BS8110-
1:1997 COLUMN DESIGN
ROOF TO SECOND FLOOR
12
1.35m
4.30m 4.30m
E
1.35m
PRELIMINARY DESIGN
Table 3.1
Strength of concrete, fcu = 30N/mm2 fcu = 30N/mm2
Fy =250N/mm
Characteristic strength of mild steel, fy = 250N/mm
Reinforcing bar diameter = 16mm
Link sizes = 10mm
Concrete density = 23.6KN/m
Column sizes
The column in question, column type C3 has a minimum size of 250mm is
adequate for 1.5 hours fire resistance.
Proposed column of dimension 250mm x 250mm
Column classification
Column is not supported at both sides. Therefore it is an unbraced
column.
REFERENCE CALCULATIONS OUTPUT
BS8110-
1:1997 END CONDITION
End condition of column: The end of the top column is
Clause monolithically connected to roof beams of depth 350mm x 225mm
3.8.1.6.2 on either side which are at least as deep as the overall dimension of
the column whiles the bottom of the column is connected to the first
floor beams in plan. (top1, bottom1) thus condition one is satisfied.
Table 3.20 Therefore = 1.2
Effective height le = lo x
= 2700mm x 1.2
= 3240mm le= 3240mm
Lex = 3240
h 250
= 12.96 15
Ley = 3240
b 225
= 12.96 15
3.8.1.3 Since l and l are less than 15 design column as short unbraced.
h b
LOADINGS
12
1.35m
0.68 B
4.30mm 4.30m
A 2.15
E
1.35m
REFERENCE CALCULATIONS OUTPUT
BS8110- CALCULATION OF LOAD AREA
1:1997 Area (A)
AA = 0.5 x h x (a + b)
= 0.5 x 2.15 x (0.68 + 1.35)
= 2.18m2
Area (B)
ABC = ( x b x h)
= ( x 0.68 x 4.30)
= 5.85 m2
LOADS MULTIPLIER
LOADINGS
Self weight of column = (23.6KN/m3 x 0.25m x 0.25m x 2.7m)
= 3.98KN
Area of A
Weight of beam = (0.35m x 0.225m x 23.6KN/m3) x 1.4
= 2.60KN/m
Area of B
Weight of beam = (0.35m x 0.225m x 23.6KN/m3) x 1.4
= 2.60KN/m
12
UDLB = 6.68KN/m
4.30m
UDLA = 7.43KN/m
1.35m
MAIN REINFORCEMENT
Clause 3.8.4.3
Equation 29 The column is design for nominal eccentricity of short columns
resisting moments and axial forces.
N = 0.4fcuAc+0.8Ascfy
Asc = N- 0.4fcuAc
0.8fy
Asc = 23.36 x 103 - 0.4 30 250 x 250
0.8250 Asc =
= - 3633.2mm - 3633.2mm2
The negative sign implies the compressive strength of column can
resist the axial load hence provide nominal reinforcement.
REFERENCE CALCULATIONS OUTPUT
BS8110-
1:1997 For Nominal Reinforcement
A sc 0.4Ac
100
A sc 0.4 (250 x 250)
100
Asprov =
A sc 250mm 1306mm
hence provide 6 R16mm bars, Asprov = 1306mm
1601 1601
1601 1601
6 R16mm
CRACKING
When the column load is small and the axial force is greater then
Clause 3.8.6 there is no need for any further check.
N 0.2fcuAc
N 0.230(250 x 250)
23.36 375KN
Since the ultimate axial load is 0.2 fcuAc further check is required
A more lightly loaded column subject to bending should be
considered as a beam for the purpose of crack control
x
y
h = ( x 2 + y 2 )
x = cover + stirrups + /2
= 25 + 10 + 16/2
= 41mm
y = cover + stirrups + /2
= 25 + 10 + 16/2
= 41mm
h = 412 + 412
= 57.98mm
Acr = h - /2
= 57.98 16/2
acr = 49.98mm
REFERENCE CALCULATIONS OUTPUT
BS8110-
1:1997 Clear distance bars in relation to fy of 250N/mm2 is 280mm
Allowable distance = 280/2
= 140mm
Since acr = 49.98 140mm as required, hence crack width is ok Cracking is
ok
REFERENCE CALCULATIONS OUTPUT
BS8110
COLUMN DESIGN
SECOND FLOOR TO FIRST FLOOR
12
1.35m
4.30m 4.30m
E
1.35m
PRELIMINARY DESIGN
Table 3.1
Strength of concrete, fcu = 30N/mm2 fcu = 30N/mm2
Fy =250N/mm
Characteristic strength of mild steel, fy = 250N/mm
Reinforcing bar diameter = 16mm
Link sizes = 10mm
Concrete density = 23.6KN/m
Column cover
Table 3.3 For mild environmental condition the cover is 25mm
Table 3.2 For 1.5hours fire resistance the nominal cover is 20mm
Cover 25mm
Table 3.4 Nominal cover is thus 25mm
Column sizes
The column in question, column type C3 has a minimum size of 250mm is
adequate for 1.5 hours fire resistance.
