TRANSFORMER TEST EQUIPMENT

1

MULTI-AMP
2 Transformer
Ohmmeter
3
Direct digital reading
4
Built-in discharge
circuitry
5
Two independent
measuring channels
6
Tests operation of
on-load tap-changers
7

9
Transformer Winding Resistance
10
and Tap-Changer Test Set
DESCRIPTION tap-changers with make-before-break associated control wiring, voltage
The Multi-Amp Transformer Ohm- contacts and voltage regulators. regulators, motors, generators, breaker
11 meter is a line-oper ated, field- The internal shutdown circuit will be contacts, all types of connections
portable instrument designed specifi- triggered by a voltage kickback of a (bolted, soldered, crimped, etc.).
cally to measure the dc resistance of few microseconds if the tap-changer Tap-changers are mechanical devices
12 all types of magnetic windings safely contacts are opened when the tap- and the most vulnerable part of a
and accurately. changer circuit is operated through all transformer. Tap-changers result in
Its predominant use is the measurement of the tap positions. more failures and outages than any
13 of the dc resistance of all types of This action will check for pitted or other component and so require fre-
transformer windings within the de- misaligned contacts as the instrument quent testing and attention to ensure
fined ranges of current and resistance. will shut down if either condition proper, reliable operation.
14 It can also test rotating machine windings occurs. The Transformer Ohmmeter can be
and perform low-current resistance Users are protected by the shutdown used to check the make-before-break
measurements on connections, circuit safety feature: any inadvertent operation of on-load tap-changers and
15 contacts and control circuits. disconnection of a test lead or loss also to measure the contact resistance
of power to the instrument will of each tap position.
Three features combine to make this
instrument unique: dual measure- safely discharge the energy stored
16 in the test sample. FEATURES AND BENEFITS
ment, load tap-changer testing and
safety shutdown. Direct digital reading saves time, no
APPLICATIONS balancing is required.
The dual set of potential inputs
17 measure the resistance of the primary The Transformer Ohmmeter is used: Built-in discharge circuit safely
and secondary windings of a single- or To verify factory test readings discharges the specimen when test is
three-phase transformer simultaneously. completed, if lead accidentally
18 As part of a regular maintenance disconnects or if power is lost.
The dual reading characteristic will program
speed up the measurement when it is Electromechanical safety indicator
used to test windings on delta-delta To help locate the presence of gives a visual indication of a charged
19 connected windings on three-phase defects in transformers, such as loose or discharged specimen, even if power
transformers. connections to the instrument is lost.
Due to circulating currents induced To check the make-before-break Two independent measuring chan-
20 when the test current is applied to the operation of on-load tap-changers nels allow simultaneous testing of
primary winding, this type of measure- A regular maintenance program that primary and secondary windings or
ment is countered by the same current includes winding resistance measure- measurement of two phases at a time.
21 on the secondary winding. This action ments is the most effective way to use The sensitive surge detection circuitry
attenuates the circulating current and this instrument. Once a benchmark is monitors the contact operation of
the reading time is improved tenfold. established, subsequent test results
22 on-load tap-changers for the proper
The Transformer Ohmmeter is can be compared to determine if make-before-break sequence. If an
extremely useful when testing the changes are occurring in the trans- open circuit condition exists, the
windings and contact resistance on formers, instrument transformers and instrument shuts down immediately.

AC-4 AVO-651 07.97


2-6 AVO INTERNATIONAL
TRANSFORMER TEST EQUIPMENT

High-accuracy, four-terminal bridge: 1


no lead compensation required.
Electronically generated and
regulated current supply overcomes 2
high-inductance transformers quickly,
allowing fast measurements to be
taken. Display of measurement occurs 3
only after test current stabilizes.
Wide resistance range allows heat-
run testing of many transformer types. 4
Lightweight and portable, the Trans-
former Ohmmeter is ideal for use in
shop or substation environments. 5
Overtemperature protection
provides automatic current shutdown 6
and LED indication to prevent
instrument damage.
Instrument and accessories come in a One-Winding Low-Voltage Simultaneous
Measurement Winding Two-Winding 7
foam-lined transport case. Measurement
High-Voltage
SPECIFICATIONS Winding
8
Measuring Principle Schematic comparison of one- and two-winding measurements
Electronic Thompson-type circuit
Overrange: Lead number one dis- 9
Input played with all other digits blanked
120/240 V, 50/60 Hz, 350 VA
Environmental 10
Output Operating: 32 to 104 F (0 to 40 C),
Current Ranges: 5 mA, 50 mA, relative humidity to 80%
500 mA, 5 A (dc) Storage: -40 to +150 F (-40 to +65 C) 11
Open-Circuit Test Voltage: 30 Vdc Temperature Coefficients: 0.05% of
Rating: Continuous use on all ranges applicable accuracy specifications
per degree Celsius of resistance
12
Resistance Measurement Inputs: Two
range
isolated high-impedance inputs,
each with separate range control Displays: Two high-temperature, 0.7 in. 13
and protection provided for flash- (18 mm), liquid-crystal, 31/2-digit dis-
over caused by inductive kickback plays showing 1999 at full scale.
Update rate is approximately three 14
Ranges
times per second.
Nominal Resolution Maximum Dimensions
(ohms) (ohms) Display 15
(ohms) Instrument
2m 0.001 m 1.999 m 11 H x 16 W x 10.5 D in.
20 m 0.01 m 19.99 m 280 H x 406 W x 267 D mm
200 m 0.1 m 199.9 m
16
Transport Case
2 0.001 1.999 13 H x 20 W x 21 D in.
20 0.01 19.99
Power utilities can reduce expensive
330 H x 508 W x 533 D mm downtime by early detection of tap-
200 0.1 199.9 17
2000 1.0 1999 changer problems using the Multi-Amp
Weight Transformer Ohmmeter.
Accuracy: 0.5% reading, 0.5% full Instrument: Net 40 lb (18 kg)
18
scale (when current has stabilized) Shipping: 66 lb (30 kg)

ORDERING INFORMATION 19
Item (Qty) Cat. No. Item (Qty) Cat. No.
Transformer Ohmmeter with Universal bushing adapters [set of 4] .................... 830285
120 volt, 60 Hz input ............................................. 830280 AC power cord ............................................................. 17032 20
240 volt, 50 Hz input ........................................ 830280-47 Transport case .......................................................... MC996
Included Accessories Instruction manual ......................................... AVTM830280
21
Lead set, including .................................................... 830282 Optional Accessories
Potential leads, 33 ft (10 m) [2 pr] Lead set, including .................................................. 830282-66
Current leads, 33 ft (10 m) [1 pr] Potential leads, 66 ft (20m) [2pr] 22
Shorting lead, 9.9 ft (3 m) [1] Current leads, 66 ft (20 m) [2 pr]
Shorting lead, 9.9 ft (3 m) [1]

AC-4 AVO-651 07.97 AVO INTERNATIONAL 2-7