Вы находитесь на странице: 1из 198

PT.

CEMINDO
GEMILANG
ADMINISTRATION & CANTEEN BUILDING
PROJECT

CONTRACT NO: /2014

DOCUMENT NO:
TITLE :

CALCULATION SHEET FOR


HVAC SYSTEM
PURPOSE :

For Review

Rev. Description Prepared Checked Approved Date


0 Issued for Review DDN

INTERNAL DOCUMENT No. :

PT SOMIT TRAKONAD
ENGINEERING & CONSTRUCTION CS-HVAC-01
SHEET 2 OF 12
DOC. NO. :
REV

CALCULATION SHEET OF HVAC SYSTEM CS-HVAC-01 0

REVISION HISTORICAL SHEET

Rev No Date Description


0 Issued for Review

DISTRIBUTION ORDER

Internal CONTRACTOR : External CONTRACTOR (by Transmittal):

DDO Attachment
Project Director OWNER
Project Manager Head Office
Engineering Manager Site Office
Procurement Manager
Construction Manager
Chief Construction Control
Chief QA & QC
Chief Safety
Civil Lead Eng.
Electrical Lead Eng.
Instrument Lead Eng.
Mechanical Lead Eng.
Piping Lead Eng.
Process Lead Eng.
SHEET 3 OF 12
DOC. NO. :
REV

CALCULATION SHEET OF HVAC SYSTEM CS-HVAC-01 0

CONTENS
PAGE

A. Introduction 4

B. Abbreviations 4

C. Reference 4

D. Software 5

E. Design Criteria 5

F. Design Metodh 6

G. Design Data & Calculations 9

Attachment 1 : Reference Table 10

Attachment 2 : : Calculation sheet 11


SHEET 4 OF 12
DOC. NO. :
REV

CALCULATION SHEET OF HVAC SYSTEM CS-HVAC-01 0

A. Introduction
This calculation for requirement of HVAC Engineering project of:
Project : ADMINISTRATION & CANTEEN BUILIDNG PROJECT
Client : PT. CEMINDO GEMILANG
Location : BAYAH BANTEN
Scope : Ventilating and Air Conditioning (VAC)

B. Abbreviations
- ASHRAE : American Society Of Heating, Refrigerating and Air-
Conditioning Engineers
- SMACNA : Sheet Methal American Contractors Nation Association
- NFPA : National Fire Protection Association
- ARI : Association Refrigeration International
C. Reference
ASHRAE Fundamental Handbook 1997
Chapter 28 NONRESIDENTIAL COOLING AND HEATING LOAD
CALCULATIONS
ASHRAE Handbook : GRP 158 Cooling & Heating Load Calculation Manual
ASHRAE Std 62 2001
Except contrary stated anywhere in the specification or construction drawings,
the following standards shall apply for this project :

i. NFPA 90 A & B - Installation of Air Conditioning and Ventilation Systems


and Installation of Warm Air Heating and Air Conditioning Systems.

ii. ANSI/ASHRAE 15 - Safety Code for Mechanical Refrigeration.

iii. ARI 360 - Commercial and Industrial Unitary Air Conditioning Equipment
testing and rating standard. (above 135,000 btuh)

iv. ARI 340 - Commercial and Industrial Unitary Heat pump


Equipment.(above 135,000 btuh)

v. ANSI/ASHRAE 37 - Testing Unitary Air Conditioning and Heat Pump


Equipment.

vi. ANSI/ASHRAE/IES 90 A - Energy Conservation in New Building Design


Standard.
SHEET 5 OF 12
DOC. NO. :
REV

CALCULATION SHEET OF HVAC SYSTEM CS-HVAC-01 0

vii. ANSI Z21.47/UL1995 - Unitary Air Conditioning Standard for safety


requirements.

viii. ARI 210 / 240 - Unitary Air-Conditioning Equipment and Air- Source Heat
Pump Equipment. (all under 135,000 btuh)

ix. ARI 370 - Sound Rating of Large Outdoor Refrigerating and Air
Conditioning Equipment.(all above 135,000 Btuh)

x. ANSI/NFPA 70-1995 - National Electric Code.

xi. SMACNA HVAC Duct Construction Standards Second Edition 1995


D. Software
Applied computer software in this calculation :
(1) Carrier E-20 Hourly Analisys Programe HAP 4.30
(2) Microsoft Excel

E. Design Criteria
Indoor Condition

No. Building Room Design Temp


1 Administration Building GF- Amblulance Driver#1 24C+1
2 Administration Building GF- Area Staff #1 24C+1
3 Administration Building GF- Area Staff #2 24C+1
4 Administration Building GF- ATM # 1 24C+1
5 Administration Building GF- Clinic#1 24C+1
6 Administration Building GF- Docter#1 24C+1
7 Administration Building GF- Hall#1 24C+1
8 Administration Building GF- Lobby, Resepsionist#1 24C+1
9 Administration Building GF- Manager#1 24C+1
10 Administration Building GF- Manager#2 24C+1
11 Administration Building GF- Manager#3 24C+1
12 Administration Building GF- Manager#4 24C+1
13 Administration Building GF- Manager#5 24C+1
14 Administration Building GF- Meeting#1 24C+1
15 Administration Building GF- Musholah#1 24C+1
16 Administration Building GF- Nurse#1 24C+1
17 Administration Building GF- Patient#1 24C+1
18 Administration Building GF- Ruang Tunggu#1 24C+1
19 Administration Building GF- Security Monitor#1 24C+1
20 Administration Building GF- Sekretaris#1 24C+1
21 Administration Building GF- Server#1 24C+1
SHEET 6 OF 12
DOC. NO. :
REV

CALCULATION SHEET OF HVAC SYSTEM CS-HVAC-01 0

22 Administration Building GF- Storage HSE#1 24C+1


23 Administration Building GF- Training#1 24C+1
24 Administration Building 1F- Area Staff#1 24C+1
25 Administration Building 1F- Area Staff#2 24C+1
26 Administration Building 1F- File Storage#1 24C+1
27 Administration Building 1F- File Storage#2 24C+1
28 Administration Building 1F- File#1 24C+1
29 Administration Building 1F GA#1 24C+1
30 Administration Building 1F- Grand Meeting#1 24C+1
31 Administration Building 1F- Manager#1 24C+1
32 Administration Building 1F- Manager#2 24C+1
33 Administration Building 1F- Manager#3 24C+1
34 Administration Building 1F- Manager#4 24C+1
35 Administration Building 1F- Manager#5 24C+1
36 Administration Building 1F- Manager#6 24C+1
37 Administration Building 1F- Meeting#1 24C+1
38 Administration Building 1F- Resepsionist#1 24C+1
39 Administration Building 1F- Ruang Tunggu#1 24C+1
40 Administration Building 1F- Security Monitor#1 24C+1
41 Administration Building 1F- Training#1 24C+1
42 Administration Building 2F- Director#1 24C+1
43 Administration Building 2F- Director#2 24C+1
44 Administration Building 2F- Director#3 24C+1
45 Administration Building 2F- Director#4 24C+1
46 Administration Building 2F- Director#5 24C+1
47 Administration Building 2F- Director#6 24C+1
48 Administration Building 2F- Exce Dining#1 24C+1
49 Administration Building 2F- File Storage#1 24C+1
50 Administration Building 2F- Function#1 24C+1
51 Administration Building 2F- Grand Meeting#1 24C+1
52 Administration Building 2F- Komisaris#1 24C+1
53 Administration Building 2F- Komisaris#2 24C+1
54 Administration Building 2F- Lobby, Secretary#1 24C+1
55 Administration Building 2F- Ruang Tunggu#1 24C+1
56 Administration Building 2F- Security Monitor#1 24C+1
57 Administration Building 3F-File Storage#1 24C+1
58 Administration Building 3F-Hall#1 24C+1
59 Administration Building 4F-Lift Room# 24C+1
SHEET 7 OF 12
DOC. NO. :
REV

CALCULATION SHEET OF HVAC SYSTEM CS-HVAC-01 0

RH : Not Conditoned
Air Change Per Hour (ACH)

No. Building Room ACH


1 Administration Building GF- Janitor#1 10
2 Administration Building GF- Me#1 6
3 Administration Building GF- Pantry#1 15
4 Administration Building GF- Toilet Clinik#1 10
5 Administration Building GF- Toilet Female#1 10
6 Administration Building GF- Toilet Male#1 10
7 Administration Building GF- Wudhu#1 10
8 Administration Building GF-Pompa#1 6
9 Administration Building GF-Electric#1 (5 cfm/KVA) 42.5
10 Administration Building 1F- Janitor #1 10
11 Administration Building 1F- Janitor#2 10
12 Administration Building 1F- Me#1 6
13 Administration Building 1F- Pantry #1 15
14 Administration Building 1F- Pantry#2 15
15 Administration Building 1F- Pompa#1 6
16 Administration Building 1F- Toilet Female#1 10
17 Administration Building 1F- Toilet Male#1 10
18 Administration Building 2F- Janitor#1 10
19 Administration Building 2F- Me#1 6
20 Administration Building 2F- Pantry#1 15
21 Administration Building 2F- Pompa #1 6
22 Administration Building 2F- Toilet Director#1 10
23 Administration Building 2F- Toilet Female#1 10
24 Administration Building 2F- Toilet Manager#1 10
25 Administration Building 2F- Toilet Lobby #2 10
26 Administration Building 2F- Toilet Lobby#1 10
27 Administration Building 2F- Toilet Male#1 10
28 Administration Building 3F- Me#1 6
29 Administration Building 3F- Pompa #1 6
SHEET 8 OF 12
DOC. NO. :
REV

CALCULATION SHEET OF HVAC SYSTEM CS-HVAC-01 0

F. Design Metodh
Calculation Metodh is Cooling Load Temperature Difference reffer to ASHRAE GRP-158.

Note:
1. Refer To ASHRAE GRP 158 table 3.1 Chapter 3
2. Refer To ASHRAE GRP158 table 3.3 Chapter 3
3. Refer To ASHRAE GRP 158 table 3.1 Chapter 3
SHEET 9 OF 12
DOC. NO. :
REV

CALCULATION SHEET OF HVAC SYSTEM CS-HVAC-01 0

Refer To ASHRAE GRP158 table 4.5


Chapter 4

Refer To ASHRAE GRP158


table 3.1 Chapter 3

Refer To ASHRAE GRP158


table 4.5 Chapter 4

Refer To ASHRAE GRP158


table 4.1 Chapter 4

Refer To ASHRAE GRP158 table 4.1


Chapter 4
SHEET 10 OF 12
DOC. NO. :
REV

CALCULATION SHEET OF HVAC SYSTEM CS-HVAC-01 0

Refer To ASHRAE GRP158 table 5.1


Chapter 5

Refer To ASHRAE GRP158 table


5.1 Chapter 5

Refer To ASHRAE GRP158


Chapter 6

G. Design Data & Calculation


Detail Design data & Calculation can be found on attached calculation sheet
SHEET 11 OF 12
DOC. NO. :
REV

CALCULATION SHEET OF HVAC SYSTEM CS-HVAC-01 0

ATTACHMENT 1. REFERENCE TABLE


Thermal and Water Vapor Transmission Data 25.5

Table 4 Typical Thermal Properties of Common Building and Insulating MaterialsDesign Valuesa
Resistancec (R)
Conductivityb Conductance For Thickness Specific
Density, (k), (C), 1/k, Listed (1/C), Heat,
Description kg/m3 W/(mK) W/(m2 K) Km/W Km2 /W kJ/(kgK)
BUILDING BOARD
Asbestos-cement board .................................................. 1900 0.58 1.73 1.00
Asbestos-cement board ......................................3.2 mm 1900 187.4 0.005
Asbestos-cement board ......................................6.4 mm 1900 93.7 0.011
Gypsum or plaster board....................................9.5 mm 800 17.6 0.056 1.09
Gypsum or plaster board..................................12.7 mm 800 12.6 0.079
Gypsum or plaster board..................................15.9 mm 800 10.1 0.099
Plywood (Douglas fir)d .................................................. 540 0.12 8.66 1.21
Plywood (Douglas fir)........................................6.4 mm 540 18.2 0.055
Plywood (Douglas fir)........................................9.5 mm 540 12.1 0.083
Plywood (Douglas fir)......................................12.7 mm 540 9.1 0.11
Plywood (Douglas fir)......................................15.9 mm 540 7.3 0.14
Plywood or wood panels ..................................19.0 mm 540 6.1 0.16 1.21
Vegetable fiber board
Sheathing, regular densitye .......................12.7 mm 290 4.3 0.23 1.30
..................................................................19.8 mm 290 2.8 0.36
Sheathing intermediate densitye................12.7 mm 350 5.2 0.19 1.30
Nail-base sheathinge .................................12.7 mm 400 5.3 0.19 1.30
Shingle backer.............................................9.5 mm 290 6.0 0.17 1.30
Shingle backer.............................................7.9 mm 290 7.3 0.14
Sound deadening board.............................12.7 mm 240 4.2 0.24 1.26
Tile and lay-in panels, plain or acoustic ................. 290 0.058 17. 0.59
....12.7 mm 290 4.5 0.22
....19.0 mm 290 3.0 0.33
Laminated paperboard .................................. 480 0.072 13.9 1.38
Homogeneous board from repulped paper.... 480 0.072 13.9 1.17
Hardboarde
Medium density ....................................................... 800 0.105 9.50 1.30
High density, service-tempered grade and service
grade...................................................................... 880 0.82 8.46 1.34
High density, standard-tempered grade.................... 1010 0.144 6.93 1.34
Particleboarde
Low density.............................................................. 590 0.102 9.77 1.30
Medium density ....................................................... 800 0.135 7.35 1.30
High density ............................................................. 1000 0.170 5.90 1.30
Underlayment.............................................15.9 mm 640 6.9 0.14 1.21
Waferboard..................................................................... 590 0.01 11.0
Wood subfloor..................................................19.0 mm 6.0 0.17 1.38
BUILDING MEMBRANE
Vaporpermeable felt ................................................... 94.9 0.011
Vaporseal, 2 layers of mopped 0.73 kg/m2 felt .......... 47.4 0.21
Vaporseal, plastic film................................................ Negl.
FINISH FLOORING MATERIALS
Carpet and fibrous pad ................................................... 2.73 0.37 1.42
Carpet and rubber pad.................................................... 4.60 0.22 1.38
Cork tile .............................................................3.2 mm 20.4 0.049 2.01
Terrazzo...............................................................25 mm 71.0 0.014 0.80
Tileasphalt, linoleum, vinyl, rubber ........................... 113.6 0.009 1.26
vinyl asbestos ........................................................... 1.01
ceramic..................................................................... 0.80
Wood, hardwood finish .......................................19 mm 8.35 0.12
INSULATING MATERIALS
Blanket and Battf,g
Mineral fiber, fibrous form processed
from rock, slag, or glass
approx. 75-100 mm ............................................ 6.4-32 0.52 1.94
approx. 90 mm ................................................... 6.4-32 0.44 2.29
approx. 90 mm ................................................... 19-26 0.38 2.63
approx. 140-165 mm.......................................... 6.4-32 0.30 3.32
approx. 140 mm ................................................. 10-16 0.27 3.67
approx. 150-190 mm.......................................... 6.4-32 0.26 3.91
approx. 210-250 mm.......................................... 6.4-32 0.19 5.34
approx. 250-330 mm.......................................... 6.4-32 0.15 6.77
Board and Slabs
Cellular glass.................................................................. 136 0.050 19.8 0.75
Glass fiber, organic bonded............................................ 64-140 0.036 27.7 0.96
Expanded perlite, organic bonded.................................. 16 0.052 19.3 1.26
Expanded rubber (rigid)................................................. 72 0.032 31.6 1.68
Expanded polystyrene, extruded (smooth skin surface)
(CFC-12 exp.) ............................................................. 29-56
25.6 2001 ASHRAE Fundamentals Handbook (SI)

Table 4 Typical Thermal Properties of Common Building and Insulating MaterialsDesign Valuesa (Continued)
Resistancec (R)
Conductivityb Conductance For Thickness Specific
Density, (k), (C), 1/k, Listed (1/C), Heat,
Description kg/m3 W/(mK) W/(m2 K) Km/W Km2 /W kJ/(kgK)
Expanded polystyrene, extruded (smooth skin surface)
(HCFC-142b exp.)h ..................................................... 29-56 0.029 34.7 1.21
Expanded polystyrene, molded beads............................ 16 0.037 26.7
20 0.036 27.7
24 0.035 28.9
28 0.035 28.9
32 0.033 30.2
Cellular polyurethane/polyisocyanuratei
(CFC-11 exp.) (unfaced) ............................................. 24 0.023-0.026 43.3-38.5 1.59
Cellular polyisocyanuratei (CFC-11 exp.)
(gas-permeable facers) ................................................ 24-40 0.023-0.026 43.3-38.5 0.92
Cellular polyisocyanuratej (CFC-11 exp.)
(gas-impermeable facers)............................................ 32 0.020 48.8 0.92
Cellular phenolic (closed cell) (CFC-11, CFC-113 exp.)k 32 0.017 56.8
Cellular phenolic (open cell).................................... 29-35 0.033 30.5
Mineral fiber with resin binder ................................ 240 0.042 23.9 0.71
Mineral fiberboard, wet felted
Core or roof insulation ............................................. 260-270 0.049 20.4
Acoustical tile .......................................................... 290 0.050 19.8 0.80
Acoustical tile .......................................................... 340 0.053 18.7
Mineral fiberboard, wet molded
Acoustical tilel ......................................................... 370 0.060 16.5 0.59
Wood or cane fiberboard
Acoustical tilel ...........................................12.7 mm 4.5 0.22 1.30
Acoustical tilel ...........................................19.0 mm 3.0 0.33
Interior finish (plank, tile)................................... 240 0.050 19.8 1.34
Cement fiber slabs (shredded wood with Portland
cement binder) ............................................................ 400-430 0.072-0.076 13.9-13.1
Cement fiber slabs (shredded wood with magnesia
oxysulfide binder) ....................................................... 350 0.082 12.1 1.30
Loose Fill
Cellulosic insulation (milled paper or wood pulp) ........ 37-51 0.039-0.046 25.6-21.7 1.38
Perlite, expanded............................................................ 32-66 0.039-0.045 25.6-22.9 1.09
66-120 0.045-0.052 22.9-19.4
120-180 0.052-0.060 19.4-16.6
Mineral fiber (rock, slag, or glass)g
approx. 95-130 mm .................................................. 9.6-32 1.94 0.71
approx. 170-220 mm................................................ 9.6-32 3.35
approx. 190-250 mm................................................ 9.6-32 3.87
approx. 260-350 mm................................................ 9.6-32 5.28
Mineral fiber (rock, slag, or glass)g
approx. 90 mm (closed sidewall application) .......... 32-56 2.1-2.5
Vermiculite, exfoliated ................................................... 110-130 0.068 14.8 1.34
64-96 0.063 15.7
Spray Applied
Polyurethane foam ......................................................... 24-40 0.023-0.026 43.3-38.5
Ureaformaldehyde foam ................................................ 11-26 0.032-0.040 31.5-24.7
Cellulosic fiber............................................................... 56-96 0.042-0.049 23.9-20.4
Glass fiber ...................................................................... 56-72 0.038-0.039 26.7-25.6
Reflective Insulation
Reflective material ( < 0.5) in center of 20 mm cavity
forms two 10 mm vertical air spacesm ........................ 1.76 0.57
METALS
(See Chapter 38, Table 3)
ROOFING
Asbestos-cement shingles .............................................. 1900 27.0 0.037 1.00
Asphalt roll roofing........................................................ 1100 36.9 0.026 1.51
Asphalt shingles ............................................................. 1100 12.9 0.077 1.26
Built-up roofing ..................................................10 mm 1100 17.0 0.058 1.46
Slate ....................................................................13 mm 114 0.009 1.26
Wood shingles, plain and plastic film faced .................. 6.0 0.166 1.30
PLASTERING MATERIALS
Cement plaster, sand aggregate...................................... 1860 0.72 1.39 0.84
Sand aggregate ..............................................10 mm 75.5 0.013 0.84
Sand aggregate ..............................................20 mm 37.8 0.026 0.84
Thermal and Water Vapor Transmission Data 25.7