Proposed column of dimension 250mm x 250mm
Column classification
Column is not supported at one side. Therefore it is unbraced
column.
REFERENCE CALCULATIONS OUTPUT
BS8110-
1:1997 END CONDITION
End condition of column: The end of the top column is
Clause monolithically connected to roof beams of depth 450mm x 225mm
3.8.1.6.2 on either side which are at least as deep as the overall dimension of
the column whiles the bottom of the column is connected to the
ground floor beams in plan. (top1and bottom1) thus condition one is
satisfied.
Table 3.20 Therefore = 1.2
SLENDERNESS RATIO
3.8.1.6.1 Clear height l = 3150mm
Equation 30 = 3150 500
= 2650mm
Effective height le = lo x
= 2650mm x 1.2
= 3180mm le= 3180mm
Lex = 3180
h 250
= 12.72 15
Ley = 3180
b 250
= 12.72 15
3.8.1.6 Since l and l are less than 15 design column as short unbraced.
h b
LOADINGS
H
1.35m
0.680 B
4.3mm 4.3m
0.68
A 2.15
16
1.350m
REFERENCE CALCULATIONS OUTPUT
BS8110
CALCULATION OF LOAD AREA
Area (A)
AA = 0.5 x h x (a + b)
= 0.5 x 2.15 x (0.68 + 1.35)
= 2.18m2
Area (B)
ABC = ( x b x h)
= ( x 4.3 x 0.68)
= 1.46 m2
LOADS MULTIPLIER
LOADINGS
Self weight of column = (23.6KN/m3 x 0.25m x 0.25m x 2.65m)
= 3.91KN
Area of A
Beam load
G beam = 0.500 0.225 23.6
=2.65KN/m
weight of slab
G slab = 0.150m 1.61m 23.6KN/m3
= 5.69KN/m
Wall loads
G wall loads = 0.150m 2.65m 22KN/m3
= 8.75KN/m
REFERENCE CALCULATIONS OUTPUT
BS8110-
1:1997
G wall finish = 1KN/m22.65m
= 2.65KN/m
Area of B
Beam load
G beam = 0.500 0.225 23.6
=2.66KN/m
weight of slab
G slab = 0.150m 0.34m 23.6KN/m3
= 1.20KN/m
LOADINGS ON COLUMN
UDLB = 28.74KN/m
4.3m
16
UDLA = 35.93KN/m
1.35m
N = 0.4fcuAc +0.8Ascfy
Asc = N - 0.4fcuAc
0.8fy
Asc = 113.31 x 103 - 0.4 30 (250 x 250)
0.8250 A sc =
= - 3183.45mm -3183.45mm
The negative sign implies the compressive strength of column can
resist the axial load hence provide nominal reinforcement
1601 1601
1601 1601
6 R16mm
DEFLECTION
For an unbraced column checks are not normally required except
Clause 3.8.5 that all columns should have le/h 30.
CRACKING
Clause 3.8.6 When the column load is small and the axial force is greater then
there is no need for any further check.
N 0.2fcuAc
N 0.230(49094)
113.31 375KN
Since the ultimate axial load is 0.2 fcuAc further check is required
A more lightly loaded column subject to bending should be
considered as a beam for the purpose of crack control
x
y
h = ( x 2 + y 2 )
x = cover + stirrups + /2
= 25 + 10 + 16/2
= 41mm
REFERENCE CALCULATIONS OUTPUT
BS8110-
1:1997 y = cover + stirrups + /2
= 25 + 10 + 16/2
= 41mm
h = 412 + 412
= 57.98mm
Acr = h - /2
= 57.98 16/2
acr = 49.98mm
Clear distance bars in relation to fy of 250N/mm2 is 280mm
Allowable distance = 280/2
= 140mm
Since acr = 49.98 140mm as required, hence crack width is ok Crack is ok
R.B
11- R1001@225mmc/c
4 R1602
B B 3000mm
Starter bars 900mm
Kicker 75mm
F.F
11- R1001@225mmc/c
4 R1601 3000mm
A A
Starter bars 900mm
Kicker 75mm
GL
150mm
300min varies
SLAB DETAILES
1602 1602
1602 1602
4 R16mm
SECTION A - A