-
found to comply with the limits for class A computing tions. This Class A digital apparatus complies with Cana-
device pursuant to Subpart B of Part 15 of FCC Rules, dian ICES-003.
which is designed to provide reasonable protection against Le present appareil numerique n'emet pas de bruits radio-
such interference when operated in a commercial environ- electriques depassant les limites applicables aux appareils
ment. Operation of this equipment in a residential area is numeriques de la classe A prescrites dans le Reglement
likely to cause interference, in which case the user will be sur le brouillage radioelectrique edicte par le ministere des
required to correct the interference at his own expense. Communications du Canada. Cet appareil numerique de la
classe A est conforme a la norme NMB-003 du Canada.

HARSH, NIS and NOTIFIRENET are all trademarks; and Acclimate Plus, FlashScan, NOTIFIER, ONYX, ONYXWorks, VeriFire and VIEW are all registered
trademarks of Honeywell International, Inc. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are registered trademarks of the
Microsoft Corporation.
2012 by Honeywell International, Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3


Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions
about our online Help or manuals, please e-mail us at FireSystems.TechPubs@honeywell.com.
On-Line Help Please include the following information:
Product name and version number (if applicable)
Topic title
The content you think should be corrected/improved
Detailed suggestions for correction/improvement
Documents Please include the following information:
Document part number and title
Page number and paragraph
The content you think should be corrected/improved
Detailed suggestions for correction/improvement
Please Note: If you have any technical issues, please contact Technical Services.

Manual Usage
This manual is written with the understanding that the user has been trained in the proper operations and services for
this product. The information provided in this manual is intended to assist the user by describing the configurations
and how they affect operations.

4 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12


Table of Contents

Table of Contents
Section 1 Product Overview .................................................................................................... 3
1.1: Product Description .......................................................................................................................................3
1.2: Features..........................................................................................................................................................3
1.3: Compatibility .................................................................................................................................................4
1.4: System Architecture.......................................................................................................................................4
Figure 1.1 Network Architecture............................................................................................................5
1.5: IP Port Requirements .....................................................................................................................................6
1.6: Installation Overview.....................................................................................................................................6
1.6.1: Required Equipment ............................................................................................................................6
1.6.2: Power Supply and Communication Connections ................................................................................7
1.6.3: Board Layout .......................................................................................................................................7
Figure 1.2 VESDA-HLI-GW Board.......................................................................................................7
Table 1.1 LED Definitions .....................................................................................................................8
Section 2 Configuration ........................................................................................................... 9
2.1: Configuration Web Page ................................................................................................................................9
2.2: Connecting the Configuration Computer.......................................................................................................9
2.3: Configuring the VESDA-HLI-GW................................................................................................................9
2.3.1: Logging into the Web Page .................................................................................................................9
2.3.2: VESDA-HLI-GW Configuration Menus...........................................................................................10
2.3.3: VESDA-HLI-GW Configuration Settings.........................................................................................10
2.3.4: Zone Mapping and Control by Event ................................................................................................12
Table 2.1 Zone Setting/Alarm State Relationships ..............................................................................12
2.3.5: Error Log ...........................................................................................................................................13
Table 2.2 Error Log Message Definition..............................................................................................13
Appendix A: IP Settings ......................................................................................................... 15
A.1: Viewing Existing Settings...........................................................................................................................15
A.2: Resetting Factory Default Settings .............................................................................................................15
Appendix B: Viewing Gateway Configuration...................................................................... 17
B.1: Required Equipment ...................................................................................................................................17
B.2: Viewing the Configuration..........................................................................................................................17

VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 1


Table of Contents

2 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12


Section 1 Product Overview

1.1 Product Description


The VESDA-HLI-GW provides a communication link between the NFN network and the VESDAnet. This
link enables event notification and control of devices on the VESDAnet through the NFN network. Event
notifications are displayed on the fire network annunciators. Control can be initiated from these
annunciators.