Table 4 Typical Thermal Properties of Common Building and Insulating MaterialsDesign Valuesa (Continued)
Resistancec (R)
Conductivityb Conductance For Thickness Specific
Density, (k), (C), 1/k, Listed (1/C), Heat,
Description kg/m3 W/(mK) W/(m2 K) Km/W Km2 /W kJ/(kgK)
Gypsum plaster:
Lightweight aggregate ..................................13 mm 720 17.7 0.056
Lightweight aggregate ..................................16 mm 720 15.2 0.066
Lightweight aggregate on metal lath.............19 mm 12.1 0.083
Perlite aggregate............................................................. 720 0.22 4.64 1.34
Sand aggregate ......................................................... 1680 0.81 1.25 0.84
Sand aggregate ..............................................13 mm 1680 63.0 0.016
Sand aggregate ..............................................16 mm 1680 51.7 0.019
Sand aggregate on metal lath ........................19 mm 43.7 0.023
Vermiculite aggregate .............................................. 720 0.24 4.09
MASONRY MATERIALS
Masonry Units
Brick, fired clay ............................................................. 2400 1.21-1.47 0.83-0.68
2240 1.07-1.30 0.94-0.77
2080 0.92-1.12 1.08-0.89
1920 0.81-0.98 1.24-1.02 0.79
1760 0.71-0.85 1.42-1.18
1600 0.61-0.74 1.65-1.36
1440 0.52-0.62 1.93-1.61
1280 0.43-0.53 2.31-1.87
1120 0.36-0.45 2.77-2.23
Clay tile, hollow
1 cell deep ........................................................75 mm 7.10 0.14 0.88
1 cell deep ......................................................100 mm 5.11 0.20
2 cells deep.....................................................150 mm 3.75 0.27
2 cells deep.....................................................200 mm 3.07 0.33
2 cells deep.....................................................250 mm 2.56 0.39
3 cells deep.....................................................300 mm 2.27 0.44
Concrete blocksn, o
Limestone aggregate
200 mm, 16.3 kg, 2210 kg/m3 concrete, 2 cores......
Same with perlite filled cores ............................... 2.73 0.37
300 mm, 25 kg, 2210 kg/m3 concrete, 2 cores.........
Same with perlite filled cores ............................... 1.53 0.65
Normal mass aggregate (sand and gravel) 200 mm
15-16 kg, 2020-2180 kg/m3 concrete, 2 or 3 cores 5.1-5.8 0.20-0.17 0.92
Same with perlite filled cores ............................... 2.84 0.35
Same with vermiculite filled cores ....................... 3.0-4.1 0.34-0.24
300 mm, 22.7 kg, 2000 kg/m3 concrete, 2 cores...... 4.60 0.217 0.92
Medium mass aggregate (combinations of normal
and low mass aggregate) 200 mm, 12-13 kg,
1550-1790 kg/m3 concrete, 2 or 3 cores .................. 3.3-4.4 0.30-0.22
Same with perlite filled cores ............................... 1.5-2.5 0.65-0.41
Same with vermiculite filled cores ....................... 1.70 0.58
Same with molded EPS (beads) filled cores ......... 1.82 0.56
Same with molded EPS inserts in cores................ 2.10 0.47
Low mass aggregate (expanded shale, clay, slate or
slag, pumice) 150 mm
7.3-7.7 kg, 1360-1390 kg/m3 concrete, 2 or 3 cores 3.0-3.5 0.34-0.29
Same with perlite filled cores ............................... 1.36 0.74
Same with vermiculite filled cores ....................... 1.87 0.53
200 mm, 8.6-10.0 mm, 1150-1380 kg/m3 concrete, 1.8-3.1 0.56-0.33 0.88
Same with perlite filled cores ............................... 0.9-1.3 1.20-0.77
Same with vermiculite filled cores ....................... 1.1-1.5 0.93-0.69
Same with molded EPS (beads) filled cores ......... 1.19 0.85
Same with UF foam filled cores ........................... 1.25 0.79
Same with molded EPS inserts in cores................ 1.65 0.62
300 mm, 14.5-16.3 kg, 1280-1440 kg/m3 concrete,
2 or 3 cores............................................................ 2.2-2.5 0.46-0.40
Same with perlite filled cores ............................... 0.6-0.9 1.6-1.1
Same with vermiculite filled cores ....................... 0.97 1.0
Stone, lime, or sand
Quartzitic and sandstone ......................................... 2880 10.4 0.10
2560 6.2 0.16
2240 3.5 0.29
1920 1.9 0.53 0.79
Calcitic, dolomitic, limestone, marble, and granite .... 2880 4.3 0.23
2560 3.2 0.32
2240 2.3 0.43
1920 1.6 0.63 0.79
1600 1.1 0.90
25.8 2001 ASHRAE Fundamentals Handbook (SI)

Table 4 Typical Thermal Properties of Common Building and Insulating MaterialsDesign Valuesa (Continued)
Resistancec (R)
Conductivityb Conductance For Thickness Specific
Density, (k), (C), 1/k, Listed (1/C), Heat,
Description kg/m3 W/(mK) W/(m2 K) Km/W Km2 /W kJ/(kgK)
Gypsum partition tile
75 by 300 by 760 mm, solid..................................... 4.50 0.222 0.79
75 by 300 by 760 mm, 4 cells .................................. 4.20 0.238
100 by 300 by 760 mm, 3 cells ................................ 3.40 0.294
Concreteso
Sand and gravel or stone aggregate concretes (concretes 2400 1.4-2.9 0.69-0.35
with more than 50% quartz or quartzite sand have 2240 1.3-2.6 0.77-0.39 0.8-1.0
conductivities in the higher end of the range)............. 2080 1.0-1.9 0.99-053
Limestone concretes ...................................................... 2240 1.60 0.62
1920 1.14 0.88
1600 0.79 1.26
Gypsum-fiber concrete (87.5% gypsum, 12.5%
wood chips) 816 0.24 4.18 0.88
Cement/lime, mortar, and stucco ................................... 1920 1.40 0.71
1600 0.97 1.04
1280 0.65 1.54
Lightweight aggregate concretes
Expanded shale, clay, or slate; expanded slags; 1920 0.9-1.3 1.08-0.76
cinders; pumice (with density up to 1600 kg/m3); 1600 0.68-0.89 1.48-1.12 0.84
and scoria (sanded concretes have conductivities in 1280 0.48-0.59 2.10-1.69 0.84
the higher end of the range) ........................................ 960 0.30-0.36 3.30-2.77
640 0.18 5.40
Perlite, vermiculite, and polystyrene beads ................ 800 0.26-0.27 3.81-3.68
640 0.20-0.22 4.92-4.65 0.63-0.96
480 0.16 6.31
320 0.12 8.67
Foam concretes .............................................................. 1920 0.75 1.32
1600 0.60 1.66
1280 0.44 2.29
1120 0.36 2.77
Foam concretes and cellular concretes .......................... 960 0.30 3.33
640 0.20 4.92
320 0.12 8.67
SIDING MATERIALS (on flat surface)
Shingles
Asbestos-cement ......................................................... 1900 27.0 0.037
Wood, 400 mm, 190 mm exposure ............................. 6.53 0.15 1.30
Wood, double, 400 mm, 300 mm exposure ................ 4.77 0.21 1.17
Wood, plus insul. backer board, 8 mm........................ 4.03 0.25 1.30
Siding
Asbestos-cement, 6.4 mm, lapped .............................. 27.0 0.037 1.01
Asphalt roll siding....................................................... 36.9 0.026 1.47
Asphalt insulating siding (12.7 mm bed.)................... 3.92 0.26 1.47
Hardboard siding, 11 mm ........................................... 8.46 0.12 1.17
Wood, drop, 20 by 200 mm......................................... 7.21 0.14 1.17
Wood, bevel, 13 by 200 mm, lapped........................... 6.98 0.14 1.17
Wood, bevel, 19 by 250 mm, lapped........................... 5.40 0.18 1.17
Wood, plywood, 9.5 mm, lapped ................................ 9.60 0.10 1.22
Aluminum, steel, or vinylp, q, over sheathing
Hollow-backed ......................................................... 9.31 0.11 1.22q
Insulating-board backed...........................................
9.5 mm nominal ....................................................... 3.12 0.32 1.34
9.5 mm nominal, foil backed ................................... 1.93 0.52
Architectural (soda-lime float) glass.............................. 56.8 0.018 0.84
WOODS (12% moisture content)e,r
Hardwoods 1.63s
Oak.............................................................................. 659-749 0.16-0.18 6.2-5.5
Birch............................................................................ 682-726 0.167-0.176 6.0-5.7
Maple .......................................................................... 637-704 0.157-0.171 6.4-5.8
Ash .............................................................................. 614-670 0.153-0.164 6.5-6.1
Softwoods 1.63s
Southern pine .............................................................. 570-659 0.144-0.161 6.9-6.2
Douglas fir-Larch........................................................ 536-581 0.137-0.145 7.3-6.9
Southern cypress ......................................................... 502-514 0.130-0.132 7.7-7.6
Hem-Fir, Spruce-Pine-Fir ........................................... 392-502 0.107-0.130 9.3-7.7
West coast woods, Cedars........................................... 347-502 0.098-0.130 10.3-7.7
California redwood ..................................................... 392-448 0.107-0.118 9.4-8.5
SHEET 12 OF 12
DOC. NO. :
REV

CALCULATION SHEET OF HVAC SYSTEM CS-HVAC-01 0

ATTACHMENT 2. CALCULATION SHEET


Air Conditioning Summary
Area Air Flow Cooling Load
No. Building Location Room Height volume btuh/m2 Design Temp. Type
(m2) CFM (MBH)

1 Administration Ground Floor GF- Lobby, Resepsionist#1 290.0 3.2 928.0 5,280 24C+1
Zone GF-01 GF- Security Monitor#1 9.0 3.2 28.8 329 24C+1
GF- Ruang Tunggu#1 26.0 3.2 83.2 550 24C+1
Total 325.0 6,159 176.50 543 Split Duct

Zone GF-03 GF- Meeting#1 30.0 3.2 96.0 1,188 24C+1


GF- Sekretaris#1 5.0 3.2 16.0 62 24C+1
GF- Area Staff #1 301.0 3.2 963.2 3,301 24C+1
GF- Manager#1 12.0 3.2 38.4 493 24C+1
GF- Manager#2 12.0 3.2 38.4 447 24C+1
GF- Manager#3 12.0 3.2 38.4 447 24C+1
GF- Manager#4 12.0 3.2 38.4 447 24C+1
Total 384.0 6,385 204 531 Split Duct

Zone GF-02-2 GF- Area Staff #2 93.0 3.2 297.6 3,883 24C+1
GF- Storage HSE#1 17.0 3.2 54.4 392 24C+1
GF- Manager#5 12.0 3.2 38.4 370 24C+1
GF- Musholah#1 27.7 3.2 88.6 805 24C+1
GF- ATM # 1 17.5 3.2 56.0 343 24C+1
Total 167.2 5,793 79.00 472 Split Duct

Zone GF-02-1 GF- Training#1 98.5 3.2 315.2 3,069 24C+1


GF- Nurse#1 15.2 3.2 48.6 84 24C+1
GF- Clinic#1 43.7 3.2 139.8 1,087 24C+1
GF- Amblulance Driver#1 5.0 3.2 16.0 57 24C+1
Total 162.4 4,297 180 1,105 Split Duct

Zone GF-05 GF- Docter#1 16.0 3.2 51.2 823 16.60 1,038 24C+1 Wall Mounted
Zone GF-06 GF- Patient#1 21.3 3.2 68.2 171 5.00 235 24C+1 Wall Mounted
Zone GF-07 GF- Server#1 11.0 3.2 35.2 665 13.40 1,218 24C+1 Wall Mounted

First Floor 1F- Resepsionist#1 284.0 3.2 908.8 5,052 24C+1


Zone 1F-01 1F- Security Monitor#1 9.4 3.2 30.1 280 24C+1
1F- Ruang Tunggu#1 26.0 3.2 83.2 577 24C+1
1F GA#1 9.0 3.2 28.8 74
Total 328.4 5,983 145.40 443 Split Duct
Air Conditioning Summary
Area Air Flow Cooling Load
No. Building Location Room Height volume btuh/m2 Design Temp. Type
(m2) CFM (MBH)

Zone 1F-02 1F- Grand Meeting#1 38.0 3.2 121.6 1,126 24C+1
1F- Area Staff#1 293.5 3.2 939.2 4,390 24C+1
1F- Manager#1 12.0 3.2 38.4 537 22C+1
1F- Manager#2 12.0 3.2 38.4 447 24C+1
1F- Manager#3 12.0 3.2 38.4 447 24C+1
1F- Manager#4 12.0 3.2 38.4 447 24C+1
1F- File#1 24.0 3.2 76.8 419 24C+1
1F- File Storage#2 26.5 3.2 84.8 568 24C+1
Total 430.0 8,381 225 522 Split Duct

Zone 1F-03-1 1F- Meeting#1 49.5 3.2 158.4 1,331 24C+1


1F- Manager#5 12.0 3.2 38.4 491 24C+1
1F- Manager#6 12.0 3.2 38.4 491 24C+1
1F- Training#1 55.5 3.2 177.6 1,583 24C+1
Total 129.0 3,896 156.90 1,216 Split Duct

Zone 1F-03-2 1F- Area Staff#2 223.0 3.2 713.6 3,883 24C+1
1F- File Storage#1 12.5 3.2 40.0 392 24C+1
Total 235.5 4,275 114 484 Split Duct

Second Floor 2F- Lobby, Secretary#1 286.0 3.2 915.2 4,916 22C+1
Zone 2F-01 2F- Security Monitor#1 9.4 3.2 30.1 323 24C+1
2F- Exce Dining#1 25.0 3.2 80.0 784 24C+1
Total 320.4 6,023 137 427 Split Duct

Zone 2F-02 2F- Ruang Tunggu#1 164.5 3.2 526.4 1,540 24C+1
2F- Director#1 49.0 3.2 156.8 1,045 24C+1
2F- Komisaris#1 53.0 3.2 169.6 873 24C+1
2F- Komisaris#2 53.0 3.2 169.6 714 24C+1
2F- Director#2 35.0 3.2 112.0 718 24C+1
2F- Director#3 37.5 3.2 120.0 1,126 24C+1
2F- Director#4 40.7 3.2 130.2 937 24C+1
Total 432.7 6,953 207 477 Split Duct

Zone 2F-03 2F- Grand Meeting#1 100.0 3.2 320.0 2,658 24C+1
2F- Function#1 116.6 3.2 373.1 3,133 24C+1
Total 216.6 5,791 257 1,188 Split Duct
Air Conditioning Summary
Area Air Flow Cooling Load
No. Building Location Room Height volume btuh/m2 Design Temp. Type
(m2) CFM (MBH)

Zone 2F-04 2F- Director#5 34.0 3.2 108.8 1,117 24C+1


2F- Director#6 37.7 3.2 120.6 896 24C+1
2F- File Storage#1 28.0 3.2 89.6 769 24C+1
Total 99.7 2,782 63 633 Split Duct

Lantai 3 Zone 3F-01 3F-File Storage#1 24.0 3.2 76.8 520 24C+1
3F-Hall#1 260.0 3.2 832.0 4,435 24C+1
Total 284.0 4,955 143 502

Lantai 4 Zone 4F-01 4F-Lift Room# 4.0 3.2 12.8 787 16.40 4,100 24C+1 Wall Mounted
VENTILATION SUMMARY
Area Height Volume Ventilation Rated EF ESP Power Electricity
No. Building Code Room ACH Qty Type
(m2) (m) (m3) (CFM) (CFM) (In WG) (Watt) (V/Ph/Hz)
Administration
Lantai Dasar GF-1 Pompa 6.0 3.2 19.2 10 112.9 120.0
GF- Me 12.7 3.2 40.6 10 239.1 240.0
360.0 0.4 230 220V/1Ph/50Hz 1 Axial Fan - duct inline
GF- Toilet Male 16.0 3.2 51.2 10 301.2 310.0
GF- Toilet Female 16.0 3.2 51.2 10 301.2 310.0
620.0
GF- Wudhu 4.0 3.2 12.8 10 75.3 80.0
GF- Pantry 4.0 3.2 12.8 15 112.9 120.0
GF- Janitor 3.0 3.2 9.6 10 56.5 60.0
GF- Toilet Clinik 5.0 3.2 16.0 10 94.1 100.0 0.4 70 220V/1Ph/50Hz 1 Axial Fan - duct inline
360.0 0.4 230 220V/1Ph/50Hz 1 Axial Fan - duct inline
GF- Electric#1 (630 kva x 15 39.3 3.2 125.8 42.5 3144.0 3150.0 0.4 220V/1Ph/50Hz 1 Axial Fan - duct inline
cfm/kva = 3150 cfm) 1980

Lantai 1 1F- Pompa 6.0 3.2 19.2 10 112.9 120.0


1F- Me 12.7 3.2 40.6 10 239.1 240.0
360.0 0.4 230 220V/1Ph/50Hz 1 Axial Fan - duct inline
1F- Toilet Male 16.0 3.2 51.2 10 301.2 310.0
1F- Toilet Female 16.0 3.2 51.2 10 301.2 310.0
620.0 0.4 390 220V/1Ph/50Hz 1 Axial Fan - duct inline
1F- Pantry 1.2 7.0 3.2 22.4 15 197.6 200.0
1F- Janitor 1.2 3.0 3.2 9.6 10 56.5 60.0
254.1 260.0 0.4 170 220V/1Ph/50Hz 1 Axial Fan - duct inline

1F- Pantry 1.1 7.0 3.2 22.4 15 197.6 200.0


1F- Janitor 1.1 3.0 3.2 9.6 10 56.5 60.0
260.0 0.4 170 220V/1Ph/50Hz 1 Axial Fan - duct inline

Lantai 2 2F- Pompa 6.0 3.2 19.2 10 112.9 120.0


2F- Me 12.7 3.2 40.6 10 239.1 240.0
360.0
2F- Toilet Lobby 1 5.0 3.2 16.0 10 94.1 100.0
2F- Toilet Lobby 2 5.0 3.2 16.0 10 94.1 100.0
200.0 0.4 130 220V/1Ph/50Hz 1 Axial Fan - duct inline
2F- Toilet Komisaris #1 4.0 3.2 12.8 10 75.3 80.0
2F- Toilet Komisaris #2 4.0 3.2 12.8 10 75.3 80.0
160.0 0.2 60 220V/1Ph/50Hz 1 Axial Fan - duct inline
2F- Pantry 7.0 3.2 22.4 15 197.6 200.0
VENTILATION SUMMARY
Area Height Volume Ventilation Rated EF ESP Power Electricity
No. Building Code Room ACH Qty Type
(m2) (m) (m3) (CFM) (CFM) (In WG) (Watt) (V/Ph/Hz)

2F- Janitor 3.0 3.2 9.6 15 84.7 90.0


290.0 0.4 190 220V/1Ph/50Hz 1 Axial Fan - duct inline
2F- Toilet Male 16.0 3.2 51.2 10 301.2 310.0 0.4 200 220V/1Ph/50Hz 1 Axial Fan - duct inline
2F- Toilet Female 16.0 3.2 51.2 10 301.2 310.0 0.4 200 220V/1Ph/50Hz 1 Axial Fan - duct inline

Lantai 3 3F- Pompa 6.0 3.2 19.2 10 112.9 120.0


3F- Me 12.7 3.2 40.6 10 239.1 240.0
360.0 0.4 230 220V/1Ph/50Hz Axial Fan - duct inline
Fresh Air Fan - 1 7671.0 0.45 5400 380V/3Ph/50Hz Axial Fan - duct inline
Fresh Air Fan - 2 7577.0 0.45 5340 380V/3Ph/50Hz Axial Fan - duct inline
Air System Sizing Summary for IU-ADM-GF01 LOBBY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:03PM

Air System Information


Air System Name .................... IU-ADM-GF01 LOBBY Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 3498.3 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 14.7 Tons Load occurs at ................................................... Jan 1600
Total coil load ...................................................... 176.5 MBH OA DB / WB .................................................... 91.0 / 80.5 F
Sensible coil load ................................................ 128.3 MBH Entering DB / WB ............................................ 78.3 / 67.5 F
Coil CFM at Jan 1600 .......................................... 6483 CFM Leaving DB / WB ............................................. 59.9 / 58.9 F
Max block CFM .................................................... 6483 CFM Coil ADP .................................................................... 57.8 F
Sum of peak zone CFM ....................................... 6483 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.727 Resulting RH ................................................................ 55 %
ft/Ton .................................................................. 237.8 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 50.5 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 6483 CFM Fan motor BHP .......................................................... 0.76 BHP
Standard CFM ...................................................... 6445 CFM Fan motor kW ............................................................ 0.56 kW
Actual max CFM/ft ............................................... 1.85 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................ 632 CFM CFM/person ............................................................. 16.63 CFM/person
CFM/ft .................................................................. 0.18 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-GF01 LOBBY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:03PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 820 ft 54813 - 820 ft - -
Wall Transmission 517 ft 1807 - 517 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 820 ft 13365 - 820 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 224 ft 9618 - 224 ft 0 -
Floor Transmission 161 ft 0 - 161 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 463 W 1009 - 0 0 -
Task Lighting 250 W 778 - 0 0 -
Electric Equipment 2400 W 7949 - 0 0 -
People 38 7531 7197 0 0 0
Infiltration - 4727 11826 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10160 1902 0% 0 0
>> Total Zone Loads - 111757 20925 - 0 0
Zone Conditioning - 102492 20925 - 0 0
Plenum Wall Load 20% 2761 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 30% 474 - 0 0 -
Return Fan Load 6483 CFM 0 - 6483 CFM 0 -
Ventilation Load 632 CFM 9508 27232 632 CFM -679 0
Supply Fan Load 6483 CFM 1922 - 6483 CFM -1922 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 10% 11176 - 10% 0 -
>> Total System Loads - 128334 48157 - -2601 0
Central Cooling Coil - 128334 48182 - -2601 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 128334 48182 - -2601 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-GF01 LOBBY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:03PM

