1MRK 580 136-BEN
Page 1
Revision: -
Issued: November 2002
Data subject to change without notice

)HDWXUHV Enabled through a binary input (circuit Caters for both manual closing and auto-
breaker close order) or automatically on matic reclosing of the circuit breaker
dead line detection
Protection function(s) released on pickup
Resets automatically after a fixed time for direct tripping during the activated time
delay following successful closure of the are selectable
circuit breaker
Caters for the complete line section

$SSOLFDWLRQ The main purpose of the SOTF switch-on-to- Generally, directional or non-directional
fault function is to provide high-speed trip- overreaching distance protection zones are
ping when energizing a power line on to a used as the protection functions to be released
short-circuit fault on the line. for direct tripping during the activated time.
When line-side potential transformers are
Automatic initiating of the SOTF function used, the use of non-directional distance
using dead line detection can only be used zones secures switch-on-to-fault tripping for
when the potential transformer is situated on fault situations there directional information
the line-side of the circuit breaker. Initiation can not be established, for example, due to
using dead line detection is highly recom- lack of polarizing voltage. Use of non-direc-
mended for busbar configurations where tional distance zones also gives fast fault
more than one circuit breaker at one line end clearance when energizing a bus from the line
can energize the protected line. with a short-circuit fault on the bus.

)XQFWLRQDOLW\ The SOTF function is a logical function built- detection. Once enabled, this remains active
up from logical elements. It is a complemen- until one second after the enabling signal has
tary function to the distance protection func- reset. The protection function(s) released for
tion. tripping during the activated time can be
freely selected from the functions included
It is enabled for operation either by the close within the terminal. Pickup of any one of the
command to the circuit breaker, by a nor- selected protection functions during the
mally closed auxiliary contact of the circuit enabled condition will result in an immediate
breaker, or automatically by the dead line trip output from the SOTF function.

)XQFWLRQEORFN
SOTF-
627)
BLOCK TRIP
NDACC
DLCND
BC

xx00000188.vsd
$XWRPDWLFVZLWFKRQWRIDXOWORJLF 627)
1MRK 580 136-BEN
Page 2

,QSXWDQGRXWSXW 7DEOH ,QSXWVLJQDOVIRUWKH627) 627) IXQFWLRQEORFN


VLJQDOV 6LJQDO 'HVFULSWLRQ
BLOCK Blocks function
NDACC Connected to function(s) to be released for immediate trip-
ping when SOTF function is enabled
DLCND Connected to dead line detection function to provide auto-
matic enabling of SOTF function
BC Enabling of SOTF function by circuit breaker close command
or normally closed auxiliary contact of the circuit breaker

Path in local HMI: ServiceReport/Functions/Impedance/ SwitchOntoFlt/FuncOutputs

7DEOH 2XWSXWVLJQDOVIRUWKH627) 627) IXQFWLRQEORFN


6LJQDO 'HVFULSWLRQ
TRIP Trip output

7HFKQLFDOGDWD
7DEOH 627)$XWRPDWLFVZLWFKRQWRIDXOWIXQFWLRQ
3DUDPHWHU 9DOXH $FFXUDF\
+] +]
Delay following dead line detection input 200 ms +/- 0.5% +/-10 ms +/- 0.5% +/-10 ms
before SOTF function is automatically enabled
Time period after circuit breaker closure in 1000 ms +/- 0.5% +/-10 ms +/- 0.5% +/-10 ms
which SOTF function is active

0DQXIDFWXUHU
$%%$XWRPDWLRQ7HFKQRORJ\3URGXFWV$%
Control & Force Measurement
Substation Automation
SE-721 59 Vsters
Sweden
Tel: +46 (0) 21 34 20 00
Fax: +46 (0) 21 14 69 18