1.2 Features
Monitor (NCA-2, LCD-160, ONYXWorks) - Highest Priority event is shown on annunciators.
Prealarm
Fire Alarms
Point Disable
Troubles:
Detector Fault
Scanner Fault
Power Fault
Low Flow
High Flow
Filter Fault
Field Wiring Fault
Auto learn Failure
No Answer.

NOTE: The trouble categorizations are generic and each encompasses several troubles.
Further information can be obtained by referring to XTralis resources.

Supervision Troubles:
Modbus Communications Fault (Indicates that VESDA-HLI-GW can not talk to VESDA
devices.)
VESDA Trouble
Read Status:
Device Type
Alarm State - Alert/Action/Fire1/Fiew2/Trouble/Isolated
Smoke Level - This is a percentage of obscuration from 0% to 3.1% as defined by VESDA
Detector Alarm Thresholds
Control (From NCA-2 and ONYXWorks):
Reset - Resets all detectors on the VESDAnet
Isolate/Enable - Isolates (Disables) and enables single detector on the VESDAnet
Silence - Silences all local piezos on detectors
Acknowledge

VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3


Product Overview Compatibility

Other:
Zone Mapping
DCC mode is supported for Canadian applications
Walk test is not supported by the VESDA gateway
History - Rolling history is maintained on the gateway
Alarms and Prealarms are latched by the VESDA detectors. Reset is required to unlatch.

1.3 Compatibility
Refer to the LS10026-051NF-E VESDA-HLI-GW Listing Document for supported panels and annunciators.
Microsoft Internet Explorer version 8 or later with the latest version of JAVA is required to configure the
VESDA-HLI-GW.

1.4 System Architecture


The VESDA-HLI-GW:
Uses a Modbus RS-232 interface to VHX-1420-HFS
Supervises the communications to the VHX-1420-HFS
Monitors 100 detectors
Displays VESDA devices as type Aspiration on the display nodes.
Multiple events per point are not supported. The detector will be in one of the following states:
All Systems Normal
Prealarm
Fire alarm
The following events can be simultaneous with the above events:
Disabled
Trouble
Supported VESDA Detectors:
VESDA Laserplus (VLP)
VESDA Laserfocus (VLF)
VESDA Laserscanner (VLS)
VESDA Lasercompact (VLC)

4 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12


System Architecture Product Overview

RS-485
VESDA VLP VESDA VLF

VESDAnet

VESDA VLC VESDA VLS

VHX-1420-HFS

RS-232

VESDA-HLI-GW

HS-NCM
OR
NCM

NFN Network

Workstation Embedded Display Node


Gateway

FACP FACP FACP

Figure 1.1 Network Architecture

VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 5


Product Overview IP Port Requirements

1.5 IP Port Requirements


The following IP ports must be available to the VESDA-HLI-GW:

Port Type

80 TCP

4016 TCP

62957 TCP

The following restrictions apply:

Functionality Restriction

Infrastructure Must have a Static IP Address, DHCP is not supported.


Web Access does not support access through an HTTP Proxy server, because
port 62957 is not accessible

1.6 Installation Overview


CAUTION: Multiple VESDA-HLI-GW Installations
! All VESDA-HLI-GWs must be installed and configured one at a time because all VESDA-HLI-GWs
use the same predefined IP address and node number.

Install the VESDA-HLI-GW as described in the VESDA-HLI-GW Listing Document (LS10023-051NF-E).

1.6.1 Required Equipment


VESDA-HLI-GW Assembly:
The following components are shipped with the VESDA-HLI-GW:
VESDA-HLI-GW printed circuit board
NUP-to-NUP Cable (P/N 75556) - Used to connect the VESDA-HLI-GW board to a standard NCM
and supported panel
USB Cable (P/N 75665) - Used to connect the VESDA-HLI-GW board an HS-NCM board:.
Wire Leads to NUP Network Communications Module power cable (P/N 75583)
Network Components:
RJ45 to RJ45 standard Ethernet network cable - Customers internet or intranet connection
NFN Network, version 5.0 or later
Cables - P/N 50110140-001 Serial cable between the HS-NCM and the VHS-1420-HFS
High-Speed Network Communication Module:

HS-NCM-W HS-NCM-MF
HS-NCM-WMF HS-NCM-SF
HS-NCM-WSF HS-NCM-MFSF

Standard Network Communication Module

NCM-W
NCM-F

Customer-Supplied Equipment:
A computer to run Internet Explorer and configure the VESDA Gateway

6 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12


Installation Overview Product Overview

VESDA Required Equipment (not including power supplies)


VHS-1420-HFS

1.6.2 Power Supply and Communication Connections


The VESDA-HLI-GW must be correctly connected to a power source meeting applicable requirements and
other equipment in the system in order to function properly. For detailed connection information, refer to the
VESDA-HLI-GW Listing Document (LS10023-051NF-E).

1.6.3 Board Layout


USB A Host (J13) USB B Device (J14)

D19
D33

D20
D15 D45

D9
D14

LED
(See Table 1.1) Ethernet Connector
(J8)

D12

D10
NUP A Serial Data
Connector (J6)
D13

D11 NUP B Serial Data


Mounting Hole Connector (J7)
(1 of 12)

Trouble Relay
(TB6)

TB1:
-24 V Out
+24 V Out
-24 V In
+24 V In

D7
D25
D8

D18

Figure 1.2 VESDA-HLI-GW Board

VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 7


Product Overview Installation Overview

Table 1.1 LED Definitions

Reference
Label Description
Designator

D7 WDT Active/Lit indicates the system has undergone a reset due to a Watchdog
circuit firing.

D8 PWR FAIL TBD

D9 ACTIVE Active/Lit indicates that WinCE is running.

D10 NUPA RX Toggles on when data is received at the NUP A port.

D11 NUPB RX Toggles on when data is received at the NUP B port.

D12 NUPA TX Toggles on when data is sent on the NUP A port.

D13 NUPB TX Toggles on when data is sent on the NUP B port

D14 NFN A TBD


D15 NFN B TBD

D18 PROGRAM Not Used

D19 USB A Active/Lit indicates a device is connected to the USB A port.

D20 USB B Active/Lit indicates a device is connected to the USB B port.

D33 LINK Active/Lit indicates an Ethernet connection.

D45 DATA Blinks to indicate data transmission to or from the Ethernet port.

8 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12


Section 2 Configuration

2.1 Configuration Web Page


The VESDA-HLI-GW is configured through a dedicated web page running on the embedded gateway itself.
Microsoft Internet Explorer version 8 or later with the latest version of JAVA is required to configure the
VESDA-HLI-GW.

2.2 Connecting the Configuration Computer


The computer used to configure the VESDA-HLI-GW must be able to establish an IP connection to the
VESDA-HLI-GW. The default IP address of the VESDA-HLI-GW is 192.168.1.2. Consult your network
administrator if unsure how to make this connection.
Refer to Appendix A, IP Settings for instructions on resetting and reviewing the IP settings for the
VESDA-HLI-GW.

2.3 Configuring the VESDA-HLI-GW


2.3.1 Logging into the Web Page
1. Start Microsoft Internet Explorer.
2. Navigate to the IP address of the VESDA-HLI-GW (default is http://192.168.1.2).
3. Depending on the version of Java installed on the configuration computer, a security prompt may
appear. If it does, click NO to proceed to the configuration web page.
4. If prompted, click Run to enable the applet.
5. When the login dialog box displays, enter the password (default is eight zero characters) and then
click Login.

VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 9


Configuration Configuring the VESDA-HLI-GW

2.3.2 VESDA-HLI-GW Configuration Menus


Menu Sub-Menu Description

File Reboot Displays a dialog box allowing the user to reboot the VESDA-HLI-GW.

Tools History Displays an events log with date, time, type of event, and description.

Set Gateway Displays a dialog box allowing the user to change the current password.
Password Default: 00000000 (eight zeros)

Passwords are case sensitive.


Alpha and numeric characters are supported.
One character minimum and 8 characters maximum.