Air System Information


Air System Name .................... IU-ADM-GF01 LOBBY Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 3498.3 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone GF-01 111.8 6159 6159 Jan 1600 0.0 3498.3 1.76

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone GF-01
GF-LOBBY 1 96.4 Jan 1600 5280 0.0 3121.5 1.69
GF-RUANG TUNGGU#1 1 10.0 Dec 1500 550 0.0 279.9 1.97
GF-SECURITY MONITOR#1 1 6.0 Jan 1800 329 0.0 96.9 3.39

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-GF01 LOBBY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:03PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-LOBBY '' IN ZONE '' Zone GF-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 756 ft 49792 - 756 ft - -
Wall Transmission 452 ft 1437 - 452 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 756 ft 12574 - 756 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 224 ft 9618 - 224 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 204 W 444 - 0 0 -
Task Lighting 250 W 778 - 0 0 -
Electric Equipment 800 W 2538 - 0 0 -
People 29 5740 5947 0 0 0
Infiltration - 4685 11721 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 8761 1767 0% 0 0
>> Total Zone Loads - 96367 19434 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-LOBBY '' IN ZONE '' Zone GF-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 214 0.403 - 791 - 0
WINDOW 1 378 1.212 0.880 6287 25154 0
DOOR 22 0.300 - 89 - 0
DOOR GLASS 43 0.580 0.880 343 2867 0
WNW EXPOSURE
WALL 214 0.403 - 646 - 0
WINDOW 1 378 1.212 0.880 6287 24638 0
DOOR 22 0.300 - 89 - 0
DOOR GLASS 43 0.580 0.880 343 2808 0
ENE EXPOSURE
WALL 24 0.403 - 0 - 0
DOOR 30 0.300 - 124 - 0
DOOR GLASS 65 0.580 0.880 514 2442 0

Hourly Analysis Program v.4.3 Page 1 of 3


Space Design Load Summary for IU-ADM-GF01 LOBBY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:03PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' GF-RUANG TUNGGU#1 '' IN ZONE '' Zone GF-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 5717 - 65 ft - -
Wall Transmission 65 ft 345 - 65 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 65 ft 742 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 632 - 0 0 -
People 7 1282 840 0 0 0
Infiltration - 40 108 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 913 95 0% 0 0
>> Total Zone Loads - 10045 1043 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' GF-RUANG TUNGGU#1 '' IN ZONE '' Zone GF-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 65 0.403 - 345 - 0
WINDOW 1 65 0.892 0.631 742 5717 0

Hourly Analysis Program v.4.3 Page 2 of 3


Space Design Load Summary for IU-ADM-GF01 LOBBY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:03PM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' GF-SECURITY MONITOR#1 '' IN ZONE '' Zone GF-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 88.5 F / 79.9 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 86 W 190 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1400 W 4777 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 546 41 0% 0 0
>> Total Zone Loads - 6003 451 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' GF-SECURITY MONITOR#1 '' IN ZONE '' Zone GF-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

Hourly Analysis Program v.4.3 Page 3 of 3


Ventilation Sizing Summary for IU-ADM-GF01 LOBBY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:03PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 632 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 570 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space GF-RUANG TUNGGU#1
Critical Space Outdoor Air Fraction ('Z') 0.191
Uncorrected Outdoor Air Fraction ('X') 0.093
Corrected Outdoor Air Fraction ('Y') 0.103
Required System Ventilation Airflow (CFM) 632

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone GF-01
GF-LOBBY 1 3121.5 29.0 5280.0 15.00 0.00 0.0 0.0 435.0 0.082 541.9
GF-RUANG TUNGGU#1 1 279.9 7.0 550.4 15.00 0.00 0.0 0.0 105.0 0.191 56.5
GF-SECURITY MONITOR#1 1 96.9 2.0 328.9 15.00 0.00 0.0 0.0 30.0 0.091 33.8
Totals (incl. Space Multipliers) 6159.2 570.0 0.191 632.1

Hourly Analysis Program v.4.3 Page 1 of 1


System Psychrometrics for IU-ADM-GF01 LOBBY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:03PM

January DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 91.0 0.02026 632 400 9508 27232
Vent - Return Mixing Outlet 78.3 0.01202 6483 805 - -
Central Cooling Coil Outlet 59.9 0.01044 6483 805 128334 48182
Central Heating Coil Outlet 59.9 0.01044 6483 805 0 -
Supply Fan Outlet 60.2 0.01044 6483 805 1922 -
Cold Supply Duct Outlet 61.9 0.01044 6159 805 - -
Zone Air - 77.4 0.01116 6159 851 102492 20925
Return Plenum Outlet 77.9 0.01116 6159 851 3235 -
Duct Leakage Air Outlet 60.2 0.01044 324 805 - -
Return Duct Outlet 77.0 0.01113 6483 848 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-01 111757 Cooling 102492 77.4 6159 851 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-GF01 LOBBY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:03PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 632 400 679 0
Vent - Return Mixing Outlet 70.1 0.00813 6483 486 - -
Central Cooling Coil Outlet 69.7 0.00813 6483 486 2601 0
Central Heating Coil Outlet 69.7 0.00813 6483 486 0 -
Supply Fan Outlet 70.0 0.00813 6483 486 1922 -
Cold Supply Duct Outlet 70.0 0.00813 6159 486 - -
Zone Air - 70.0 0.00813 6159 495 0 0
Return Plenum Outlet 70.0 0.00813 6159 495 0 -
Duct Leakage Air Outlet 70.0 0.00813 324 486 - -
Return Duct Outlet 70.0 0.00813 6483 495 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-01 0 Deadband 0 70.0 6159 495 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-GF01 LOBBY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:03PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: January DESIGN COOLING DAY, 1600
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet
8. Return Duct Outlet 1
0.020

Specific Humidity ( lb/lb )


0.018
0.016
0.014
2
3 45
6 0.012
8 7
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-GF02 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:08PM

Air System Information


Air System Name .................. IU-ADM-GF02 NORTH1 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 1748.1 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 15.0 Tons Load occurs at ................................................... Feb 1600
Total coil load ...................................................... 179.5 MBH OA DB / WB .................................................... 91.0 / 80.5 F
Sensible coil load ................................................ 101.5 MBH Entering DB / WB ............................................ 81.9 / 71.9 F
Coil CFM at Feb 1600 .......................................... 4513 CFM Leaving DB / WB ............................................. 61.0 / 60.1 F
Max block CFM .................................................... 4513 CFM Coil ADP .................................................................... 58.6 F
Sum of peak zone CFM ....................................... 4513 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.566 Resulting RH ................................................................ 58 %
ft/Ton .................................................................. 116.9 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) .......................................................... 102.7 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 4513 CFM Fan motor BHP .......................................................... 0.53 BHP
Standard CFM ...................................................... 4487 CFM Fan motor kW ............................................................ 0.39 kW
Actual max CFM/ft ............................................... 2.58 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1560 CFM CFM/person ............................................................. 15.00 CFM/person
CFM/ft .................................................................. 0.89 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-GF02 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:08PM

Air System Information


Air System Name .................. IU-ADM-GF02 NORTH1 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 1748.1 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone GF-02A 78.2 4288 4288 Apr 1500 0.0 1748.1 2.45

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone GF-02A
GF-CLINIC#1 1 19.7 Apr 1500 1078 0.0 470.4 2.29
GF-NURSE#1 1 1.5 Jan 1700 84 0.0 163.6 0.51
GF-AMBULANCE DRIVER#1 1 1.0 Jan 1700 57 0.0 53.8 1.06
GF-RUANG TRAINING#1 1 56.0 Apr 1500 3069 0.0 1060.2 2.89

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-GF02 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:08PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 1560 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM)
Zone GF-02A
GF-CLINIC#1 1 470.4 3.0 1078.2 15.00 0.00 0.0 0.0 45.0
GF-NURSE#1 1 163.6 2.0 83.9 15.00 0.00 0.0 0.0 30.0
GF-AMBULANCE DRIVER#1 1 53.8 1.0 56.8 15.00 0.00 0.0 0.0 15.0
GF-RUANG TRAINING#1 1 1060.2 98.0 3068.7 15.00 0.00 0.0 0.0 1470.0
Totals (incl. Space Multipliers) 4287.7 1560.0

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-GF02 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:08PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Feb 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 323 ft 30959 - 323 ft - -
Wall Transmission 484 ft 2397 - 484 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 323 ft 3956 - 323 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 54 ft 1319 - 54 ft 0 -
Floor Transmission 291 ft 0 - 291 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1517 W 3305 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 6345 - 0 0 -
People 104 19373 12820 0 0 0
Infiltration - 230 541 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 6788 1336 0% 0 0
>> Total Zone Loads - 74672 14697 - 0 0
Zone Conditioning - 70341 14697 - 0 0
Plenum Wall Load 20% 1355 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 30% 1553 - 0 0 -
Return Fan Load 4513 CFM 0 - 4513 CFM 0 -
Ventilation Load 1560 CFM 23210 63276 1560 CFM -1675 0
Supply Fan Load 4513 CFM 1338 - 4513 CFM -1338 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 3734 - 5% 0 -
>> Total System Loads - 101529 77973 - -3013 0
Central Cooling Coil - 101529 77976 - -3013 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 101529 77976 - -3013 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-GF02 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:08PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-CLINIC#1 '' IN ZONE '' Zone GF-02A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10522 - 97 ft - -
Wall Transmission 291 ft 1658 - 291 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 97 ft 853 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 54 ft 2019 - 54 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 936 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 55 152 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1789 77 0% 0 0
>> Total Zone Loads - 19679 844 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-CLINIC#1 '' IN ZONE '' Zone GF-02A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 118 0.403 - 444 - 0
WINDOW 1 97 0.892 0.631 853 10522 0
NNE EXPOSURE
WALL 172 0.403 - 1214 - 0
DOOR 11 0.300 - 32 - 0
DOOR GLASS 43 0.580 0.880 246 1740 0

Hourly Analysis Program v.4.3 Page 1 of 4


Space Design Load Summary for IU-ADM-GF02 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:08PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' GF-NURSE#1 '' IN ZONE '' Zone GF-02A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 379 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 637 - 0 0 -
People 2 377 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 139 24 0% 0 0
>> Total Zone Loads - 1532 264 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' GF-NURSE#1 '' IN ZONE '' Zone GF-02A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

Hourly Analysis Program v.4.3 Page 2 of 4


Space Design Load Summary for IU-ADM-GF02 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:08PM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' GF-AMBULANCE DRIVER#1 '' IN ZONE '' Zone GF-02A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 48 W 105 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 637 - 0 0 -
People 1 201 205 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 94 21 0% 0 0
>> Total Zone Loads - 1037 226 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' GF-AMBULANCE DRIVER#1 '' IN ZONE '' Zone GF-02A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

Hourly Analysis Program v.4.3 Page 3 of 4


Space Design Load Summary for IU-ADM-GF02 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:08PM

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' GF-RUANG TRAINING#1 '' IN ZONE '' Zone GF-02A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 226 ft 24551 - 226 ft - -
Wall Transmission 194 ft 647 - 194 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 226 ft 1991 - 226 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 864 W 1871 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1200 W 3789 - 0 0 -
People 98 17944 11760 0 0 0
Infiltration - 123 342 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 5092 1210 0% 0 0
>> Total Zone Loads - 56008 13312 - 0 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' GF-RUANG TRAINING#1 '' IN ZONE '' Zone GF-02A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 194 0.403 - 647 - 0
WINDOW 1 226 0.892 0.631 1991 24551 0

Hourly Analysis Program v.4.3 Page 4 of 4


System Psychrometrics for IU-ADM-GF02 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:08PM

February DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 91.0 0.02026 1560 400 23210 63276
Vent - Return Mixing Outlet 81.9 0.01463 4513 803 - -
Central Cooling Coil Outlet 61.0 0.01097 4513 803 101529 77976
Central Heating Coil Outlet 61.0 0.01097 4513 803 0 -
Supply Fan Outlet 61.2 0.01097 4513 803 1338 -
Cold Supply Duct Outlet 62.0 0.01097 4288 803 - -
Zone Air - 77.3 0.01170 4288 1027 70341 14697
Return Plenum Outlet 78.0 0.01170 4288 1027 2907 -
Duct Leakage Air Outlet 61.2 0.01097 226 803 - -
Return Duct Outlet 77.1 0.01166 4513 1016 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-02A 74672 Cooling 70341 77.3 4288 1027 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-GF02 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:08PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 1560 400 1675 0
Vent - Return Mixing Outlet 70.3 0.00813 4513 413 - -
Central Cooling Coil Outlet 69.7 0.00813 4513 413 3013 0
Central Heating Coil Outlet 69.7 0.00813 4513 413 0 -
Supply Fan Outlet 70.0 0.00813 4513 413 1338 -
Cold Supply Duct Outlet 70.0 0.00813 4288 413 - -
Zone Air - 70.0 0.00813 4288 421 0 0
Return Plenum Outlet 70.0 0.00813 4288 421 0 -
Duct Leakage Air Outlet 70.0 0.00813 226 413 - -
Return Duct Outlet 70.0 0.00813 4513 421 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-02A 0 Deadband 0 70.0 4288 421 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-GF02 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:08PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: February DESIGN COOLING DAY, 1600
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet
8. Return Duct Outlet 1
0.020

Specific Humidity ( lb/lb )


0.018
2 0.016
0.014
67
35 8 0.012
4 0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

Air System Information


Air System Name .................. IU-ADM-GF02 NORTH2 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 1762.1 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .......................................................... 6.6 Tons Load occurs at .................................................. Dec 0800
Total coil load ........................................................ 79.0 MBH OA DB / WB .................................................... 78.6 / 77.8 F
Sensible coil load .................................................. 63.1 MBH Entering DB / WB ............................................ 77.0 / 66.8 F
Coil CFM at Dec 0800 .......................................... 3673 CFM Leaving DB / WB ............................................. 61.0 / 60.1 F
Max block CFM .................................................... 3673 CFM Coil ADP .................................................................... 59.2 F
Sum of peak zone CFM ....................................... 3673 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.798 Resulting RH ................................................................ 56 %
ft/Ton .................................................................. 267.6 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 44.8 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 3673 CFM Fan motor BHP .......................................................... 0.43 BHP
Standard CFM ...................................................... 3651 CFM Fan motor kW ............................................................ 0.32 kW
Actual max CFM/ft ............................................... 2.08 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................ 267 CFM CFM/person ............................................................. 15.71 CFM/person
CFM/ft .................................................................. 0.15 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

Air System Information


Air System Name .................. IU-ADM-GF02 NORTH2 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 1762.1 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone GF-02B 60.9 3489 3489 Jan 0800 0.0 1762.1 1.98

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone GF-02B
GF-AREA STAFF#2 1 26.4 Jan 0800 1445 0.0 1001.0 1.44
GF-STORAGE-HSE#1 1 9.6 Jan 0800 526 0.0 204.5 2.57
GF-MANAGER#5 1 6.8 Jan 0800 370 0.0 129.2 2.87
GF-MUSHOLA#1 1 14.7 Jan 0800 805 0.0 298.2 2.70
GF-ATM#1 1 6.3 Apr 1600 343 0.0 129.2 2.65

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................... 267 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM)
Zone GF-02B
GF-AREA STAFF#2 1 1001.0 8.0 1445.2 15.00 0.00 0.0 0.0 120.0
GF-STORAGE-HSE#1 1 204.5 0.0 526.1 0.00 0.06 0.0 0.0 12.1
GF-MANAGER#5 1 129.2 3.0 370.1 15.00 0.00 0.0 0.0 45.0
GF-MUSHOLA#1 1 298.2 5.0 805.3 15.00 0.00 0.0 0.0 75.0
GF-ATM#1 1 129.2 1.0 342.6 15.00 0.00 0.0 0.0 15.0
Totals (incl. Space Multipliers) 3489.3 267.1

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 78.6 F / 77.8 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 323 ft 36679 - 323 ft - -
Wall Transmission 722 ft 2220 - 722 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 323 ft 1277 - 323 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 31 ft 570 - 31 ft 0 -
Floor Transmission 344 ft 0 - 344 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1370 W 2810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2800 W 8474 - 0 0 -
People 17 2825 3061 0 0 0
Infiltration - 60 680 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 5492 374 0% 0 0
>> Total Zone Loads - 60408 4115 - 0 0
Zone Conditioning - 56065 4115 - 0 0
Plenum Wall Load 20% 1009 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 30% 1403 - 0 0 -
Return Fan Load 3673 CFM 0 - 3673 CFM 0 -
Ventilation Load 267 CFM 503 11796 267 CFM -287 0
Supply Fan Load 3673 CFM 1089 - 3673 CFM -1089 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 3020 - 5% 0 -
>> Total System Loads - 63089 15911 - -1376 0
Central Cooling Coil - 63089 15924 - -1376 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 63089 15924 - -1376 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-AREA STAFF#2 '' IN ZONE '' Zone GF-02B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 14666 - 129 ft - -
Wall Transmission 301 ft 1143 - 301 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 129 ft 626 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 636 W 1304 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1600 W 4842 - 0 0 -
People 8 1354 1641 0 0 0
Infiltration - 44 372 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2398 201 0% 0 0
>> Total Zone Loads - 26377 2214 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-AREA STAFF#2 '' IN ZONE '' Zone GF-02B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 301 0.403 - 1143 - 0
WINDOW 1 129 0.892 0.631 626 14666 0

Hourly Analysis Program v.4.3 Page 1 of 5


Space Design Load Summary for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' GF-STORAGE-HSE#1 '' IN ZONE '' Zone GF-02B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 7333 - 65 ft - -
Wall Transmission 43 ft 114 - 43 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 65 ft 313 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 354 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 605 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 9 76 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 873 8 0% 0 0
>> Total Zone Loads - 9602 84 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' GF-STORAGE-HSE#1 '' IN ZONE '' Zone GF-02B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 43 0.403 - 114 - 0
WINDOW 1 65 0.892 0.631 313 7333 0

Hourly Analysis Program v.4.3 Page 2 of 5


Space Design Load Summary for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' GF-MANAGER#5 '' IN ZONE '' Zone GF-02B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 32 ft 3666 - 32 ft - -
Wall Transmission 65 ft 240 - 65 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 32 ft 157 - 32 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 354 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1211 - 0 0 -
People 3 508 615 0 0 0
Infiltration - 6 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 614 66 0% 0 0
>> Total Zone Loads - 6755 730 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' GF-MANAGER#5 '' IN ZONE '' Zone GF-02B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 65 0.403 - 240 - 0
WINDOW 1 32 0.892 0.631 157 3666 0

Hourly Analysis Program v.4.3 Page 3 of 5


Space Design Load Summary for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' GF-MUSHOLA#1 '' IN ZONE '' Zone GF-02B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10999 - 97 ft - -
Wall Transmission 54 ft 126 - 54 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 97 ft 470 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 354 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 605 - 0 0 -
People 5 794 600 0 0 0
Infiltration - 13 111 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1336 71 0% 0 0
>> Total Zone Loads - 14698 782 - 0 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' GF-MUSHOLA#1 '' IN ZONE '' Zone GF-02B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 54 0.403 - 126 - 0
WINDOW 1 97 0.892 0.631 470 10999 0

Hourly Analysis Program v.4.3 Page 4 of 5


Space Design Load Summary for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' GF-ATM#1 '' IN ZONE '' Zone GF-02B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.0 F / 78.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 259 ft 1888 - 259 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 31 ft 1844 - 31 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 216 W 471 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1269 - 0 0 -
People 1 198 205 0 0 0
Infiltration - 15 27 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 568 23 0% 0 0
>> Total Zone Loads - 6252 255 - 0 0

TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' GF-ATM#1 '' IN ZONE '' Zone GF-02B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 215 0.403 - 1670 - 0
WNW EXPOSURE
WALL 44 0.403 - 218 - 0
DOOR 10 0.300 - 28 - 0
DOOR GLASS 22 0.580 0.880 121 1694 0

