Вы находитесь на странице: 1из 6

(CN) Cable

Quick Splice II
5451 and 5452 (JCN) Cable Accessory Splice Jacket

25 kV Molded Rubber Inline Splicing Kits


Data Sheet
1. Product Description 2. Applications
The 3M Quick Splice II 5451 and 5452 are 25 kV class To splice 25 kV class distribution cables:
inline splices designed for joining concentric neutral (CN)
For inline splicing
and jacketed concentric neutral (JCN) distribution class
power cables. Each splice is a one-piece molded design For concentric neutral (CN) cables
made of specially formulated, peroxide cured EPDM For jacketed concentric neutral (JCN) cables, when used
rubbers. Each splice is production tested on CN cable to with an accessory splice jacket (e.g., 3M SJ2A or
ensure reliability. The splice is designed for use with HSJ2 Jacket Kit)
special CIseries Inline Compression Connectors, for 3M 5451 for insulation diameter sizes of 0.83 to 1.04
connecting either aluminum or copper conductors. The (21,1 to 26,4 mm)
Quick Splice II 5451 and 5452 splices meet the 25 kV
3M 5452 for insulation diameter sizes of 1.00 to 1.15
voltage rating requirements of ANSI/IEEE Std. 4041986.
(25,4 to 29,2 mm)
Kit Contents: For use with 3M CIA and CI840 Series Connectors
1 Molded Rubber Splice Body (Al/Cu) for conductor sizes 2 1/0 AWG (35 50 mm2)
1 Porta-Pencil For use with 3M CI Series Connectors (Al/Cu) for
conductor sizes 2/0 4/0 AWG (70 95 mm2)
2 Packets of Silicone Grease
For direct burial installations
1 Template
For aerial installations
1 Instruction Sheet
For submerged locations
Splice Features:
One-piece design, for simple installation 3. Data: Physical and Electrical
Production tested, partial discharge and alternating current Properties
withstand, for long term reliability The 3M 5451 and 5452 Quick Splice II kits can be used on
Peroxide cured EPDM rubber construction, for long term distribution class cables with a rated operating temperature
elastic memory (sealing) and easy installation of 90C, and an emergency overload rating of 130C.
Computer designed, for compact size and optimal Splices made with these kits are rated for 25 kV and meet
distribution of the electrical field the 25 kV rating requirements of ANSI/IEEE Std.
4041986, IEEE Standard for Cable Joints for Use with
Direct contact between insulation shields, for complete
shield continuity between splice and cables Extruded Dielectric Cable Rated 5000 V through 46,000
V. The current rating of the splice meets or exceeds the
Visual reference of splice positioning, for accurate current rating for the cables on which it is installed. BIL
inspection of installation rating of splice is 200 kV.
Special 3M CI Series connectors are used with the splice.
They are crimped with a standard 5/8 die or 840 die,
depending upon the connector. The connectors meet the
requirements of ANSI C119.41986, Connectors for Use
Between Aluminum or Aluminum-Copper Overhead
Conductors.
A. Selection Table
5451 SPLICE AND CONNECTOR SELECTION TABLE
       
      

Kit Cable Insulation Conductor Size Cable Insulation 3M Connector Number *


Number (O.D. Range) (AWG) Thickness (mils)
280
2 Solid 295 CI22A or CI22840

260
2 Stranded 280 CI1A or CI2A or
295 CI21840

260
1 Solid 280 CI1A or CI2A or
295 CI21840

0.83 1.04 in. 260


5451 (21,1 26,4 mm) 280
1 Stranded CI1A or CI21840
295
260
1/0 Solid 280 CI1A or CI21840
295
260
1/0 Stranded 280 CI1/0A or CI1/0840
295
2/0 Stranded 260 CI2/0

Table 1

5451 SPLICE KIT(WITH CONNECTOR INCLUDED) SELECTION TABLE


       
      

Kit Number Cable Insulation Conductor Size Cable Insulation Thickness


(With Connector) * (O.D. Range) (AWG) (mils)
0.83 1.04 in. 280
5451CI22840 (21,1 26,4 mm) 2 Solid 295
0.83 1.04 in. 280
5451CI22A (21,1 26,4 mm) 2 Solid 295
260
5451CI2A 0.83 1.04 in. 2 Stranded 280
(21,1 26,4 mm) 1 Solid 295
260
5451CI21840 0.83 1.04 in. 2 or 1 Stranded 280
(21,1 26,4 mm) 1 or 1/0 Solid 295
260
5451CI1A 0.83 1.04 in. 2 or 1 Stranded 280
(21,1 26,4 mm) 1 or 1/0 Solid 295
260
5451CI1/0A 0.83 1.04 in. 1/0 Stranded 280
(21,1 26,4 mm) 295
260
5451CI1/0840 0.83 1.04 in. 1/0 Stranded 280
(21,1 26,4 mm) 295
0.83 1.04 in.
5451CI2/0 (21,1 26,4 mm) 2/0 Stranded 260