Backup... Browse to the folder where you would like to store current VESDA-HLI-GW
configuration settings, and then click Save.

Restore... Displays a dialog box allowing that allows the user to restore the VESDA-
HLI-GW configuration settings to a previously saved state.

Delete Objects Displays a dialog box allowing the user to choose to delete the objects
Database database and reboot.

Upgrade Firmware In the Look In drop down menu, select the file name that begins,
#VGNUW and has the extension .AR. Then click Open. An on-screen
dialog indicates a successful upgrade.

Language Displays a dialog box from which the user can navigate to and select the
desired language file.

2.3.3 VESDA-HLI-GW Configuration Settings


Navigation Property/
Sub-Item Description
Pane Item Node

VESDA Type Displays the gateway type by name.


Gateway
(read only)

Version Displays the gateway version number.

Board Type Displays the hardware model type.

Kernel Version Displays additional software version information.

Boot Version Displays additional software version information.

Current Time/ Displays the current date/time information.


Date

Additional IP Address IP Address Click the value to change the IP address.


Properties Settings (Default is 192.168.1.2)
Refer to Appendix A:, "IP Settings" for additional information.

Subnet Mask Click the value to change the subnet address.


(Default is 255.255.255.0)

IP Gateway Click the value and enter the IP address of the IP Gateway for the host
network.
(Default is 0.0.0.0)
MAC Address This is the Media Access Control (MAC) address of the gateway
Ethernet port and is not configurable.
NFN Settings Node Click value to assign the NFN node number of the VESDA-HLI-GW.
(Default is 0)

10 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 : 6/26/12


Configuring the VESDA-HLI-GW Configuration

Navigation Property/
Sub-Item Description
Pane Item Node

Additional NFN Settings Panel Label Click value to enter panel label.
Properties (Contd) (Default is Vesda Gateway)
(Contd)

DCC Enable Check the box for DCC (Display and Control Center) participation. This
network function ensures that one location at a time is in command of
the Acknowledge, System Reset, Signal Silence, and Drill functions.
Channel A Select High for a high-noise NFN network.
Threshold Set to Low for a low-noise NFN network.

Channel B Select High for a high-noise NFN network.


Threshold Set to Low for a low-noise NFN network.

Style 7 Check the box for a Style 7 SLC (Signaling Line Circuit) configured
NFN network.
Uncheck the box for a Style 4 SLC configured NFN network.

NFN Connection Displays Serial when the VESDA-HLI-GW connects to an NCM


Information Port through the serial port or if there is no NFN connection.
(Read Only) Displays USB when the VESDA-HLI-GW connects to an HS-NCM
via USB.
Connection Describes how the gateway is connected to the NFN.
Type
NCM Version Displays the NCM version number.

Note: NCM Version does not appear when there is no NFN connection.

NCM Status Displays the NCM status, which can be: Piezo, UPS Failure, Network
Bits Fail Port A, Network Fail Port B, High Speed Audio, NCM Sniffer Mode
Active, Local Connection Limit Exceeded, or None.

Note: NCM Status Bits does not appear if when there is no NFN
connection.
Fire Network Always displays Accept Time since VESDA-HLI-GW accepts the time
Time Policy from the network, but does not broadcast time to the network.
Mapping Check the box next to each detector with which the gateway will
communicate. Once mapped, the gateway is able to access detector
information.
Zone Label Double-click to display a list of zone labels.
Configuration Click on the zone to display its property screen.
Label Click on the value to change the zone label.
Click Save to save the change.
Monitored Label Click the value to enter the label for the detector.
Zone List

Extended Read only.


Label

Zone Displays a list of the ten general zones supported by the gateway and
Configuration their settings.

Click on the zone number or <Enter Zone> label to enter/change the


zone to be monitored.
Click the value and select the Cooperative Control By Event (CCBE)
level from the drop-down menu.
Click Save to save the changes.

Refer to 2.3.4, "Zone Mapping and Control by Event" for details.

