MM-613E
Series FS4-3T
General Purpose
Liquid Flow Switch
ELECTRICAL RATINGS
Motor Switch Rating (Amperes) CE Circuit Rating
Voltage Full Load Locked Rotor Pilot Duty 7.4 (7.4)/120~ 0.3/120=
120 VAC 7.4 44.4 125 VA at 3.7 (3.7)/240~ 0.15/240=
240 VAC 3.7 22.2 120 or 240 VAC
50 or 60 cycles
This Control: is for continuous operations system switch operation rate of less than 5 times
is not electronic per minute, and any one cycle greater than 3 sec-
has Type 1C action (micro interruption onds on and 3 seconds off.
on operation)
Additional suppression may be required for applica-
LVD 73/23/EEC tions outside these ranges.
Declaration of Conformity
EMC 89/33/EEC Available on request.
For applications with loads between 14mA and 3.7
Amps, power factors exceeding 0.65, an anticipated
2
FLOW RATES
Flow rates required to activate the flow switch Settings will vary when used to sense flow of other
are shown in chart below.These values were fluids.
calculated using clean water in a horizontal pipe.
Flow Rates
Pipe Mode of Operation Max. Flow
Rate gpm
Model Size NPT Flow No Flow (lpm) w/o
Number in. (mm) Settings gpm (lpm) gpm (lpm) Paddle Damage
Factory or
FS4-3T1-34 3
4 (20) Minimum 4.4 (16.7) 2.6 (9.8)
Maximum 10.5 (39.7) 9.8 (37.1)
Factory or
FS4-3T2-34 3
4 (20) Minimum 3.7 (14) 2.2 (8.3) 16.62
Maximum 8.9 (33.7) 8.3 (31.4) (63)
Factory or
FS4-3T3-34 3
4 (20) Minimum 2 (7.6) 1.2 (4.5)
Maximum 4.5 (17) 4.1 (15.5)
Factory or
FS4-3T1-1 1 (25) Minimum 5 (18.9) 3.2 (12.1)
Maximum 11.5 (43.5) 11 (41.6)
Factory or
FS4-3T2-1 1 (25) Minimum 4.8 (18.1) 2.9 (11) 27
Maximum 10.1 (38.2) 9.4 (35.6) (102)
Factory or
FS4-3T3-1 1 (25) Minimum 2 (7.6) 1.2 (4.5)
Maximum 4.5 (17) 4.1 (15.5)
Values are 10%
3
INSTALLATION
STEP 1 - Determine the Location of the Flow Switch
The flow switch should be located in a horizontal
section of pipe where there is a straight horizontal run
of at least 5 pipe diameters on each side of the flo w
switch. The flow switch may be installed in a vertical
pipe if the flow is in the upward direction.
4
STEP 3 - Electrical Installation
! WARNING
To prevent electrical shock, turn off the electrical power before making electrical connections.
To prevent an electrical fire or equipment damage, electrical wiring insulation must have a rating of
167F (75C) if the liquids temperature exceeds 180F (82C).
To prevent electrocution, when the electrical power is connected to the flow switch, do not touch the
terminals.
Make sure flow switch electrical cover is secured before turning on electric power.
Failure to follow this warning could cause property damage, personal injury or death.
5
c. Determine which switch action is required for the
flow switch.
Flow means that the switch will close circuit
C.-N.O. and open circuit C.-N.C. when flow rate
is increased above setpoint of flow switch.
(Common( (Normally
open (
(Normally
closed (
LINE LINE
FS4-3 FS4-3
3 1 3 1
2 2
HOT HOT
LOAD LOAD
Fig. 1 Fig. 2
6
STEP 4 - Testing
SECTION 5 - Adjustment
7
Xylem Inc.
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Phone: (847) 966-3700
Fax: (847) 965-8379
www.xyleminc.com/brands/mcdonnellmiller