Hourly Analysis Program v.4.3 Page 5 of 5


System Psychrometrics for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

December DESIGN COOLING DAY, 0800

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 78.6 0.02050 267 400 503 11796
Vent - Return Mixing Outlet 77.0 0.01182 3673 906 - -
Central Cooling Coil Outlet 61.0 0.01090 3673 906 63089 15924
Central Heating Coil Outlet 61.0 0.01090 3673 906 0 -
Supply Fan Outlet 61.3 0.01090 3673 906 1089 -
Cold Supply Duct Outlet 62.1 0.01090 3489 906 - -
Zone Air - 77.1 0.01115 3489 949 56065 4115
Return Plenum Outlet 77.7 0.01115 3489 949 2412 -
Duct Leakage Air Outlet 61.3 0.01090 184 906 - -
Return Duct Outlet 76.9 0.01114 3673 946 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-02B 60408 Cooling 56065 77.1 3489 949 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 267 400 287 0
Vent - Return Mixing Outlet 70.1 0.00813 3673 520 - -
Central Cooling Coil Outlet 69.7 0.00813 3673 520 1376 0
Central Heating Coil Outlet 69.7 0.00813 3673 520 0 -
Supply Fan Outlet 70.0 0.00813 3673 520 1089 -
Cold Supply Duct Outlet 70.0 0.00813 3489 520 - -
Zone Air - 70.0 0.00813 3489 529 0 0
Return Plenum Outlet 70.0 0.00813 3489 529 0 -
Duct Leakage Air Outlet 70.0 0.00813 184 520 - -
Return Duct Outlet 70.0 0.00813 3673 529 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-02B 0 Deadband 0 70.0 3489 529 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-GF02 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:15PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: December DESIGN COOLING DAY, 0800
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet 1
8. Return Duct Outlet
0.020

Specific Humidity ( lb/lb )


0.018
0.016
0.014
2
35 7 0.012
8
4 6
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

Air System Information


Air System Name .................... IU-ADM-GF03 SOUTH Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 4133.3 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 17.0 Tons Load occurs at .................................................. Dec 1500
Total coil load ...................................................... 203.9 MBH OA DB / WB .................................................... 90.4 / 80.6 F
Sensible coil load ................................................ 136.0 MBH Entering DB / WB ............................................ 79.8 / 69.3 F
Coil CFM at Dec 1500 .......................................... 6722 CFM Leaving DB / WB ............................................. 61.0 / 60.0 F
Max block CFM .................................................... 6722 CFM Coil ADP .................................................................... 58.9 F
Sum of peak zone CFM ....................................... 6722 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.667 Resulting RH ................................................................ 57 %
ft/Ton .................................................................. 243.3 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 49.3 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 6722 CFM Fan motor BHP .......................................................... 0.78 BHP
Standard CFM ...................................................... 6682 CFM Fan motor kW ............................................................ 0.58 kW
Actual max CFM/ft ............................................... 1.63 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1185 CFM CFM/person ............................................................. 15.00 CFM/person
CFM/ft .................................................................. 0.29 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

Air System Information


Air System Name .................... IU-ADM-GF03 SOUTH Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 4133.3 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone GF-03 114.8 6386 6386 Dec 1500 0.0 4133.3 1.54

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone GF-03
GF-MEETING#1 1 21.7 Dec 1500 1188 0.0 322.9 3.68
GF-SECRETARIS#1 1 1.1 Jan 1700 62 0.0 53.8 1.16
GF-AREA STAFF#1 1 60.2 Jun 1000 3301 0.0 3239.9 1.02
GF-MANAGER#1 1 9.0 Dec 1500 493 0.0 129.2 3.81
GF-MANAGER#2 1 8.2 Dec 1500 447 0.0 129.2 3.46
GF-MANAGER#3 1 8.2 Dec 1500 447 0.0 129.2 3.46
GF-MANAGER#4 1 8.2 Dec 1500 447 0.0 129.2 3.46

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 1185 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM)
Zone GF-03
GF-MEETING#1 1 322.9 24.0 1188.4 15.00 0.00 0.0 0.0 360.0
GF-SECRETARIS#1 1 53.8 1.0 62.4 15.00 0.00 0.0 0.0 15.0
GF-AREA STAFF#1 1 3239.9 42.0 3300.6 15.00 0.00 0.0 0.0 630.0
GF-MANAGER#1 1 129.2 3.0 492.6 15.00 0.00 0.0 0.0 45.0
GF-MANAGER#2 1 129.2 3.0 447.3 15.00 0.00 0.0 0.0 45.0
GF-MANAGER#3 1 129.2 3.0 447.3 15.00 0.00 0.0 0.0 45.0
GF-MANAGER#4 1 129.2 3.0 447.3 15.00 0.00 0.0 0.0 45.0
Totals (incl. Space Multipliers) 6385.7 1185.0

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 767 ft 44728 - 767 ft - -
Wall Transmission 1235 ft 7863 - 1235 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 767 ft 8806 - 767 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 678 ft 0 - 678 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 3840 W 8317 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6000 W 18946 - 0 0 -
People 79 15122 14159 0 0 0
Infiltration - 598 1540 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10438 1570 0% 0 0
>> Total Zone Loads - 114818 17268 - 0 0
Zone Conditioning - 104682 17268 - 0 0
Plenum Wall Load 20% 3354 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 30% 3931 - 0 0 -
Return Fan Load 6722 CFM 0 - 6722 CFM 0 -
Ventilation Load 1185 CFM 16336 50616 1185 CFM -1272 0
Supply Fan Load 6722 CFM 1993 - 6722 CFM -1993 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 5741 - 5% 0 -
>> Total System Loads - 136037 67884 - -3265 0
Central Cooling Coil - 136037 67867 - -3265 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 136037 67867 - -3265 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-MEETING#1 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 11434 - 129 ft - -
Wall Transmission 43 ft 77 - 43 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 129 ft 1483 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 470 W 1019 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 24 4395 2880 0 0 0
Infiltration - 47 120 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1972 300 0% 0 0
>> Total Zone Loads - 21689 3300 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-MEETING#1 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 43 0.403 - 77 - 0
WINDOW 1 129 0.892 0.631 1483 11434 0

Hourly Analysis Program v.4.3 Page 1 of 7


Space Design Load Summary for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' GF-SECRETARIS#1 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 86 W 189 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 637 - 0 0 -
People 1 201 205 0 0 0
Infiltration - 8 17 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 103 22 0% 0 0
>> Total Zone Loads - 1138 245 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' GF-SECRETARIS#1 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

Hourly Analysis Program v.4.3 Page 2 of 7


Space Design Load Summary for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' GF-AREA STAFF#1 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 74.6 F / 73.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 452 ft 29508 - 452 ft - -
Wall Transmission 797 ft 1113 - 797 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 452 ft -385 - 452 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 2592 W 5414 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3800 W 11664 - 0 0 -
People 42 7465 8613 0 0 0
Infiltration - -13 615 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 5476 923 0% 0 0
>> Total Zone Loads - 60241 10151 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' GF-AREA STAFF#1 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 258 0.403 - 450 - 0
SSW EXPOSURE
WALL 237 0.403 - -45 - 0
WINDOW 1 129 0.892 0.631 -110 1649 0
NNE EXPOSURE
WALL 301 0.403 - 708 - 0
WINDOW 1 323 0.892 0.631 -275 27858 0

Hourly Analysis Program v.4.3 Page 3 of 7


Space Design Load Summary for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' GF-MANAGER#1 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 40 ft 3573 - 40 ft - -
Wall Transmission 218 ft 1896 - 218 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 40 ft 463 - 40 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 817 66 0% 0 0
>> Total Zone Loads - 8991 730 - 0 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' GF-MANAGER#1 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 151 0.403 - 1488 - 0
SSW EXPOSURE
WALL 67 0.403 - 408 - 0
WINDOW 1 40 0.892 0.631 463 3573 0

Hourly Analysis Program v.4.3 Page 4 of 7


Space Design Load Summary for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' GF-MANAGER#2 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0

TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' GF-MANAGER#2 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0

Hourly Analysis Program v.4.3 Page 5 of 7


Space Design Load Summary for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' GF-MANAGER#3 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0

TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' GF-MANAGER#3 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0

Hourly Analysis Program v.4.3 Page 6 of 7


Space Design Load Summary for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' GF-MANAGER#4 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0

TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' GF-MANAGER#4 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0

Hourly Analysis Program v.4.3 Page 7 of 7


System Psychrometrics for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

December DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 90.4 0.02049 1185 400 16336 50616
Vent - Return Mixing Outlet 79.8 0.01304 6722 956 - -
Central Cooling Coil Outlet 61.0 0.01090 6722 956 136037 67867
Central Heating Coil Outlet 61.0 0.01090 6722 956 0 -
Supply Fan Outlet 61.2 0.01090 6722 956 1993 -
Cold Supply Duct Outlet 62.1 0.01090 6386 956 - -
Zone Air - 77.4 0.01147 6386 1082 104682 17268
Return Plenum Outlet 78.4 0.01147 6386 1082 7285 -
Duct Leakage Air Outlet 61.2 0.01090 336 956 - -
Return Duct Outlet 77.6 0.01144 6722 1075 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-03 114818 Cooling 104682 77.4 6386 1082 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 1185 400 1272 0
Vent - Return Mixing Outlet 70.2 0.00813 6722 439 - -
Central Cooling Coil Outlet 69.7 0.00813 6722 439 3265 0
Central Heating Coil Outlet 69.7 0.00813 6722 439 0 -
Supply Fan Outlet 70.0 0.00813 6722 439 1993 -
Cold Supply Duct Outlet 70.0 0.00813 6386 439 - -
Zone Air - 70.0 0.00813 6386 447 0 0
Return Plenum Outlet 70.0 0.00813 6386 447 0 -
Duct Leakage Air Outlet 70.0 0.00813 336 439 - -
Return Duct Outlet 70.0 0.00813 6722 447 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-03 0 Deadband 0 70.0 6386 447 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-GF03 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:20PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: December DESIGN COOLING DAY, 1500
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet 1
8. Return Duct Outlet
0.020

Specific Humidity ( lb/lb )


0.018
0.016
2 0.014
67 0.012
35
8
4 0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-GF05 DOCTER
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:23PM

Air System Information


Air System Name .................. IU-ADM-GF05 DOCTER Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area ................................................................ 172.2 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .......................................................... 1.4 Tons Load occurs at ................................................... Mar 1600
Total coil load ........................................................ 16.6 MBH OA DB / WB .................................................... 89.0 / 79.5 F
Sensible coil load .................................................. 14.8 MBH Entering DB / WB ............................................ 77.6 / 66.1 F
Coil CFM at Mar 1600 ............................................ 823 CFM Leaving DB / WB ............................................. 60.8 / 59.7 F
Max block CFM ...................................................... 823 CFM Coil ADP .................................................................... 58.9 F
Sum of peak zone CFM ......................................... 823 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.893 Resulting RH ................................................................ 54 %
ft/Ton .................................................................. 124.5 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 96.4 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ..................................................... 823 CFM Fan motor BHP .......................................................... 0.05 BHP
Standard CFM ........................................................ 818 CFM Fan motor kW ............................................................ 0.04 kW
Actual max CFM/ft ............................................... 4.78 CFM/ft Fan static ................................................................... 0.20 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 30 CFM CFM/person ............................................................. 15.00 CFM/person
CFM/ft .................................................................. 0.17 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-GF05 DOCTER
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:23PM

Air System Information


Air System Name .................. IU-ADM-GF05 DOCTER Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area ................................................................ 172.2 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone GF-04 15.0 823 823 Apr 1500 0.0 172.2 4.78

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone GF-04
GF-DOCTOR#1 1 15.0 Apr 1500 823 0.0 172.2 4.78

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-GF05 DOCTER
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:23PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ..................................................................... 30 CFM
Uncorrected Outdoor Airflow Rate ................................................................ 30 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space GF-DOCTOR#1
Critical Space Outdoor Air Fraction ('Z') 0.036
Uncorrected Outdoor Air Fraction ('X') 0.036
Corrected Outdoor Air Fraction ('Y') 0.036
Required System Ventilation Airflow (CFM) 30

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone GF-04
GF-DOCTOR#1 1 172.2 2.0 822.6 15.00 0.00 0.0 0.0 30.0 0.036 30.0
Totals (incl. Space Multipliers) 822.6 30.0 0.036 30.0

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-GF05 DOCTER
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:23PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Mar 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 89.0 F / 79.5 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 9967 - 97 ft - -
Wall Transmission 118 ft 941 - 118 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 97 ft 1014 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 538 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 634 - 0 0 -
People 2 396 410 0 0 0
Infiltration - 23 63 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1351 47 0% 0 0
>> Total Zone Loads - 14864 521 - 0 0
Zone Conditioning - 14318 521 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 823 CFM 0 - 823 CFM 0 -
Ventilation Load 30 CFM 381 1256 30 CFM -32 0
Supply Fan Load 823 CFM 122 - 823 CFM -122 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 14821 1777 - -154 0
Central Cooling Coil - 14821 1778 - -154 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 14821 1778 - -154 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-GF05 DOCTER
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:23PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-DOCTOR#1 '' IN ZONE '' Zone GF-04 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10522 - 97 ft - -
Wall Transmission 118 ft 697 - 118 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 97 ft 853 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 535 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 632 - 0 0 -
People 2 390 410 0 0 0
Infiltration - 20 60 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1365 47 0% 0 0
>> Total Zone Loads - 15013 517 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-DOCTOR#1 '' IN ZONE '' Zone GF-04 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 118 0.403 - 697 - 0
WINDOW 1 97 0.892 0.631 853 10522 0

Hourly Analysis Program v.4.3 Page 1 of 1


System Psychrometrics for IU-ADM-GF05 DOCTER
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:23PM

March DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 89.0 0.01974 30 400 381 1256
Vent - Return Mixing Outlet 77.6 0.01119 823 889 - -
Central Cooling Coil Outlet 60.8 0.01073 823 889 14821 1778
Central Heating Coil Outlet 60.8 0.01073 823 889 0 -
Supply Fan Outlet 60.9 0.01073 823 889 122 -
Cold Supply Duct Outlet 60.9 0.01073 823 889 - -
Zone Air - 77.1 0.01086 823 908 14318 521
Return Plenum Outlet 77.1 0.01086 823 908 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-04 14864 Cooling 14318 77.1 823 908 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-GF05 DOCTER
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:23PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 30 400 32 0
Vent - Return Mixing Outlet 70.0 0.00814 823 656 - -
Central Cooling Coil Outlet 69.9 0.00814 823 656 154 0
Central Heating Coil Outlet 69.9 0.00814 823 656 0 -
Supply Fan Outlet 70.0 0.00814 823 656 122 -
Cold Supply Duct Outlet 70.0 0.00814 823 656 - -
Zone Air - 70.0 0.00814 823 666 0 0
Return Plenum Outlet 70.0 0.00814 823 666 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-04 0 Deadband 0 70.0 823 666 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-GF05 DOCTER
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:23PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: March DESIGN COOLING DAY, 1600
1
1. Outdoor Air
0.020
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Room Air
0.018
0.016

Specific Humidity ( lb/lb )


0.014

2 0.012
34
5
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-GF06 PATIENT
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:29PM

Air System Information


Air System Name .................. IU-ADM-GF06 PATIENT Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area ................................................................ 229.3 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .......................................................... 0.4 Tons Load occurs at ................................................... Jan 1600
Total coil load .......................................................... 5.0 MBH OA DB / WB .................................................... 91.0 / 80.5 F
Sensible coil load .................................................... 3.4 MBH Entering DB / WB ............................................ 79.7 / 69.0 F
Coil CFM at Jan 1600 ............................................ 171 CFM Leaving DB / WB ............................................. 60.9 / 60.0 F
Max block CFM ...................................................... 171 CFM Coil ADP .................................................................... 58.8 F
Sum of peak zone CFM ......................................... 171 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.689 Resulting RH ................................................................ 56 %
ft/Ton .................................................................. 552.2 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 21.7 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ..................................................... 171 CFM Fan motor BHP .......................................................... 0.01 BHP
Standard CFM ........................................................ 170 CFM Fan motor kW ............................................................ 0.01 kW
Actual max CFM/ft ............................................... 0.74 CFM/ft Fan static ................................................................... 0.20 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 30 CFM CFM/person ............................................................. 15.00 CFM/person
CFM/ft .................................................................. 0.13 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-GF06 PATIENT
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:29PM

Air System Information


Air System Name .................. IU-ADM-GF06 PATIENT Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area ................................................................ 229.3 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone GF-05 3.1 171 171 Jan 1700 0.0 229.3 0.74

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone GF-05
GF-PATIENT#1 1 3.1 Jan 1700 171 0.0 229.3 0.74

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-GF06 PATIENT
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:29PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ..................................................................... 30 CFM
Uncorrected Outdoor Airflow Rate ................................................................ 30 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space GF-PATIENT#1
Critical Space Outdoor Air Fraction ('Z') 0.176
Uncorrected Outdoor Air Fraction ('X') 0.176
Corrected Outdoor Air Fraction ('Y') 0.176
Required System Ventilation Airflow (CFM) 30

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone GF-05
GF-PATIENT#1 1 229.3 2.0 170.5 15.00 0.00 0.0 0.0 30.0 0.176 30.0
Totals (incl. Space Multipliers) 170.5 30.0 0.176 30.0

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-GF06 PATIENT
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:29PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 538 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1903 - 0 0 -
People 2 372 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 281 24 0% 0 0
>> Total Zone Loads - 3094 264 - 0 0
Zone Conditioning - 2967 264 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 171 CFM 0 - 171 CFM 0 -
Ventilation Load 30 CFM 442 1284 30 CFM -32 0
Supply Fan Load 171 CFM 25 - 171 CFM -25 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3434 1548 - -57 0
Central Cooling Coil - 3434 1548 - -57 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 3434 1548 - -57 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-GF06 PATIENT
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:29PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-PATIENT#1 '' IN ZONE '' Zone GF-05 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 541 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1912 - 0 0 -
People 2 377 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 283 24 0% 0 0
>> Total Zone Loads - 3112 264 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-PATIENT#1 '' IN ZONE '' Zone GF-05 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

Hourly Analysis Program v.4.3 Page 1 of 1


System Psychrometrics for IU-ADM-GF06 PATIENT
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:29PM

January DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 91.0 0.02026 30 400 442 1284
Vent - Return Mixing Outlet 79.7 0.01278 171 870 - -
Central Cooling Coil Outlet 60.9 0.01085 171 870 3434 1548
Central Heating Coil Outlet 60.9 0.01085 171 870 0 -
Supply Fan Outlet 61.1 0.01085 171 870 25 -
Cold Supply Duct Outlet 61.1 0.01085 171 870 - -
Zone Air - 77.3 0.01118 171 970 2967 264
Return Plenum Outlet 77.3 0.01118 171 970 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-05 3094 Cooling 2967 77.3 171 970 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-GF06 PATIENT
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:29PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 30 400 32 0
Vent - Return Mixing Outlet 70.2 0.00813 171 439 - -
Central Cooling Coil Outlet 69.9 0.00813 171 439 57 0
Central Heating Coil Outlet 69.9 0.00813 171 439 0 -
Supply Fan Outlet 70.0 0.00813 171 439 25 -
Cold Supply Duct Outlet 70.0 0.00813 171 439 - -
Zone Air - 70.0 0.00813 171 448 0 0
Return Plenum Outlet 70.0 0.00813 171 448 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-05 0 Deadband 0 70.0 171 448 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-GF06 PATIENT
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:29PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: January DESIGN COOLING DAY, 1600
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Room Air
0.022
1
0.020

Specific Humidity ( lb/lb )


0.018
0.016
2 0.014
34 5 0.012
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-GF07 SERVER#1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:32PM

Air System Information


Air System Name .............. IU-ADM-GF07 SERVER#1 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area ................................................................ 118.4 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .......................................................... 1.1 Tons Load occurs at .................................................. Dec 1600
Total coil load ........................................................ 13.4 MBH OA DB / WB .................................................... 90.0 / 80.5 F
Sensible coil load .................................................. 12.5 MBH Entering DB / WB ............................................ 77.6 / 65.5 F
Coil CFM at Dec 1600 ............................................ 665 CFM Leaving DB / WB ............................................. 60.1 / 59.0 F
Max block CFM ...................................................... 665 CFM Coil ADP .................................................................... 58.2 F
Sum of peak zone CFM ......................................... 665 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.930 Resulting RH ................................................................ 52 %
ft/Ton .................................................................. 106.0 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) .......................................................... 113.3 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ..................................................... 665 CFM Fan motor BHP .......................................................... 0.04 BHP
Standard CFM ........................................................ 661 CFM Fan motor kW ............................................................ 0.03 kW
Actual max CFM/ft ............................................... 5.61 CFM/ft Fan static ................................................................... 0.20 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 15 CFM CFM/person ............................................................. 15.00 CFM/person
CFM/ft .................................................................. 0.13 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-GF07 SERVER#1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:32PM

Air System Information


Air System Name .............. IU-ADM-GF07 SERVER#1 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area ................................................................ 118.4 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone GF-07 12.1 665 665 Jan 1700 0.0 118.4 5.61

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone GF-07
GF-SERVER#1 1 12.1 Jan 1700 665 0.0 118.4 5.61