Error Log Label text is red when there is an error. Click to display date, time, and
error description information. Refer to 2.3.5, "Error Log" for details.

VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 11


Configuration Configuring the VESDA-HLI-GW

2.3.4 Zone Mapping and Control by Event


The VESDA-HLI-GW can be configured for 10 general zones per VESDA device. Zones 0 to 999 are
supported with Zone 0 being a general alarm zone that is active if any detectors are in the FIRE1 or FIRE2
state. The zones have the following characteristics:
All Zones activated by the gateway remain active until there is a reset issued from the NFN. At that
time, all the zones related to detectors being reset are cleared.
A zone remains active as long as any detectors assigned to that zone are active.
A zone goes into trouble state when any of its detectors become disabled or in trouble. The zone
remains in a troubled state until all of its detectors are enabled and not in trouble.
When the detector is disabled, zones can go off (if the point goes off), but cannot go on (if the point
goes on). Note that enabling a point may also result in zones going active, if the point went active
while it was disabled.
Disabling of zones is not supported by the VESDA-HLI-GW. Zone disables are ignored. Points must
be disabled individually.
Force On/Off of zones is not supported.
Read Status of zones is supported.
The Table 2.1, Zone Setting/Alarm State Relationships describes when zones are activated for each zone
setting for each alarm state. An X indicates that the zone will be activated.
There are two labels, the 20-byte standard label and the 12-byte custom label. The Network Control
Annunciator (NCA) displays them along with the events. There are 10 slots for Cooperative Control By
Event (CCBE) per detector. Each slot can be set to one of the zones 1-999. In the Value column of the slot
there is a selection for what type of event will cause the one to go active. The possible types of events are
Alert, Action, Fire1, Fire2 and Any. Zones are cumulative in the given order. For example, an Action event
triggers the Action and Alert zones. A Fire1 event triggers the Fire1, Action and Alert zones. A Fire 2
event triggers all zones.
Table 2.1 Zone Setting/Alarm State Relationships

Alarm State

Alert Action Fire1 Fire2

Alert X X X X
Zone State Setting

Action X X X

Fire1 X X

Fire2 X

Any X X X X

12 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 : 6/26/12


Configuring the VESDA-HLI-GW Configuration

2.3.5 Error Log


The error log displays specific information when the VESDA-HLI-GW detects a trouble condition. When a
trouble condition is present, the output relay also de-energizes. The following table defines the possible
errors displayed in the log:
Table 2.2 Error Log Message Definition

Error Description

VESDA Trouble The VESDAnet has encountered a condition such as a break or


open condition. A VSC from Xtralis is necessary to interpret the
error code.

Connection Not Supported Device has an invalid wiring configuration on the NUP port, for
example, trying to attach an HSNCM with a serial cable.

Modbus Communication Fault Cannot communicate with HLI. For example, HLI is unplugged.

Missing Detector # Indicates a detector programmed into the system is offline (for
example # is a numeric value which is the detector number).

VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 13


Configuration Configuring the VESDA-HLI-GW

14 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 : 6/26/12


Viewing Existing Settings IP Settings

Appendix A: IP Settings
NOTE: The procedures in this appendix require the use of a USB flash memory drive.

A.1 Viewing Existing Settings


1. Connect the flash drive to the VESDA-HLI-GW.
2. Reboot the gateway.
A file is created that matches the configured IP address of the gateway, followed by the extension .txt
(e.g., 192.168.1.2.txt). If the file already exists on the drive, it will be altered to match the Gateway
configuration. The file contains additional information such as the MAC address of the gateway.
3. Connect the drive to a PC and view the files.
The flash drive should contain a file that matches the configured IP address of the gateway, followed by
the extension .txt (e.g., 192.168.1.2.txt). If the file already exists on the drive, it has been altered to
match the gateway configuration. The file contains additional information such as the MAC address of
the gateway.

