Computed By:

Project:
Checked By:

Date: Approved By:

NOVEC 1230 Total Flooding System Calculations


Hazard Area No.1
Protected Hazard Dimensions

Name of Protected Hazard Area Tel

Height 3.0 m

Area 100.0 m2

Volume 300 m3

Volume of Fixed Structures


0.0 m3
Impervious to Agent vapor

Design Parameters

Class of Fire Hazard A

Net Volume of Hazard Area 300.0 m3

Design Temperature in Hazard Area 20 o


C

Agent Specific Volume @ 1 Atm. pressure 0.072 m3/kg

Minimum Design Concentration 4.2 % per volume

Agent Design Concentration 5.4 % per volume

Tee Count of Piping System 6.0

Hazard Area Pressure 1.0 atm

Design Safety Factor 0.02

System Sizing

Agent Net Capacity 243.0 kg


Computed By:
Project:
Checked By:

Date: Approved By:

Agent Net Capacity Percentage 67 %

Total Agent Flow Rate 24.3 kg/sec

Required No. of discharge Nozzels 3

Acual Flow per Nozzel 8.1 kg/sec

Nozzel and Branch Pipe Diameters 1 1/2 inch

Main Pipe Diameter 2 1/2 inch


Computed By:
Project:
Checked By:

Date: Approved By:

Hazard Area No.2


Protected Hazard Dimensions

Name of Protected Hazard Area elect

Height 3.0 m

Area 50.0 m2

Volume 150 m3

Volume of Fixed Structures


0.0 m3
Impervious to Agent vapor

Design Parameters

Class of Fire Hazard C

Net Volume of Hazard Area 150.0 m3

Design Temperature in Hazard Area 20 o


C

Agent Specific Volume @ 1 Atm. pressure 0.072 m3/kg

Minimum Design Concentration 4.2 % per volume

Agent Design Concentration 5.4 % per volume

Tee Count of Piping System 6.0

Hazard Area Pressure 1.0 atm

Design Safety Factor 0.02

System Sizing

Agent Net Capacity 121.5 kg

Agent Net Capacity Percentage 33 %


Computed By:
Project:
Checked By:

Date: Approved By:

Total Agent Flow Rate 12.1 kg/sec

Required No. of discharge Nozzels 2

Acual Flow per Nozzel 6.1 kg/sec

Nozzel and Branch Pipe Diameters 1 1/2 inch

Main Pipe Diameter 2 inch


Computed By:
Project:
Checked By:

Date: Approved By:

Combined System Sizing

Agent Total Net Capacity 364.5 kg

Container Size
Container Size Selection 900 Ib

Total Required No. of Containers 1

Agent Net Capacity in Each Container 364.5 kg


803.5 Ibs

Total Agent Flow Rate 36.4 kg/sec

Maximum Agent Flow Rate per Nozzel 9.07 kg/sec

Total Required No. of discharge Nozzels 5

System Main Pipe Diameter 3 inch

Checking Agent Concentration in a Combind Space with Directional Valve

Name of Protected Hazard Area Tel

Height 3.0 m

Area 200.0 m2

Volume 600 m3

Volume of Fixed Structures


0.0 m3
Impervious to Agent vapor

Design Parameters

Class of Fire Hazard B

Minimum Design Concentration 4.2 % per volume

Net Volume of Hazard Area 600.0 m3


Computed By:
Project:
Checked By:

Date: Approved By:

Design Temperature in Hazard Area 27 o


C

Agent Specific Volume @ 1 Atm. pressure 0.074 m3/kg

Tee Count of Piping System 6.0

Hazard Area Pressure 1.0 atm

Design Safety Factor 0.02

Agent Design Concentration 4.2 %


Computed By:
Project:
Checked By:

Date: Approved By:

General Design Considerations

- Max. No. of Nozzels in the System 20


- Maximum Agent Flow Rate per Nozzel 9.07 kg/sec
- Maximum Discharge Time 10 sec
- Nozzel Maximum Coverage Radius 8.70 m
10.90
- Min. Nozzel Pressure 73 psi
- Maximum Ceiling Height 4.87 m
- Nozzel Max. Distance from Ceiling 0.30 m
- False Ceiling or Raised Floor Min. Height 0.30 m
- Space Min. agent percentage in combind system 10 %
- Beams that are less than 0.3 m below the slab need not be considered. Obstructions greater than 300
mm (12) can affect the distribution of agent and may require additional nozzles.
- The max. elevation difference between the container outlet and the furthest horizontal pipe run or
discharge nozzle (whichever is furthest) shall not exceed 9.1 m.
- The max. elevation difference between the furthest horizontal pipe runs or discharge nozzles (whicheve
is furthest) shall not exceed 9.1 m.
- The agent design concentration shall be checked to insure that it is under NOAEL at maximum
anticipated temperature in the hazard space.
- Sizing is based on NFPA-2001
Eng. H.S & E.S
Eng. M. Gamal

Dr. H. Soliman

em Calculations

1076.4 ft2

535.7 Ibs
Eng. H.S & E.S
Eng. M. Gamal

Dr. H. Soliman

Accepted

53.6 Ibs/sec

17.9 Ibs/sec

3
Eng. H.S & E.S
Eng. M. Gamal

Dr. H. Soliman

538.2 ft2

267.8 Ibs

Accepted
Eng. H.S & E.S
Eng. M. Gamal

Dr. H. Soliman

26.8 Ibs/sec

13.4 Ibs/sec

2 1/2
Eng. H.S & E.S
Eng. M. Gamal

Dr. H. Soliman

803.5 Ibs

Minimum Fill
###Ibs
455

Accepted

80.4 Ibs/sec

20 Ibs/sec

Accepted

with Directional Valve

2152.8 ft2
Eng. H.S & E.S
Eng. M. Gamal

Dr. H. Soliman

Accepted
Eng. H.S & E.S
Eng. M. Gamal

Dr. H. Soliman

20 Ibs/sec

360o Nozzel Type


180o Nozzel Type

dered. Obstructions greater than 300


onal nozzles.
e furthest horizontal pipe run or

e runs or discharge nozzles (whichever

s under NOAEL at maximum