CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section A L1

X Y
(mm) (mm)
3356 0 Grillage Member
4575 0
4385 381 2500
3377 381
1981 1559 2000
1981 1783
3661 1826 1500
3523 2102
1000
1753 2057
0 2057 500
0 1803
1219 1803 0
3356 0 0 500 100015002000250030003500400045005000

CROSS SECTIONAL AREA = 2176108.5 mm2


CENTROID X = 2445.00 mm
CENTROID Y = 1260.56 mm
SECOND MOMENT OF AREA Ixx = 1.1687E+12 mm4
SECOND MOMENT OF AREA Iyy = 2.6044E+12 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section A L2

X Y
(mm) (mm)
1051 0 Grillage Member
2270 0
2459 381 2500
2067 381
1915 533 2000
1915 1719
2067 1871 1500
3116 1902
1000
3358 2187
0 2102 500
137 1826
1254 1885 0
1406 1706 0 500 1000 1500 2000 2500 3000 3500 4000
1406 533
1254 381
860 381
1051 0

CROSS SECTIONAL AREA = 2206110 mm2


CENTROID X = 1664.57 mm
CENTROID Y = 1247.10 mm
SECOND MOMENT OF AREA Ixx = 1.2802E+12 mm4
SECOND MOMENT OF AREA Iyy = 8.4363E+11 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section A L3

X Y
(mm) (mm)
0 0 Grillage Member
1219 0
3349 1987 2500
4569 1987
4569 2241 2000
1114 2241
946 1902 1500
2588 1946
1000
2588 1693
1181 381 500
189 381
0 0 0
0 500 100015002000250030003500400045005000

CROSS SECTIONAL AREA = 2264179.5 mm2


CENTROID X = 2126.85 mm
CENTROID Y = 1378.71 mm
SECOND MOMENT OF AREA Ixx = 1.4286E+12 mm4
SECOND MOMENT OF AREA Iyy = 2.6184E+12 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section A T1

X Y
(mm) (mm)
0 0 Grillage Member
2667 0
2667 254 300
0 254
0 0 250

200

150

100

50

0
0 500 1000 1500 2000 2500 3000

CROSS SECTIONAL AREA = 677418 mm2


CENTROID X = 1333.50 mm
CENTROID Y = 127.00 mm
SECOND MOMENT OF AREA Ixx = 3.6420E+09 mm4
SECOND MOMENT OF AREA Iyy = 4.0153E+11 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section A T2

X Y
(mm) (mm)
0 0 Grillage Member
2667 0
2667 381 2500
0 381
0 0 2000
0 1854
2667 1854 1500
2667 2144
1000
0 2144
0 1854 500

0
0 500 1000 1500 2000 2500 3000

CROSS SECTIONAL AREA = 1016127 mm2


CENTROID X = 1333.50 mm
CENTROID Y = 190.50 mm
SECOND MOMENT OF AREA Ixx = 1.2292E+10 mm4
SECOND MOMENT OF AREA Iyy = 6.0230E+11 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section A T3

X Y
(mm) (mm)
0 0 Grillage Member
2667 0
2667 381 2500
0 381
0 0 2000
0 0
0 1930 1500
2667 1930
1000
2667 2210
0 2210 500
0 1930
0
0 500 1000 1500 2000 2500 3000

CROSS SECTIONAL AREA = 1016127 mm2


CENTROID X = 1333.50 mm
CENTROID Y = 190.50 mm
SECOND MOMENT OF AREA Ixx = 1.2292E+10 mm4
SECOND MOMENT OF AREA Iyy = 6.0230E+11 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section A T4

X Y
(mm) (mm)
0 0 Grillage Member
2667 0
2667 254 300
0 254
0 0 250

200

150

100

50

0
0 500 1000 1500 2000 2500 3000

CROSS SECTIONAL AREA = 677418 mm2


CENTROID X = 1333.50 mm
CENTROID Y = 127.00 mm
SECOND MOMENT OF AREA Ixx = 3.6420E+09 mm4
SECOND MOMENT OF AREA Iyy = 4.0153E+11 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section B L1