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-GF07 SERVER#1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:32PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ..................................................................... 15 CFM
Uncorrected Outdoor Airflow Rate ................................................................ 15 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space GF-SERVER#1
Critical Space Outdoor Air Fraction ('Z') 0.023
Uncorrected Outdoor Air Fraction ('X') 0.023
Corrected Outdoor Air Fraction ('Y') 0.023
Required System Ventilation Airflow (CFM) 15

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone GF-07
GF-SERVER#1 1 118.4 1.0 664.5 15.00 0.00 0.0 0.0 15.0 0.023 15.0
Totals (incl. Space Multipliers) 664.5 15.0 0.023 15.0

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-GF07 SERVER#1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:32PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 590 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 10236 - 0 0 -
People 1 198 205 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1102 21 0% 0 0
>> Total Zone Loads - 12126 226 - 0 0
Zone Conditioning - 12168 226 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 665 CFM 0 - 665 CFM 0 -
Ventilation Load 15 CFM 204 708 15 CFM -16 1
Supply Fan Load 665 CFM 99 - 665 CFM -99 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 12471 933 - -115 1
Central Cooling Coil - 12471 939 - -115 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 12471 939 - -115 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-GF07 SERVER#1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:32PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-SERVER#1 '' IN ZONE '' Zone GF-07 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 590 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 10236 - 0 0 -
People 1 201 205 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1103 21 0% 0 0
>> Total Zone Loads - 12129 226 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-SERVER#1 '' IN ZONE '' Zone GF-07 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

Hourly Analysis Program v.4.3 Page 1 of 1


System Psychrometrics for IU-ADM-GF07 SERVER#1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:32PM

December DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 90.0 0.02049 15 400 204 708
Vent - Return Mixing Outlet 77.6 0.01072 665 809 - -
Central Cooling Coil Outlet 60.1 0.01042 665 809 12471 939
Central Heating Coil Outlet 60.1 0.01042 665 809 0 -
Supply Fan Outlet 60.3 0.01042 665 809 99 -
Cold Supply Duct Outlet 60.3 0.01042 665 809 - -
Zone Air - 77.3 0.01049 665 818 12168 226
Return Plenum Outlet 77.3 0.01049 665 818 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-07 12126 Cooling 12168 77.3 665 818 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-GF07 SERVER#1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:32PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 15 400 16 -1
Vent - Return Mixing Outlet 70.0 0.00815 665 791 - -
Central Cooling Coil Outlet 69.9 0.00815 665 791 115 0
Central Heating Coil Outlet 69.9 0.00815 665 791 0 -
Supply Fan Outlet 70.0 0.00815 665 791 99 -
Cold Supply Duct Outlet 70.0 0.00815 665 791 - -
Zone Air - 70.0 0.00815 665 800 0 0
Return Plenum Outlet 70.0 0.00815 665 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone GF-07 0 Deadband 0 70.0 665 800 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-GF07 SERVER#1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 09:32PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: December DESIGN COOLING DAY, 1600
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Room Air
1
0.022
0.020

Specific Humidity ( lb/lb )


0.018
0.016
0.014
2 0.012
34
5
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-1F01 RECEPSIONIST
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:31PM

Air System Information


Air System Name ....... IU-ADM-1F01 RECEPSIONIST Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 3534.9 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 12.1 Tons Load occurs at .................................................. Dec 1600
Total coil load ...................................................... 145.4 MBH OA DB / WB .................................................... 90.0 / 80.5 F
Sensible coil load ................................................ 119.9 MBH Entering DB / WB ............................................ 77.8 / 66.5 F
Coil CFM at Dec 1600 .......................................... 6345 CFM Leaving DB / WB ............................................. 60.2 / 59.2 F
Max block CFM .................................................... 6345 CFM Coil ADP .................................................................... 58.3 F
Sum of peak zone CFM ....................................... 6345 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.825 Resulting RH ................................................................ 53 %
ft/Ton .................................................................. 291.8 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 41.1 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 6345 CFM Fan motor BHP .......................................................... 0.74 BHP
Standard CFM ...................................................... 6307 CFM Fan motor kW ............................................................ 0.55 kW
Actual max CFM/ft ............................................... 1.79 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................ 454 CFM CFM/person ............................................................. 23.33 CFM/person
CFM/ft .................................................................. 0.13 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-1F01 RECEPSIONIST
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:31PM

Air System Information


Air System Name ....... IU-ADM-1F01 RECEPSIONIST Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 3534.9 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone 1F-01 109.3 6027 6027 Jan 1600 0.0 3534.9 1.71

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone 1F-01
1F-RECEPSIONIST#1 1 92.2 Jan 1600 5052 0.0 3057.0 1.65
1F-R.TUNGGU#1 1 10.5 Dec 1500 577 0.0 279.9 2.06
1F-SECURITY MONITOR#1 1 5.9 Jan 1700 323 0.0 101.2 3.20
1F-GA#1 1 1.4 Jan 1700 74 0.0 96.9 0.76

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-1F01 RECEPSIONIST
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:31PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 454 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 292 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space 1F-GA#1
Critical Space Outdoor Air Fraction ('Z') 0.405
Uncorrected Outdoor Air Fraction ('X') 0.048
Corrected Outdoor Air Fraction ('Y') 0.075
Required System Ventilation Airflow (CFM) 454

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone 1F-01
1F-RECEPSIONIST#1 1 3057.0 9.5 5052.4 15.00 0.00 0.0 0.0 142.0 0.028 380.6
1F-R.TUNGGU#1 1 279.9 6.0 577.4 15.00 0.00 0.0 0.0 90.0 0.156 43.5
1F-SECURITY MONITOR#1 1 101.2 2.0 323.5 15.00 0.00 0.0 0.0 30.0 0.093 24.4
1F-GA#1 1 96.9 2.0 74.0 15.00 0.00 0.0 0.0 30.0 0.405 5.6
Totals (incl. Space Multipliers) 6027.3 292.0 0.405 454.1

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-1F01 RECEPSIONIST
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:31PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 1043 ft 66039 - 1043 ft - -
Wall Transmission 851 ft 3887 - 851 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 1043 ft 15435 - 1043 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 796 W 1733 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2400 W 7949 - 0 0 -
People 19 3666 2676 0 0 0
Infiltration - 470 1352 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9918 403 0% 0 0
>> Total Zone Loads - 109097 4431 - 0 0
Zone Conditioning - 102041 4431 - 0 0
Plenum Wall Load 20% 3323 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 30% 814 - 0 0 -
Return Fan Load 6345 CFM 0 - 6345 CFM 0 -
Ventilation Load 454 CFM 6374 21038 454 CFM -488 0
Supply Fan Load 6345 CFM 1881 - 6345 CFM -1881 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 5455 - 5% 0 -
>> Total System Loads - 119888 25468 - -2369 0
Central Cooling Coil - 119888 25486 - -2369 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 119888 25486 - -2369 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-1F01 RECEPSIONIST
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:31PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 1F-RECEPSIONIST#1 '' IN ZONE '' Zone 1F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 978 ft 59965 - 978 ft - -
Wall Transmission 787 ft 3542 - 787 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 978 ft 15856 - 978 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 450 W 980 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1269 - 0 0 -
People 9 1759 1136 0 0 0
Infiltration - 459 1182 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 8383 232 0% 0 0
>> Total Zone Loads - 92214 2550 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 1F-RECEPSIONIST#1 '' IN ZONE '' Zone 1F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 216 0.403 - 807 - 0
WINDOW 1 441 1.212 0.880 7335 29346 0
WNW EXPOSURE
WALL 539 0.403 - 2671 - 0
WINDOW 1 441 1.212 0.880 7335 28744 0
ENE EXPOSURE
WALL 32 0.403 - 65 - 0
WINDOW 1 97 0.892 0.631 1187 1875 0

Hourly Analysis Program v.4.3 Page 1 of 4


Space Design Load Summary for IU-ADM-1F01 RECEPSIONIST
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:31PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 1F-R.TUNGGU#1 '' IN ZONE '' Zone 1F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 5717 - 65 ft - -
Wall Transmission 65 ft 345 - 65 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 65 ft 742 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 6 1099 720 0 0 0
Infiltration - 40 112 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 958 83 0% 0 0
>> Total Zone Loads - 10539 916 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 1F-R.TUNGGU#1 '' IN ZONE '' Zone 1F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 65 0.403 - 345 - 0
WINDOW 1 65 0.892 0.631 742 5717 0

Hourly Analysis Program v.4.3 Page 2 of 4


Space Design Load Summary for IU-ADM-1F01 RECEPSIONIST
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:31PM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 1F-SECURITY MONITOR#1 '' IN ZONE '' Zone 1F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 86 W 189 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1400 W 4777 - 0 0 -
People 2 401 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 537 41 0% 0 0
>> Total Zone Loads - 5904 451 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 1F-SECURITY MONITOR#1 '' IN ZONE '' Zone 1F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

Hourly Analysis Program v.4.3 Page 3 of 4


Space Design Load Summary for IU-ADM-1F01 RECEPSIONIST
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:31PM

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' 1F-GA#1 '' IN ZONE '' Zone 1F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 86 W 189 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 637 - 0 0 -
People 2 401 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 123 41 0% 0 0
>> Total Zone Loads - 1351 451 - 0 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' 1F-GA#1 '' IN ZONE '' Zone 1F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

Hourly Analysis Program v.4.3 Page 4 of 4


System Psychrometrics for IU-ADM-1F01 RECEPSIONIST
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:31PM

December DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 90.0 0.02049 454 400 6374 21038
Vent - Return Mixing Outlet 77.8 0.01138 6345 798 - -
Central Cooling Coil Outlet 60.2 0.01052 6345 798 119888 25486
Central Heating Coil Outlet 60.2 0.01052 6345 798 0 -
Supply Fan Outlet 60.5 0.01052 6345 798 1881 -
Cold Supply Duct Outlet 61.4 0.01052 6027 798 - -
Zone Air - 77.1 0.01068 6027 830 102041 4431
Return Plenum Outlet 77.8 0.01068 6027 830 4137 -
Duct Leakage Air Outlet 60.5 0.01053 317 798 - -
Return Duct Outlet 76.9 0.01067 6345 828 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1F-01 109097 Cooling 102041 77.1 6027 830 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-1F01 RECEPSIONIST
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:31PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 454 400 488 0
Vent - Return Mixing Outlet 70.1 0.00813 6345 522 - -
Central Cooling Coil Outlet 69.7 0.00813 6345 522 2369 0
Central Heating Coil Outlet 69.7 0.00813 6345 522 0 -
Supply Fan Outlet 70.0 0.00813 6345 522 1881 -
Cold Supply Duct Outlet 70.0 0.00813 6027 522 - -
Zone Air - 70.0 0.00813 6027 531 0 0
Return Plenum Outlet 70.0 0.00813 6027 531 0 -
Duct Leakage Air Outlet 70.0 0.00813 317 522 - -
Return Duct Outlet 70.0 0.00813 6345 531 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1F-01 0 Deadband 0 70.0 6027 531 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-1F01 RECEPSIONIST
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:31PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: December DESIGN COOLING DAY, 1600
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet 1
8. Return Duct Outlet
0.020

Specific Humidity ( lb/lb )


0.018
0.016
0.014
2 0.012
35 6
4 8 7 0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

Air System Information


Air System Name ..................... IU-ADM-1F02 SOUTH Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 4628.5 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 18.7 Tons Load occurs at .................................................. Dec 1400
Total coil load ...................................................... 224.5 MBH OA DB / WB .................................................... 90.0 / 80.5 F
Sensible coil load ................................................ 164.5 MBH Entering DB / WB ............................................ 78.6 / 68.2 F
Coil CFM at Dec 1400 .......................................... 8823 CFM Leaving DB / WB ............................................. 61.3 / 60.3 F
Max block CFM .................................................... 8823 CFM Coil ADP .................................................................... 59.3 F
Sum of peak zone CFM ....................................... 8823 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.733 Resulting RH ................................................................ 57 %
ft/Ton .................................................................. 247.4 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 48.5 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 8823 CFM Fan motor BHP .......................................................... 1.03 BHP
Standard CFM ...................................................... 8771 CFM Fan motor kW ............................................................ 0.77 kW
Actual max CFM/ft ............................................... 1.91 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1064 CFM CFM/person ............................................................. 16.36 CFM/person
CFM/ft .................................................................. 0.23 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

Air System Information


Air System Name ..................... IU-ADM-1F02 SOUTH Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 4628.5 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone 1F-02 142.0 8382 8382 Dec 1500 0.0 4628.5 1.81

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone 1F-02
1F-GRAND MEETING#1 1 20.5 Dec 1500 1126 0.0 409.0 2.75
1F-AREA STAFF#1 1 80.1 Apr 0800 4390 0.0 3159.2 1.39
1F-MANAGER#1 1 9.8 Dec 1500 537 0.0 129.2 4.16
1F-MANAGER#2 1 8.2 Dec 1500 447 0.0 129.2 3.46
1F-MANAGER#3 1 8.2 Dec 1500 447 0.0 129.2 3.46
1F-MANAGER#4 1 8.2 Dec 1500 447 0.0 129.2 3.46
1F-FILE#1 1 7.7 Jun 0900 419 0.0 258.3 1.62
1F-FILE STORAGE#2 1 10.4 Jun 0900 568 0.0 285.2 1.99

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................. 1064 CFM
Uncorrected Outdoor Airflow Rate ............................................................ 1007 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space 1F-GRAND MEETING#1
Critical Space Outdoor Air Fraction ('Z') 0.173
Uncorrected Outdoor Air Fraction ('X') 0.120
Corrected Outdoor Air Fraction ('Y') 0.127
Required System Ventilation Airflow (CFM) 1064

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone 1F-02
1F-GRAND MEETING#1 1 409.0 13.0 1125.9 15.00 0.00 0.0 0.0 195.0 0.173 142.9
1F-AREA STAFF#1 1 3159.2 40.0 4390.4 15.00 0.00 0.0 0.0 600.0 0.137 557.1
1F-MANAGER#1 1 129.2 3.0 537.0 15.00 0.00 0.0 0.0 45.0 0.084 68.1
1F-MANAGER#2 1 129.2 3.0 447.3 15.00 0.00 0.0 0.0 45.0 0.101 56.7
1F-MANAGER#3 1 129.2 3.0 447.3 15.00 0.00 0.0 0.0 45.0 0.101 56.7
1F-MANAGER#4 1 129.2 3.0 447.3 15.00 0.00 0.0 0.0 45.0 0.101 56.7
1F-FILE#1 1 258.3 0.0 419.2 0.00 0.06 0.0 0.0 15.3 0.036 53.2
1F-FILE STORAGE#2 1 285.2 0.0 567.7 0.00 0.06 0.0 0.0 16.8 0.030 72.0
Totals (incl. Space Multipliers) 8381.9 1007.1 0.173 1063.5

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 1033 ft 50590 - 1033 ft - -
Wall Transmission 1528 ft 8715 - 1528 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 1033 ft 11466 - 1033 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 4097 W 8817 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11200 W 35191 - 0 0 -
People 65 12326 12221 0 0 0
Infiltration - 207 554 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 12731 1278 0% 0 0
>> Total Zone Loads - 140045 14053 - 0 0
Zone Conditioning - 132004 14053 - 0 0
Plenum Wall Load 20% 3950 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 30% 4193 - 0 0 -
Return Fan Load 8823 CFM 0 - 8823 CFM 0 -
Ventilation Load 1064 CFM 14725 45937 1064 CFM -1142 0
Supply Fan Load 8823 CFM 2616 - 8823 CFM -2616 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 7002 - 5% 0 -
>> Total System Loads - 164491 59990 - -3758 0
Central Cooling Coil - 164491 59996 - -3758 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 164491 59996 - -3758 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 1F-GRAND MEETING#1 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 11434 - 129 ft - -
Wall Transmission 75 ft 307 - 75 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 129 ft 1483 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 518 W 1123 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1895 - 0 0 -
People 13 2380 1560 0 0 0
Infiltration - 59 153 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1868 171 0% 0 0
>> Total Zone Loads - 20550 1884 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 1F-GRAND MEETING#1 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 75 0.403 - 307 - 0
WINDOW 1 129 0.892 0.631 1483 11434 0

Hourly Analysis Program v.4.3 Page 1 of 8


Space Design Load Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 1F-AREA STAFF#1 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 75.6 F / 75.1 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 549 ft 32418 - 549 ft - -
Wall Transmission 926 ft 1806 - 926 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 549 ft 703 - 549 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 2498 W 5124 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 8600 W 26026 - 0 0 -
People 40 6769 8200 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 7285 820 0% 0 0
>> Total Zone Loads - 80130 9020 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 1F-AREA STAFF#1 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 344 0.403 - 734 - 0
WINDOW 1 291 0.892 0.631 372 20888 0
ESE EXPOSURE
WALL 377 0.403 - 830 - 0
WINDOW 1 129 0.892 0.631 165 10087 0
SSW EXPOSURE
WALL 205 0.403 - 243 - 0
WINDOW 1 129 0.892 0.631 165 1443 0

Hourly Analysis Program v.4.3 Page 2 of 8


Space Design Load Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#1 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 210 ft 1824 - 210 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 891 66 0% 0 0
>> Total Zone Loads - 9800 730 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#1 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 151 0.403 - 1488 - 0
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0

Hourly Analysis Program v.4.3 Page 3 of 8


Space Design Load Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#2 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#2 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0

Hourly Analysis Program v.4.3 Page 4 of 8


Space Design Load Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#3 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0

TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#3 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0

Hourly Analysis Program v.4.3 Page 5 of 8


Space Design Load Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#4 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0

TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#4 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0

Hourly Analysis Program v.4.3 Page 6 of 8


Space Design Load Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' 1F-FILE#1 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 72.5 F / 72.0 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 5790 - 65 ft - -
Wall Transmission 86 ft 162 - 86 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 65 ft -137 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 259 W 537 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 610 - 0 0 -
People 0 0 0 0 0 0
Infiltration - -6 44 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 695 4 0% 0 0
>> Total Zone Loads - 7650 48 - 0 0

TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' 1F-FILE#1 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 86 0.403 - 162 - 0
WINDOW 1 65 0.892 0.631 -137 5790 0

Hourly Analysis Program v.4.3 Page 7 of 8


Space Design Load Summary for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' 1F-FILE STORAGE#2 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 72.5 F / 72.0 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 8685 - 97 ft - -
Wall Transmission 54 ft 68 - 54 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 97 ft -205 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 130 W 268 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 610 - 0 0 -
People 0 0 0 0 0 0
Infiltration - -7 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 942 5 0% 0 0
>> Total Zone Loads - 10361 53 - 0 0

TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' 1F-FILE STORAGE#2 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 54 0.403 - 68 - 0
WINDOW 1 97 0.892 0.631 -205 8685 0

Hourly Analysis Program v.4.3 Page 8 of 8


System Psychrometrics for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

December DESIGN COOLING DAY, 1400

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 90.0 0.02049 1064 400 14725 45937
Vent - Return Mixing Outlet 78.6 0.01244 8823 944 - -
Central Cooling Coil Outlet 61.3 0.01100 8823 944 164491 59996
Central Heating Coil Outlet 61.3 0.01100 8823 944 0 -
Supply Fan Outlet 61.5 0.01100 8823 944 2616 -
Cold Supply Duct Outlet 62.3 0.01100 8382 944 - -
Zone Air - 77.0 0.01136 8382 1023 132004 14053
Return Plenum Outlet 77.9 0.01136 8382 1023 8143 -
Duct Leakage Air Outlet 61.5 0.01100 441 944 - -
Return Duct Outlet 77.1 0.01134 8823 1018 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1F-02 140045 Cooling 132004 77.0 8382 1023 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 1064 400 1142 0
Vent - Return Mixing Outlet 70.1 0.00813 8823 466 - -
Central Cooling Coil Outlet 69.7 0.00813 8823 466 3758 0
Central Heating Coil Outlet 69.7 0.00813 8823 466 0 -
Supply Fan Outlet 70.0 0.00813 8823 466 2616 -
Cold Supply Duct Outlet 70.0 0.00813 8382 466 - -
Zone Air - 70.0 0.00813 8382 475 0 0
Return Plenum Outlet 70.0 0.00813 8382 475 0 -
Duct Leakage Air Outlet 70.0 0.00813 441 466 - -
Return Duct Outlet 70.0 0.00813 8823 475 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1F-02 0 Deadband 0 70.0 8382 475 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-1F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:40PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: December DESIGN COOLING DAY, 1400
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet 1
8. Return Duct Outlet
0.020

Specific Humidity ( lb/lb )


0.018
0.016

2
0.014
35 6 0.012
7
4 8
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-1F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:53PM

