Академический Документы
Профессиональный Документы
Культура Документы
Supplier: PowerWare
Reference: 1021485
Version: C
179747/H
Installation and Users Manual
for UPS 2kVA and 3kVA
1. Introduction
2. Safety Information
3. Installation
3.1 General Information
3.2 Location of the Unit
3.3 Logistics
3.4 Handling
3.5 Procedures
3.6 Storage of UPS
3.7 Storage of Battery
4. Technical specifications
4.1 General
4.2 Input
4.3 Output
4.4 Environmental
4.5 Mechanical
4.6 Battery
DRAWINGS
Main schematics Drawing UPS with distribution board 1021435
Dimensional Drawing 1023060
Dimensional Drawing 1023832
2. SAFETY INFORMATION
Since the UPS unit operates on line power and contains a bank of high-current backup
batteries, the information in this chaper is important to all personnel involved. Please
read the safety manual provided with this UPS.
WARNING!
Do not open the UPS cabinet. Some components inside the UPS cabinet
carry high voltage. To touch them may prove fatal. All operations inside the
unit must be carried out only by authorized personnel only.
This UPS contains its own energy source (batteries). The output may carry
live voltage even when the UPS is not connected to an AC supply.
Users operations
The only users operations permitted are:
Starting up and shutting down the UPS unit
Operating the users interface
WARNING!
The UPS contains high voltage and current which can injure or kill
personnel and damage equipment.
All repairs and service should be performed by authorized personnel only.
There are no serviceable parts inside the UPS.
WARNING!
Batteries may contain high energy and voltages, and caustic, toxic and
flammable substance.
Because of the battery string the output receptacles may carry high
voltage even when the AC supply is not connected to the UPS.
Read the shut down instruction of the Users and Installation manual.
WARNING!
UPS
Batteries
Figure 1.
3.3 Logistics
General safety precautions should be followed when working on the UPS.
3.4 Handling
Appropriate equipment should be used and care must be taken when handling the UPS
units.
3.5 Procedures
3.5.1 Mechanical Installation
The UPS shall be fastened to the floor through two 5 mm mounting rails. Diameter of
bolts is 8 mm, see the attached dimensional drawing no. 1023060.
Figure 3
If specific alarm indication are required the jumper connection must be disconnected and
a new connection made according to the table 1.
Refer to figure 4.
Refer to figure 4.
NOTE!
WARNING!
Batteries may contain high energy and voltages, caustic, toxic and
flammable substances.
Do not discard batteries or battery material in public disposal systems.
Follow all applicable local regulations for storage, handling and disposal of
batteries and battery material
Never dispose batteries in fire. Batteries may explode when exposed to
flame.
Never open or damage batteries. Released electrolyte is harmful to the skin
and eyes, and may be extremely toxic.
4.1 General
Rated power 2000 VA, 3000 VA at p.f. 0,7
Technology On-line, double conversion topology with
automatic and maintenance bypass
4.2 Input
Phase Single phase with ground
Input Voltage 90 to 144 VAC / 176 to 264 VAC
Frequency 50/60Hz
Frequency window from mains 45 65Hz
Synchronization window +/- 3Hz
Input current (230VAC/2kVA) 7,7A
(230VAC/3kVA) 12,0A
(120VAC/3kVA) 24,0A
Input Power factor 0.97
4.3 Output
Output Voltage 120VAC / 230VAC
Voltage regulation +/- 2%
Voltage distortion < 5% THD at full non-linear load
< 3% THD at full linear load
Frequency regulation +/- 0,25% (battery mode or free running)
Overload capacity 100 125% 1 min
125 150% 10 sec
Efficiency 0,86
Output fuse breakers 6 Amps.
4.4 Environmental
Ambient temperature +0C +40C
Recommended temperature +15C +25C
Storage temperature -15C +50C
Cooling Forced air cooling
Humidity 0 95%, non-condensing
4.6 Battery
Type Panasonic LC-X1224AP
Number of batteries 8
Nominal voltage 12 V
Rated capacity 24 Ah