X Y
(mm) (mm)
3356 0 Grillage Member
4575 0
4384 381 2500
3849 381
2692 1357 2000
2692 1801
3662 1826 1500
3524 2102
1000
1752 2057
0 2057 500
0 1803
1219 1803 0
3356 0 0 500 100015002000250030003500400045005000

CROSS SECTIONAL AREA = 2921966 mm2


CENTROID X = 2529.88 mm
CENTROID Y = 1230.89 mm
SECOND MOMENT OF AREA Ixx = 1.3080E+12 mm4
SECOND MOMENT OF AREA Iyy = 2.8159E+12 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section B L2

X Y
(mm) (mm)
1051 0 Grillage Member
2270 0
2459 381 2500
2219 381
2067 533 2000
2067 1723
2219 1879 1500
3217 1904
1000
3358 2187
0 2102 500
138 1826
1104 1850 0
1254 1723 0 500 1000 1500 2000 2500 3000 3500 4000
1254 533
1102 381
860 381
1051 0

CROSS SECTIONAL AREA = 2687011.5 mm2


CENTROID X = 1666.90 mm
CENTROID Y = 1233.76 mm
SECOND MOMENT OF AREA Ixx = 1.3833E+12 mm4
SECOND MOMENT OF AREA Iyy = 9.4434E+11 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section B L3

X Y
(mm) (mm)
0 0 Grillage Member
1219 0
3349 1987 2500
4569 1987
4569 2241 2000
3197 2241
1087 2187 1500
946 1904
1000
1876 1928
1876 1446 500
733 381
189 381 0
0 0 0 500 100015002000250030003500400045005000

CROSS SECTIONAL AREA = 2999831.5 mm2


CENTROID X = 2046.59 mm
CENTROID Y = 1323.47 mm
SECOND MOMENT OF AREA Ixx = 1.5676E+12 mm4
SECOND MOMENT OF AREA Iyy = 2.8234E+12 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section B T1

X Y
(mm) (mm)
0 0 Grillage Member
2642 0
2642 254 300
0 254
0 0 250

200

150

100

50

0
0 500 1000 1500 2000 2500 3000

CROSS SECTIONAL AREA = 671068 mm2


CENTROID X = 1321.00 mm
CENTROID Y = 127.00 mm
SECOND MOMENT OF AREA Ixx = 3.6079E+09 mm4
SECOND MOMENT OF AREA Iyy = 3.9035E+11 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section B T2

X Y
(mm) (mm)
0 0 Grillage Member
2642 0
2642 381 2500
0 381
0 0 2000
0 1850
2642 1850 1500
2642 2144
1000
0 2144
0 1850 500

0
0 500 1000 1500 2000 2500 3000

CROSS SECTIONAL AREA = 1006602 mm2


CENTROID X = 1321.00 mm
CENTROID Y = 190.50 mm
SECOND MOMENT OF AREA Ixx = 1.2177E+10 mm4
SECOND MOMENT OF AREA Iyy = 5.8552E+11 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section B T3

X Y
(mm) (mm)
0 0 Grillage Member
2642 0
2642 381 2500
0 381
0 0 2000
0 0
0 1879 1500
2642 1879
1000
2642 2210
0 2210 500
0 1879
0
0 500 1000 1500 2000 2500 3000

CROSS SECTIONAL AREA = 1006602 mm2


CENTROID X = 1321.00 mm
CENTROID Y = 190.50 mm
SECOND MOMENT OF AREA Ixx = 1.2177E+10 mm4
SECOND MOMENT OF AREA Iyy = 5.8552E+11 mm4
CALCULATION SHEET No:

Project: Swalwell Interchange Superstructure Assessment By - RAC Date- 05/06

Subject: Section Properties Check Check


SECTION PROPERTIES : Longitudinal Section B T4

X Y
(mm) (mm)
0 0 Grillage Member
2642 0
2642 254 300
0 254
0 0 250

200

150

100

50

0
0 500 1000 1500 2000 2500 3000

CROSS SECTIONAL AREA = 671068 mm2


CENTROID X = 1321.00 mm
CENTROID Y = 127.00 mm
SECOND MOMENT OF AREA Ixx = 3.6079E+09 mm4
SECOND MOMENT OF AREA Iyy = 3.9035E+11 mm4