Air System Information


Air System Name ................... IU-ADM-1F03 NORTH1 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 1388.5 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 13.1 Tons Load occurs at ................................................... Feb 1600
Total coil load ...................................................... 156.9 MBH OA DB / WB .................................................... 91.0 / 80.5 F
Sensible coil load .................................................. 91.3 MBH Entering DB / WB ............................................ 81.7 / 71.5 F
Coil CFM at Feb 1600 .......................................... 4102 CFM Leaving DB / WB ............................................. 60.9 / 60.1 F
Max block CFM .................................................... 4102 CFM Coil ADP .................................................................... 58.6 F
Sum of peak zone CFM ....................................... 4102 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.582 Resulting RH ................................................................ 57 %
ft/Ton .................................................................. 106.2 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) .......................................................... 113.0 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 4102 CFM Fan motor BHP .......................................................... 0.48 BHP
Standard CFM ...................................................... 4078 CFM Fan motor kW ............................................................ 0.36 kW
Actual max CFM/ft ............................................... 2.95 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1328 CFM CFM/person ............................................................. 18.45 CFM/person
CFM/ft .................................................................. 0.96 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-1F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:53PM

Air System Information


Air System Name ................... IU-ADM-1F03 NORTH1 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 1388.5 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone 1F-03A 71.1 3897 3897 Apr 1500 0.0 1388.5 2.81

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone 1F-03A
1F-MANAGER#5 1 9.0 Apr 1500 491 0.0 129.2 3.80
1F-MANAGER#6 1 9.0 Apr 1500 491 0.0 129.2 3.80
1F-RUANG TRAINING#1 1 28.9 Apr 1500 1583 0.0 597.4 2.65
1F-MEETING#1 1 24.3 Apr 1500 1331 0.0 532.8 2.50

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-1F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:53PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................. 1328 CFM
Uncorrected Outdoor Airflow Rate ............................................................ 1080 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space 1F-RUANG TRAINING#1
Critical Space Outdoor Air Fraction ('Z') 0.464
Uncorrected Outdoor Air Fraction ('X') 0.277
Corrected Outdoor Air Fraction ('Y') 0.341
Required System Ventilation Airflow (CFM) 1328

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone 1F-03A
1F-MANAGER#5 1 129.2 3.0 491.0 15.00 0.00 0.0 0.0 45.0 0.092 167.4
1F-MANAGER#6 1 129.2 3.0 491.0 15.00 0.00 0.0 0.0 45.0 0.092 167.4
1F-RUANG TRAINING#1 1 597.4 49.0 1583.5 15.00 0.00 0.0 0.0 735.0 0.464 539.8
1F-MEETING#1 1 532.8 17.0 1331.2 15.00 0.00 0.0 0.0 255.0 0.192 453.8
Totals (incl. Space Multipliers) 3896.7 1080.0 0.464 1328.4

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-1F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:53PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Feb 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 323 ft 30959 - 323 ft - -
Wall Transmission 657 ft 3425 - 657 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 323 ft 3956 - 323 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1516 W 3302 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 6345 - 0 0 -
People 72 13451 9150 0 0 0
Infiltration - 208 501 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 6165 965 0% 0 0
>> Total Zone Loads - 67811 10617 - 0 0
Zone Conditioning - 63962 10617 - 0 0
Plenum Wall Load 20% 1518 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 30% 1551 - 0 0 -
Return Fan Load 4102 CFM 0 - 4102 CFM 0 -
Ventilation Load 1328 CFM 19674 55000 1328 CFM -1426 0
Supply Fan Load 4102 CFM 1216 - 4102 CFM -1216 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 3391 - 5% 0 -
>> Total System Loads - 91313 65617 - -2643 0
Central Cooling Coil - 91313 65623 - -2643 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 91313 65623 - -2643 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-1F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:53PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#5 '' IN ZONE '' Zone 1F-03A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 5261 - 48 ft - -
Wall Transmission 59 ft 222 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 427 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 15 43 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 815 66 0% 0 0
>> Total Zone Loads - 8962 724 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#5 '' IN ZONE '' Zone 1F-03A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 59 0.403 - 222 - 0
WINDOW 1 48 0.892 0.631 427 5261 0

Hourly Analysis Program v.4.3 Page 1 of 4


Space Design Load Summary for IU-ADM-1F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:53PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#6 '' IN ZONE '' Zone 1F-03A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 5261 - 48 ft - -
Wall Transmission 59 ft 222 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 427 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 15 43 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 815 66 0% 0 0
>> Total Zone Loads - 8962 724 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#6 '' IN ZONE '' Zone 1F-03A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 59 0.403 - 222 - 0
WINDOW 1 48 0.892 0.631 427 5261 0

Hourly Analysis Program v.4.3 Page 2 of 4


Space Design Load Summary for IU-ADM-1F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:53PM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 1F-RUANG TRAINING#1 '' IN ZONE '' Zone 1F-03A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10522 - 97 ft - -
Wall Transmission 452 ft 3026 - 452 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 97 ft 853 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 936 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1895 - 0 0 -
People 49 8972 5880 0 0 0
Infiltration - 70 197 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2627 608 0% 0 0
>> Total Zone Loads - 28901 6685 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 1F-RUANG TRAINING#1 '' IN ZONE '' Zone 1F-03A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 344 0.403 - 2633 - 0
WNW EXPOSURE
WALL 108 0.403 - 393 - 0
WINDOW 1 97 0.892 0.631 853 10522 0

Hourly Analysis Program v.4.3 Page 3 of 4


Space Design Load Summary for IU-ADM-1F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:53PM

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' 1F-MEETING#1 '' IN ZONE '' Zone 1F-03A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 14029 - 129 ft - -
Wall Transmission 86 ft 254 - 86 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 129 ft 1137 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 738 W 1598 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1895 - 0 0 -
People 17 3113 2040 0 0 0
Infiltration - 62 176 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2209 222 0% 0 0
>> Total Zone Loads - 24297 2438 - 0 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' 1F-MEETING#1 '' IN ZONE '' Zone 1F-03A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 86 0.403 - 254 - 0
WINDOW 1 129 0.892 0.631 1137 14029 0

Hourly Analysis Program v.4.3 Page 4 of 4


System Psychrometrics for IU-ADM-1F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:53PM

February DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 91.0 0.02026 1328 400 19674 55000
Vent - Return Mixing Outlet 81.7 0.01432 4102 763 - -
Central Cooling Coil Outlet 60.9 0.01093 4102 763 91313 65623
Central Heating Coil Outlet 60.9 0.01093 4102 763 0 -
Supply Fan Outlet 61.2 0.01093 4102 763 1216 -
Cold Supply Duct Outlet 62.0 0.01093 3897 763 - -
Zone Air - 77.3 0.01151 3897 946 63962 10617
Return Plenum Outlet 78.0 0.01151 3897 946 3070 -
Duct Leakage Air Outlet 61.2 0.01093 205 763 - -
Return Duct Outlet 77.2 0.01148 4102 937 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1F-03A 67811 Cooling 63962 77.3 3897 946 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-1F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:53PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 1328 400 1426 0
Vent - Return Mixing Outlet 70.3 0.00813 4102 417 - -
Central Cooling Coil Outlet 69.7 0.00813 4102 417 2643 0
Central Heating Coil Outlet 69.7 0.00813 4102 417 0 -
Supply Fan Outlet 70.0 0.00813 4102 417 1216 -
Cold Supply Duct Outlet 70.0 0.00813 3897 417 - -
Zone Air - 70.0 0.00813 3897 426 0 0
Return Plenum Outlet 70.0 0.00813 3897 426 0 -
Duct Leakage Air Outlet 70.0 0.00813 205 417 - -
Return Duct Outlet 70.0 0.00813 4102 426 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1F-03A 0 Deadband 0 70.0 3897 426 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-1F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 04:53PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: February DESIGN COOLING DAY, 1600
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet
8. Return Duct Outlet 1
0.020

Specific Humidity ( lb/lb )


0.018
0.016
2
0.014
67 0.012
35 8
4 0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-1F03 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:14PM

Air System Information


Air System Name ................... IU-ADM-1F03 NORTH2 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 2534.9 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .......................................................... 9.5 Tons Load occurs at ................................................... Feb 1500
Total coil load ...................................................... 113.9 MBH OA DB / WB .................................................... 91.4 / 80.6 F
Sensible coil load .................................................. 84.8 MBH Entering DB / WB ............................................ 78.6 / 67.9 F
Coil CFM at Feb 1500 .......................................... 4500 CFM Leaving DB / WB ............................................. 61.0 / 60.0 F
Max block CFM .................................................... 4500 CFM Coil ADP .................................................................... 59.1 F
Sum of peak zone CFM ....................................... 4500 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.744 Resulting RH ................................................................ 57 %
ft/Ton .................................................................. 267.1 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 44.9 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 4500 CFM Fan motor BHP .......................................................... 0.52 BHP
Standard CFM ...................................................... 4473 CFM Fan motor kW ............................................................ 0.39 kW
Actual max CFM/ft ............................................... 1.78 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................ 493 CFM CFM/person ............................................................. 15.39 CFM/person
CFM/ft .................................................................. 0.19 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-1F03 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:14PM

Air System Information


Air System Name ................... IU-ADM-1F03 NORTH2 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 2534.9 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone 1F-03B 78.0 4275 4275 Jan 0800 0.0 2534.9 1.69

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone 1F-03B
1F-AREA STAFF#2 1 70.9 Jan 0800 3883 0.0 2400.4 1.62
1F-FILE STORAGE#1 1 7.1 Jan 0800 392 0.0 134.5 2.91

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-1F03 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:14PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 493 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 488 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space 1F-AREA STAFF#2
Critical Space Outdoor Air Fraction ('Z') 0.124
Uncorrected Outdoor Air Fraction ('X') 0.114
Corrected Outdoor Air Fraction ('Y') 0.115
Required System Ventilation Airflow (CFM) 493

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone 1F-03B
1F-AREA STAFF#2 1 2400.4 32.0 3883.0 15.00 0.00 0.0 0.0 480.0 0.124 447.5
1F-FILE STORAGE#1 1 134.5 0.0 391.6 0.00 0.06 0.0 0.0 7.9 0.020 45.1
Totals (incl. Space Multipliers) 4274.6 487.9 0.124 492.6

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-1F03 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:14PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 501 ft 26368 - 501 ft - -
Wall Transmission 264 ft 1662 - 264 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 501 ft 6194 - 501 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1889 W 4091 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6600 W 20841 - 0 0 -
People 32 6241 6562 0 0 0
Infiltration - 390 937 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 6579 750 0% 0 0
>> Total Zone Loads - 72366 8250 - 0 0
Zone Conditioning - 68872 8250 - 0 0
Plenum Wall Load 20% 1393 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 30% 1933 - 0 0 -
Return Fan Load 4500 CFM 0 - 4500 CFM 0 -
Ventilation Load 493 CFM 7615 20867 493 CFM -529 0
Supply Fan Load 4500 CFM 1334 - 4500 CFM -1334 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 3618 - 5% 0 -
>> Total System Loads - 84766 29117 - -1863 0
Central Cooling Coil - 84766 29122 - -1863 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 84766 29122 - -1863 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-1F03 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:14PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 1F-AREA STAFF#2 '' IN ZONE '' Zone 1F-03B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 452 ft 32877 - 452 ft - -
Wall Transmission 237 ft 686 - 237 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 452 ft 2192 - 452 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1846 W 3785 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6400 W 19368 - 0 0 -
People 32 5415 6562 0 0 0
Infiltration - 105 918 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 6443 748 0% 0 0
>> Total Zone Loads - 70871 8228 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 1F-AREA STAFF#2 '' IN ZONE '' Zone 1F-03B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 11 0.403 - 0 - 0
WINDOW 1 194 0.892 0.631 939 3545 0
ESE EXPOSURE
WALL 226 0.403 - 686 - 0
WINDOW 1 258 0.892 0.631 1252 29332 0

Hourly Analysis Program v.4.3 Page 1 of 2


Space Design Load Summary for IU-ADM-1F03 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:14PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 1F-FILE STORAGE#1 '' IN ZONE '' Zone 1F-03B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 5500 - 48 ft - -
Wall Transmission 27 ft 63 - 27 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 235 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 43 W 89 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 605 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 6 51 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 650 5 0% 0 0
>> Total Zone Loads - 7147 57 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 1F-FILE STORAGE#1 '' IN ZONE '' Zone 1F-03B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 27 0.403 - 63 - 0
WINDOW 1 48 0.892 0.631 235 5500 0

Hourly Analysis Program v.4.3 Page 2 of 2


System Psychrometrics for IU-ADM-1F03 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:14PM

February DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 91.4 0.02026 493 400 7615 20867
Vent - Return Mixing Outlet 78.6 0.01226 4500 994 - -
Central Cooling Coil Outlet 61.0 0.01089 4500 994 84766 29122
Central Heating Coil Outlet 61.0 0.01089 4500 994 0 -
Supply Fan Outlet 61.3 0.01089 4500 994 1334 -
Cold Supply Duct Outlet 62.1 0.01089 4275 994 - -
Zone Air - 77.1 0.01130 4275 1072 68872 8250
Return Plenum Outlet 77.8 0.01130 4275 1072 3327 -
Duct Leakage Air Outlet 61.3 0.01089 225 994 - -
Return Duct Outlet 77.0 0.01128 4500 1067 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1F-03B 72366 Cooling 68872 77.1 4275 1072 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-1F03 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:14PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 493 400 529 0
Vent - Return Mixing Outlet 70.1 0.00813 4500 479 - -
Central Cooling Coil Outlet 69.7 0.00813 4500 479 1863 0
Central Heating Coil Outlet 69.7 0.00813 4500 479 0 -
Supply Fan Outlet 70.0 0.00813 4500 479 1334 -
Cold Supply Duct Outlet 70.0 0.00813 4275 479 - -
Zone Air - 70.0 0.00813 4275 489 0 0
Return Plenum Outlet 70.0 0.00813 4275 489 0 -
Duct Leakage Air Outlet 70.0 0.00813 225 479 - -
Return Duct Outlet 70.0 0.00813 4500 489 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1F-03B 0 Deadband 0 70.0 4275 489 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-1F03 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:14PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: February DESIGN COOLING DAY, 1500
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet
8. Return Duct Outlet 1
0.020

Specific Humidity ( lb/lb )


0.018
0.016
0.014
2
35 8
67 0.012
4 0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-2F01 LOBBY-SECRETARY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:20PM

Air System Information


Air System Name IU-ADM-2F01 LOBBY-SECRETARY Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 3954.7 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 11.4 Tons Load occurs at .................................................. Dec 1600
Total coil load ...................................................... 136.9 MBH OA DB / WB .................................................... 90.0 / 80.5 F
Sensible coil load ................................................ 116.9 MBH Entering DB / WB ............................................ 77.5 / 66.1 F
Coil CFM at Dec 1600 .......................................... 6341 CFM Leaving DB / WB ............................................. 60.3 / 59.2 F
Max block CFM .................................................... 6341 CFM Coil ADP .................................................................... 58.4 F
Sum of peak zone CFM ....................................... 6341 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.854 Resulting RH ................................................................ 54 %
ft/Ton .................................................................. 346.7 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 34.6 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 6341 CFM Fan motor BHP .......................................................... 0.74 BHP
Standard CFM ...................................................... 6303 CFM Fan motor kW ............................................................ 0.55 kW
Actual max CFM/ft ............................................... 1.60 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................ 335 CFM CFM/person ............................................................. 16.73 CFM/person
CFM/ft .................................................................. 0.08 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-2F01 LOBBY-SECRETARY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:20PM

Air System Information


Air System Name IU-ADM-2F01 LOBBY-SECRETARY Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 3954.7 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone 2F-01 109.1 6024 6024 Jan 1600 0.0 3954.7 1.52

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone 2F-01
2F-LOBBY& SECRETARY#1 1 89.7 Jan 1600 4916 0.0 3584.4 1.37
2F-SECURITY MONITOR#1 1 5.9 Jan 1700 323 0.0 101.2 3.20
2F-EXCE DINNING#1 1 14.3 Dec 1500 784 0.0 269.1 2.92

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-2F01 LOBBY-SECRETARY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:20PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 335 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 300 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space 2F-EXCE DINNING#1
Critical Space Outdoor Air Fraction ('Z') 0.153
Uncorrected Outdoor Air Fraction ('X') 0.050
Corrected Outdoor Air Fraction ('Y') 0.056
Required System Ventilation Airflow (CFM) 335

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone 2F-01
2F-LOBBY& SECRETARY#1 1 3584.4 10.0 4915.9 15.00 0.00 0.0 0.0 150.0 0.031 273.0
2F-SECURITY MONITOR#1 1 101.2 2.0 323.5 15.00 0.00 0.0 0.0 30.0 0.093 18.0
2F-EXCE DINNING#1 1 269.1 8.0 784.5 15.00 0.00 0.0 0.0 120.0 0.153 43.6
Totals (incl. Space Multipliers) 6023.8 300.0 0.153 334.5

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-2F01 LOBBY-SECRETARY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:20PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 1043 ft 66039 - 1043 ft - -
Wall Transmission 572 ft 2319 - 572 ft 0 -
Roof Transmission 269 ft 2439 - 269 ft 0 -
Window Transmission 1043 ft 15435 - 1043 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 511 W 1114 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2200 W 7315 - 0 0 -
People 20 3741 2570 0 0 0
Infiltration - 542 1557 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9894 413 0% 0 0
>> Total Zone Loads - 108837 4540 - 0 0
Zone Conditioning - 101355 4540 - 0 0
Plenum Wall Load 20% 2931 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 30% 523 - 0 0 -
Return Fan Load 6341 CFM 0 - 6341 CFM 0 -
Ventilation Load 335 CFM 4744 15460 335 CFM -359 0
Supply Fan Load 6341 CFM 1880 - 6341 CFM -1880 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 5442 - 5% 0 -
>> Total System Loads - 116875 20000 - -2239 0
Central Cooling Coil - 116875 20014 - -2239 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 116875 20014 - -2239 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-2F01 LOBBY-SECRETARY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:20PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 2F-LOBBY& SECRETARY#1 '' IN ZONE '' Zone 2F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 978 ft 59965 - 978 ft - -
Wall Transmission 464 ft 1530 - 464 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 978 ft 15856 - 978 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 252 W 549 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1269 - 0 0 -
People 10 1858 1200 0 0 0
Infiltration - 538 1366 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 8157 257 0% 0 0
>> Total Zone Loads - 89722 2823 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 2F-LOBBY& SECRETARY#1 '' IN ZONE '' Zone 2F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 216 0.403 - 807 - 0
WINDOW 1 441 1.212 0.880 7335 29346 0
WNW EXPOSURE
WALL 216 0.403 - 658 - 0
WINDOW 1 441 1.212 0.880 7335 28744 0
ENE EXPOSURE
WALL 32 0.403 - 65 - 0
WINDOW 1 97 0.892 0.631 1187 1875 0

Hourly Analysis Program v.4.3 Page 1 of 3


Space Design Load Summary for IU-ADM-2F01 LOBBY-SECRETARY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:20PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 2F-SECURITY MONITOR#1 '' IN ZONE '' Zone 2F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 86 W 189 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1400 W 4777 - 0 0 -
People 2 401 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 537 41 0% 0 0
>> Total Zone Loads - 5904 451 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 2F-SECURITY MONITOR#1 '' IN ZONE '' Zone 2F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

Hourly Analysis Program v.4.3 Page 2 of 3


Space Design Load Summary for IU-ADM-2F01 LOBBY-SECRETARY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:20PM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 2F-EXCE DINNING#1 '' IN ZONE '' Zone 2F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 5717 - 65 ft - -
Wall Transmission 108 ft 653 - 108 ft 0 -
Roof Transmission 269 ft 2763 - 269 ft 0 -
Window Transmission 65 ft 742 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 8 1465 960 0 0 0
Infiltration - 39 108 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1302 107 0% 0 0
>> Total Zone Loads - 14317 1175 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 2F-EXCE DINNING#1 '' IN ZONE '' Zone 2F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 108 0.403 - 653 - 0
WINDOW 1 65 0.892 0.631 742 5717 0
H EXPOSURE
ROOF 269 0.134 - 2763 - 0

Hourly Analysis Program v.4.3 Page 3 of 3


System Psychrometrics for IU-ADM-2F01 LOBBY-SECRETARY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:20PM

December DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 90.0 0.02049 335 400 4744 15460
Vent - Return Mixing Outlet 77.5 0.01121 6341 805 - -
Central Cooling Coil Outlet 60.3 0.01055 6341 805 116875 20014
Central Heating Coil Outlet 60.3 0.01055 6341 805 0 -
Supply Fan Outlet 60.6 0.01055 6341 805 1880 -
Cold Supply Duct Outlet 61.4 0.01055 6024 805 - -
Zone Air - 77.1 0.01070 6024 829 101355 4540
Return Plenum Outlet 77.6 0.01070 6024 829 3454 -
Duct Leakage Air Outlet 60.6 0.01055 317 805 - -
Return Duct Outlet 76.8 0.01070 6341 828 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 2F-01 108837 Cooling 101355 77.1 6024 829 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-2F01 LOBBY-SECRETARY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:20PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 335 400 359 0
Vent - Return Mixing Outlet 70.1 0.00813 6341 577 - -
Central Cooling Coil Outlet 69.7 0.00813 6341 577 2239 0
Central Heating Coil Outlet 69.7 0.00813 6341 577 0 -
Supply Fan Outlet 70.0 0.00813 6341 577 1880 -
Cold Supply Duct Outlet 70.0 0.00813 6024 577 - -
Zone Air - 70.0 0.00813 6024 587 0 0
Return Plenum Outlet 70.0 0.00813 6024 587 0 -
Duct Leakage Air Outlet 70.0 0.00813 317 577 - -
Return Duct Outlet 70.0 0.00813 6341 587 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 2F-01 0 Deadband 0 70.0 6024 587 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-2F01 LOBBY-SECRETARY
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:20PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: December DESIGN COOLING DAY, 1600
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet 1
8. Return Duct Outlet
0.020