*Note: CI-A Series Connectors are sized for 5/8 crimping die;
CI-2/0 and CI-840 Series Connectors are sized for 840 crimping die.
Table 2

2
5452 SPLICE AND CONNECTOR SELECTION TABLE
       
      
Kit Cable Insulation Conductor Size Cable Insulation 3M Connector Number *
Number (O.D. Range) (AWG) Thickness (mils)
280
2/0 Stranded 295 CI2/0

1.00 1.15 in. 260


5452 (25,4 29,2 mm) 3/0 Stranded 280 CI3/0
295
260
4/0 Stranded 280 CI4/0

Table 3

5452 SPLICE KIT(WITH CONNECTOR INCLUDED) SELECTION TABLE


       
      
Kit Number Cable Insulation Conductor Size Cable Insulation Thickness
(With Connector) * (O.D. Range) (AWG) (mils)
1.00 1.15 in. 280
5452CI2/0 (25,4 29,2 mm) 2/0 Stranded 295
260
5452CI3/0 1.00 1.15 in. 3/0 Stranded 280
(25,4 29,2 mm) 295
1.00 1.15 in. 260
5452CI4/0 (25,4 29,2 mm) 4/0 Stranded 280

*Note: CI-2/0, CI3/0 and CI4/0 Connectors are sized for 840 crimping die.
Table 4

B. Typical Dimensions

C B

Dimension
Kit Number
A B C
14.4 in. 2.47 in. 0.76 in.
5451 (366 mm) (63 mm) (19 mm)
15.4 in. 2.63 in. 0.88 in.
5452 (391 mm) (67 mm) (22 mm)

Table 5

3
C. Typical Physical and Electrical Properties

Insulating EPDM Rubber D Ultimate Tensile Strength 1700 psi min.


ASTM D 412 (11.7 MPa min.)
Physical Properties
D Shore A Hardness 70
Test Method Typical Value* ASTM D 2240
D Color White D Die C Tear 225 lbs/in min.
D Ultimate Elongation 570% min. ASTM D 624 (39.4 KN/m min.)
ASTM D 412 D Permanent Set 20% max.
D Ultimate Tensile Strength 900 psi min. (3M Test Method TM 86A)
ASTM D 412 (6.21 MPa min.)
D 100% Modulus 400 psi
D Shore A Hardness 55 ASTM D 412 (2.8 MPa)
ASTM D 2240
D 300% Modulus 1800 psi
D Permanent Set 25% ASTM D 412 (12.4 MPa)
(3M Test Method: 100% strain
with 5 min. recovery) D Ozone Resistance No Cracking
(70 hrs., 150 ppm @ 20% strain)
D Compression Set 19%
ASTM D 395, Method B D UV Resistance No Cracking
D 100% Modulus 185 psi (70 hrs. @ 20% strain)
ASTM D 412 (1.28 MPa)
Electrical Properties
D 300% Modulus 650 psi
ASTM D 412 (4.49 MPa) Test Method Typical Value*
Electrical Properties D Volume Resistivity 15.4 Ohminch max.
(3M Test Method TM 80) (40 Ohmcm max.)
Test Method Typical Value*
* This data is not to be used for specification. Values
D Dielectric Constant listed are for typical properties and should not be
ASTM D 150 considered minimum or maximum.
73_F (23_C) 2.71
194_F (90_C) 2.58
266_F (130_C) 2.56 4. Specification
D Dissipation Factor
ASTM D 150 Product
73_F (23_C) 0.4% (Open Specification)
194_F (90_C) 1.3%
The concentric neutral (CN) and jacketed concentric
266_F (130_C) 4.7%
neutral (JCN) cable splice must meet the requirements of
D Dielectric Strength ANSI/ IEEE Std. 4041986 for a 25 kV rating, and must be
ASTM D 149 rated by the manufacturer for use on 25 kV distribution
25 mil thick slab 1177 Volts/mil systems. It must be rated for continuous operation at 90_C,
(46.4 MV/m) with an emergency overload temperature rating of 130_C.
100 mil thick slab 518 Volts/mil The splice shall be a one-piece, slip-on design made of
(20.4 MV/m) molded peroxide cured EPDM rubber. It shall be rated for
D 20 Days @ 96% RH and indoor, outdoor and direct burial applications.
194_F (90_C) Engineering/Architectural
25 mil thick slab 1066 Volts/mil
(42.0 MV/m) (Closed Specification)
100 mil thick slab 790 Volts/mil Splicing of all 2 2/0 AWG 25 kV rated concentric neutral
(31.1 MV/m) (CN) and jacketed concentric neutral (JCN) cables shall be
performed in accordance with the instructions provided
with the 3M 5451 Quick Splice II Molded Rubber Splicing
Splice Jacket Semi-Conductive Rubber Kit. Splicing of all 3/0 4/0 AWG 25 kV rated concentric
Physical Properties neutral (CN) and jacketed concentric neutral (JCN) cables
shall be performed in accordance with the instructions
Test Method Typical Value* provided with the 3M 5452 Quick Splice II Molded Rubber
Splicing Kit. For JCN applications, the splice shall be
D Color Black
sealed with an additional jacket installed in accordance
D Ultimate Elongation 300% min. with the instructions provided with the 3M SJ2A Cold
ASTM D 412 Shrink Jacket Kit.

