HYDRAULIC CALCULATION USING DARCY METHOD

1
2 PROCESS DATA
3
4
5 Liquid : Saturated Water
6 Liquid temp. : 110 o
C
7 Capacity 20000 kg/hr
8 : 21.04 m3/hr
9 Density@pumping temp. : 950.57 kg/m3
10 Dynamic viscosity@40oC : 0.3 cP
11 1 bar abs : 10.73 m liq abs
12
13 PIPING DATA AND EQUIVALENT LENGTH
14
15
16 Flowrate : 21 m3/hr
17 Size : 4.00 inch
18 Pipe schedule : 40
19 Inside diameter : 0.10226 m
20 Pipe Roughness : 0.05 mm
21 Material : Carbon Steel
22 Straight pipe length : 7.6 m
23
24 FITTINGS
25
26 Type Le/D Le
27 Tee (side outlet) : 0 65 0
28 Tee (straight through) : 0 20 0
29 Elbow 90O : 6 20 120
30 Elbow 45O : 0 16 0
31 Nozzle : 0 32 0
32 Reducer/Expander : 1 8 8
Gate Valve : 0 13 0
Check Valve : 1 135 135
Globe Valve : 1 300 300
33
34 EQUIVALENT LENGTH
35 Section 1
36 Total equivalent length : 57.57238
37 Total pipe length : 65.17238
38 (add 20% safety margin) : 78.206856
39
40 PRESSURE DROP CALCULATION
41
42
43 Pipe Cross-sectional Area : 0.0082 m2
44 Fluid Velocity : 0.7116 m/s
45 Reynolds No. : 258105.365
46 Friction Factor : 0.0185
47 Line loss : 43459.5691 Pa/100m
48 : 0.4346 bar/100m
49 : 0.3399 bar
50 Additional Press. Drop : 0.0000 bar
51 Total Pressure Drop : 0.3399 bar
52 : 3.6461 m liquid
53
54
55
56
57
58
59
60
61
62
###
###
###
###
###
###
HYDRAULIC CALCULATION USING DARCY METHOD

1 Project: 114174@ Boiler Feedwater pump


2 PROCESS DATA
3
4
5 Liquid : Saturated Water
6 Liquid temp. : 105 o
C
7 Capacity 48000 kg/hr < change 71603 kg/hr <calculated
8 : 50.28 m3/hr < calculated 75 m3/hr <change
9 Density@pumping temp. : 954.71 kg/m3
10 Dynamic viscosity@60oC : 0.267 cP
11 1 bar abs : 10.68 m liq abs
12
13 PIPING DATA AND EQUIVALENT LENGTH
14
15
16 Flowrate : 50.28 m3/hr
17 Size : 4.00 inch
18 Pipe schedule : 40
19 Inside diameter : 0.10226 m
20 Pipe Roughness : 0.05 mm
21 Material : Carbon Steel
22 Straight pipe length : 30 m
23
24 FITTINGS
25
26 Type Le/D Le
27 Tee (side outlet) : 3 65 195
28 Tee (straight through) : 0 20 0
29 Elbow 90O : 15 20 300
30 Elbow 45O : 0 16 0
31 Nozzle : 5 32 160
32 Reducer/Expander : 0 8 0
Gate Valve : 4 13 52
Check Valve : 2 135 270
Globe Valve : 0 300 0
33 Total: 977
34 EQUIVALENT LENGTH
35 Section 1
36 Total equivalent length : 99.90802
37 Total pipe length : 129.90802
38 (add 20% safety margin) : 155.889624
39
40 PRESSURE DROP CALCULATION
41
42
43 Pipe Cross-sectional Area : 0.008213 m2
44 Fluid Velocity : 1.7005 m/s
45 Reynolds No. : 621772.923
46 Friction Factor : 0.0175
47 Line loss : 23648.8029 Pa/100m
48 : 0.2365 bar/100m
49 : 0.3687 bar
50 Additional Press. Drop
: 0.0000 bar
: 0.0000 bar
- Economizer @HE dp : 2.0000 bar
- Level control valve : 1.0000 bar
- Flowmeter Orifice : 0.5000 bar
51 Total Pressure Drop : 3.8687 bar
52 : 41.3208 m liquid
53 Operation:
54 Boiler Operating Pressure : 17 bar
Boiler Entry Pressure : 2 bar

55 Pump Discharge Pressure : 22.8687 bar


56 244.26 m head
57