Specific Humidity ( lb/lb )


0.018
0.016
0.014
35
2
6 7 0.012
8
4 0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

Air System Information


Air System Name ..................... IU-ADM-2F02 SOUTH Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 4657.5 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 17.2 Tons Load occurs at .................................................. Dec 1500
Total coil load ...................................................... 206.6 MBH OA DB / WB .................................................... 90.4 / 80.6 F
Sensible coil load ................................................ 158.2 MBH Entering DB / WB ............................................ 80.9 / 68.9 F
Coil CFM at Dec 1500 .......................................... 7739 CFM Leaving DB / WB ............................................. 61.9 / 60.8 F
Max block CFM .................................................... 7739 CFM Coil ADP .................................................................... 59.8 F
Sum of peak zone CFM ....................................... 7739 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.766 Resulting RH ................................................................ 58 %
ft/Ton .................................................................. 270.5 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 44.4 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 7739 CFM Fan motor BHP .......................................................... 0.90 BHP
Standard CFM ...................................................... 7693 CFM Fan motor kW ............................................................ 0.67 kW
Actual max CFM/ft ............................................... 1.66 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................ 877 CFM CFM/person ............................................................. 16.86 CFM/person
CFM/ft .................................................................. 0.19 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

Air System Information


Air System Name ..................... IU-ADM-2F02 SOUTH Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 4657.5 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone 2F-02 117.7 7352 7352 Dec 1500 0.0 4657.5 1.58

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone 2F-02
2F-R.TUNGGU#1 1 35.4 Dec 1500 1940 0.0 1770.7 1.10
2F-Director#1 1 19.1 Dec 1500 1045 0.0 527.4 1.98
2F-Director#2 1 15.9 Jun 1000 873 0.0 376.7 2.32
2F-Director#3 1 13.0 Jun 1000 714 0.0 403.6 1.77
2F-Director#4 1 13.1 Jun 1000 718 0.0 438.1 1.64
2F-Komisaris#1 1 20.5 Dec 1500 1126 0.0 570.5 1.97
2F-Komisaris#2 1 17.1 Dec 1500 937 0.0 570.5 1.64

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 877 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 780 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space 2F-R.TUNGGU#1
Critical Space Outdoor Air Fraction ('Z') 0.217
Uncorrected Outdoor Air Fraction ('X') 0.106
Corrected Outdoor Air Fraction ('Y') 0.119
Required System Ventilation Airflow (CFM) 877

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone 2F-02
2F-R.TUNGGU#1 1 1770.7 28.0 1939.9 15.00 0.00 0.0 0.0 420.0 0.217 231.4
2F-Director#1 1 527.4 4.0 1045.3 15.00 0.00 0.0 0.0 60.0 0.057 124.7
2F-Director#2 1 376.7 4.0 872.7 15.00 0.00 0.0 0.0 60.0 0.069 104.1
2F-Director#3 1 403.6 4.0 713.7 15.00 0.00 0.0 0.0 60.0 0.084 85.1
2F-Director#4 1 438.1 4.0 718.1 15.00 0.00 0.0 0.0 60.0 0.084 85.6
2F-Komisaris#1 1 570.5 4.0 1125.5 15.00 0.00 0.0 0.0 60.0 0.053 134.2
2F-Komisaris#2 1 570.5 4.0 936.8 15.00 0.00 0.0 0.0 60.0 0.064 111.7
Totals (incl. Space Multipliers) 7352.1 780.0 0.217 876.8

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 969 ft 48998 - 969 ft - -
Wall Transmission 1550 ft 9750 - 1550 ft 0 -
Roof Transmission 3081 ft 9491 - 3081 ft 0 -
Window Transmission 969 ft 11124 - 969 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 3852 W 8343 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2800 W 8842 - 0 0 -
People 52 9808 8282 0 0 0
Infiltration - 674 1735 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10703 1002 0% 0 0
>> Total Zone Loads - 117732 11019 - 0 0
Zone Conditioning - 109683 11019 - 0 0
Plenum Wall Load 20% 4143 - 0 0 -
Plenum Roof Load 70% 22146 - 0 0 -
Plenum Lighting Load 30% 3943 - 0 0 -
Return Fan Load 7739 CFM 0 - 7739 CFM 0 -
Ventilation Load 877 CFM 10082 37406 877 CFM -941 0
Supply Fan Load 7739 CFM 2295 - 7739 CFM -2295 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 5887 - 5% 0 -
>> Total System Loads - 158179 48425 - -3236 0
Central Cooling Coil - 158178 48437 - -3236 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 158178 48437 - -3236 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 2F-R.TUNGGU#1 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 323 ft 14989 - 323 ft - -
Wall Transmission 646 ft 4323 - 646 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 323 ft 3708 - 323 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1164 W 2521 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 28 5127 3360 0 0 0
Infiltration - 256 660 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3219 402 0% 0 0
>> Total Zone Loads - 35406 4422 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 2F-R.TUNGGU#1 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 183 0.403 - 1075 - 0
WINDOW 1 129 0.892 0.631 1483 11434 0
NNE EXPOSURE
WALL 183 0.403 - 564 - 0
WINDOW 1 161 0.892 0.631 1854 2711 0
ESE EXPOSURE
WALL 280 0.403 - 2684 - 0
WINDOW 1 32 0.892 0.631 371 843 0

Hourly Analysis Program v.4.3 Page 1 of 7


Space Design Load Summary for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 2F-Director#1 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 11434 - 129 ft - -
Wall Transmission 75 ft 307 - 75 ft 0 -
Roof Transmission 527 ft 1625 - 527 ft 0 -
Window Transmission 129 ft 1483 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 4 780 820 0 0 0
Infiltration - 76 197 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1734 102 0% 0 0
>> Total Zone Loads - 19078 1118 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#1 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 75 0.403 - 307 - 0
WINDOW 1 129 0.892 0.631 1483 11434 0
H EXPOSURE
ROOF 527 0.134 - 1625 - 0

Hourly Analysis Program v.4.3 Page 2 of 7


Space Design Load Summary for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 2F-Director#2 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 74.6 F / 73.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 11143 - 129 ft - -
Wall Transmission 75 ft 138 - 75 ft 0 -
Roof Transmission 570 ft 650 - 570 ft 0 -
Window Transmission 129 ft -110 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 346 W 722 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1228 - 0 0 -
People 4 711 820 0 0 0
Infiltration - -2 69 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1448 89 0% 0 0
>> Total Zone Loads - 15929 978 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#2 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 75 0.403 - 138 - 0
WINDOW 1 129 0.892 0.631 -110 11143 0
H EXPOSURE
ROOF 570 0.134 - 650 - 0

Hourly Analysis Program v.4.3 Page 3 of 7


Space Design Load Summary for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' 2F-Director#3 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 74.6 F / 73.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 8357 - 97 ft - -
Wall Transmission 108 ft 268 - 108 ft 0 -
Roof Transmission 404 ft 460 - 404 ft 0 -
Window Transmission 97 ft -83 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 902 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1228 - 0 0 -
People 4 711 820 0 0 0
Infiltration - -2 74 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1184 89 0% 0 0
>> Total Zone Loads - 13026 983 - 0 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#3 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 108 0.403 - 268 - 0
WINDOW 1 97 0.892 0.631 -83 8357 0
H EXPOSURE
ROOF 404 0.134 - 460 - 0

Hourly Analysis Program v.4.3 Page 4 of 7


Space Design Load Summary for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' 2F-Director#4 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 74.6 F / 73.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 8357 - 97 ft - -
Wall Transmission 118 ft 302 - 118 ft 0 -
Roof Transmission 438 ft 499 - 438 ft 0 -
Window Transmission 97 ft -83 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 902 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1228 - 0 0 -
People 4 711 820 0 0 0
Infiltration - -2 80 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1192 90 0% 0 0
>> Total Zone Loads - 13107 990 - 0 0

TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#4 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 118 0.403 - 302 - 0
WINDOW 1 97 0.892 0.631 -83 8357 0
H EXPOSURE
ROOF 438 0.134 - 499 - 0

Hourly Analysis Program v.4.3 Page 5 of 7


Space Design Load Summary for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' 2F-Komisaris#1 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 8576 - 97 ft - -
Wall Transmission 409 ft 3689 - 409 ft 0 -
Roof Transmission 570 ft 1758 - 570 ft 0 -
Window Transmission 97 ft 1112 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 653 W 1414 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 4 780 820 0 0 0
Infiltration - 83 213 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1867 103 0% 0 0
>> Total Zone Loads - 20542 1136 - 0 0

TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' 2F-Komisaris#1 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 344 0.403 - 3402 - 0
SSW EXPOSURE
WALL 65 0.403 - 288 - 0
WINDOW 1 97 0.892 0.631 1112 8576 0
H EXPOSURE
ROOF 570 0.134 - 1758 - 0

Hourly Analysis Program v.4.3 Page 6 of 7


Space Design Load Summary for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' 2F-Komisaris#2 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 8576 - 97 ft - -
Wall Transmission 118 ft 558 - 118 ft 0 -
Roof Transmission 570 ft 1758 - 570 ft 0 -
Window Transmission 97 ft 1112 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 653 W 1414 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 4 780 820 0 0 0
Infiltration - 83 213 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1554 103 0% 0 0
>> Total Zone Loads - 17098 1136 - 0 0

TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' 2F-Komisaris#2 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 65 0.403 - 288 - 0
WINDOW 1 97 0.892 0.631 1112 8576 0
WNW EXPOSURE
WALL 54 0.403 - 270 - 0
H EXPOSURE
ROOF 570 0.134 - 1758 - 0

Hourly Analysis Program v.4.3 Page 7 of 7


System Psychrometrics for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

December DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 90.4 0.02049 877 400 10082 37406
Vent - Return Mixing Outlet 80.9 0.01248 7739 861 - -
Central Cooling Coil Outlet 61.9 0.01115 7739 861 158178 48437
Central Heating Coil Outlet 61.9 0.01115 7739 861 0 -
Supply Fan Outlet 62.1 0.01115 7739 861 2295 -
Cold Supply Duct Outlet 62.9 0.01115 7352 861 - -
Zone Air - 76.8 0.01147 7352 923 109683 11019
Return Plenum Outlet 80.6 0.01147 7352 923 30232 -
Duct Leakage Air Outlet 62.1 0.01115 387 861 - -
Return Duct Outlet 79.7 0.01145 7739 920 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 2F-02 117732 Cooling 109683 76.8 7352 923 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 877 400 941 0
Vent - Return Mixing Outlet 70.1 0.00813 7739 474 - -
Central Cooling Coil Outlet 69.7 0.00813 7739 474 3236 0
Central Heating Coil Outlet 69.7 0.00813 7739 474 0 -
Supply Fan Outlet 70.0 0.00813 7739 474 2295 -
Cold Supply Duct Outlet 70.0 0.00813 7352 474 - -
Zone Air - 70.0 0.00813 7352 484 0 0
Return Plenum Outlet 70.0 0.00813 7352 484 0 -
Duct Leakage Air Outlet 70.0 0.00813 387 474 - -
Return Duct Outlet 70.0 0.00813 7739 484 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 2F-02 0 Deadband 0 70.0 7352 484 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-2F02 SOUTH
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:25PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: December DESIGN COOLING DAY, 1500
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet 1
8. Return Duct Outlet
0.020

Specific Humidity ( lb/lb )


0.018
0.016

2
0.014
35 6 8 0.012
7
4
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-2F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:30PM

Air System Information


Air System Name ................... IU-ADM-2F03 NORTH1 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 2331.5 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 21.4 Tons Load occurs at ................................................... Feb 1500
Total coil load ...................................................... 257.3 MBH OA DB / WB .................................................... 91.4 / 80.6 F
Sensible coil load ................................................ 150.6 MBH Entering DB / WB ............................................ 83.9 / 72.4 F
Coil CFM at Feb 1500 .......................................... 6095 CFM Leaving DB / WB ............................................. 60.9 / 60.0 F
Max block CFM .................................................... 6095 CFM Coil ADP .................................................................... 58.3 F
Sum of peak zone CFM ....................................... 6095 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.585 Resulting RH ................................................................ 57 %
ft/Ton .................................................................. 108.7 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) .......................................................... 110.4 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 6095 CFM Fan motor BHP .......................................................... 0.71 BHP
Standard CFM ...................................................... 6059 CFM Fan motor kW ............................................................ 0.53 kW
Actual max CFM/ft ............................................... 2.61 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 2161 CFM CFM/person ............................................................. 17.71 CFM/person
CFM/ft .................................................................. 0.93 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-2F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:30PM

Air System Information


Air System Name ................... IU-ADM-2F03 NORTH1 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 2331.5 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone 2F-03 105.7 5790 5790 Mar 1500 0.0 2331.5 2.48

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone 2F-03
2F-GRAND MEETING#1 1 48.5 Mar 1500 2658 0.0 1076.4 2.47
2F-FUNCTION#1 1 57.2 Apr 1500 3133 0.0 1255.1 2.50

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-2F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:30PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................. 2161 CFM
Uncorrected Outdoor Airflow Rate ............................................................ 1830 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space 2F-FUNCTION#1
Critical Space Outdoor Air Fraction ('Z') 0.469
Uncorrected Outdoor Air Fraction ('X') 0.316
Corrected Outdoor Air Fraction ('Y') 0.373
Required System Ventilation Airflow (CFM) 2161

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone 2F-03
2F-GRAND MEETING#1 1 1076.4 24.0 2657.6 15.00 0.00 0.0 0.0 360.0 0.135 991.8
2F-FUNCTION#1 1 1255.1 98.0 3132.8 15.00 0.00 0.0 0.0 1470.0 0.469 1169.2
Totals (incl. Space Multipliers) 5790.4 1830.0 0.469 2161.0

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-2F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:30PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 452 ft 43491 - 452 ft - -
Wall Transmission 743 ft 3393 - 743 ft 0 -
Roof Transmission 2331 ft 7551 - 2331 ft 0 -
Window Transmission 452 ft 5594 - 452 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 2306 W 4995 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1600 W 5052 - 0 0 -
People 122 22339 14640 0 0 0
Infiltration - 359 844 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9278 1548 0% 0 0
>> Total Zone Loads - 102053 17032 - 0 0
Zone Conditioning - 95144 17032 - 0 0
Plenum Wall Load 20% 1626 - 0 0 -
Plenum Roof Load 70% 17619 - 0 0 -
Plenum Lighting Load 30% 2361 - 0 0 -
Return Fan Load 6095 CFM 0 - 6095 CFM 0 -
Ventilation Load 2161 CFM 26924 89730 2161 CFM -2320 0
Supply Fan Load 6095 CFM 1807 - 6095 CFM -1807 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 5103 - 5% 0 -
>> Total System Loads - 150584 106762 - -4128 0
Central Cooling Coil - 150584 106764 - -4127 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 150584 106764 - -4127 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-2F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:30PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 2F-GRAND MEETING#1 '' IN ZONE '' Zone 2F-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Mar 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 89.4 F / 79.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 258 ft 27349 - 258 ft - -
Wall Transmission 161 ft 500 - 161 ft 0 -
Roof Transmission 1076 ft 3251 - 1076 ft 0 -
Window Transmission 258 ft 2736 - 258 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1183 W 2563 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 3158 - 0 0 -
People 24 4395 2880 0 0 0
Infiltration - 146 366 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4410 325 0% 0 0
>> Total Zone Loads - 48505 3571 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 2F-GRAND MEETING#1 '' IN ZONE '' Zone 2F-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 161 0.403 - 500 - 0
WINDOW 1 258 0.892 0.631 2736 27349 0
H EXPOSURE
ROOF 1076 0.134 - 3251 - 0

Hourly Analysis Program v.4.3 Page 1 of 2


Space Design Load Summary for IU-ADM-2F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:30PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 2F-FUNCTION#1 '' IN ZONE '' Zone 2F-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 194 ft 21044 - 194 ft - -
Wall Transmission 581 ft 3521 - 581 ft 0 -
Roof Transmission 1255 ft 3292 - 1255 ft 0 -
Window Transmission 194 ft 1706 - 194 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1123 W 2433 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1895 - 0 0 -
People 98 17944 11760 0 0 0
Infiltration - 146 410 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 5198 1217 0% 0 0
>> Total Zone Loads - 57178 13387 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 2F-FUNCTION#1 '' IN ZONE '' Zone 2F-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 237 0.403 - 888 - 0
WINDOW 1 194 0.892 0.631 1706 21044 0
NNE EXPOSURE
WALL 344 0.403 - 2633 - 0
H EXPOSURE
ROOF 1255 0.134 - 3292 - 0

Hourly Analysis Program v.4.3 Page 2 of 2


System Psychrometrics for IU-ADM-2F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:30PM

February DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 91.4 0.02026 2161 400 26924 89730
Vent - Return Mixing Outlet 83.9 0.01458 6095 754 - -
Central Cooling Coil Outlet 60.9 0.01086 6095 754 150584 106764
Central Heating Coil Outlet 60.9 0.01086 6095 754 0 -
Supply Fan Outlet 61.2 0.01086 6095 754 1807 -
Cold Supply Duct Outlet 62.0 0.01086 5790 754 - -
Zone Air - 77.3 0.01149 5790 958 95144 17032
Return Plenum Outlet 80.8 0.01149 5790 958 21606 -
Duct Leakage Air Outlet 61.2 0.01086 305 754 - -
Return Duct Outlet 79.8 0.01146 6095 948 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 2F-03 102053 Cooling 95144 77.3 5790 958 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-2F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:30PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 2161 400 2320 0
Vent - Return Mixing Outlet 70.4 0.00813 6095 412 - -
Central Cooling Coil Outlet 69.7 0.00813 6095 412 4127 0
Central Heating Coil Outlet 69.7 0.00813 6095 412 0 -
Supply Fan Outlet 70.0 0.00813 6095 412 1807 -
Cold Supply Duct Outlet 70.0 0.00813 5790 412 - -
Zone Air - 70.0 0.00813 5790 419 0 0
Return Plenum Outlet 70.0 0.00813 5790 419 0 -
Duct Leakage Air Outlet 70.0 0.00813 305 412 - -
Return Duct Outlet 70.0 0.00813 6095 419 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 2F-03 0 Deadband 0 70.0 5790 419 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-2F03 NORTH1
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:30PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: February DESIGN COOLING DAY, 1500
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet
8. Return Duct Outlet 1
0.020

Specific Humidity ( lb/lb )


0.018
2
0.016
0.014
6 87 0.012
35
4 0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-2F04 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:34PM

Air System Information


Air System Name ................... IU-ADM-2F04 NORTH2 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 1073.2 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .......................................................... 5.3 Tons Load occurs at ................................................... Jan 0800
Total coil load ........................................................ 63.1 MBH OA DB / WB .................................................... 79.6 / 77.7 F
Sensible coil load .................................................. 54.4 MBH Entering DB / WB ............................................ 77.6 / 66.1 F
Coil CFM at Jan 0800 .......................................... 2929 CFM Leaving DB / WB ............................................. 60.3 / 59.2 F
Max block CFM .................................................... 2929 CFM Coil ADP .................................................................... 58.4 F
Sum of peak zone CFM ....................................... 2929 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.863 Resulting RH ................................................................ 53 %
ft/Ton .................................................................. 204.2 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 58.8 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 2929 CFM Fan motor BHP .......................................................... 0.34 BHP
Standard CFM ...................................................... 2912 CFM Fan motor kW ............................................................ 0.25 kW
Actual max CFM/ft ............................................... 2.73 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................ 140 CFM CFM/person ............................................................. 17.53 CFM/person
CFM/ft .................................................................. 0.13 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-2F04 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:34PM

Air System Information


Air System Name ................... IU-ADM-2F04 NORTH2 Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 1073.2 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone 2F-04 50.8 2782 2782 Jan 0800 0.0 1073.2 2.59

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone 2F-04
2F-Director#5 1 20.4 Jan 0800 1117 0.0 366.0 3.05
2F-Director#6 1 16.4 Jan 0800 896 0.0 405.8 2.21
2F-FILE STORAGE#1 1 14.0 Jan 0800 769 0.0 301.4 2.55