A.2 Resetting Factory Default Settings


1. Connect the flash drive to a PC and create a file named default.ldc. The contents of the file is not
significant; however, ensure that the file does not have an additional hidden file extension. This file will
be automatically deleted from the flash drive.
2. Eject the flash drive from the PC.
3. Disconnect power from the gateway.
4. Disconnect the communication cable to the Gateway USB port (if present) and connect the flash drive.
5. Reconnect the 24 VDC power supply to the gateway.
6. After approximately one minute, disconnect the flash drive from the USB port and (if necessary)
reconnect the cable removed in Step 4.
7. Connect the flash drive to the PC and verify that the file named 192.168.12.txt is on the drive.
If the file is on the flash drive, the reset has been accomplished.
If the file is not on the flash drive
The flash drive may not have been connected during the reboot period or was removed early.
The flash drive is not seen as a valid drive by the hardware.
A software error has occurred and technical support may need to be contacted.

VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 15


IP Settings Resetting Factory Default Settings

16 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12


Required Equipment Viewing Gateway Configuration

Appendix B: Viewing Gateway Configuration

B.1 Required Equipment


VESDA-HLI-GW
USB flash memory drive
PC

B.2 Viewing the Configuration


1. Connect the flash drive to the VESDA-HLI-GW.
2. Reboot the Gateway.
A file is created that matches the configured IP address of the gateway, followed by the
extension .txt (e.g., 192.168.1.2.txt). If the file already exists on the drive, it will be altered
to match the Gateway configuration. The file contains additional information such as the MAC
address of the Gateway.
3. Connect the drive to a PC and view the files.
The flash drive should contain a file that matches the configured IP address of the gateway,
followed by the extension .txt (e.g., 192.168.1.2.txt). If the file already exists on the drive, it
has been altered to match the Gateway configuration. The file contains additional information
such as the MAC address of the Gateway.

VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev: A2 6/26/12 17


Viewing Gateway Configuration Viewing the Configuration

18 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev: A2 6/26/12


Limited Warranty
Honeywell International Inc. warrants products manufactured by
it to be free from defects in materials and workmanship for
eighteen (18) months from the date of manufacture, under normal
use and service. Products are date stamped at time of
manufacture. The sole and exclusive obligation of Honeywell
International Inc. is to repair or replace, at its option, free of charge
for parts and labor, any part that is defective in materials or
workmanship under normal use and service. All returns for credit
are subject to inspection and testing at the factory before actual
determination is made to allow credit. Honeywell International
Inc. does not warrant products not manufactured by it, but assigns
to the purchaser any warranty extended by the manufacturer of
such products. This warranty is void if the product is altered or
repaired by anyone other than Honeywell International Inc. or as
expressly authorized by Honeywell International Inc. in writing, or
is serviced by anyone other than Honeywell International Inc. or
its authorized distributors. This warranty is also void if there is a
failure to maintain the products and systems in which they operate
in a proper and workable manner. In case of defect, secure a
Return Material Authorization form from our Return Authorization
Department.
This writing constitutes the only warranty made by Honeywell
International Inc., with respect to its products. Honeywell
International Inc., does not represent that its products will prevent
any loss by fire or otherwise, or that its products will in all cases
provide the protection for which they are installed or intended.
Buyer acknowledges that Honeywell International Inc., is not an
insurer and assumes no risk for loss or damages or the cost of any
inconvenience, transportation damage, misuse, abuse, accident or
similar incident.
HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY,
EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR
ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH
EXTENDS BEYOND THE DESCRIPTION ON THE FACE
HEREOF. UNDER NO CIRCUMSTANCES SHALL HONEYWELL
INTERNATIONAL INC. BE LIABLE FOR ANY LOSS OF OR
DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR
CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR
INABILITY TO USE HONEYWELL INTERNATIONAL INC.S
PRODUCTS. FURTHERMORE, HONEYWELL INTERNATIONAL
INC. SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR
DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A
RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE
OF ITS PRODUCTS.

BACNET-GW-3 Operation and Programming Manual - P/N: LS10014-000NF-E: Rev. A2 6/26/12 25


World Headquarters
12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
fax 203-484-7118

www.notifier.com

Вам также может понравиться