4
5. Performance Tests
IEEE Std. 4041986
25 kV Voltage Rating
Design Test and Sequence Test Requirements
Minimum Partial Discharge (Corona) Level (kVrms @ <3 pC) 21.6
Alternating-Current 1 Minute Withstand (kVrms) 52
Direct -Current 15 Minute Withstand (kVdc) 100
Impulse Withstand (BIL) at 68F (20C) (kVcrest) 150
Impulse Withstand (BIL) at 266F (130C) (kVcrest) 150
Minimum Partial Discharge (Corona) Level (kVrms @ <3 pC) 21.6
Cyclic Aging (kVrms) 43
High Voltage Time
5 Hour Alternating-Current Withstand (kVrms) 52
1 Hour Alternating-Current Withstand (kVrms) 78
Short-Time Current (sec.)
(ICEA P32382 and ANSI/IEEE C37.091979) 0.17

Alternating-Current 1 Minute Withstand (kVrms) 52


Shielding IEEE Std. 5921990
ANSI/NEMA CC31978
Connector Thermal and Mechanical and ANSI C119.41986

Production Test Test Requirements


Production Units Tested (%) 100
Minimum Partial Discharge (Corona) Level (kVrms @ <3 pC) 21.6
Alternating-Current 1 Minute Withstand (kV-rms) 52

Table 6

6. Installation Techniques f. Slide splice into final position over connector, centering
it between the ends of the cable semi-cons.
Detailed Instructions for installing the Quick Splice II are
included with each kit. The following is a brief summary of
the installation steps required for the 5451 and 5452
splicing kits: CABLE X CABLE Y

a. Prepare cables using standard procedures. g. Connect neutral wire, attaching one wire from each
b. Lubricate cable insulation and semi-con jacket of cable to the splice grounding eyes.
CABLE X with silicone grease provided.
c. Slide splice onto CABLE X until Porta-Pencil is
exposed. CABLE X CABLE Y

d. Install CIConnector.
h. JCN Cables Only: Install accessory splice jacket over
splice and exposed neutral wires.

CABLE X CABLE Y

Accessory Splice Jacket


e. Lubricate connector and cable insulation of CABLE Y
CABLE X CABLE Y
with silicone grease provided.
5
7. Maintenance 8. Availability
Components of the 3M 5451 and 5452 Quick Splice II Kits 3M 5451 and 5452 Quick Splice II Kits are available to
are stable under normal storage conditions. Normal stock splice 25 kV CN and JCN distribution class cables. They
rotation procedures are recommended. The splice can be are available in kits with the CIConnector included. It is
field tested using normal field cable testing procedures also available as a kit without a connector, where the
(reference: ANSI/IEEE Std. 400, Guide for Making CI-Connector must be ordered separately. These kits are
High-Direct-Voltage Tests on Power Cable Systems in the available from your local authorized 3M electrical
Field). distributor.

Important Notice to Purchaser:


All statements, technical information and recommendations related lieu of all warranties expressed or implied, including but not
to the Seller's products are based on information believed to be limited to the implied warranties of merchantability and fitness for
reliable, but the accuracy or completeness thereof is not a particular purpose which warranties are hereby expressly
guaranteed. Before utilizing the product, the user should disclaimed.
determine the suitability of the product for its intended use. The
SELLER SHALL NOT BE LIABLE TO THE USER OR ANY OTHER
user assumes all risks and liability whatsoever in connection with
PERSON UNDER ANY LEGAL THEORY, INCLUDING BUT NOT
such use.
LIMITED TO NEGLIGENCE OR STRICT LIABILITY, FOR ANY
Any statements or recommendations of the Seller which are not INJURY OR FOR ANY DIRECT OR CONSEQUENTIAL DAMAGES
contained in the Seller's current publications shall have no force or SUSTAINED OR INCURRED BY REASON OF THE USE OF ANY
effect unless contained in an agreement signed by an authorized OF THE SELLER'S PRODUCTS.
officer of the Seller. The statements contained herein are made in

Electrical Products Division


Recycled paper Litho in USA
6801 River Place Blvd. 40% pre-consumer 1995 3M
Austin, TX 78726-9000 10% post-consumer 806108-5075-4