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-2F04 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:34PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 140 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 138 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space 2F-Director#6
Critical Space Outdoor Air Fraction ('Z') 0.067
Uncorrected Outdoor Air Fraction ('X') 0.050
Corrected Outdoor Air Fraction ('Y') 0.050
Required System Ventilation Airflow (CFM) 140

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone 2F-04
2F-Director#5 1 366.0 4.0 1117.4 15.00 0.00 0.0 0.0 60.0 0.054 56.3
2F-Director#6 1 405.8 4.0 896.5 15.00 0.00 0.0 0.0 60.0 0.067 45.2
2F-FILE STORAGE#1 1 301.4 0.0 768.6 0.00 0.06 0.0 0.0 17.8 0.023 38.7
Totals (incl. Space Multipliers) 2782.5 137.8 0.067 140.2

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-2F04 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:34PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 323 ft 36665 - 323 ft - -
Wall Transmission 237 ft 663 - 237 ft 0 -
Roof Transmission 1073 ft 809 - 1073 ft 0 -
Window Transmission 323 ft 1566 - 323 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 994 W 2038 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 3026 - 0 0 -
People 8 1354 1641 0 0 0
Infiltration - 47 423 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4617 206 0% 0 0
>> Total Zone Loads - 50784 2270 - 0 0
Zone Conditioning - 47217 2270 - 0 0
Plenum Wall Load 20% 594 - 0 0 -
Plenum Roof Load 70% 1889 - 0 0 -
Plenum Lighting Load 30% 1017 - 0 0 -
Return Fan Load 2929 CFM 0 - 2929 CFM 0 -
Ventilation Load 140 CFM 323 6330 140 CFM -151 0
Supply Fan Load 2929 CFM 868 - 2929 CFM -868 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 2539 - 5% 0 -
>> Total System Loads - 54447 8601 - -1019 0
Central Cooling Coil - 54447 8611 - -1019 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 54447 8611 - -1019 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-2F04 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:34PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 2F-Director#5 '' IN ZONE '' Zone 2F-04 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 14666 - 129 ft - -
Wall Transmission 75 ft 183 - 75 ft 0 -
Roof Transmission 366 ft 276 - 366 ft 0 -
Window Transmission 129 ft 626 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 886 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1211 - 0 0 -
People 4 677 820 0 0 0
Infiltration - 16 144 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1854 96 0% 0 0
>> Total Zone Loads - 20394 1061 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#5 '' IN ZONE '' Zone 2F-04 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 75 0.403 - 183 - 0
WINDOW 1 129 0.892 0.631 626 14666 0
H EXPOSURE
ROOF 366 0.134 - 276 - 0

Hourly Analysis Program v.4.3 Page 1 of 3


Space Design Load Summary for IU-ADM-2F04 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:34PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 2F-Director#6 '' IN ZONE '' Zone 2F-04 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10999 - 97 ft - -
Wall Transmission 97 ft 309 - 97 ft 0 -
Roof Transmission 406 ft 306 - 406 ft 0 -
Window Transmission 97 ft 470 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 886 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1211 - 0 0 -
People 4 677 820 0 0 0
Infiltration - 18 160 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1487 98 0% 0 0
>> Total Zone Loads - 16362 1078 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#6 '' IN ZONE '' Zone 2F-04 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 97 0.403 - 309 - 0
WINDOW 1 97 0.892 0.631 470 10999 0
H EXPOSURE
ROOF 406 0.134 - 306 - 0

Hourly Analysis Program v.4.3 Page 2 of 3


Space Design Load Summary for IU-ADM-2F04 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:34PM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 2F-FILE STORAGE#1 '' IN ZONE '' Zone 2F-04 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10999 - 97 ft - -
Wall Transmission 65 ft 171 - 65 ft 0 -
Roof Transmission 301 ft 227 - 301 ft 0 -
Window Transmission 97 ft 470 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 130 W 266 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 605 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 13 119 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1275 12 0% 0 0
>> Total Zone Loads - 14027 131 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 2F-FILE STORAGE#1 '' IN ZONE '' Zone 2F-04 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 65 0.403 - 171 - 0
WINDOW 1 97 0.892 0.631 470 10999 0
H EXPOSURE
ROOF 301 0.134 - 227 - 0

Hourly Analysis Program v.4.3 Page 3 of 3


System Psychrometrics for IU-ADM-2F04 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:34PM

January DESIGN COOLING DAY, 0800

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 79.6 0.02026 140 400 323 6330
Vent - Return Mixing Outlet 77.6 0.01115 2929 831 - -
Central Cooling Coil Outlet 60.3 0.01053 2929 831 54447 8611
Central Heating Coil Outlet 60.3 0.01053 2929 831 0 -
Supply Fan Outlet 60.6 0.01053 2929 831 868 -
Cold Supply Duct Outlet 61.4 0.01053 2782 831 - -
Zone Air - 77.2 0.01070 2782 854 47217 2270
Return Plenum Outlet 78.4 0.01070 2782 854 3500 -
Duct Leakage Air Outlet 60.6 0.01053 146 831 - -
Return Duct Outlet 77.5 0.01069 2929 852 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 2F-04 50784 Cooling 47217 77.2 2782 854 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-2F04 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:34PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 140 400 151 0
Vent - Return Mixing Outlet 70.0 0.00813 2929 592 - -
Central Cooling Coil Outlet 69.7 0.00813 2929 592 1019 0
Central Heating Coil Outlet 69.7 0.00813 2929 592 0 -
Supply Fan Outlet 70.0 0.00813 2929 592 868 -
Cold Supply Duct Outlet 70.0 0.00813 2782 592 - -
Zone Air - 70.0 0.00813 2782 601 0 0
Return Plenum Outlet 70.0 0.00813 2782 601 0 -
Duct Leakage Air Outlet 70.0 0.00813 146 592 - -
Return Duct Outlet 70.0 0.00813 2929 601 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 2F-04 0 Deadband 0 70.0 2782 601 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-2F04 NORTH2
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:34PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: January DESIGN COOLING DAY, 0800
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet
8. Return Duct Outlet 1
0.020

Specific Humidity ( lb/lb )


0.018
0.016
0.014
35
27 0.012
6
4 8 0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-3F01 HALL
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:45PM

Air System Information


Air System Name ........................ IU-ADM-3F01 HALL Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 3057.0 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 11.9 Tons Load occurs at .................................................. Dec 1500
Total coil load ...................................................... 142.6 MBH OA DB / WB .................................................... 90.4 / 80.6 F
Sensible coil load ................................................ 115.1 MBH Entering DB / WB ............................................ 81.5 / 68.2 F
Coil CFM at Dec 1500 .......................................... 5216 CFM Leaving DB / WB ............................................. 60.9 / 59.7 F
Max block CFM .................................................... 5216 CFM Coil ADP .................................................................... 58.7 F
Sum of peak zone CFM ....................................... 5216 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.807 Resulting RH ................................................................ 56 %
ft/Ton .................................................................. 257.3 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 46.6 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ................................................... 5216 CFM Fan motor BHP .......................................................... 0.61 BHP
Standard CFM ...................................................... 5185 CFM Fan motor kW ............................................................ 0.45 kW
Actual max CFM/ft ............................................... 1.71 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................ 296 CFM CFM/person ............................................................. 11.39 CFM/person
CFM/ft .................................................................. 0.10 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-3F01 HALL
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:45PM

Air System Information


Air System Name ........................ IU-ADM-3F01 HALL Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .............................................................. 3057.0 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone 3F-01 89.7 4955 4955 Jan 1600 0.0 3057.0 1.62

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone 3F-01
3F-FILE STORAGE#1 1 9.5 Dec 1500 520 0.0 258.3 2.01
3F-HALL#1 1 81.0 Jan 1600 4435 0.0 2798.6 1.58

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-3F01 HALL
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:45PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 296 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 295 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space 3F-HALL#1
Critical Space Outdoor Air Fraction ('Z') 0.063
Uncorrected Outdoor Air Fraction ('X') 0.060
Corrected Outdoor Air Fraction ('Y') 0.060
Required System Ventilation Airflow (CFM) 296

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone 3F-01
3F-FILE STORAGE#1 1 258.3 0.0 520.0 0.00 0.06 0.0 0.0 15.3 0.029 31.1
3F-HALL#1 1 2798.6 26.0 4435.4 0.00 0.10 0.0 0.0 279.9 0.063 265.1
Totals (incl. Space Multipliers) 4955.3 295.1 0.063 296.2

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-3F01 HALL
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:45PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 652 ft 43830 - 652 ft - -
Wall Transmission 801 ft 3939 - 801 ft 0 -
Roof Transmission 3057 ft 9418 - 3057 ft 0 -
Window Transmission 652 ft 9911 - 652 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1138 W 2464 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 3158 - 0 0 -
People 26 5071 5332 0 0 0
Infiltration - 3049 7979 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 8084 1331 0% 0 0
>> Total Zone Loads - 88925 14642 - 0 0
Zone Conditioning - 80709 14642 - 0 0
Plenum Wall Load 20% 2245 - 0 0 -
Plenum Roof Load 70% 21975 - 0 0 -
Plenum Lighting Load 30% 1164 - 0 0 -
Return Fan Load 5216 CFM 0 - 5216 CFM 0 -
Ventilation Load 296 CFM 3003 12856 296 CFM -318 0
Supply Fan Load 5216 CFM 1547 - 5216 CFM -1547 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 4446 - 5% 0 -
>> Total System Loads - 115089 27498 - -1865 0
Central Cooling Coil - 115089 27508 - -1865 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 115089 27508 - -1865 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-3F01 HALL
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:45PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-FILE STORAGE#1 '' IN ZONE '' Zone 3F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 5717 - 65 ft - -
Wall Transmission 75 ft 422 - 75 ft 0 -
Roof Transmission 258 ft 796 - 258 ft 0 -
Window Transmission 65 ft 742 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 130 W 281 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 632 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 39 101 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 863 10 0% 0 0
>> Total Zone Loads - 9490 111 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-FILE STORAGE#1 '' IN ZONE '' Zone 3F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 75 0.403 - 422 - 0
WINDOW 1 65 0.892 0.631 742 5717 0
H EXPOSURE
ROOF 258 0.134 - 796 - 0

Hourly Analysis Program v.4.3 Page 1 of 2


Space Design Load Summary for IU-ADM-3F01 HALL
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:45PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 3F-HALL#1 '' IN ZONE '' Zone 3F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 588 ft 38725 - 588 ft - -
Wall Transmission 725 ft 4012 - 725 ft 0 -
Roof Transmission 2799 ft 8068 - 2799 ft 0 -
Window Transmission 588 ft 9782 - 588 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1008 W 2196 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 800 W 2538 - 0 0 -
People 26 5146 5332 0 0 0
Infiltration - 3124 7501 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 7359 1283 0% 0 0
>> Total Zone Loads - 80951 14116 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 3F-HALL#1 '' IN ZONE '' Zone 3F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 363 0.403 - 2209 - 0
WINDOW 1 294 1.212 0.880 4891 19563 0
WNW EXPOSURE
WALL 363 0.403 - 1803 - 0
WINDOW 1 294 1.212 0.880 4891 19162 0
H EXPOSURE
ROOF 2799 0.134 - 8068 - 0

Hourly Analysis Program v.4.3 Page 2 of 2


System Psychrometrics for IU-ADM-3F01 HALL
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:45PM

December DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 90.4 0.02049 296 400 3003 12856
Vent - Return Mixing Outlet 81.5 0.01181 5216 911 - -
Central Cooling Coil Outlet 60.9 0.01070 5216 911 115089 27508
Central Heating Coil Outlet 60.9 0.01070 5216 911 0 -
Supply Fan Outlet 61.2 0.01070 5216 911 1547 -
Cold Supply Duct Outlet 62.1 0.01070 4955 911 - -
Zone Air - 77.2 0.01132 4955 944 80709 14642
Return Plenum Outlet 82.0 0.01132 4955 944 25385 -
Duct Leakage Air Outlet 61.2 0.01070 261 911 - -
Return Duct Outlet 81.0 0.01129 5216 942 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 3F-01 88925 Cooling 80709 77.2 4955 944 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-3F01 HALL
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:45PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 296 400 318 0
Vent - Return Mixing Outlet 70.1 0.00813 5216 557 - -
Central Cooling Coil Outlet 69.7 0.00813 5216 557 1865 0
Central Heating Coil Outlet 69.7 0.00813 5216 557 0 -
Supply Fan Outlet 70.0 0.00813 5216 557 1547 -
Cold Supply Duct Outlet 70.0 0.00813 4955 557 - -
Zone Air - 70.0 0.00813 4955 566 0 0
Return Plenum Outlet 70.0 0.00813 4955 566 0 -
Duct Leakage Air Outlet 70.0 0.00813 261 557 - -
Return Duct Outlet 70.0 0.00813 5216 566 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 3F-01 0 Deadband 0 70.0 4955 566 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-3F01 HALL
Project Name: Bayah - Administration Building 05/01/2014
Prepared by: Mepcons 05:45PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: December DESIGN COOLING DAY, 1500
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet 1
8. Return Duct Outlet
0.020

Specific Humidity ( lb/lb )


0.018
0.016
0.014
2
6 7 0.012
35 8
4 0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Sizing Summary for IU-ADM-4F01 LIFT ROOM
Project Name: Bayah - Administration Building 06/03/2014
Prepared by: Mepcons 08:33PM

Air System Information


Air System Name .............. IU-ADM-4F01 LIFT ROOM Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .................................................................. 43.1 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .......................................................... 1.4 Tons Load occurs at ................................................... Feb 1500
Total coil load ........................................................ 16.4 MBH OA DB / WB .................................................... 91.4 / 80.6 F
Sensible coil load .................................................. 15.5 MBH Entering DB / WB ............................................ 76.9 / 64.8 F
Coil CFM at Feb 1500 ............................................ 828 CFM Leaving DB / WB ............................................. 59.5 / 58.3 F
Max block CFM ...................................................... 828 CFM Coil ADP .................................................................... 57.5 F
Sum of peak zone CFM ......................................... 828 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.942 Resulting RH ................................................................ 51 %
ft/Ton .................................................................... 31.4 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) .......................................................... 381.7 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM ..................................................... 828 CFM Fan motor BHP .......................................................... 0.10 BHP
Standard CFM ........................................................ 823 CFM Fan motor kW ............................................................ 0.07 kW
Actual max CFM/ft ............................................. 19.23 CFM/ft Fan static ................................................................... 0.40 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 15 CFM CFM/person ............................................................. 15.00 CFM/person
CFM/ft .................................................................. 0.35 CFM/ft

Hourly Analysis Program v.4.3 Page 1 of 1


Zone Sizing Summary for IU-ADM-4F01 LIFT ROOM
Project Name: Bayah - Administration Building 06/03/2014
Prepared by: Mepcons 08:33PM

Air System Information


Air System Name .............. IU-ADM-4F01 LIFT ROOM Number of zones ............................................................ 1
Equipment Class ........................................ SPLT AHU Floor Area .................................................................. 43.1 ft
Air System Type ............................................... SZCAV Location .............................................. Bayah, Indonesia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft
Zone 4F-01 14.4 787 787 Feb 1500 0.0 43.1 18.27

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft
Zone 4F-01
4F-LIFT ROOM 1 14.4 Feb 1500 787 0.0 43.1 18.27

Hourly Analysis Program v.4.3 Page 1 of 1


Ventilation Sizing Summary for IU-ADM-4F01 LIFT ROOM
Project Name: Bayah - Administration Building 06/03/2014
Prepared by: Mepcons 08:33PM

1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ..................................................................... 15 CFM
Uncorrected Outdoor Airflow Rate ................................................................ 15 CFM

2. ASHRAE Std 62 Analysis Details


Sizing Data For:
Terminal boxes full open
Critical Space 4F-LIFT ROOM
Critical Space Outdoor Air Fraction ('Z') 0.019
Uncorrected Outdoor Air Fraction ('X') 0.019
Corrected Outdoor Air Fraction ('Y') 0.019
Required System Ventilation Airflow (CFM) 15

3. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected Uncorrected Corrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft) Occupants (CFM) (CFM/person) (CFM/ft) (CFM) (% of supply) (CFM) Ratio 'Z' (CFM)
Zone 4F-01
4F-LIFT ROOM 1 43.1 1.0 786.6 15.00 0.00 0.0 0.0 15.0 0.019 15.0
Totals (incl. Space Multipliers) 786.6 15.0 0.019 15.0

Hourly Analysis Program v.4.3 Page 1 of 1


Air System Design Load Summary for IU-ADM-4F01 LIFT ROOM
Project Name: Bayah - Administration Building 06/03/2014
Prepared by: Mepcons 08:33PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 22 ft 70 - 22 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 258 ft 0 - 258 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 72 W 156 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 682 - 0 0 -
People 1 195 205 0 0 0
Infiltration - 7 18 - 0 0
Miscellaneous - 11942 0 - 0 0
Safety Factor 10% / 10% 1305 22 0% 0 0
>> Total Zone Loads - 14357 245 - 0 0
Zone Conditioning - 14041 245 - 0 0
Plenum Wall Load 20% 0 - 0 0 -
Plenum Roof Load 70% 163 - 0 0 -
Plenum Lighting Load 30% 74 - 0 0 -
Return Fan Load 828 CFM 0 - 828 CFM 0 -
Ventilation Load 15 CFM 238 709 15 CFM -16 3
Supply Fan Load 828 CFM 246 - 828 CFM -246 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 718 - 5% 0 -
>> Total System Loads - 15479 954 - -262 3
Central Cooling Coil - 15479 955 - -262 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 15479 955 - -262 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1


Space Design Load Summary for IU-ADM-4F01 LIFT ROOM
Project Name: Bayah - Administration Building 06/03/2014
Prepared by: Mepcons 08:33PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 4F-LIFT ROOM '' IN ZONE '' Zone 4F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 22 ft 70 - 22 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 258 ft 0 - 258 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 72 W 156 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 682 - 0 0 -
People 1 195 205 0 0 0
Infiltration - 7 18 - 0 0
Miscellaneous - 11942 0 - 0 0
Safety Factor 10% / 10% 1305 22 0% 0 0
>> Total Zone Loads - 14357 245 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 4F-LIFT ROOM '' IN ZONE '' Zone 4F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
H EXPOSURE
ROOF 22 0.134 - 70 - 0

Hourly Analysis Program v.4.3 Page 1 of 1


System Psychrometrics for IU-ADM-4F01 LIFT ROOM
Project Name: Bayah - Administration Building 06/03/2014
Prepared by: Mepcons 08:33PM

February DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 91.4 0.02026 15 400 238 709
Vent - Return Mixing Outlet 76.9 0.01042 828 807 - -
Central Cooling Coil Outlet 59.5 0.01017 828 807 15479 955
Central Heating Coil Outlet 59.5 0.01017 828 807 0 -
Supply Fan Outlet 59.7 0.01017 828 807 246 -
Cold Supply Duct Outlet 60.6 0.01017 787 807 - -
Zone Air - 77.2 0.01024 787 815 14041 245
Return Plenum Outlet 77.5 0.01024 787 815 236 -
Duct Leakage Air Outlet 59.7 0.01017 41 807 - -
Return Duct Outlet 76.6 0.01024 828 814 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 4F-01 14357 Cooling 14041 77.2 787 815 0 0

Hourly Analysis Program v.4.3 Page 1 of 2


System Psychrometrics for IU-ADM-4F01 LIFT ROOM
Project Name: Bayah - Administration Building 06/03/2014
Prepared by: Mepcons 08:33PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 71.0 0.00813 15 400 16 -3
Vent - Return Mixing Outlet 70.0 0.00817 828 793 - -
Central Cooling Coil Outlet 69.7 0.00817 828 793 262 0
Central Heating Coil Outlet 69.7 0.00817 828 793 0 -
Supply Fan Outlet 70.0 0.00817 828 793 246 -
Cold Supply Duct Outlet 70.0 0.00817 787 793 - -
Zone Air - 70.0 0.00817 787 800 0 0
Return Plenum Outlet 70.0 0.00817 787 800 0 -
Duct Leakage Air Outlet 70.0 0.00817 41 793 - -
Return Duct Outlet 70.0 0.00817 828 800 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 4F-01 0 Deadband 0 70.0 787 800 0 0

Hourly Analysis Program v.4.3 Page 2 of 2


Psychrometric Analysis for IU-ADM-4F01 LIFT ROOM
Project Name: Bayah - Administration Building 06/03/2014
Prepared by: Mepcons 08:33PM

Location: Bayah, Indonesia


Altitude: 164.0 ft.
Data for: February DESIGN COOLING DAY, 1500
1. Outdoor Air
2. Mixed Air 0.024
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Duct Heat
6. Room Air 0.022
7. Return Plenum Outlet
8. Return Duct Outlet 1
0.020

Specific Humidity ( lb/lb )


0.018
0.016
0.014
0.012
35 27
8 0.010
4 6
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )

Hourly Analysis Program v.4.3 Page 1 of 1